OPCION 1 - ROCIADORES BULBO ALMACEN ACOPIO - REV A PAGE 1

Similar documents
Calculation of Pipe Friction Loss

Hydraulic Considerations for Citrus Microirrigation Systems 1

TOTAL HEAD, N.P.S.H. AND OTHER CALCULATION EXAMPLES Jacques Chaurette p. eng., June 2003

Guidelines for the Installation of SYGEF Pipes, Fittings and Valves

PIPING SYSTEMS. Pipe and Tubing Standards Sizes for pipes and tubes are standardized. Pipes are specified by a nominal diameter and a schedule number.

Purpose of Today s Presentation

Northern Lesson 2 Gear Pump Terminology. Gear Pump 101. Lesson 2: Gear Pump Terminology. When your reputation depends on it!

LECTURE 6- ENERGY LOSSES IN HYDRAULIC SYSTEMS SELF EVALUATION QUESTIONS AND ANSWERS

Sprinkler Irrigation

CVE 372 HYDROMECHANICS EXERCISE PROBLEMS

PumpTech Customer Education

Chapter 6. Hydraulic cylinders/rams (linear motors), and Lines/fittings. - Transforms the flow of a pressurized fluid into a push or pull of a rod.

Water Circuit Lab. The pressure drop along a straight pipe segment can be calculated using the following set of equations:

LECTURE 8. Hydraulic machines and systems II 2002 MIT PSDAM LAB

ERRATA TO THE 2000 INTERNATIONAL PLUMBING CODE. Fourth Printing, October 2002

Chapter Four Hydraulic Machines

WATER DISTRIBUTION NETWORKS

3301 East 120 th Avenue Assited Living & Memory Care

ME 309 Fluid Mechanics Fall 2010 Exam 2 1A. 1B.

Experiment (4): Flow measurement

Chapter 6. Losses due to Fluid Friction

Chapter Four fluid flow mass, energy, Bernoulli and momentum

Chapter Four Hydraulic Machines

Pumping Stations Design For Infrastructure Master Program Engineering Faculty-IUG

Analysis Methods for Water Distribution Systems-3 rd Class )طرق تحليل أنظمة توزيع المياه( Dr. Sataa A. Al-Bayati (10-11)

PUMP PERFORMANCE MEASUREMENTS Jacques Chaurette p. eng. April 2003

Fluid Properties: := 1.35 cp liquid viscosoty. m 3 density of the flowing liquid. sg:= specific gravity of the flowing liquid. Pipe System Conditions:

Hydraulics and hydrology

Fachgesprach 12. HVAC Pumps. For Project Managers

Pipe Flow. Lecture 17

Applied Fluid Mechanics

405 Compact Orifice Series and 1595 Conditioning Orifice Plate Flow Test Data Book and Flow Handbook

405 Compact Orifice Series and 1595 Conditioning Orifice Plate Flow Test Data Book and Flow Handbook

Eastlake Assited Living & Memory Care

Properties and Definitions Useful constants, properties, and conversions

TECHNICAL IRRIGATION INFORMATION

ME3560 Tentative Schedule Spring 2019

Backflow Prevention. Rule Update. Water Distribution Systems Workshop December 10, 2014

Flowmeter Discharge Coefficient Estimation

EXPERIMENT NO: F5. Losses in Piping Systems

ME3560 Tentative Schedule Fall 2018

P & I Design Limited. 2 Reed Street, Gladstone Industrial Estate, Thornaby, TS17 7AF. Tel: +44 (0) Fax: +44 (0)

Exam #2: Fluid Kinematics and Conservation Laws April 13, 2016, 7:00 p.m. 8:40 p.m. in CE 118

Pressure and Flow Characteristics

2.The lines that are tangent to the velocity vectors throughout the flow field are called steady flow lines. True or False A. True B.

THE HANDBOOK OF TECHNICAL IRRIGATION INFORMATION

Lesson 6 Review of fundamentals: Fluid flow

Basic Math Concepts for Water and Wastewater Operators. Daniel B. Stephens & Associates, Inc.

Modeling of Head Loss Components in Water Distribution to a Group of Buildings

Chapter (6) Energy Equation and Its Applications

Plant Design LECTURE 8: REBOILER CIRCUIT DESIGN. Daniel R. Lewin Department of Chemical Engineering Technion, Haifa, Israel

405 Compact Orifice Series and 1595 Conditioning Orifice Plate Flow Test Data Book and Flow Handbook

THE APPLICATION OF THERMODYNAMICS TO PUMP SYSTEMS

TECHNICAL INFORMATION

FE Fluids Review March 23, 2012 Steve Burian (Civil & Environmental Engineering)

LOSSES DUE TO PIPE FITTINGS

Fluid Flow Analysis Penn State Chemical Engineering

Mechanical Engineering Programme of Study

COURSE CODE : 3072 COURSE CATEGORY : B PERIODS/ WEEK : 5 PERIODS/ SEMESTER : 75 CREDIT : 5 TIME SCHEDULE

Big Hanaford Combined Cycle Plant. Calculation for Cooling Water System Transient Load Analysis. 6 November, 2001

Flow Switches. Liquid Flow Switches. McDonnell & Miller. Mounting Methods

An Expression for Obtaining Total Heads for Lift Pump Selection

Name: 10/21/2014. NE 161 Midterm. Multiple choice 1 to 10 are 2 pts each; then long problems 1 through 4 are 20 points each.

CIVE HYDRAULIC ENGINEERING PART I Pierre Julien Colorado State University

Review of pipe flow: Friction & Minor Losses

Reynolds, an engineering professor in early 1880 demonstrated two different types of flow through an experiment:

Fluid Mechanics II 3 credit hour. Fluid flow through pipes-minor losses

1.060 Engineering Mechanics II Spring Problem Set 4

EXPERIMENT No.1 FLOW MEASUREMENT BY ORIFICEMETER

SIZING 2 E DEFINITIONS AND UNITS OF MEASUREMENT 2.1 CALCULATION OF THE ACCUMULATOR 2.2

M E 320 Professor John M. Cimbala Lecture 24

Backflow Prevention Rule Update

Information and slides provided by RFD

INTERNAL FLOWS / FLOWS IN DUCTS

Frictional Losses in Straight Pipe

Fluid Statics, Hydrodynamics and Hydraulic Machines

The Expansibility Factor Equations in ISO and ISO : Do They Deliver What They Promise?

Viscous Flow in Ducts

Heating, Ventilating, Air Conditioning and Refrigerating, Sixth Edition, First Printing ERRATA

Piping Systems and Flow Analysis (Chapter 3)

V-Cone Flowmeter DATASHEET

STEADY FLOW THROUGH PIPES DARCY WEISBACH EQUATION FOR FLOW IN PIPES. HAZEN WILLIAM S FORMULA, LOSSES IN PIPELINES, HYDRAULIC GRADE LINES AND ENERGY

Sourabh V. Apte. 308 Rogers Hall

An overview of the Hydraulics of Water Distribution Networks

FLOW MEASUREMENT IN PIPES EXPERIMENT

Chapter 3 Bernoulli Equation

Lecture 4. Lab this week: Cartridge valves Flow divider Properties of Hydraulic Fluids. Lab 8 Sequencing circuit Lab 9 Flow divider

CIVE HYDRAULIC ENGINEERING PART II Pierre Julien Colorado State University

University of Minnesota St. Anthony Falls Hyd.rauJ.ic Laboratory. Project Report No. 174 MODEL STUDY OF TEE VAN LARE OVERFLOW DISTRIBUTION STRUCTURE

Tanjung Priok GFPPEP. Presentation and discussion, 22 October 2009 PT. PLN (Persero) Jasa Enjiniring Office Jl. KS Tubun I/2 Petamburan, Jakarta

LEAKLESS COOLING SYSTEM V.2 PRESSURE DROP CALCULATIONS AND ASSUMPTIONS

FLUID MECHANICS D203 SAE SOLUTIONS TUTORIAL 2 APPLICATIONS OF BERNOULLI SELF ASSESSMENT EXERCISE 1

Signature: (Note that unsigned exams will be given a score of zero.)

CEE 481 Midterm Exam 1b, Aut 2008

PVC - WHITE PRESSURE FITTINGS PRODUCTS PRICE LIST INCLUDES: PVC SCHEDULE 40, CLASS 125, POOL/SPA, LASCOTITE, ULTRAFIX REPAIR COUPLINGS PRICE GROUP

EGN 3353C Fluid Mechanics

n = Kinematic viscosity (cst) SG = specific gravity or 1 Poise = 100 cp 1 Stoke = 100 cst Q = capacity (m 3 /s) A = tube area (m 2 ) or

PUMP SYSTEM ANALYSIS AND SIZING. BY JACQUES CHAURETTE p. eng.

4 Mechanics of Fluids (I)

CEE 3310 Control Volume Analysis, Oct. 7, D Steady State Head Form of the Energy Equation P. P 2g + z h f + h p h s.

Transcription:

OPCION 1 - ROCIADORES BULBO ALMACEN ACOPIO - REV A PAGE 1 HYDRAULIC CALCULATIONS AT SPECIFIED DENSITY THE FOLLOWING SPRINKLERS ARE OPERATING IN: [ ] TEST AREA 1 [ ] TEST AREA 2 [ ] TEST AREA 3 [ ] REMOTE AREA Elevation of sprinklers = Elevation above water test. REF. PT. K ELEV. FLOW PRESSURE ft gpm psi 901 11.00 14.00 40.55 13.59 902 11.00 14.00 40.47 13.54 903 11.00 14.00 40.00 13.22 904 11.00 14.00 39.91 13.16 905 11.00 14.00 39.82 13.10 906 11.00 14.00 39.82 13.10 THE SPRINKLER SYSTEM FLOW IS 240.57 gpm THE OUTSIDE HOSE FLOW AT REFERENCE POINT N0. 1 IS 0.00 gpm [ ] THE INSIDE HOSE [ ] RACK SPKLR'S. [ ] YARD HYDT. FLOW IS 500.00 gpm THE MINIMUM DENSITY PROVIDED BY THIS SYSTEM IS 0.400 gpm/sq. ft. THE FOLLOWING PRESSURES & FLOWS OCCUR ---> AT REF. PT. 1 <--- STATIC PRESSURE 137.50 psi RESIDUAL PRESSURE 81.25 psi AT 750.00 gpm TOTAL SYSTEM FLOW 740.57 gpm AVAILABLE PRESSURE 82.55 psi AT 740.57 gpm OPERATING PRESSURE 58.90 psi AT 740.57 gpm PRESSURE REMAINING 23.65 psi

OPCION 1 - ROCIADORES BULBO ALMACEN ACOPIO - REV A PAGE 2 FITTING Equivalent Length per NFPA 13 1994, 6-4.3 '-' Indicates Equivalent Length. 'T' Indicates Threaded Fitting 1=45 Elbow, 2=90 Elbow, 3='T'/Cross, 4=Butterfly Valve, 5=Gate Valve, 6=Swing Check Valve ============================================================================================= FROM TO FLOW PIPE FITS EQV. H-W PIPE DIA. FRIC. ELEV. FROM TO DIFF (gpm) (ft) (ft) C TYPE (in) (psi) (psi) (psi) (psi) (psi) 1 2 740.57 10.00 46 42.00 120 1 6.065 0.020 0.000 58.90 57.85 1.05 2 100 740.57 200.00222222 40.80 120 1 4.026 0.149 0.000 57.85 21.93 35.92 100 101 240.57 14.00 462 40.80 120 1 4.026 0.019 6.067 21.93 14.85 1.01 101 110 240.57 4.00 22 13.60 120 1 4.026 0.019 0.000 14.85 14.53 0.33 110 111 120.20 9.00 0 0.00 120 1 4.026 0.005 0.000 14.53 14.47 0.06 110 901 120.37 6.00 3 10.80 120 1 2.469 0.056 0.000 14.53 13.59 0.94 111 902 120.20 6.00 3 10.80 120 1 2.469 0.056 0.000 14.47 13.54 0.93 901 903 79.82 13.00 0 0.00 120 1 2.469 0.026 0.000 13.59 13.22 0.37 902 904 79.73 13.00 0 0.00 120 1 2.469 0.026 0.000 13.54 13.16 0.37 903 905 39.82 13.00 0 0.00 120 1 2.469 0.007 0.000 13.22 13.10 0.12 904 906 39.82 13.00 0 0.00 120 1 2.469 0.007 0.000 13.16 13.10 0.06 A MAX. VELOCITY OF 18.66 ft./sec. OCCURS BETWEEN REF. PT. 2 AND 100 Sprinkler-CALC Release 7.2 Win By Walsh Engineering Inc. North Kingstown R.I. U.S.A.

H Y D R A U L I C C A L C U L A T I O N S C O V E R S H E E T OPCION 1 - ROCIADORES BULBO ALMACEN ACOPIO - REV A STATIC PRESSURE (psi) 137.5 RESIDUAL PRESSURE (psi) 81.25 RESIDUAL FLOW (gpm) 750 NUMBER OF BOOSTER PUMPS 0 W A T E R S U P P L Y B O O S T E R P U M P S S P R I N K L E R S MAXIMUM SPACING OF SPRINKLERS (ft) 12.14 MAXIMUM SPACING OF SPRINKLER LINES (ft) 8.2 SPECIFIED DISCHARGE DENSITY (gpm/sq. ft.).4 THIS SPRINKLER SYSTEM WILL DELIVER A DENSITY OF.4 gpm/sq. ft. FOR A DESIGN AREA OF 3000 SQ. FT. OF FLOOR AREA THIS SYSTEM OPERATES AT A FLOW OF 240.57 gpm AT A PRESSURE OF 21.93 psi AT THE BASE OF THE RISER (REF. PT. %100) PIPES USED FOR THIS SYSTEM ====================================== 001 SCHEDULE 40

OPCION 2 - ROCIADORES ESPUM ALMACEN ACOPIO - REV A PAGE 1 HYDRAULIC CALCULATIONS AT SPECIFIED DENSITY THE FOLLOWING SPRINKLERS ARE OPERATING IN: [ ] TEST AREA 1 [ ] TEST AREA 2 [ ] TEST AREA 3 [ ] REMOTE AREA Elevation of sprinklers = Elevation above water test. REF. PT. K ELEV. FLOW PRESSURE ft gpm psi 901 8.10 14.00 30.62 14.29 902 8.10 14.00 30.56 14.23 903 8.10 14.00 30.28 13.97 904 8.10 14.00 30.22 13.92 905 8.10 14.00 30.09 13.80 906 8.10 14.00 30.04 13.75 907 8.10 14.00 30.04 13.75 908 8.10 14.00 30.00 13.72 THE SPRINKLER SYSTEM FLOW IS 241.85 gpm THE OUTSIDE HOSE FLOW AT REFERENCE POINT N0. 1 IS 0.00 gpm [ ] THE INSIDE HOSE [ ] RACK SPKLR'S. [ ] YARD HYDT. FLOW IS 250.00 gpm THE MINIMUM DENSITY PROVIDED BY THIS SYSTEM IS 0.300 gpm/sq. ft. THE FOLLOWING PRESSURES & FLOWS OCCUR ---> AT REF. PT. 1 <--- STATIC PRESSURE 137.50 psi RESIDUAL PRESSURE 81.25 psi AT 750.00 gpm TOTAL SYSTEM FLOW 491.85 gpm AVAILABLE PRESSURE 111.75 psi AT 491.85 gpm OPERATING PRESSURE 55.53 psi AT 491.85 gpm PRESSURE REMAINING 56.22 psi THE ABOVE RESULTS INCLUDE 10.00 psi FRICTION LOSS AT REF. PT. # 50 FOR A [ ] BACKFLOW PREVENTER [ ] METER [ ] DETECTOR CHECK VALVE [ ] OTHER DEVICE

OPCION 2 - ROCIADORES ESPUM ALMACEN ACOPIO - REV A PAGE 2 FITTING Equivalent Length per NFPA 13 1994, 6-4.3 '-' Indicates Equivalent Length. 'T' Indicates Threaded Fitting 1=45 Elbow, 2=90 Elbow, 3='T'/Cross, 4=Butterfly Valve, 5=Gate Valve, 6=Swing Check Valve ============================================================================================= FROM TO FLOW PIPE FITS EQV. H-W PIPE DIA. FRIC. ELEV. FROM TO DIFF (gpm) (ft) (ft) C TYPE (in) (psi) (psi) (psi) (psi) (psi) 1 2 491.85 10.00 46 42.00 120 1 6.065 0.010 0.000 55.53 55.04 0.49 2 50 491.85 200.00222222 40.80 120 1 4.026 0.070 0.000 55.04 38.21 16.83 50 51 491.85 17.00 462 40.80 120 1 4.026 0.070 0.000 38.21 24.17 14.04 51 100 491.85 10.00 22 13.60 120 1 4.026 0.070 0.000 24.17 22.52 1.65 100 101 241.85 14.00 462 40.80 120 1 4.026 0.019 6.067 22.52 15.42 1.03 101 110 241.85 4.00 22 13.60 120 1 4.026 0.019 0.000 15.42 15.09 0.33 110 111 120.82 10.00 0 0.00 120 1 4.026 0.005 0.000 15.09 15.03 0.06 110 901 121.03 3.44 3 10.80 120 1 2.469 0.056 0.000 15.09 14.29 0.80 111 902 120.82 3.44 3 10.80 120 1 2.469 0.056 0.000 15.03 14.23 0.80 901 903 90.41 10.00 0 0.00 120 1 2.469 0.033 0.000 14.29 13.97 0.32 902 904 90.26 10.00 0 0.00 120 1 2.469 0.033 0.000 14.23 13.92 0.31 903 905 60.13 10.00 0 0.00 120 1 2.469 0.015 0.000 13.97 13.80 0.18 904 906 60.04 10.00 0 0.00 120 1 2.469 0.015 0.000 13.92 13.75 0.17 905 907 30.04 10.00 0 0.00 120 1 2.469 0.004 0.000 13.80 13.75 0.04 906 908 30.00 10.00 0 0.00 120 1 2.469 0.004 0.000 13.75 13.72 0.03 A MAX. VELOCITY OF 12.39 ft./sec. OCCURS BETWEEN REF. PT. 51 AND 100 Sprinkler-CALC Release 7.2 Win By Walsh Engineering Inc. North Kingstown R.I. U.S.A.

H Y D R A U L I C C A L C U L A T I O N S C O V E R S H E E T OPCION 2 - ROCIADORES ESPUM ALMACEN ACOPIO - REV A STATIC PRESSURE (psi) 137.5 RESIDUAL PRESSURE (psi) 81.25 RESIDUAL FLOW (gpm) 750 NUMBER OF BOOSTER PUMPS 0 W A T E R S U P P L Y B O O S T E R P U M P S S P R I N K L E R S MAXIMUM SPACING OF SPRINKLERS (ft) 10 MAXIMUM SPACING OF SPRINKLER LINES (ft) 10 SPECIFIED DISCHARGE DENSITY (gpm/sq. ft.).3 THIS SPRINKLER SYSTEM WILL DELIVER A DENSITY OF.3 gpm/sq. ft. FOR A DESIGN AREA OF 3000 SQ. FT. OF FLOOR AREA THIS SYSTEM OPERATES AT A FLOW OF 241.85 gpm AT A PRESSURE OF 22.52 psi AT THE BASE OF THE RISER (REF. PT. %100) PIPES USED FOR THIS SYSTEM ====================================== 001 SCHEDULE 40

OPCION 3 - ALTA EXPANSION ALMACEN ACOPIO - REV A PAGE 1 HYDRAULIC CALCULATIONS AT SPECIFIED FLOW THE FOLLOWING SPRINKLERS ARE OPERATING IN: [ ] TEST AREA 1 [ ] TEST AREA 2 [ ] TEST AREA 3 [ ] REMOTE AREA Elevation of sprinklers = Elevation above water test. REF. PT. K ELEV. FLOW PRESSURE ft gpm psi 901 4.85 14.00 42.00 74.98 THE SPRINKLER SYSTEM FLOW IS 42.00 gpm THE OUTSIDE HOSE FLOW AT REFERENCE POINT N0. 1 IS 0.00 gpm [ ] THE INSIDE HOSE [ ] RACK SPKLR'S. [ ] YARD HYDT. FLOW IS 0.00 gpm THE FOLLOWING PRESSURES & FLOWS OCCUR ---> AT REF. PT. 1 <--- STATIC PRESSURE 137.50 psi RESIDUAL PRESSURE 81.25 psi AT 750.00 gpm TOTAL SYSTEM FLOW 42.00 gpm AVAILABLE PRESSURE 137.23 psi AT 42.00 gpm OPERATING PRESSURE 97.26 psi AT 42.00 gpm PRESSURE REMAINING 39.97 psi THE ABOVE RESULTS INCLUDE 10.00 psi FRICTION LOSS AT REF. PT. # 50 FOR A [ ] BACKFLOW PREVENTER [ ] METER [ ] DETECTOR CHECK VALVE [ ] OTHER DEVICE

OPCION 3 - ALTA EXPANSION ALMACEN ACOPIO - REV A PAGE 2 FITTING Equivalent Length per NFPA 13 1994, 6-4.3 '-' Indicates Equivalent Length. 'T' Indicates Threaded Fitting 1=45 Elbow, 2=90 Elbow, 3='T'/Cross, 4=Butterfly Valve, 5=Gate Valve, 6=Swing Check Valve ============================================================================================= FROM TO FLOW PIPE FITS EQV. H-W PIPE DIA. FRIC. ELEV. FROM TO DIFF (gpm) (ft) (ft) C TYPE (in) (psi) (psi) (psi) (psi) (psi) 1 2 42.00 10.00 46 42.00 120 1 6.065 0.000 0.000 97.26 97.25 0.01 2 50 42.00 200.00222222 40.80 120 1 4.026 0.001 0.000 97.25 97.08 0.18 50 51 42.00 17.00 462 25.30 120 1 2.469 0.008 0.000 97.08 86.74 10.34 51 100 42.00 10.00 22 5.20 120 1 1.610 0.064 0.000 86.74 85.77 0.97 100 101 42.00 14.00 462 11.60 120 1 1.610 0.064 6.067 85.77 78.08 1.63 101 102 42.00 12.00 22 5.20 120 1 1.610 0.064 0.000 78.08 76.98 1.10 102 901 42.00 21.00 2222 10.40 120 1 1.610 0.064 0.000 76.98 74.98 2.00 A MAX. VELOCITY OF 6.61 ft./sec. OCCURS BETWEEN REF. PT. 102 AND 901 Sprinkler-CALC Release 7.2 Win By Walsh Engineering Inc. North Kingstown R.I. U.S.A.

H Y D R A U L I C C A L C U L A T I O N S C O V E R S H E E T OPCION 3 - ALTA EXPANSION ALMACEN ACOPIO - REV A STATIC PRESSURE (psi) 137.5 RESIDUAL PRESSURE (psi) 81.25 RESIDUAL FLOW (gpm) 750 NUMBER OF BOOSTER PUMPS 0 W A T E R S U P P L Y B O O S T E R P U M P S S P R I N K L E R S MINIMUM FLOW PER SPRINKLER (gpm) 42 MINIMUM PRESSURE PER SPRINKLER (psi) 74.98 THIS SYSTEM OPERATES AT A FLOW OF 42.00 gpm AT A PRESSURE OF 85.77 psi AT THE BASE OF THE RISER (REF. PT. %100) PIPES USED FOR THIS SYSTEM ====================================== 001 SCHEDULE 40