Passivity Preserving Model Order Reduction For the SMIB

Similar documents
The Important State Coordinates of a Nonlinear System

Balancing of Lossless and Passive Systems

CHAPTER 2 DYNAMIC STABILITY MODEL OF THE POWER SYSTEM

ECE 585 Power System Stability

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability

When Gradient Systems and Hamiltonian Systems Meet

Dynamics of the synchronous machine

Transient stability analysis and control of power systems with considering flux decay by energy function approach

arxiv: v1 [cs.sy] 24 Mar 2016

SCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS. Transient Stability LECTURE NOTES SPRING SEMESTER, 2008

Stabilization and Passivity-Based Control

From now, we ignore the superbar - with variables in per unit. ψ ψ. l ad ad ad ψ. ψ ψ ψ

Model reduction for linear systems by balancing

Self-Tuning Control for Synchronous Machine Stabilization

Simultaneous IDA-Passivity-based control of a Wound Rotor Synchronous Motor

Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines)

The synchronous machine (detailed model)

A STUDY OF THE EIGENVALUE ANALYSIS CAPABILITIES OF POWER SYSTEM DYNAMICS SIMULATION SOFTWARE

SPEED-GRADIENT-BASED CONTROL OF POWER NETWORK: CASE STUDY

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)

Robust Hamiltonian passive control for higher relative degree outputs Carles Batlle, Arnau Dòria-Cerezo, Enric Fossas

An introduction to Birkhoff normal form

CURENT Course Power System Coherency and Model Reduction

Parameter Sensitivity Analysis of an Industrial Synchronous Generator

Mathematical Model of a Synchronous Machine under Complicated Fault Conditions

The Effects of Machine Components on Bifurcation and Chaos as Applied to Multimachine System

Analysis and Control of Multi-Robot Systems. Elements of Port-Hamiltonian Modeling

Weighted balanced realization and model reduction for nonlinear systems

Interconnection and Damping Assignment Approach for Reliable PM Synchronous Motor Control

Balanced realization and model order reduction for nonlinear systems based on singular value analysis

SUPPLEMENTARY INFORMATION

Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS

Part A: From (14.19) in your text (see notes Stability1 ), we have

3 Gramians and Balanced Realizations

Passivity Indices for Symmetrically Interconnected Distributed Systems

Analysis of Bifurcations in a Power System Model with Excitation Limits

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines

Stabilization of a 3D Rigid Pendulum

SIMULTANEOUS INTERCONNECTION AND DAMPING ASSIGNMENT PASSIVITY BASED CONTROL: TWO PRACTICAL EXAMPLES 1

Design of PSS and SVC Controller Using PSO Algorithm to Enhancing Power System Stability

Transient stability improvement through excitation control

Review: control, feedback, etc. Today s topic: state-space models of systems; linearization

Power system modelling under the phasor approximation

Stability of Feedback Solutions for Infinite Horizon Noncooperative Differential Games

Understanding the Inductances

Decomposition of Linear Port-Hamiltonian Systems

CHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS

MCE693/793: Analysis and Control of Nonlinear Systems

1 Unified Power Flow Controller (UPFC)

Applied Math Qualifying Exam 11 October Instructions: Work 2 out of 3 problems in each of the 3 parts for a total of 6 problems.

Converse Lyapunov theorem and Input-to-State Stability

Parameter Estimation of Three Phase Squirrel Cage Induction Motor

GEOPLEX: Back-to-back converter for an electrical machine application. C. Batlle, A. Dòria, E. Fossas, C. Gaviria, R. Griñó

Published in: Proceedings of the 2nd IFAC Workshop on Lagrangian and Hamiltonian Methods for Nonlinear Control

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

A new passivity property of linear RLC circuits with application to Power Shaping Stabilization

INDUCTION MOTOR MODEL AND PARAMETERS

Simulations and Control of Direct Driven Permanent Magnet Synchronous Generator

L 2 -induced Gains of Switched Systems and Classes of Switching Signals

Design and Application of Fuzzy PSS for Power Systems Subject to Random Abrupt Variations of the Load

A Chaotic Phenomenon in the Power Swing Equation Umesh G. Vaidya R. N. Banavar y N. M. Singh March 22, 2000 Abstract Existence of chaotic dynamics in

Transient Stability Analysis of Single Machine Infinite Bus System by Numerical Methods

θ α W Description of aero.m

Structure preserving model reduction of network systems

A Power System Dynamic Simulation Program Using MATLAB/ Simulink

Decay rates for partially dissipative hyperbolic systems

The Geometry Underlying Port-Hamiltonian Systems

Use of the finite element method for parameter estimation of the circuit model of a high power synchronous generator

TTK4150 Nonlinear Control Systems Solution 6 Part 2

Lecture 9: Space-Vector Models

Steady State Modeling of Doubly Fed Induction Generator

A Novel Adaptive Estimation of Stator and Rotor Resistance for Induction Motor Drives

Towards Power-Based Control Strategies for a Class of Nonlinear Mechanical Systems Rinaldis, Alessandro de; Scherpen, Jacquelien M.A.

(Refer Slide Time: 00:55) Friends, today we shall continue to study about the modelling of synchronous machine. (Refer Slide Time: 01:09)

Representation of a general composition of Dirac structures

Differential Equations 2280 Sample Midterm Exam 3 with Solutions Exam Date: 24 April 2015 at 12:50pm

Model Reduction for Unstable Systems

Dynamical Systems & Lyapunov Stability

The synchronous machine (SM) in the power system (2) (Where does the electricity come from)?

Mathematics for Control Theory

Power based control of physical systems: two case studies

Generalized Theory of Electrical Machines- A Review

Balanced Truncation 1

Module 3 : Sequence Components and Fault Analysis

Power System Transient Stability Analysis Using Sum Of Squares Programming

H 2 optimal model reduction - Wilson s conditions for the cross-gramian

1. Find the solution of the following uncontrolled linear system. 2 α 1 1

Stability Analysis Through the Direct Method of Lyapunov in the Oscillation of a Synchronous Machine

Examples of Applications of Potential Functions in Problem Solving (Web Appendix to the Paper)

Feedback Linearization Lectures delivered at IIT-Kanpur, TEQIP program, September 2016.

Unified Power Flow Controller (UPFC) Based Damping Controllers for Damping Low Frequency Oscillations in a Power System

BALANCING AS A MOMENT MATCHING PROBLEM

Numerical Algorithms as Dynamical Systems

Aldi Mucka Tonin Dodani Marjela Qemali Rajmonda Bualoti Polytechnic University of Tirana, Faculty of Electric Engineering, Republic of Albania

Chapter 4. Synchronous Generators. Basic Topology

Power System Stability GENERATOR CONTROL AND PROTECTION

Physics 202 Laboratory 5. Linear Algebra 1. Laboratory 5. Physics 202 Laboratory

HAMILTONIAN FORMULATION OF PLANAR BEAMS. Goran Golo,,1 Arjan van der Schaft,1 Stefano Stramigioli,1

Linear Quadratic Zero-Sum Two-Person Differential Games

Port-Hamiltonian systems: network modeling and control of nonlinear physical systems

Transcription:

Proceedings of the 47th IEEE Conference on Decision and Control Cancun, Mexico, Dec. 9-11, 28 Passivity Preserving Model Order Reduction For the SMIB Tudor C. Ionescu Industrial Technology and Management Fac. Math. & Natural Sciences University of Groningen Nijenborgh 4, 9747 AG Groningen t.c.ionescu@rug.nl Jacquelien M. A. Scherpen Industrial Technology and Management Fac. Math. & Natural Sciences University of Groningen Nijenborgh 4, 9747 AG Groningen j.m.a.scherpen@rug.nl Abstract We apply (linear) positive real balancing to the model of a single machine connected to an infinite bus. For that we compute the available storage and the required supply using Taylor approximation and define axis positive real singular value functions. Furthermore, we apply linear positive real balancing to the nonlinear model and analyze the results. I. INTRODUCTION One of the main issues in the power systems stability/dissipativity analysis and control is the complexity of the models, see e.g. [6]. A power system consists of interconnected machines. The model of the synchronous machine consists of eight states, seven fluxes and the angular momentum and its corresponding angle, which satisfy eight nonlinear equations, see e.g [9]. The machine is usually connected through a transmission line, to a network which can be represented as an infinite bus. Such power system is called the single machine infinite bus system, as in [1], [7]. This configuration is used in transient stability studies, see [4]. However, this nonlinear model is still complicated to use as it is and model reduction is called for, [4]. In the power systems community there are two ways to simplify the SMIB, based on the physical interpretation of the behaviours of the elements that are parts of the systems, see e.g.[1], [7]. Thus, two types of models are obtained, the Flux Decay Model [4], [7] and another one based on integral manifold concepts and singular perturbation analysis [4] and references therein. However these models lack passivity. We propose another way of reducing the SMIB, based on positive real balancing for nonlinear passive systems. We compute the positive real singular value functions of the system and split the states into less and more dissipative ones. Then we project onto the space of the more/less dissipative singular values. In this paper, we calculate a nonlinear approximation of the available storage and the required supply, and then continue with the linear positive real balancing method. The method is used for determining a linear projection on a reduced order subspace, resulting in a passive reduced order system. In Section 2 we present the model of the SMIB and choose the outputs such that the system is strictly passive. In Section 3 we give a brief overview of the reduction techniques used in the power systems community to obtain the so called, Flux-Decay Model. In Section 4 we give a way to compute the passivity energy functions and define the axis positive real singular values. We also find the linear projections and obtain a reduced order model based on these linear projections. In Section 5 we give a numerical example. In the end we state some conclusions and open problems. II. MODEL OF THE MACHINE CONNECTED TO THE INFINITE BUS We present the model of a single machine connected to an infinite bus, e.g. [7], [1]: Fig. 1. A single machine connected to an infinite bus through a transmission line The machine under consideration has one field winding, three stator windings, two q-axis amortisseur circuits and one d-axis amortisseur circuit, all magnetically coupled consisting of electrical and mechanical equations. The electrical equations are as follows Stator voltage equations: Ψ d = ωψ q + R a i d + e d Ψ q = ωψ d + R a i q + e q, where Ψ d, e d, i d represent the stator flux, voltage and current in the d - axis; Ψ q, e q, i q are the stator flux, voltage, current in the q - axis and R a is the stator resistance. Rotor field voltage equation: (1) Ψ fd = R fd i fd + e fd, (2) where Ψ fd, i fd, e fd represent the rotor flux due to the field circuit, field current and voltage and R fd is the field circuit resistance. Amortisseurs rotor voltage equations Ψ r = R r i r, r {1d,1q,2q}, (3) with Ψ i, i i, i {1d,1q,2d} the rotor fluxes due to the amortisseurs and amortisseur currents and R i,i {1d,1q,2d} as the amortisseurs resistances. The mechanical (swing) equations are: 978-1-4244-3124-3/8/$25. 28 IEEE 4879

j ω = K d ω + T m (Ψ d i q Ψ q i d ) δ = ω. ω represents the angular velocity, δ is the rotor angle, T m is the mechanical input power, K D the damping constant and j the inertia of the rotor. The network equations are obtained by applying Kirchhoff s voltage law in the figure 1 and using Park s transformation (see [1]), we have: di d e d = R E i d X E ωi q + E b sinδ + X E dt (5) di q e q = R E i q + X E ωi d + E b cos δ + X E dt. R E,X E are transmission line resistance and reactance and E b is the infinite bus voltage. Substituting the network equations (5) in the stator voltage equations and denoting by Ψ ds = Ψ d + X E i d and Ψ qs = Ψ q + X E i q, we can write the full model as: Ψ ds = ωψ q + (R a + R e )i d ωx e i q + E b sinδ Ψ qs = ωψ d + (R a + R e )i q + ωx e i d + E b cos δ Ψ fd = R fd i fd + e fd (6) Ψ r = R r i r, r {1d,1q,2q} j ω = K d ω + T m (Ψ d i q Ψ q i d ) δ = ω. The relation between fluxes and current is given as: Ψ = Li, where L = L ds L ad L ad L qs L aq L aq L ad L f1d L ad L f1d L 11d L aq L 11q L aq L aq L aq L 22q Ψ = [Ψ ds Ψ qs Ψ fd Ψ 1d Ψ 1q Ψ 2q ] T, i = [ i d i q i fd i 1d i 1q i 2q ] T, >, with L ds = L ad +L l +X e and L qs = L aq +L l +X e. Below we give the definitions of the inductances: L l leakage inductance L ai, i {d,q} mutual inductance in the d,q axis L iiq self inductance of rotor circuits in q axis, i {1,2} L kkd self inductance of rotor circuits in d axis, k {2,f} The total energy of the system is: H(i,ω) = H(Ψ,p) = 1 2 ΨT i + 1 2 jω2 = 1 2 ΨT L 1 Ψ + 1 p 2 2 j = 1 [ ] i 2 [ΨT p] = 1 [ ] ω 2 [ΨT p]d 1 Ψ, H() =, p (8) where D = diag{l,j} and p = jω is the angular momentum. Then without the dynamics of δ, system (6) can be rewritten as: (4) (7) with [ Ψ ṗ ] J(Ψ,p) = = (J(Ψ,p) R) T H(Ψ,p) skew symmetric, δ = ω = 1 j p, + M(δ)u (9) ωx E Ψ q ωx E Ψ d Ψ q Ψ d R = diag{r a +R E,R a +R E,R fd,r 1d,R 1q,R 2q,K d } >, M T (δ) = sinδ cos δ... 1...... 1, u = E b e fd T m H(Ψ,p) = [Ψ T p]d 1. We treat δ separately, as a parameter, since it appears only in the input vectorfield and it is in the non-minimal subspace. Making this assumption, the system with the states Ψ,p is minimal and positive real balanced truncation can be applied. Having the total energy defined as in (8) and using equations described in (6) we have: Ḣ(Ψ,p) = Ḣ(i,ω) = (R a + R E )(i 2 d + i 2 q) R fd i 2 fd i T r R r i r K d ω 2 }{{} dissipated power E b (i d sinδ + i q cos δ) + e fd i fd + ωt m. }{{} power supplied at terminals Choosing y = M T (δ)d 1 [ Ψ p then, ] + u = M T (δ) H(Ψ,p) + u (1) Ḣ(Ψ,p) y T u = H(Ψ,p) H(Ψ,p) R T u T u <, (11) which means that the system formed by (9), (1) with the parameter δ, is strictly passive as in e.g. [9], [11]. The feedthrough term is taken for computational reasons. It renders the problem of finding the available storage and required supply functions corresponding to the system into a nonsingular optimal control problem with the solution given by a Hamilton-Jacobi equation as it will be seen in Section IV. Remark 1. Linearizing the model (9) around an equilibrium point x = [Ψ p ], we get a system with the following realization: (A,M(δ),M(δ) T D 1,I 3 ), which is minimal and asymptotically stable. 488

III. EXISTING MODEL ORDER REDUCTION SCHEMES FOR THE SMIB Here we review how conventional reduction is performed on (6) within the power systems community in order to obtain a model suitable for simulation and/or control as in [4], [5], [7] and references therein. First, the dynamics of the dq fluxes, in (6), are considered small compared to the ωψ d,q terms, so Ψ d =, Ψq = are taken. An assumption is also made upon the transmission line which is considered to run in steady state, rendering Ψ ds = and Ψ qs =. Then, the dq equations become: Ψ q = (R a + R e )i d + X E i q E b sin(δ) (12) Ψ d = (R a + R e )i q + X E i d + E b cos(δ), where ω[pu] = 1 is assumed since the changes of the angular velocity are considered small and to have less significant effect on the voltages. In the power systems community this is a typical assumption used in the models for transient stability analysis and it is explained in [7] that in this way the effect of neglecting Ψ d and Ψ q is counterbalanced. The second assumption is that the effect of the damper windings on the transient under study are negligible, so set i 1d = i 1q = i 2q = which leads to: Ψ q = L q i q Ψ d = L di d + L ad (13) Ψ fd Substituting (12) and (13) in the electrical equations of the system it is obtained that: i d = 1 [(R a + R E )E b sinδ L ad (X E + L q )Ψ fd + (X E + L q )E b cos δ] (14) with L q = L aq + L l, L d = L ad + L l, L d = L d L2 ad, [ = (XE + L q )(X E L d ) + (R a + R E ) 2]. Also it can be written i fd = 1 (Ψ fd + L ad i d ). A third, typical, assumption is: R a + R E =. Substituting (14) in (13) the model can be written as: δ = ω j ω = T m T e K D ω T dė q = (L d L d ) (L d + X E) E b cos δ (L d + X E ) (L d + X E) E q + E fd, (15) 1 where T e = L d +X E be E q sinδ (L q L d )E2 b (X E +L d )(L q+x E ) sinδ cos δ] and E L q = ad Ψ fd, E fd = L ad R fd e fd and T d = R fd. The equations described in (15) are known as the Flux-Decay Model. This model can be rewritten in a compact form [4]: ẋ 1 = x 2 ẋ 2 = b 1 sinx 1 + b 2 sinx 1 cos x 1 Dx 2 + P (16) ẋ 3 = b 3 cos x 1 b 4 x 3 + E + u, with x 1 = δ, x 2 = ω, x 3 = E q, u is an additional signal representing the control input and E b b 1 = j(l d + X E), b ω Eb 2 2 = (L q L d ) (L d + X E)(L q + X E ) b 3 = (L d L q)e b (T d )(L d + X E), b L d + X E 4 = (T d )(L d + X E), P = T m j, E = E fd T d, D = K D j. Remark 2. In [4] an alternative way to obtain the Flux Decay Model (15) is presented. The following assumptions are made: only one damping circuit in the q axis, i.e. the 1d and 2q equations from (6) are considered negligible; the damping circuit is expressed in terms of its proportional voltage E ds and there is no damping in the swing equation. Then the model is first reduced to 5 states and is given as in [4, Section 2.5, (2.19)-(2.24)]. Then assuming that R a + R E =, then Ψ ds = E b cos δ, Ψ qs = E b sinδ defines an integral manifold for the (2.19)-(2.24) system. Substituting, the remaining differential equations yield the so called Two-Axis model, of dimension four. Then doing a singular perturbation analysis on one of the states of the Two-Axis model, yields the Flux Decay Model. IV. ENERGY FUNCTIONS FOR THE SYSTEM In this section we calculate a nonlinear approximation of a pair of energy functions necessary for the positive real balancing procedure, namely, the available storage and the required supply, of the system (9), see e.g. [8] for more details. They are the total internal energy plus or minus the dissipated energy of the system. However it is difficult to quantify the dissipated energy, so there is need for a computation scheme. For the sequel, we make the following notations: x = [Ψ T, p] T, with Ψ defined in Section II, (7) and p = jω. We write f(x) = (J(x) R) T H(x), where x J(x), R and H(x) are defined in Section II, (9) and choose the output from relation (1). Definition 3. The available storage of a passive system with is given by: S a (x,u T y) = inf u,x()=x T u T ydt (17) The required supply of the system is: S r (x,u T y) = inf u T ydt (18) u,x()=x T Remark 4. If the passive system has dissipation and the total internal energy H, then S a = H dissipated energy and S r = H + dissipated energy. We will consider system (9) with δ as a parameter and we assume the equilibrium point x =,u =. Since the system is strictly passive, we have from (11) that for u = : H(x) >, H() = and Ḣ(x) <, and so by Lyapunov s second method, is an asymptotically stable equilibrium point of the system. Then, the model (9) with the above notations is liable for applying the results in [8]. 4881

Proposition 5. The strictly passive system (9) has the available storage S a (x) and the required supply S r (x) as the smooth stabilizing and antistabilizing, respectively, solutions of the Hamilton-Jacobi equation: S x f(x) + 1 ( ) S 2 x M(δ) xt D 1 M(δ) ) (19) (M T (δ) ST x M(δ)D 1 x = We compute the solutions of this PDE using an the approximation method of Lukes, based on Taylor expansion around the equilibrium point. We split the storage functions into a sum of a quadratic term plus higher order terms, making the following notations with respect to system (9): F 1 (x) = Ax + F (2) (x), S i (x) = 1 2 xt Kx + S (h) i (x), i {a,r} where h represent higher order terms. Substituting, equation (19) splits in two parts: an algebraic Riccati one for the quadratic part of S and a polynomial algebraic system for the higher order terms. For the quadratic part of the required supply the corresponding Riccati equation is: AK r + K r A T + (K r D 1 )M(δ)M T (δ)(k r D 1 ) = (2) For the quadratic part of the available storage, we solve the dual algebraic Riccati equation: A T K a +K a A+(K a D 1 I)M(δ)M T (δ)(d 1 K r I) =, (21) where the variables are as in Remark 1. The higher order terms satisfy the following equation for all h > 3 is: S i (x)f (h) 1 (x) = 1 2 S(h 1) i (x)(m 1 )S (h 1)T i (x) S (h 1) i (x)ax, (22) where i {r,a}, A = A + M(δ)M(δ) T (K D 1 ) and S i (x) = S i x. We can write S i(x) = x T K i + S (2) i + S (3)+... i = x T K i + S (h 1) i,i {r,a}. The higher order terms of the gradient S i (x) have the upper index h 1, since the elements of the vector are polynomials in x of order h 1. Then (22) is a system of polynomial equalities which is solved by finding the solution of a linear system of coefficients. For instance for h = 3, we can write S r (3) (x) = 8 i=1,j=i,k=j x i x j x k, which means that all the terms in S r (2) (x) have degree 2. The equation to be solved for h = 3 is: x T K r F (2) (x) = S (2) r (x)ax, (23) yielding a linear system of equations with c i,j,k as unknowns. Following the reasoning in [3] for general nonlinear systems, we define, for the strictly passive system (9) the axis positive real singular values as: such that ρ i (s) = S a (ξ i (s)) S r (ξ i (s)), x = ξ i(s) (24) S a (x) supρ 1 (s) = sup s x S r (x). This represents the maximum energy available at the ports with respect with to the effort energy put in through the same ports. We consider the system in S r normal S a diagonal form if there exists ξ i (s), i = 1,...,n such that: S r (ξ i (s)) = s2 2, S a(ξ i (s)) = s2 ρ i (s). (25) 2 These axis singular values and energy functions in this form are used for model reduction. Computing Φ(z) = x, s.t. Φ(,...,z i,...,) = ξ i (z i ), then, if ρ i (s) ρ i+1 (s) we have that ρ 2 i (z i) > ρ 2 i+1 (z i+1), meaning that the state components z 1 = [z 1,..., z i ] are less dissipative than the states z 2 = [z i+1,..., z n ]. Based on this ordering, we can retain for the reduced model either z 1 or z 2 setting z 2 = or z 1 = (projecting on z 1, or z 2 ), respectively, according to the use and accuracy of it. V. LINEAR TRANSFORMATIONS AND TRUNCATION In this section we continue with the linear part of the available storage and required supply approximated in the previous section, that is we use K r solution of (2) and K a, the solution of (21), respectively. We compute the linear positive real singular values of the strictly passive system (9): 1 π 1 > π 2 >... > π n >. Let q be such that π q π q+1. Then the reduced order state is the projection of the original state on the space spanned by the eigenvectors corresponding to the largest singular values, i.e the less dissipative, or to the smallest singular values,i.e the least dissipative. The result is a strictly passive reduced order system. We proceed as in [2]. Since K r and K a are positive definite, let K r = UU T, K a = LL T. Let Σ n = diag(π 1,π 2,...π n ) and the singular value decomposition U T L = ZΣ n Y T. Let W = LY q Σ 1 2 q, V = UZ q Σ 1 2 q, where Z q = Z(:,1 : q) and Y q = Y (:,1 : q). The product V W = Π defines a projector and W T V = I q. Then x = V z, where z has dimension q and is the reduced order model state and z = W T x. Substituting in (9) we obtain: V ż = f(v z) + Mu, y = M T D 1 V z. Premultiplying with W T we obtain a reduced passive nonlinear order model given by: ż = W T f(v z) + W T Mu ỹ = M T (δ)d 1 (26) V z 4882

VI. CASE STUDY Consider a system as in figure 1, described by the equations (9) with δ considered an external parameter. We have the following parameters for the machine, i.e. matrix D = diag{l,j}, Ψ = Li and the dissipation matrix R, taken from e.g. [7]: D =.22.1.1.219.9.9.1 1.825 1.66.1 1.66 1.8313.9.9.9.9.134 6, R = diag{.31,.31,.6,.284,.619,.23638,1} We consider, as an equilibrium point which is asymptotically stable as presented in Section IV. Linearizing around this equilibrium point we obtain a minimal asymptotically stable linear realization with δ as a parameter. Solving (2), (21) and (23) and we get: Computing x = V z we notice that x 7 = p =, meaning that the angular momentum does not have any influence in the reduced order model, since it is the most dissipative. The reduced order model has 3 states in this case and with the output ỹ 3 = that does not approximate y 3 = 1 j p, at all. Simulating this model for u = [E b e fd T m ] T = [1 1] T we obtain: 25 2 15 1 5 y 1 2 4 6 8 1 12 14 16 S r (x) = 1 2 xt K r x + S (3) r (x) =.15x 2 1 +.41x 2 7+.188x 2 6 +.289x 2 2.95x 1 x 2 x 7.36x 1 x 3 +.66x 1 x 4.14x 2 x 5.41x 2 x 6.31x 3 x 4 +.348x 5 x 6 +.276x 2 5 +.12x 2 4 +.655x 1 x 6 x 7 +.1x 4 x 5 x 7 +.183x 3 x 5 x 7.172x 2 x 4 x 7 +.767x 1 x 5 x 7 +.852x 2 x 3 x 7 +.81x 4 x 6 x 7 +.12x 3 x 6 x 7 (27).2.4.6.8 1 1.2 1.4 y 2 and S a (x) = 1 2 xt K a x + S (3) a (x) = 2.1x 2 1 + 61x 2 7 +.67x 2 6+.441x 2 3 +.466x 2 2 + 1.26x 2 4 + 1.38x 2 5 +.182x 1 x 3 1.6 1.8 2 1 2 3 4 5 6 2.56x 1 x 4.624x 2 x 5 +.486x 2 x 6.492x 3 x 4 1.2x 5 x 6.239x 1 x 2 x 7 2.53x 1 x 6 x 7 +.213x 4 x 5 x 7 +.249x 3 x 5 x 7.438x 1 x 5 x 7.312x 4 x 6 x 7.349x 3 x 6 x 7. (28) We continue with the quadratic part of the solutions and we compute the linear positive real singular values of the system: π 1 =.9715, π 2 =.9638, π 3 =.824, π 4 =.5386, π 5 =.2413, π 6 =.1946, π 7 =.693. It is noticed that starting with π 4 the decay rate of the singular values is higher, thus we can choose π 3 >> π 4. So π 1,π 2,π 3 correspond to the less dissipative components (currents). We are going to project onto the space of these singular values. The following projection matrices are built: W = V =.2419.2899 1.4972.9157.162.3254.667.5219.472.5326.6791.1646.4359.1949 1.649,.9652.1568.2445.2943.2477.2783.8922.129.713.629.3454.2.552.8135.689.59.419.3421.4932.6523.52 4883 The dashed line represents the reduced order model output ỹ that approximates y, represented by the continuous line. It is noted that due to very little dissipation present and the truncation of the mechanical swing equations, the second output ỹ 2 has a long transient component. The large unwanted error is also noticed. However, ỹ 1 is close to y 1 which depends on the least dissipative states. Alternatively, we explore the smaller singular values corresponding to the more dissipative states, that is π 6 =.1946 < π 5 and π 7 =.693 < π 6 and build the corresponding projections: W = 1.2 1.23.2577 1.3115.2688 1.617.482, V =.1712.1476.364.1942.328.2314 2.4495 Substituting, we get the following passive reduced order model with the parameter δ:

ż 1 =.76z 2 2 1z 1 +.48T m ż 2 =.175z 2 +.31z 1 z 2 sin(δ)e b + 1.23cos(δ)E b.258e fd ỹ 1 =.171sin(δ)z 2 +.149cos(δ)z 2 + E b ỹ 2 =.357z 2 + e fd ỹ 3 = 2.45z 1 + T m (29) For the simulation the input vector is taken u = [E b e fd T m ] T = [1 1] T and we let the parameter δ vary according to the equation δ = x 7 = 14.7z 1. 2 1 1 2 3 4 1 2 3 4 5 6.25.2.15.1.5.5.1 2 4 6 8 1 12 14 16 18 2 The continuous line represents the output y of the full model, the dashed line is the output ỹ of reduced model obtained in (29) and the dotted line represents (15). It is noticed that ỹ 3 of the reduced model captures the behaviour of y 3 = 1 j p, however there are certain error and oscillations in the transients as can be seen in the figure above. The linear term (damping) is dominant in the first equation of (29) and this is reflected in the output ỹ 3. The transient in ỹ 2 has large oscillations which are not desired, but it approximates quite well the output y 2, the field current. ỹ 1 is not a satisfactory approximation of y 1. Basically, the reduced order model obtained by truncating the less dissipative states retains the mechanical part as the most important dynamics of the system, the idea being similar to the one used in the models of the power systems community, different from the model obtained projecting on the less dissipative subspace, which y 2 y 3 consists only of electrical equations and where the mechanics has no influence on the field behaviour. Still, (15) performs better than (29) in the electrical equation. We conjecture that it will be the same case when the nonlinear singular value functions will be computed and the transformations will be nonlinear. This is future work, since the computations are quite involved. VII. CONCLUSIONS AND FUTURE WORK In this paper we present another way to reduce the SMIB. It is based on the positive real balancing, which is a passivity preserving model order reduction technique. The reduced model is the projection of the original model on either the less or the more dissipative positive real singular values. The latter yields a third order model containing the swing equation and an electrical equation too and the reduced order model is passive. However, the transformations used here are linear. This represents a starting point for the future work where a procedure to completely compute the nonlinear positive real axis singular value functions will be constructed and consequently the nonlinear projections will be performed, in order to obtain a fully nonlinear model order reduction procedure for the SMIB. ACKNOWLEDGMENT We thank NWO (Dutch Science Foundation) for supporting this research. We would also like to thank prof. Romeo Ortega (Laboratoire de Signaux et Systemes, Supelec, France), Wissam Dib (Laboratoire de Signaux et Systemes, Supelec, France) and Alvaro Giusto (Departamento de Control y Electronica Industrial, IIE, Uruguay) for presenting the problem in the power systems area, which led to the idea of this paper. Finally we would like to thank the NWO Van Gogh exchange project. REFERENCES [1] P. M. Anderson, A. A. Fouad, Power Systems Control and Stability, IEEE Press, New York, 1994. [2] A. C. Antoulas, Approximation of Large-Scale Dynamical Systems, SIAM (25). [3] K. Fujimoto, J. M. A. Scherpen, Nonlinear Input-Normal Realizations Based on the Differential Eigenstructure of Hankel Operators, IEEE Trans. On Aut. Control, vol. 5, 25, pp. 2-18. [4] M. Galaz, Nonlinear Control of Power Systems, PhD thesis, LSS, Supelec France, 23. [5] M. Galaz, R. Ortega, A. Bazanella, Transient stabilization of power systems via total energy shaping: A comparative simulation study with the classical scheme, Proc. of CLCA, December 22. [6] A. Giusto, R. Ortega, A. Stankovic, On Transient Stabilization of Power Systems: A Power-Shaping Solution for Structure-Preserving Models, Proc. of 45th IEEE CDC, 26, pp. 427-431. [7] P. Kundur, Power Systems Stability and Control, McGraw-Hill, 1994. [8] T. C. Ionescu, J. M. A. Scherpen Positive Real Balancing for Nonlinear Systems, SCEE Proceedings, 26. [9] R. Ortega, A. Stankovic, P. Stefanov, A passivation approach to power systems stabilization, IEEE Symp. on Nonlinear Control Sysyems, 1998. [1] E. Pai, Energy Function Analysis for Power Systems Stabilization, Kluwer Academic Publishers, Boston, 1989. [11] A. J. van der Schaft, L 2 -gain and Passivity Techniques in Nonlinear Control, Springer-Verlag, 2. 4884