Trajectory Sensitivity Analysis as a Means of Performing Dynamic Load Sensitivity Studies in Power System Planning

Similar documents
ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 3 Load Modeling

Dynamic Voltage Stability Enhancement of a Microgrid with Static and Dynamic Loads Using Microgrid Voltage Stabilizer

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

VOLTAGE stability has become a major concern for the

Harmonic Modeling of Networks

Reliability of Bulk Power Systems (cont d)

Real-Time Wide-Area Dynamic Monitoring Using Characteristic Ellipsoid Method

Cascading Outages in Power Systems. Rui Yao

Two-Layer Network Equivalent for Electromagnetic Transients

Proper Security Criteria Determination in a Power System with High Penetration of Renewable Resources

FLEXIBLE ac transmission system (FACTS) devices give

Chapter 8 VOLTAGE STABILITY

Phase Boundary Computation for Fault Induced Delayed Voltage Recovery

Hybrid Time Domain Simulation: Application to Fault Induced Delayed Voltage Recovery (FIDVR)

STATE ESTIMATION IN DISTRIBUTION SYSTEMS

LOAD MODELING STUDY USING MEASUREMENT DATA FOR TAIWAN POWER SYSTEM

Generalized Injection Shift Factors and Application to Estimation of Power Flow Transients

Real Time Phasor Data Processing using Complex Number Analysis Methods R.A. DE CALLAFON 1, C.H. WELLS 2 USA

LINE FLOW ANALYSIS OF IEEE BUS SYSTEM WITH THE LOAD SENSITIVITY FACTOR

PMU-Based Power System Real-Time Stability Monitoring. Chen-Ching Liu Boeing Distinguished Professor Director, ESI Center

A Novel Technique to Improve the Online Calculation Performance of Nonlinear Problems in DC Power Systems

Significance of Load Modelling in Power System Dynamics

Dynamic state based on autoregressive model for outgoing line of high voltage stations

An Equivalent Circuit Formulation of the Power Flow Problem with Current and Voltage State Variables

On-Line TSA and Control at EMS Control Centers for Large Power Grids

CIGRE US National Committee 2015 Grid of the Future Symposium. Setting-less Protection: Laboratory Experiments and Field Trials

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability

New criteria for Voltage Stability evaluation in interconnected power system

Impact of Photovoltaic Generation On The Power System Stability

ECE 522 Power Systems Analysis II 3.3 Voltage Stability

ECE 476. Exam #2. Tuesday, November 15, Minutes

A COMPUTER PROGRAM FOR SHORT CIRCUIT ANALYSIS OF ELECTRIC POWER SYSTEMS

Analytical Study Based Optimal Placement of Energy Storage Devices in Distribution Systems to Support Voltage and Angle Stability

Systematic Tuning of Nonlinear Power System Controllers

ECE 585 Power System Stability

Grid Issues and Challenges Addressed by High Temperature Superconductor (HTS) Technology

Entropy Based Analysis of Delayed Voltage Recovery

A Generalized Hamiltonian Model for Power System Dynamics with Relay Action. Raja Timihiri. Project Advisor: Christopher DeMarco

Simultaneous placement of Distributed Generation and D-Statcom in a radial distribution system using Loss Sensitivity Factor

Test Case: Power System Voltage Stability

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 8 - Voltage Stability

Smart Grid State Estimation by Weighted Least Square Estimation

IEEE PES Task Force on Benchmark Systems for Stability Controls

The N k Problem using AC Power Flows

TIME-domain simulation is an important approach for

Minimization of Energy Loss using Integrated Evolutionary Approaches

Enforcing Passivity for Admittance Matrices Approximated by Rational Functions

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study.

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER

Inventory of Load Models in Electric Power Systems via Parameter Estimation

Quasi-Newton Power Flow Using Partial Jacobian Updates

Enhanced Newton Method Based Radial Distribution System Load Flow Analysis with Extrapolation Techniques

Fault Locating PRESENTED BY ERIK SCHELLENBERG IDAHO POWER

Power System Security. S. Chakrabarti

ECEN 667 Power System Stability Lecture 20: Oscillations, Small Signal Stability Analysis

Risk Analysis for Assessment of Vegetation Impact on Outages in Electric Power Systems. T. DOKIC, P.-C. CHEN, M. KEZUNOVIC Texas A&M University USA

State Estimation and Power Flow Analysis of Power Systems

Simulating a Power System

PowerApps Optimal Power Flow Formulation

Optimal PMU Placement

A PROPOSED STRATEGY FOR CAPACITOR ALLOCATION IN RADIAL DISTRIBUTION FEEDERS

Real Time Synchrophasor Measurements Based Voltage Stability Monitoring and Control

Unified Power System Analyses and Models using Equivalent Circuit Formulation

Power Flow Analysis of Radial Distribution System using Backward/Forward Sweep Method

Chapter 2. Planning Criteria. Turaj Amraee. Fall 2012 K.N.Toosi University of Technology

Stochastic Unit Commitment with Topology Control Recourse for Renewables Integration

Module 6 : Preventive, Emergency and Restorative Control. Lecture 27 : Normal and Alert State in a Power System. Objectives

URTDSM Initiative in India and Controlled Islanding using PMU Measurements

A New Approach to Constructing Seasonal Nomograms in Planning and Operations Environments at Idaho Power Co.

Statistical approach in complex circuits by a wavelet based Thevenin s theorem

Dynamic Decomposition for Monitoring and Decision Making in Electric Power Systems

Sample average approximation and cascading failures of power grids. Daniel Bienstock, Guy Grebla, Tingjun Chen, Columbia University GraphEx 15

Role of Synchronized Measurements In Operation of Smart Grids

POWER system dynamic behavior is subject to performance

Transient Stability Analysis of Single Machine Infinite Bus System by Numerical Methods

Increasing Transmission Capacities with Dynamic Monitoring Systems

New Tools for Analysing Power System Dynamics

Performance Evaluation and Review of System Protection Scheme Design with the help of Synchrophasor Measurements

ECEN 667 Power System Stability Lecture 17: Transient Stability Solutions, Load Models

PROPOSED STRATEGY FOR CAPACITOR ALLOCATION IN RADIAL DISTRIBUTION FEEDERS

A DC Power Flow Extension

DYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID

Modeling of Power System Components During Electromagnetic Transients

Comparison between Interval and Fuzzy Load Flow Methods Considering Uncertainty

Modeling of Transmission Line and Substation for Insulation Coordination Studies

KINGS COLLEGE OF ENGINEERING Punalkulam

UNIVERSIDAD DE CASTILLA-LA MANCHA

Fine Tuning Of State Estimator Using Phasor Values From Pmu s

Control Lyapunov Functions for Controllable Series Devices

Dynamic optimization based reactive power planning for improving short-term voltage performance

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

IBIS Modeling Using Latency Insertion Method (LIM)

Nonlinear Dynamic Model Evaluation From Disturbance Measurements

WHEN studying distributed simulations of power systems,

WECC Dynamic Probing Tests: Purpose and Results

A Stable Finite Horizon Model Predictive Control for Power System Voltage Collapse Prevention

CAPACITOR PLACEMENT IN UNBALANCED POWER SYSTEMS

Fast Decoupled Power Flow for Unbalanced Radial Distribution Systems

Quantitative Transient Voltage Dip Assessment of Contingencies using Trajectory Sensitivities. Lei Tang, James McCalley

The Study of Overhead Line Fault Probability Model Based on Fuzzy Theory

Transcription:

21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium Trajectory Sensitivity Analysis as a Means of Performing Dynamic Load Sensitivity Studies in Power System Planning P. MITRA V. VITTAL P. POURBEIK A. GAIKWAD Arizona State University Electric Power Research Institute USA USA SUMMARY One of the most important aspects of time-domain simulations for power system planning studies is the modeling of load. The North American Reliability Corporation (NERC) Transmission Planning (TPL) Standard -001-4 states that System peak load levels shall include a load model which represents the expected dynamic behavior of loads that could impact the study area, considering the behavior of induction motor loads. This further emphasizes the need to consider detailed load modeling from the perspective of present reliability standards in North America. One of the major challenges with load modeling is determining the exact composition of the load and establishing reasonable aggregated load models. The process of developing such aggregated load models for transmission planning studies inherently introduces significant uncertainties and approximations into the model. Thus, it is important to consider methods for performing load sensitivity studies in a more systematic way. This paper presents some initial research results for using a methodology known as trajectory sensitivity analysis for performing load sensitivity studies. KEYWORDS Load modeling, Trajectory Sensitivity, Transient Stability ppourbeik@epri.com or pouyan@ieee.org

1. INTRODUCTION One of the most important aspects of time-domain simulations for power system planning studies is the modeling of load [1]. Many utilities and reliability entities worldwide are increasing giving renewed attention to the subject of load modeling and in particular dynamic load models for timedomain stability studies in planning [1], [2]. The subject of load modeling is not a new one, and much research and work has been done in the past relative to load models [3], [4], [5], [6] and [7]. Recently, however, a significant body of work has been done in the Western Electricity Coordinating Council (WECC) Load Modeling Task Force which lead to the development of a new composite load model now being adopted in WECC and starting to get used elsewhere in North America [8]. The significant contribution of this work was in the development of the residential air-conditioner compressor motor model, which was the result of a collaborative effort of laboratory testing of such loads [9]. The North American Reliability Corporation (NERC) Transmission Planning (TPL) Standard -001-4 states that System peak load levels shall include a load model which represents the expected dynamic behavior of loads that could impact the study area, considering the behavior of induction motor loads. As the NERC standards become enforced in the near future, utilities in North America will need to adopt dynamic load model structures similar to the WECC composite load model (cmpldw). In transmission planning studies, loads are modeled as single aggregated load models at a substation node in the transmission model. This is true of the WECC cmpldw model as well as all the other models in the references mentioned above. Thus, a significant remaining challenge with load modeling is determining the exact composition of the load and establishing reasonable parameters for the aggregated load models. There have been many approaches proposed for determining the parameters of the aggregated model including such techniques as measurement based model parameter derivation [10]. However, all these methods have significant limitations (e.g. capturing useful event for parameter derivation during peak load hours/seasons) and thus the process of developing such aggregated load models for transmission planning studies inherently introduces significant uncertainties and approximations into the model. Due to these shortcomings, and other reasons [11], it is important to consider methods for performing load sensitivity studies in a more systematic way. This paper presents some initial research results for using a methodology known as trajectory sensitivity analysis for performing load sensitivity studies. The idea of the approach is a follows: (i) a single simulation of a critical outage under a peak load scenario is performed on the power system model, (ii) all the sensitivities relative to each load model parameter are calculated using the power flow Jacobian at each step of the time domain solution, and (iii) sensitivities to the system response trajectory (e.g. how the voltage at a major bus recovers) to variations in the load model parameters are calculated from the sensitivities without the need for re-simulating the case. As a result the process of sensitivity analysis becomes more systematic and also offers the potential for time savings 2. THE TRAJECTORY SENSITIVITY ANALYSIS METHOD A power system can be represented by a set of differential algebraic equations [12] x & = f ( x, y, λ) (1.1) g ( x, y, λ ) = 0 for < 0 (1.2) y k + g ( x, y, λ ) = 0 for 0 (1.3) where, x represents the network dynamic states, y represents the network algebraic variables and λ represents the parameters of the system of interest. For the purpose of this paper, λ represents the load x(t) model parameters. The trajectory sensitivities to a change in a parameter λ are given by and λ y k 1

y(t) ; the first order partial derivatives. The predicted trajectories can be the calculated by a first λ order approximation as x x( t) = x t + λ λ pred ( ) old (1.4) y y( t) = y t + λ λ pred ( ) old (1.5) A detailed description of trajectory sensitivity analysis and the computation method can be found in [12] and [13]. Calculation of the sensitivities involves using the power flow Jacobian at each step of the time domain solution. The power flow Jacobian is available as a by-product of a traditional time domain simulation routine, which incorporates an implicit integration algorithm. The runtime availability of the power flow Jacobian reduces the computation effort in evaluating the sensitivities and it can be done simultaneously while performing a time domain simulation. Since the sensitivities of different parameters are independent of each other, these can be evaluated in parallel using some parallel computing architecture, enabling additional savings in time. Reference [14] provides details of trajectory sensitivity analysis using cluster computing. 3. THE LOAD AND SYSTEM MODEL Since the approach uses an implicit integration technique, and for the sake of ensuring maximum flexibility during the R&D phase, this work was done in MATLAB using the PSAT 1 package. A summer peak case for the WECC system was imported into the PSAT environment in MATLAB. The WECC cmpldw [8] model was developed in MATLAB and all the loads in the system were represented using this model. The initial load composition was set based on the WECC load model task force spreadsheet with estimates of load composition based on climatic regions. The rest of the load model parameters were set to the default settings. The WECC cmpldw model structure is shown in Figure 1. A WECC model was used in order to ensure that the test case closely represented a practical real-life scenario. However, it must be understood that this work constitutes research and hence none of the results shown here necessarily reflect actual system performance. Transmission bus Distribution Transformer Distribution bus Shunt Static Load AC Figure 1: Composite load model in MATLAB based PSAT 4. APPLYING TRAJECTORY SENSITIVITY Trajectory sensitivity analysis was used to study the effect of change in load composition at different buses on the system algebraic and state variables following a single disturbance. A WECC 2012 summer peak system model was used for this work. A three-phase fault was applied on a major 500 ST SM LM 1 http://faraday1.ucd.ie/psat.html 2

kv line. The fault is cleared by opening the line after 5 cycles. The sensitivity of voltage and frequency to percentage changes in the air-conditioning (AC) load at 20 buses were studied. ACs were observed to stall at these 20 buses and hence these 20 buses were selected to study the effect of change in load composition. Let K p designate the percentage of AC load at each load bus. Then, K p is the percentage change in AC load at each bus. Figure 2 shows the actual and predicted bus voltages at bus 1 for a K p of 5 percent at the 20 study buses. It can be seen that the predicted and actual voltages follow closely. Bus 1 is a major system load bus electrically close to the disturbance. Figure 2: Actual and predicted voltage at bus 1 for a Kp of 5 at 20 buses Figure 3 shows the actual and predicted bus voltages at bus 2 for a K p of 5 percent at the 20 study buses. Bus 2 is major system load bus, which is electrically far from the fault location. It can be seen that actual and predicted trajectories follow each other closely. Figure 3: Actual and predicted voltage at bus 2 for a Kp of 5 at 20 buses Relays, contactors and discontinuities in the load characteristics introduce severe non-linearity in the load models. Nonlinear models lead to approximation errors in a trajectory sensitivity based approach since the method relies on the assumption of linearity. The trajectory sensitivity based approach can be erroneous when the base case and the actual case to be predicted do not encounter and traverse the same switching surfaces [12]. As an example, the base case and actual case (to be predicted) should have same number of motors tripping and same number of ACs (stalling / restarting) to get an accurate linear prediction of trajectories. For the present scenario simulated, ACs account for majority of the load. Stalling of additional AC units has a pronounced effect on the linear approximation. Large, small and quick trip motors form a smaller portion of the load in the area under study. Due to their smaller percentage unequal tripping of motors, do not have a significant impact on the trajectories system 3

wide. However, at buses where motors do not trip in the base case but do in the actual case, the error introduced is significant. In this study, during the base case simulation, small motors where observed to trip due to under voltage at 36 buses. However, for a K p of 5 at 20 buses, the repeat simulation revealed 43 buses where small motors tripped due to under voltage. Figure 4 shows the actual and predicted bus voltages at bus 3 for a K p of 5 at the 20 buses under study. The small motors constitute 14 percent of the load at this bus. From Figure 4, it can be seen that unequal number of motors tripping in the base case and actual case introduces prediction error towards the end of the simulation. However, this effect is not pronounced at buses, which are electrically far from bus this load bus. Thus the error is somewhat localized. Figure 4: Actual and predicted voltage at bus 3 for 5 percent load change at 20 buses For a better understanding of the effect mentioned above, a K p of 6 is considered at 20 buses. Stalling of AC units were observed on 20 buses in the base case. After a repeat simulation with a K p of 6 at 20 buses, stalling of AC units were observed on 27 buses. Bus 4 is a load bus where ACs stall in the actual case but not in the base case. Figure 5 shows the plot of actual and predicted voltage at bus 4 for a K p of 6 at 20 buses. Figure 5 shows that stalling of unequal number of ACs in the actual and base case introduces substantial error in the trajectory prediction. Figure 6 shows the actual and predicted voltage at bus 1, which is electrically far from bus 4. From Figure 6, it can be seen that unequal AC stalling introduces some but relatively minimal approximation error at this remote bus. Some further research is needed to look into possible ways to address such issues. Figure 5: Actual and predicted voltage at bus 4 for 6 percent load change at 20 buses 4

Figure 6: Actual and predicted voltage at bus 1 for 6 percent load change at 20 buses Solution metrics for trajectory sensitivity analysis The time requirements for performing the trajectory sensitivity analysis for the cases studied here are shown in column 2 of Table 2. The size of the file containing the Jacobian entries is 9 GB in this process. It should be noted that a trapezoidal method of integration is used in the trajectory sensitivity analysis. The increased simulation time is due to increased Newton-Raphson iterations required for convergence of solution during disturbances. To address the issue of increased time, an optimal multiplier can be used in conjunction with the Newton-Raphson update [15]. An optimal multiplier typically finds usage when the values of the variables oscillate near the final solution [15]. The problem is formulated as follows. The intermediate step of a time domain simulation involving differential-algebraic equations can be stated as a set of nonlinear equations given by f ( x) = 0 (1.6) The Newton's method transforms the problem in to a sequence of linear equations, whose solution approaches the solution of (1.6) iteratively. If the initial guess of the solution vector is x 0 then the linear problem is given by f ( x 0 ) = J x (1.7) Where J is the Jacobian matrix containing the partial derivatives of f with respect to x and x is the correction vector by which x 0 is incremented. The next approximation of the solution x 1 is given by x 1 = x 0 + x (1.8) This approach can be modified by introducing an optimal multiplier α, such the new estimate for the solution is given by x 1 = x 0 + α x (1.9) The value of α is calculated by solving a one dimensional minimization problem t α = arg min( f ( x0 + α x) f ( x0 + α x)) (1.10) The exact solution of the one dimensional optimization problem in (1.10) is time consuming. For this study, a cubic interpolation technique has been used to find an inexact value of α. A detailed description of this approach can be found in [15]. The optimal multiplier is used only if the N-R routine does not converge in 3 iterations. The following observations were made after the introduction of the optimal multiplier α in the N R routine (i) a reduction of more than 30 minutes in the total simulation time, (ii) a reduction in the stored data (Jacobian entries) from 9 GB to 5 GB, and (iii) a slight increase in error in the trajectory approximation. The trajectory sensitivity analysis of Case 1 5

and Case 2 were repeated using the optimal mal multiplier method. As an example, Figure 7 shows the actual and predicted bus voltages at the same bus as shown in Figure 2. As can be seen this approach introduces a small increase in the error in the sensitivity calculation. Table 2 shows the comparison of the computation time by both methods, it can be seen that a saving of about 30 minutes in computation time is achieved by introducing an optimal multiplier with a minimal additional error. Figure 7: Actual and predicted voltage at bus 1 for 5 percent load change at 20 buses (N-R method with optimal multiplier) Table 2: Comparison of simulation metrics Routines Time (N-R without optimal Time (N-R with optimal Time domain simulation (includes storing Jacobian) 3487.729 sec 1695.548 sec Calculate initial values of sensitivities 1.708 sec No change Calculate the sensitivities 913.87 sec 353.97 sec Create the final trajectory 32.29 sec No change Total time 4435.59 sec (74 mins) 2083.108 sec (35 mins) Size of file containing Jacobian entries 9 GB 5 GB 5. CONCLUSIONS Dynamic load modeling is becoming a more important aspect of performing time-domain stability studies for transmission planning. One of the key challenges in load modeling is determining the composition and aggregate model parameters. An approach to addressing the issue of uncertainties in the composition and/or model parameters is the application of load model sensitivity analysis. In this paper, an approach has been presented using trajectory sensitivity analysis. The main benefit of this method is that it allows a planner to study multiple scenarios with uncertain load parameters without the need of multiple simulations. Since, multiple sensitivities can be computed in parallel it enables additional savings in computational effort. The main disadvantage at present is that being a linear approach it cannot sufficiently handle severe non-linearity in load models. If the sensitivity cases push the system into additional motors stalling and/or tripping, the predicted trajectory can have significant errors associated with it. One other concern is the required computation time due to the implicit integration methods and the large overhead associated with calculating and storing the sensitivity data. However, it has been shown that at the expense of a relatively small additional error the computational time can be significantly reduced with an optimal multiplier in the integration algorithm. Further research will be needed to address the issues with non-linearities. 6

REFERENCES [1] CIGRE Technical Brochure 566, Modelling and Aggregation of Loads in Flexible Power Networks, Prepared by CIGRE WG C4.605, February 2014 (www.e-cigre.org) [2] Z. Y. Dong, A. Borghetti, K. Yamashita, A. Gaikwad, P. Pourbeik and J. V. Milanovic, CIGRE WG C4.605 Recommendations on Measurement Based and Component Based Load Modelling Practice, CIGRE SC C4 2012 Colloquium, Hakodate, Japan, October 2012. [3] IEEE Task Force, Load Representation for Dynamic Performance Analysis, IEEE Trans. PWRS, pp 472-482, 1993. [4] IEEE Task Force, Standard Load Models for Power Flow and Dynamic Performance Simulations, IEEE Trans. PWRS, pp 1302-1312, 1995. [5] EPRI Research Project 849-7 EL-5003, Load Modeling for Power Flow and Transient Stability Computer Studies Volumes 1 to 4, January 1987. [6] L. M. Hajagos and B. Danai Laboratory Measurements and Models of Modern Loads and Their Effect on Voltage Stability Studies IEEE Transactions on Power Systems, Volume: 13,Issue: 2, May 1998 Pages:584 592 [7] K. Tomiyama, J. P. Daniel and S. Ihara, Modeling air conditioner load for power system studies, IEEE Trans. Power Systems, Volume 13, Issue 2, May 1998, pp 414 421. [8] Composite Load Model for Dynamic Simulations, Report 1.0, June 12, 2012, WECC [9] A. M. Gaikwad, R. J. Bravo, D. Kosterev, S. Yang, A. Maitra, P. Pourbeik, B. Agrawal, R. Yinger, and D. Brooks, Results of Residential Air Conditioner Testing in WECC, Proceedings of the IEEE PES General Meeting, Pittsburg, July 2008. [10]. A. Maitra, A. Gaikwad, P. Pourbeik and D. Brooks, Load Model Parameter Derivation Using an Automated Algorithm and Measured Data, Proceedings of the IEEE PES General Meeting, Pittsburg, July 2008. [11] P. Pourbeik, Approaches to Validation of Power System Models for System Planning Studies, Proceedings of the IEEE PES General Meeting, Minneapolis, MN, July 2010. [12] I. A. Hiskens, M. A. Pai Trajectory sensitivity analysis of hybrid systems, IEEE Trans. on Circuits and Systems, v. 47, No. 3, pp. 204 220, Feb 2000 [13] G. Hou, Trajectory sensitivity based power system dynamic security assessment, PhD. Dissertation, Dept. of Electrical Computer and Energy Engineering, Arizona State University, Tempe, April 2012. [14] G. Hou, V. Vittal, Cluster computing based trajectory sensitivity analysis application to the WECC system, IEEE Trans. Power Syst. v. 27, No. 1, pp. 502 509, July 2013 [15] A.M. Sasson, C. Trevino, F. Aboytes, Improved Newton's load flow through a minimization technique, IEEE Trans. on Power Apparatus and Systems, v. 90, No. 5, pp 1974 1981, Sept 1971 7