Numerical Calculation and Analysis on the Surface Electric Field Characteristics of Hot-Line Robot

Similar documents
Electric Filed Simulation and Structure Optimization for 40.5kV GIS Based on Finite Element Method

Computation of Electric Field for FGM Spacer Using Di-Post Insulator in GIS

The Distortion Influence Simulation and Experimental Study of Human Body to High Voltage Power Frequency Electric Field

Electric Field Stress Calculation for different spacer types in Bus Duct

Lecture 15 Perfect Conductors, Boundary Conditions, Method of Images

Physics (

Influence of Grounding Material s Property on the Impulse Grounding Resistance of Grounding Grids

Analysis of Very Fast Transients in EHV Gas Insulated Substations

Consider a point P on the line joining the two charges, as shown in the given figure.

with embedded electrode

Modeling and Simulation of Air Insulated and Gas Insulated Substations

A Novel Optimized Design for Busbar Structures using Finite Element Methods

EFFECT OF DIELECTRIC BARRIERS TO THE ELECTRIC FIELD OF ROD-PLANE AIR GAP

Thickness Optimization of a Piezoelectric Converter for Energy Harvesting

PARTICLE TRAJECTORIES IN A THREE PHASE COMMON ENCLOSURE GAS INSULATED BUSDUCT WITH MONTE CARLO TECHNIQUE

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

NUMERICAL ANALYSES OF ELECTROMAGNETIC FIELDS IN HIGH VOLTAGE BUSHING AND IN ELECTROMAGNETIC FLOW METER

Research Article Simulation Analysis of Transient Earth Voltages Aroused by Partial Discharge in Switchgear

Railway Research. Study of Superconducting Fault Current Limiter Device in a AC Railway System. 1. Introduction. International Journal of

Electric Field and Thermal Properties of Dry Cable Using FEM

Comparison of Partial Discharge Characteristics for Different Defect Types in SF 6 Gas Insulation System

CALCULATION OF POWER FREQUENCY FIELDS FROM HIGH VOLTAGE OVERHEAD LINES IN RESIDENTIAL AREAS

Magnetic Field Simulation of a Miniature Circuit Breaker s Coil

Modeling Electric Fields in High Voltage Submersible Changeover Switch

Electromagnetics in COMSOL Multiphysics is extended by add-on Modules

Keywords: HVDC cable, Analytical calculation, PMLTCT, PMITD.

The Study of Overhead Line Fault Probability Model Based on Fuzzy Theory

MEASUREMENTS AND CALCULATIONS OF NON-IONIZING RADIATION LEVELS IN VICINITY OF 35 KV OVERHEAD POWER LINES

Magnetic and Thermal Analysis of Current Transformer in Normal and Abnormal Conditions

Modeling Electric Field and Potential Distribution of an Model of Insulator in Two Dimensions by the Finite Element Method

Lightning performance of EHV and UHV overhead transmission Lines in China southern power grid

device. Zhang Bo and Yang Huina at Tsinghua University used frequency domain electromagnetic field numerical calculation method to study substation gr

Lab 6 Electrostatic Charge and Faraday s Ice Pail

Optimization of High Voltage Arc Assist Interrupters

Flashover Performance of Station Post Insulators under Icing Conditions based on Electric Field Distribution

Finite Element Analysis of Disc Insulator Type and Corona Ring Effect on Electric Field Distribution over 230-kV Insulator Strings

Coupled electromagnetic, thermal and stress analysis of large power electrical transformers

PREDICTION OF TEMPERATURE VARIATIONS FOR INDUSTRIAL BUS DUCT SYSTEM UNDER FORCED CONVECTION COOLING WITH VARIOUS ASPECT RATIOS USING MATLAB

The Simulation Analysis of Electromagnetic Repulsion Mechanism for. High-voltage Current-Limiting Fuse

Simulation of Partial Discharge in Solid Dielectric Material

Influence Analysis of Transmission Lines Insulator on the Conductor Ice-shedding

Partial discharge (PD) is well established as a diagnostic

Finite Element Method Application in Analyzing Magnetic Fields of High Current Bus Duct

Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation

TRANSMISSION LINES. All aluminum alloy conductor (AAAC) Aluminum conductor alloy reinforced (ACAR)

Comparison of Finite Element Analysis to IEC for Predicting Underground Cable Ampacity

Jinzhou Power Supply Company, Liaoning Electric Power Company Limited, State Grid, China

Power system conductor volume calculation

3-D Thermal Field Analysis of 10kV High Voltage Switchgear

The Lightning Study of Overhead Transmission Lines

1. Voltage is how much work is being done for a charge. 2. Lightning is the electric breakdown of air by weak electric fields and is a flow of energy.

Calculation of Magnetic Field Produced by OHTL under Normal and Abnormal Conditions

Magnetic Field Analysis

Lab 1: Numerical Solution of Laplace s Equation

TRANSIENTS POWER SYSTEM. Theory and Applications TERUO OHNO AKIH1RO AMETANI NAOTO NAGAOKA YOSHIHIRO BABA. CRC Press. Taylor & Francis Croup

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

NR/RR. Set No. 2 CODE NO: NR/RR210204

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008


For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Examples of magnetic field calculations in indoor distribution substations

Calculation of Electric and Magnetic Field Safety Limits Under UHV AC Transmission Lines

Magnetic Force on a Moving Charge

Electric Field and Potential Distributions along Dry and Clean Non-Ceramic Insulators. Integrated Engineering Software - Website Links

Adaptive numerical simulation of Streamer. Shailendra Singh

International Journal of Advances in Engineering & Technology, May IJAET ISSN: D. Deepak Chowdary 1, J.Amarnath 2

Modeling of Transmission Line and Substation for Insulation Coordination Studies

Keywords: Electric Machines, Rotating Machinery, Stator faults, Fault tolerant control, Field Weakening, Anisotropy, Dual rotor, 3D modeling

STUDY OF THE FACTORS THAT INFLUENCE THE EFECTIVE PERMITTIVITY OF THE DIELECTRIC MIXTURES

Comparison of Transient Simulations on Overhead Cables by EMTP and FDTD

THE APPROACH TO THE ANALYSIS OF ELECTRICAL FIELD DISTRIBUTION IN THE SETUP OF PAPER INSULATED ELECTRODES IN OIL

Arrangement of conductors in 220 kv double circuit line to reduce E-fields in view of public exposure

Energy Stored in Capacitors

Medical Physics & Science Applications

Available online at ScienceDirect. Procedia Computer Science 83 (2016 )

A Novel Analytical Expressions Model for Corona Currents Based on Curve Fitting Method Using Artificial Neural Network

EXPERIMENTAL AND THEORETICAL STUDY OF BREAKDOWN VOLTAGE INITIATED BY PARTICLE CONTAMINATION IN GIS

International Journal of Scientific & Engineering Research, Volume 7, Issue 7, July-2016 ISSN

VKES. Contents. Page 2 No 213, 13th Main RBI Layout JP Nagar 7th Phase, Bangalore Vidyuth Kanti Engineering Services

Open Access AC Contactor Electromagnetic Mechanism Dynamic Simulation Study

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

I, THERMAL ANALYSIS OF BUS-BAR FOR SWITCH BOARD

Dynamic Simulation on a Broken Test of Conductors

INSTITUTE OF AERONAUTICAL ENGINERING DUNDIGAL ELECTRICAL AND ELECTRONICS ENGINEERING

Power System Engineering Prof. Debrapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur

ELECTRO MAGNETIC FIELDS

Different Techniques for Calculating Apparent and Incremental Inductances using Finite Element Method

CHAPTER 8 CONSERVATION LAWS

Numerical Analyze of Corona Discharge on HVDC Transmission Lines

Renewable Energy Systems

Computation of Electromagnetic Energy Absorption in the Human Body Tissues by High Frequency Structure Simulator

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING

Full-Maxwell Simulations of Very Fast Transients in GIS: case study to compare 3D and 2D-axisymmetric models of 1100 kv test set-up

Research of High Voltage Intelligent Capacitor

Capacitors and Capacitance

Philippe Wendling

Measurement and simulation of the electric field of high voltage suspension insulators

Mitigation and Analysis of Very Fast Transient over Voltages (VFTOs) in 765/245kV Gas Insulated Substation (GIS) by Wavelet Transforms

Copyright 2014 IEEE. Paper presented at 2014 IEEE conference on electrical insulation and dielectric phenomena, Des Moines, USA, October, 2014.

Analytical Solution of Magnetic Field in Permanent-Magnet Eddy-Current Couplings by Considering the Effects of Slots and Iron-Core Protrusions

Transcription:

2017 International Conference on Computer Science and Application Engineering (CSAE 2017) ISBN: 978-1-60595-505-6 Numerical Calculation and Analysis on the Surface Electric Field Characteristics of Hot-Line Robot Liqiang Zhong 1, Liang Wu 2* and Hongyu Xiang 1 1 Electric Power Research Institute of Guangdong Power Grid Corporation, 510080 Guangzhou, China 2 School of Electrical Engineering, Wuhan University, 430072 Wuhan, China ABSTRACT Hot-Line robot (HLR) is an automatic transmission line inspection device developed in recent years. The mounting device should be contacted with the high voltage transmission line thus to realize the voltage transfer at the first operation stage of the HLR, and the HLR device which is regarded as a floating electrode might be damaged by discharge induced by the filed distortion during the voltage transfer process. The surface electric field of HLR device is optimized to improve its operation reliability, and a static-electric field finite element model of the transmission line which includes the HLR device is developed in this paper, and the dynamic surface electric filed characteristics of HLR during elevating operation process are studied by the finite elements model. Results show that influenced by the electric field which induced by high-voltage transmission line, the induced electric field can be generated on the surface of HLR during the process of elevating operation. The induced electric field distorts on the edge chamfer of HLR device which is regarded as a floating electrode. The maximum field strength position is influenced by the arrangement of the overhead wire conductor, and the edge chamfers are the key points of the electric field optimization of the HLR. The results of this study could provide theoretical basis and technical support for the optimization of HLR insulation characteristics, which is of great value to improve its operation reliability. INTRODUCTION Hot-Line robot (HLR) is an automatic transmission line inspection device developed in recent years, which can insure the safety of hot-line work, reduce the workload of manual hot-line work, decrease the operator's labor intensity, reduce the danger caused by strong electric field and improve the level of line operation and maintenance[1-2]. Influenced by the electric field around the high-voltage transmission lines, there will be an electric potential rise on HLR s surface in the process of its upper and lower lines: when approaching the transmission line, a sharp change in the electric field strength may cause damage to the HLR as well as the control circuit of the elevating device [3-4]. Therefore, it is necessary to calculate and optimize the surface of the HLR at the product design stage to ensure the operational safety and reliability of the equipment under high voltage environment. At present, the design research of HLR at home and abroad mainly focus on two aspects: structural function design and environmental adaptability design[8-14]. There 293

is little research on the safety of the initial phase (mount phase) of the HLR operation. In the process of close to the high voltage transmission line, the HLR forms a suspended electric potential by the impact of alternating electric field, the electric potential increases on surface will affect the operational reliability of the device body. There are a lot of researches on the distribution of power frequency electric field near AC overhead transmission lines. The main methods include charging simulation method, finite element method and boundary element method[5-7]. The research mainly focused on how the transmission line influence the building and the human body, but the research about the influence of the transmission line on the HLR is litter, which limits the improvement of the HLR insulation design technology. Based on the finite element theory of electrostatic field, this paper establishes the numerical model of electrostatic field of transmission line (including HLR), and based on this model, the electric potential distribution and field strength characteristics of the HLR surface under different transmission line voltage level are analyzed, and then the HLR surface insulation optimization method is put forward, the research results for the HLR insulation design can provide a theoretical basis. MATHEMATICAL MODEL OF ELECTROSTATIC FIELD FOR HIGH VOLTAGE TRANSMISSION LINE In order to obtain the of the HLR and analyze the safety of the HLR under different operating conditions, the electric field numerical modeling of the overhead line containing the HLR should be carried out first. Under normal operating condition, the electric field around the overhead line changes with time, since the change frequency of the electric field under 50Hz current is low, so that it can be considered that the around the overhead line subject to the law of electrostatic field. Therefore, finite element numerical model of the electric field around the transmission line is established by using the theory of electrostatic field. HLR Physical Model HLR is mainly composed of the robot body and the live operation compositions. Fully enclosed metal shell is used on the main electronic components of the body to achieve electromagnetic shielding; the body goes upper and lower line by using the live operation of the robot lifting mechanism. Since the automatic mounting part is made of insulating material, the HLR in the upper/lower line operation can be regarded as a floating electric potential in the electric field of the high voltage transmission line. Therefore, the finite element method (FEM) is used to calculate the electric field distribution on the surface of the equipment. A finite element model of electrostatic field with a target about 126kV voltage HLR is established, its physical structure is shown in Figure 1, the robot body shell material is the aluminum alloy 6063-T6, shell size is 100cm (L) * 100cm (H) * 60cm (W); Automatic loading device material is the polyethylene, the arm length (D) is 0.3 m, in the process of establishing a numerical calculation model, the geometrical characteristics of the automatic mounting part of the device are ignored for the simplified calculation. 294

High voltage wire A Section A-A 1 Walking parts D Mounting device H Robot body L A 1 W Figure 1. Physics model and equivalent of hot line robot. Mathematical Model of Electrostatic Field The Maxwell equations in the electrostatic field can be expressed as: E 0 (1) D (2) Where ρ is the charge density, for linear media, the relationship between the electric flux density D and the electric field intensity E can be expressed as: D E (3) Where E is the electric field strength, D is the electrical density, ε is the material dielectric constant. As the electrostatic field is free of rotation field, the scalar potential φ is introduced as the auxiliary quantity to simplify the calculation. The relationship between the electric field intensity and the scalar potential is as follows: E (4) The scalar potential is substituted into the electrostatic field control equation, and the Poisson equation in the electrostatic field problem is obtained as: Boundary Conditions (5) 2 For the overhead transmission lines containing HLR, the boundary conditions of the surrounding electrostatic field distribution should be: As for the three-phase high-voltage conductor of the transmission line, the boundary of the calculation domain obeys to the Dirichlet boundary: g( ) (6) Where Γ is the conductor and shell surface boundary, g (Γ) is the voltage function, which can be constant and zero. When it is zero, it indicates that it is grounded. The boundary conditions on the interface between the surface soil and the air medium are the tangential and normal boundary conditions of the interfacial field of different media, called natural boundary conditions. The natural boundary conditions for the electric 295

field strength and the electrical density of the medium 1 and the medium 2 interface in the electrostatic field are Et1 Et2 (7) Dn1 Dn 2 s Where Et1 and Et2 are the tangential components of the electric field intensity on both sides of the interface, Dn1 and Dn2 are the normal components of the electrical density on both sides of the interface, and ρs is the free surface charge density at the interface of the medium. For the HLR surface, apply the floating potential boundary condition: ds Q (8) s n Where n is the outer normal vector of the surface S of the HLR, Q is the surface charge of the suspended conductor, and Q = 0. ELECTROSTATIC FIELD NUMERICAL MODEL OF HLR SURFACE The physical model of the overhead line for the finite element numerical calculation of the electrostatic field is shown in Figure 2, The solution domain of the electrostatic field is composed of three-phase conductor, live working robot, soil, and air medium. The conductor is made of steel core aluminum hinge line LGJ-150/20. The overhead line s height from ground is referenced to the typical 110kV overhead transmission line standard (ZM-18-type straight pole tower, tower spacing between 100m, 18 meters above the ground level, sag 1.02m), the three-phase conductor spacing is 3.5m. The lowest point (sag maximum) from the ground on the overhead line is regarded as the calculation of cross-section for two-dimensional electrostatic field modeling, and the geometrical characteristics of the HLR s internal components are ignored. Calculate domain boundaries W1 W2 A B C D1 Mounting device Air Ground surface Soil Figure 2. Static electric field solution region of overhead line. Based on the electrostatic field finite element model of the transmission line established in this paper, of the surface of HLR under different operating conditions is calculated by the Ansoft. Firstly, the CAD software is used to build the solid model of overhead line and the HLR, and then import the physical model 296

and set the physical parameters of the model (the relative dielectric constant of the air region is 1, the conductivity is 2 10-14S / m, the relative permittivity of the soil is 10, the conductivity is set to 1 10-4S / m) through the Ansoft geometric interface. The HLR is set as a floating electrode during the calculation, the three-phase wires are respectively applied with a potential load, simultaneously applying infinite boundaries at the boundary of the solution domain. Finally, set the grid parameters and solver parameters of the model. In order to ensure the accuracy of the calculation, set the local grid control area near the surface of the HLR, near the tip the mesh size was set to 1/5 of its minimum characteristic curvature size, and the total energy tolerance is set to 1e-3. DISTRIBUTION OF ELECTRIC FIELD ON HLR SURFACE UNDER DIFFERENT OPERATING CONDITIONS The HLR rises from the ground to get to the high voltage conductors in the process of operation, when the distance between the HLR and the high voltage conductor reduced to a certain value (0.3 m), the robot arm is extended to contact with the high voltage line. The finite model of the transmission field is used to calculate the HLR s surface under different operating conditions. In order to maximize the influence of the overhead line electric field on the electric field distribution of the HLR s surface, the voltage of the corresponding phase conductor of the live operation robot is set to the maximum value. Surface Electric Field Distribution of the HLR on A - phase Conductor Operation Under A-phase conductor operating condition (A phase voltage 89.8kV, B phase voltage -44.9kV, C phase voltage -44.9kV), when the live robot is 0.3m from the overhead line, the electric field intensity near the overhead line and the surface of HLR is shown in Figure 3. Results show that the electric field around the overhead line is affected by the A-phase conductor voltage and is not evenly distributed; A-phase conductor and its vicinity electric field intensity is the largest. By the influence of the electric field of the overhead line conductor, an induced electric field is established on the surface of the HLR, and there is an electric field concentration at the edge chamfer. So the edge chamfer is the key point of the electric field optimization of the HLR; Since there is a certain distance from the line to the HLR, the maximum field strength of the HLR(4.64e5V / m) is smaller than the that of the conductor surface(1.35e6 V / m). 1.34e6 3.08e5 1.02e5 3.38e4 1.12e4 3.70e3 1.23e3 4.61e2 1.34e2 4.60e5 6.75e4 1.60e4 3.80e3 9.01e2 2.14e2 5.07e1 1.20e1 2.85e0 Wire (a)transmission line (b)hlr surface Figure 3. Surface field distributions of HLR under A-phase working. 297

Under A-phase conductor operating condition, the relationship between the maximum electric field strength on the surface of the HLR and the distance from the overhead line to the HLR as shown in Figure 4. Results show that with the increase of the distance, the electric field intensity of the device surface gradually decreases. When the distance increases from 0.3m to 1.8m, the maximum electric field strength decreases from 4.64e5V / m to 2.67e5V / m, for different voltage levels of the line, HLR should be located at a specific location from the overhead line to start the mechanical mount device to ensure that the surface of the electric field strength does not exceed the maximum allowable value. Electric field strength(v/m) distance(m) Figure 4. Relationship between maximum surface field strength of HLR and line distance under A-phase working condition. Surface Electric Field Distribution of the HLR on B - phase Conductor Operation Under B-phase conductor operating condition (A phase voltage -44.9kV, B phase voltage 89.8kV, C phase voltage -44.9Kv), when the live robot is 0.3m from the overhead line, the surface field strength near the overhead line and the HLR is shown in Figure 5. Results show that the electric field around the overhead line is affected by the B-phase conductor voltage and is not evenly distributed, the intensity of the electric field in the B-phase conductor and its vicinity is the largest; By the influence of the electric field of the overhead line conductor, an induced electric field is formed on the surface of the HLR, and there is an electric field concentration at the edge chamfer. The maximum electric field strength is lower than that under the A-phase conductor operating condition. So the edge chamfer is the key part of the electric field optimization of the HLR. Since there is a certain distance from the line to the HLR, the maximum field strength of the HLR (4.11e5V/m) is smaller than the field strength of the conductor surface (1.69e6 V / m). 1.69e6 3.87e5 1.28e5 4.25e4 1.41e4 4.66e3 1.54e3 5.11e2 1.69e2 (a)transmission line 4.11e5 9.42e4 3.12e4 1.03e4 3.42e3 1.13e3 3.75e2 1.24e2 4.11e1 Wire (b)hlr surface Figure 5. Surface field distributions of HLR under B-phase working condition. Under B-phase conductor operating conditions, the relationship between the maximum electric field strength on the surface of the HLR and the distance from the 298

overhead line to the HLR as shown in Figure 6. It can be seen from the figure that with the increase of the distance between the HLR and the overhead conductor, the electric field intensity of the device surface gradually decreases. When the distance between the HLR and the overhead line increases from 0.3m to 1.8m, the maximum electric field strength decreases from 4.11e5V / m to 1.27e5V / m. It can be seen from the calculation results, for different voltage levels of the line, HLR should be located at a specific location from the overhead line to start the mechanical mount device to ensure that the strength of the electric field does not exceed the maximum allowable value. Electric field strength(v/m) distance(m) Figure 6. Relationship between maximum surface field strength of HLR and line distance under B-phase working condition. Surface Electric Field Distribution of the HLR on C - phase Conductor Operation Under C-phase conductor operating condition (A phase voltage -44.9kV, B phase voltage -44.9kV, C phase voltage 89.8kV), when the live robot is 0.3m from the overhead line, the surface field strength near the overhead line and the HLR is shown in Figure 7. Results show that the electric field around the overhead line is affected by the C-phase conductor voltage and is not evenly distributed, the intensity of the electric field in the C-phase conductor and its vicinity is the largest. By the influence of the electric field of the overhead line conductor, an induced electric field is formed on the surface of the HLR, and there is an electric field concentration at the edge chamfer. So the edge chamfer is the key part of the electric field optimization of the HLR; Since there is a certain distance from the line to the HLR, the maximum field strength of the HLR(5.09e5V / m) is smaller than the field strength of the conductor surface(1.35e6 V/m). 1.35e6 3.09e5 1.02e5 3.39e4 1.12e4 3.71e3 1.23e3 4.07e2 1.35e2 (a)transmission line 5.09e5 1.24e5 4.30e4 1.49e4 5.18e3 1.80e3 6.24e2 2.16e2 7.51e1 Wire (b)hlr surface Figure 7. Surface field distributions of HLR under C phase working condition. 299

Under C-phase conductor operating conditions, the relationship between the maximum electric field strength on the surface of the HLR and the distance from the overhead line to the HLR as shown in Figure 8. It can be seen from the figure that with the increase of the distance between the HLR and the overhead conductor, the electric field intensity of the device surface gradually decreases. When the distance between the HLR and the overhead line increases from 0.3m to 1.8m, the maximum electric field strength decreases from 5.09e5V / m to 2.67e5V / m. It can be seen from the calculation results, for different voltage levels of the line, HLR should be located at a specific location from the overhead line to start the mechanical mount device to ensure that the surface of the electric field strength does not exceed the maximum allowable value. Electric field strength(v/m) distance(m) Figure 8. Relationship between maximum surface field strength of HLR and line distance under C phase working condition. CONCLUSIONS The finite element numerical model of the overhead line electric field is established and the s of the HLR under different operating conditions are calculated. On this basis, the distributions of electric field on the surface of HLR under different operating conditions are studied. The main conclusions are as follows: (1) The electric field around the overhead line is affected by the conductor voltage, the electric field strength of the overhead wire conductor and its vicinity is the highest; By the influence of the electric field of the overhead line conductor, the HLR can be regarded as a floating electric potential, an induced electric field is formed on its surface, and an electric field distortion occurs at the edge chamfer. The maximum field strength position is influenced by the arrangement of the overhead wire conductor, and the edge chamfers are the key points of the electric field optimization of the HLR. (2) As there is a certain distance from the line to the HLR, the maximum field strength of the HLR surface is smaller than the conductor surface field strength. And in the process of the HLR approaching the high voltage wire, the maximum electric field strength of the HLR gradually increase, the increase of the electric field is related to the arrangement of the overhead wire conductor. REFERENCES 1. Hui Qi, Bingqiang Li, and Zaixin Gu. 2003. Study on Insulation Protection Technology of High Voltage Live Working Robot, High Voltage Technology, 29(5): 19-20. 2. Shouyin Lu, Xiangdong Shi, and Jianjun Su. 2006. Insulation protection design of 10kV live operation robot, High Voltage Apparatus, 42(1): 8-10. 300

3. Takuma T., and Kawamoto T. 1997. Numerical calculation of electric fields with a floating conductor, IEEE Trans on Dielectrics and Electrical Insulation, 4 (2): 77-88. 4. K. Azumi, H. Kuwahara, and I. Sakon. etc. 1980. Design Considerations on Three Phase Enclosure Type Gas Insulated Substation, IEEE Transactions on Power Apparatus and Systems, PAS-99(3): 947-955. 5. Y. Mukaiyama, I. Takagi, and K. Izumi, etc. 1990. Investigation on Abnormal Phenomena of Contacts Using Disconnecting Switch and Detachable Bus in 300kV GIS, IEEE Trans on Power Delivery, 15(1): 189-195. 6. Zhiyang Xie. 2009. Fault Analysis on Deficiency Depth Insert of GIS Bus Conductor, High Voltage Apparatus, 45(3):160-163. 7. Okabe. 2007. Insulation Properties and Degradation Mechanism of Insulating Spacers in Gas Insulated Switchgear (GIS) for Repeated/Long Voltage Application, IEEE Trans on Dielectrics and Electrical Insulation, 14 (2): 101-110. 8. Jianyuan Xu, Chunwei Ren, and BingE Si, etc. 2008. Three Dimensional Electric Field Analysis of 40.5 kv SF6 Cubicle Gas-insulated Metal-enclosed Switchgear, Proceedings of The Chinese Society for Electrical, 28(15):136-140. 9. Zhiniu Xu, Fangcheng Lv, and Heming Li, etc. 2011. Influencing Factors of Insulator Electric Field Analysis by Finite Element Method and Its Optimization, Proceedings of The Chinese Society for Electrical, 37(4):944-951. 10. Jianyuan Xu, Lu Lu, and Xin Lin. 2008. Numerical Analysis of Electric Field of 1100 kv Disconnector in GIS, High Voltage Engineering, 34(10): 2102-2106. 11. Jianyuan Xu, Feng Wang, and Rongtao He, etc. 1999. The Research on the Electric Field Characteristics and the Insulation Breakdown Property of the Disconnector Switchgear Inside of Three Phase in One Tank Type 110kv GIS, Proceedings of The Chinese Society for Electrical, 19(9):31-35. 12. Jianyuan Xu, Feng Wang, and Fengliang Xiao. 2000. Three Dimensional Electric Field Calculation of the Disk Type Insulator inside of Three Phase in one Tank Type of GIS, High Voltage Technology, 26(01): 11-13. 13. Jianyuan Xu, Feng Wang, and Fengliang Xiao. 2000. Three-dimensional Electric Field Calculation and Insulation Analysis of Current Transformer in Three-Phase Box Type GIS, High Voltage Apparatus, 2000(01): 11-15. 14. Wenhui Chen, Zhong Li, and Zhanrong Jin, etc. 2006. Static Electric Field Analyses of GIS Including Fixed Particle Based on Finite Element, Power System Technology, 32(1):16-17. 301