Fault Location in Distribution Feeders with Distributed Generation using Positive Sequence Apparent Impedance

Similar documents
Chapter 8: Unsymmetrical Faults

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *

HYBRID FAULT DIAGNOSIS FORMULATION FOR UNBALANCED UNDERGROUND DISTRIBUTION FEEDERS

Module 3 : Sequence Components and Fault Analysis

Traveling Wave Relays. Fault Location

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2)

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

Further improvements on impedance-based fault location for power distribution systems

NEW RECLOSER CHARACTERISTIC TO IMPROVE FUSE SAVING IN DISTRIBUTION NETWORKS WITH DISTRIBUTED GENERATION

1 Unified Power Flow Controller (UPFC)

Last Comments on Short-Circuit Analysis

A Generalized Admittance Based Method for Fault Location Analysis of Distribution System

Fault Diagnosis in Distribution Networks with Distributed Generation

Adaptive Distance Relaying Scheme for Power Swing Tripping Prevention

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

The influence of the self-excited induction machine into the electrical grid under instability situation - Real case measurement

Fault Calculation Methods

A Model-Based Approach for Small-Signal Stability Assessment of Unbalanced Power Systems

IEEE PES Task Force on Benchmark Systems for Stability Controls

ABSTRACT. residential Photovoltaic (PV) systems. The investigation is done on both conventional and

OVER CURRENT RELAYS PROTECTIVE COORDINATION IN DISTRIBUTION SYSTEMS IN PRESENCE OF DISTRIBUTED GENERATION

KINGS COLLEGE OF ENGINEERING Punalkulam

Fault Locating PRESENTED BY ERIK SCHELLENBERG IDAHO POWER

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study.

Harmonic Modeling of Networks

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

Module 3 : Sequence Components and Fault Analysis

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

In the previous chapter, attention was confined

A COMPUTER PROGRAM FOR SHORT CIRCUIT ANALYSIS OF ELECTRIC POWER SYSTEMS

A STATIC AND DYNAMIC TECHNIQUE CONTINGENCY RANKING ANALYSIS IN VOLTAGE STABILITY ASSESSMENT

DYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID

Impact of Distributed Synchronous Generators on Distribution Feeder Stability

ECE 585 Power System Stability

Critical clearing time evaluation of Nigerian 330kV transmission system

Performance Improvement of the Radial Distribution System by using Switched Capacitor Banks

Power Flow Analysis of Radial Distribution System using Backward/Forward Sweep Method

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

A New Fault-Location Method with High Robustness for Distribution Systems

1. Introduction. Keywords Transient Stability Analysis, Power System, Swing Equation, Three-Phase Fault, Fault Clearing Time

Study of Transient Stability with Static Synchronous Series Compensator for an SMIB

A Power System Dynamic Simulation Program Using MATLAB/ Simulink

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

CHAPTER 8 UNSYMMETRICAL FAULTS

Simultaneous placement of Distributed Generation and D-Statcom in a radial distribution system using Loss Sensitivity Factor

Power system model. Olof Samuelsson. EIEN15 Electric Power Systems L2

Voltage Stability Monitoring using a Modified Thevenin Impedance

NEW DESIGN OF GROUND FAULT PROTECTION

EE 451 Power System Stability

Power system model. Olof Samuelsson. EIEN15 Electric Power Systems L2 1

ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 3 Load Modeling

CHAPTER 2 LOAD FLOW ANALYSIS FOR RADIAL DISTRIBUTION SYSTEM

Fault Analysis Power System Representation

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

Transient Stability Improvement of a Multi- Machine Power System by Using Superconducting Fault Current Limiters

Locating Distributed Generation. Units in Radial Systems

Mathematical Model of a Synchronous Machine under Complicated Fault Conditions

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

EE5250 TERM PROJECT. Report by: Akarsh Sheilendranath

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability

Optimal Capacitor Placement in Distribution System with Random Variations in Load

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)

Research on Fault Location Method Based on Nonlinear Impedance Model

Selecting the current rating for equipment

Determination of Fault Location in Shunt Capacitor Bank through Compensated Neutral Current

Role of Synchronized Measurements In Operation of Smart Grids

QFT Framework for Robust Tuning of Power System Stabilizers

Power Flow Analysis. The voltage at a typical bus i of the system is given in polar coordinates by

Railway Research. Study of Superconducting Fault Current Limiter Device in a AC Railway System. 1. Introduction. International Journal of

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Reactive Power Solutions

ALPS. Advanced Line Protection System

EVALUATION OF THE IMPACT OF POWER SECTOR REFORM ON THE NIGERIA POWER SYSTEM TRANSIENT STABILITY

Congestion Alleviation using Reactive Power Compensation in Radial Distribution Systems

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

Electromagnetic Torque From Event Report Data A Measure of Machine Performance

Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

Cascading Outages in Power Systems. Rui Yao

Smart Grid State Estimation by Weighted Least Square Estimation

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

Real Time Voltage Control using Genetic Algorithm

A STUDY OF THE EIGENVALUE ANALYSIS CAPABILITIES OF POWER SYSTEM DYNAMICS SIMULATION SOFTWARE

DC Arc Flash Analysis

Analysis of a Relay Operation for an Intercircuit Fault

Chapter 9: Transient Stability

A Computational Contribution to Analyse the Connection of an Independent Power Producer to the Grid

Analysis of factors affecting station capacitor bank switching transients

Dynamic state based on autoregressive model for outgoing line of high voltage stations

EDSA IEC 909 SHORT CIRCUIT ANALYSIS

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz

Estimating Generator Capability Curves

Transmission Line Fault Analysis using Bus Impedance Matrix Method

Research on the Effect of Substation Main Wiring on the Power System Reliability Yuxin Zhao 1, a, Tao Liu 2,b and Yanxin Shi 3,c

Mixed Integer Linear Programming and Nonlinear Programming for Optimal PMU Placement

IJSER. 1. Introduction

Power System Security Analysis. B. Rajanarayan Prusty, Bhagabati Prasad Pattnaik, Prakash Kumar Pandey, A. Sai Santosh

SSSC Modeling and Damping Controller Design for Damping Low Frequency Oscillations

Transcription:

Fault Location in Distribution Feeders with Distributed Generation using Positive Sequence Apparent Impedance ARTURO SUMAN BRETAS Federal University of Rio Grande do Sul Department of Electrical Engineering Av. Osvaldo Aranha, 103 Porto Alegre, RS BRAZIL abretas@ece.ufrgs.br RODRIGO HARTSTEIN SALIM Federal University of Rio Grande do Sul Department of Electrical Engineering Av. Osvaldo Aranha, 103 Porto Alegre, RS BRAZIL salim@eletro.ufrgs.br Abstract: The existing methods of fault location for distribution systems consider that the system has a radial power flow, in other words, they don t consider the presence of another generator in the distribution line. Thus, in systems with the presence of distributed generation, these methods show to be inefficient. In this paper, it is presented a new fault location method based on positive sequence apparent impedance. Computational simulations were made and the method was tested and compared with other existing fault location techniques in order to validate the method. The basic characteristics of the method, the new algorithm and a variety of case studies are presented in the paper in order to illustrate its efficiency. Key Words: Distribution Systems, Distributed Generation, Protection Systems, Fault Location, Apparent Impedance 1 Introduction The correct fault location in power distribution systems (PDS) is a basic theme in the protection systems. With a good estimative of the location of a fault the problems in the network are solved faster, and bigger problems that might occur in consequence of these faults can be avoided. This reduces the interruption time and increases the system reliability. Since the early days of electric power engineering the fault location problem has been studied and several techniques were developed. But the power systems have been changing since those days and new problems arrive each day. The new challenge for the power protection engineers nowadays is to combine the new trend on PDS, known as distributed generation (DG), with the protection schemes, in which the fault location is included. Distributed generation is defined as the generation of power inside the PDS [1], and because of that, it changes the characteristics of the distribution systems, occasioning an impact in the protection schemes. That includes the fault location, since the current methods do not consider the power generation inside the PDS, which is shown in this paper. This way, to maintain the system security, efficiency, quality and reliability it is necessary to develop new fault location techniques. Since the major part of fault location methods for transmission systems in use nowadays are based in positive sequence apparent impedance with one-terminal data [2], it is developed and presented in this paper a new method based in this measurement. In this way, the compatibility with the current protection systems is maintained. The present article starts showing a classic fault location technique for PDS that don t consider DG in the system. The impacts of DG in PDS are discussed in the third section and the complete proposed method is shown in the fourth section. In the fifth and sixth sections, the results and the conclusions are presented, respectively. 2 Fault Location Using Positive Sequence Apparent Impedance Consider the circuit shown in Figure 1, which represents a faulted distribution system without DG. All the load after the location of the fault are represented as one equivalent load Z r and the total current dispatched to it is I La [3]. The voltage measured at the local terminal is

Local Terminal Load Figure 1: Faulted distribution system. given by the Equation 1: V Sa = x (Z laa I Sa ) + R f I f (1) where: Figure 2: Voltage and Current update at the local terminal. 5. Using the voltage at the fault point calculated in the above step, a new load current (I La ) is calculated. V Sa I Sa Z l x V fa I f R f I La Z r Phase a Voltage (measured) Phase a Current (measured) Line Impedance Matrix [per km] Fault Distance Phase a Fault Point Voltage Fault Current Fault Resistance Phase a Load Current Equivalent Load Matrix Multiplying both sides of Equation 1 by If (fault current complex conjugate) and observing that I f If R f is a real number, Equation 2 is obtained: where: x = I ( I ) V Sa If ( Z La I Sa If ) (2) I f = I Sa I La (3) The Equations 2 and 3 are valid for phase-toground faults and the following algorithm can be used to locate the fault: 1. It is assumed I La as the total load current before the fault occurrence (I Sapre fault ). 2. Using Equation 3 an estimative of the fault current is calculated. 3. Using Equation 2 a fault point is estimated. 4. Using Equation 4 the voltage at the estimated fault point is calculated. V fa V Sa Z La I Sa V fb = V Sb x Z Lb I Sb (4) V fc V Sc Z Lc I Sc 6. With an updated load current, the algorithm restarts at step 2. On step 5 of the described algorithm, it is necessary to calculate the system load current. This current is obtained with the direct circuit analysis. As shown in Figure 1, the load current is the current beyond the fault point. Knowing the voltage at the fault point, which is estimated, and the equivalent load, obtained using a constant impedance model of the loads and considering the line impedances, it is easy to obtain the load current I La. After the convergence of this algorithm the fault will be estimated in any section of the PDS. If the fault is localized in any section after the first one, an update of V Sa and I Sa for the values of voltage and current at the next bus is done. This update is done to diminish the errors referring to the line losses and the unique topology of PDS, which is the distributed loads along the lines. As shown in Figure 2 the voltage and current update is done by the Equations 5 to 7: V k+1 = V k Z k I k (5) I Lk = V k Y Lk (6) I k = I k 1 I Lk (7) With the voltage and current at the local terminal updated, the algorithm starts again and a new fault point is determined. This process rests until the fault is estimated at the same section of the updated voltage and current, V Sa and I Sa, or the feeder ends.

3 Distributed Generation Impacts The problems related to the connection of power generators inside the PDS appears in different areas of power engineering: stability, voltage regulation, protection systems and others. Many different consequences enclose at the same time more than one area, as the occurrence of voltage sag when using overcurrent protection in systems with DG, as described in [4]. The main impact is the change of the power flow of the system. Distribution systems were naturally radial, because they had only one source of power. Now with DG, the distribution systems can have more than one source of power. In this way, the system is no longer radial. In fault analysis, the insertion of a distributed generation in a distribution system makes the fault current to vary, since it contributes with power in the fault state. Thus, parameters like the fault current magnitude are changed, since there is a dynamic influence of the new machine on the system. Besides the fault current magnitude, the fault current direction (angle of the current phasor) in the different sections of the system is also a parameter that changes. The DG contribution to the system in the fault state can change the current direction in some of the feeder sections. The magnitude and the direction of the fault current are parameters that vary with the injected power by the DG and the siting of it in the system [5]. Another important impact of the DG in PDS inhabits directly on the protection systems. The protection schemes of PDS commonly use nondirectional overcurrent relays, sectionalizers, automatic reclosers, fuses and circuit breakers [6]. The presence of the DG in PDS modifies, as explained, the fault current magnitude and direction. Thus, the coordination and adjustment of these equipment must be done again [7], this time considering the DG. Still, since DG affects the radial characteristic of the system, new protection equipment with directional characteristic must be incorporated to the system in order to detect faults correctly, in order to promote an efficient protection of the system. 4 Modified Fault Location Method Considering Distributed Generation Consider the PDS with DG shown in Figure 3. The system can be splitted in two separate parts: the part before the generator and the part after the generator. As shown in Figure 3, the part before the DG corresponds to the buses 1 to j 1 and the part after the DG corresponds to the buses j + 1 to n + 2. The proposed fault location algorithm considering DG starts with steps 1 to 6 described on section 2. However, a electric modeling of the generator is done in these steps, in order to consider the DG in the fault location process. The algorithm starts considering a fault in the beginning of the feeder, thus, before the DG: 1. I La is assumed as the load current before the fault state (I Sapre fault ). 2. Equation 3 is used to calculate the fault current. 3. Using Equation 2 the fault point is estimated. 4. The voltage at the fault point is calculated. For that, all system topology is considered, including DG, using the modeling described on section 4.1. Voltages and currents out of the buses for buses before the faulted bus are calculated. As shown in Figure 2, the fault point voltage is calculated using Equation 8: V f = V n 1 I n 1 Z line x (8) where Z line is the line impedance per km in the faulted section and x is the distance from bus n 1 until the fault point (in km). 5. Using the voltage at the fault point calculated at the previous step, a Thévenin equivalent circuit of all system beyond the fault Local Terminal Distributed generation Figure 3: Distribution system with distributed generation.

point is done. If the estimated fault location in step 3 is after DG, the equivalent circuit is simply the parallel of all loads mixed with the line impedance after the estimated fault point, for there are no generating devices after the fault. After that, the load current is updated again, with equation 4, but this time with the voltage and current values, V Sa and I Sa, updated to data of the first bus before the fault point. If the fault is estimated before the DG, the Thévenin equivalent circuit will have a source of power. In this case the new load current is obtained using Equation 9: I La = (V f V th ) Z th (9) 6. Back to step 2, with the updated data of the load current. 4.1 Distributed Generation Modeling The distributed generation electric model used in the algorithm is the model of a synchronous generator in the subtransient time period (very first cycles after the occurrence of a fault), as described in [8]. The model, shown in Figure 4, is composed by the machine subtransient reactance X s, its armature resistance R a and its internal voltage E g. The generator internal voltage can be obtained by a power flow algorithm for PDS including DG, as described in [9], where the voltage at the generator bus and the current injected by it is obtained using the pre-fault state measured characteristics of the system. As the study period is the subtransient one, it is assumed that the internal voltage of the generator is kept constant during the fault, and an electrical model for the DG is obtained. 4.2 Voltages and Currents Calculation With the faulted system and assuming that loads, line impedances and local terminal voltage and current data are available, the voltage and current of the bus very before the distributed generation Figure 4: Distributed generation model. Local Terminal Distributed Generation Figure 5: Faulted distribution system with distributed generation. is obtained through successive voltage and current calculations in the buses before the fault, as shown in Equations 10 to 12, only to load buses: V k+1 = V k Z line I k (10) I Lk = V k /Z k (11) I k = I k 1 I Lk (12) where V k and I k are related to the already calculated bus, V k+1 and I k+1 are related to the interested values of voltage and current of the bus to be calculated and Z k is the load impedance of the bus k. With the voltage and current at the local terminal during the fault period known, the voltages and currents at the posterior buses are calculated successively, until the estimated fault section. If the DG is in the way between the local terminal and the fault, the influence of the DG must be calculated, using the Expressions 13 to 15 (using the notation of Figure 5): V j = V j 1 Z line I j (13) I GD = V j E g (X s R a) (14) I j+1 = I j I GD (15) where in Equation 14 the machine parameters developed on Section 4.1 appear. 5 Simulations and Results Towards the method validation a total of 67 threephase solid faults in a distribution feeder were simulated. The distribution system was taken from the literature [10] and a distributed generation facility was added. The system was modeled in the ATP/EMTP software [11], and also where the faults were simulated. The fault location algorithm was implemented in the MATLAB R software [12]. The study system, shown in Figure 6, has a total three-phase power of 14,5 MVA and works

Distributed Generation 0,2 Substation Figure 6: Distribution system with distributed generation for study. in 13,8 kv. The DG contributes with 3,2 MVA of this power and works with 440 V. It is connected to the system by a transformer. The total line length is 27,6 km, and the DG is in the km 11,86. First the classic fault location technique described in [3] was implemented and the 67 faults simulated tested its efficiency. The results are shown in Figure 7. The distributed generation influences the results of this method, specially for faults located after the DG point, where the error increases, getting to high levels of error, around 20%. The same 67 fault cases were tested with the proposed technique in this work. As the results shown in Figure 8, the method revealed efficient in the location of the simulated faults. The error introduced by the DG in [3] is diminished with the new methodology. The error is practically zero for all simulated fault (0,2% = 55 meters), including for faults after the DG, without the influence of the fault point. As the fault distance increases in relation to the local terminal, the error is held in a constant level, even after the point where the DG is inserted (11,86 km). Thus, the method shows its robustness in relation to the possible different DG locations in the system, estimating the fault points with precision independently from where the DG is inserted. Error [% line] 20 15 10 5 0 0 3 5 7 9 11 13 15 17 19 21 23 25 27 Fault Distance [km] Figure 7: Classic method results in DG systems. Error [% line] 0,15 0,1 0,05 0 0 3 5 7 9 11 13 15 17 19 21 23 25 27 Fault distance [km] Figure 8: Proposed technique results is DG systems. 6 Conclusions In this article a new fault location method considering the DG is proposed, described and analyzed. The results obtained show the high precision of the method when compared to methods that are currently in use, showing that the methodology is worthy of continued research aiming the improvement of the fault point estimative in the present distribution systems. Acknowledgments: The authors would like to thank Companhia Estadual de Energia Elétrica do Rio Grande do Sul (CEEE-RS) for financing this work, via project #9923983. References: [1] T. Ackerman, G. Andersson and L. Soder, Distributed generation: A definition, Electric Power Systems Research, Vol.57, No.3, 2001, pp. 195-204. [2] T. Takagi et al, Development of a new type fault locator using the one-terminal voltage and current data, IEEE Transactions on Power Apparatus and Systems, Vol.101, No.8, 1982, pp. 2892-2898. [3] Seung-Jae Lee et al, An Intelligent and Efficient Fault Location and Diagnosis Scheme for Radial Distribution Systems, IEEE Transactions on Power Delivery, Vol.19, No.2, 2004, pp. 524-532. [4] J. C. Gómez and M. M. Morcos, Coordination of Voltage Sag and Overcurrent Protection in DG systems, IEEE Transactions on Power Delivery, Vol.20, No.1, 2005, pp. 214 218. [5] G. Carpinelli, G. Celli, F. Pilo and A. Russo, Distributed generation siting and sizing un-

der uncertainty, Proc. IEEE Power Tech Proceedings, Porto, Sep. 2001. [6] H. S. Horowitz and A. G. Phadke, Power System Relaying, Research Studies Press LTD, 1995. [7] A. Girgis and S. Brahma, Effect of Distributed Generation on Protective Device coordination in distribution system, Conference on Large Engineering Systems, July 2001. [8] P. Kundur, Power System Stability and Control, McGraw-Hill, 1994. [9] Y. Zhu and K. Tomsovic, Adaptative Power Flow Method for Distribution Systems with Dispersed Generation, IEEE Transactions on Power Delivery, Vol.17, No.3, 2002, pp. 822-827. [10] J. J. Wakileh and A. Pahwa, Optimization of distribution system design to accommodate cold load pickup, IEEE Transactions on Power Delivery, Vol.12, No.1, 1997, pp. 339-345. [11] L. Prikler and H. K. Hoidalen, ATPDraw Version 3.5 User s Manual: preliminary release no. 1.0, 2002. [12] The Mathworks Inc., Matlab: The Language of Technical Computing. Version 6.5R13, 2002.