Week No. 6 Chapter Six: Power Factor Improvement The electrical energy is almost wholly generated, transmitted and distributed in the form of alternating current. Therefore, the question of power factor immediately comes into picture. Most of the loads (e.g. induction motors, arc lamps) are inductive in nature and hence have low lagging power factor. The low power factor is highly undesirable as it causes an increase in current, resulting in additional losses of active. In order to ensure most favorable conditions for a supply system from engineering and economical standpoint, it is important to have power factor as close to unity as possible. Thus, it is important to discuss the various methods of power factor improvement 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 1
6.1 Power Factor The cosine of angle between voltage and current in an a.c. circuit is known as power factor. The term cos φ is called the power factor of the circuit. Consider an inductive circuit taking a lagging current I from supply voltage V; the angle of lag being φ. The phasor diagram of the circuit is shown in Fig. 6.1. The circuit current I can be resolved into two perpendicular components, namely ; (a) I cos φ in phase with V (b) I sin φ 90 o out of phase with V 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 2
The component I cos φ is known as active or wattful component, whereas component I sin φ is called the reactive or wattless component. Circuit having small reactive current (i.e., I sin φ) will have high power factor and vice-versa. 6.2 Power Triangle The analysis of power factor can also be made in terms of power drawn by the a.c. circuit. The power triangle OAB shown in Fig. 6.2 where OA = VI cos φ and represents the active power in watts or kw AB = VI sin φ and represents the reactive power in VAR or kvar OB = VI and represents the apparent power in VA or kva 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 3
The following points may be noted form the power triangle : (i) The apparent power in an a.c. circuit has two components viz., active and reactive power at right angles to each other. OB 2 = OA 2 + AB 2 or (apparent power) 2 = (active power) 2 + (reactive power) 2 or (kva) 2 = (kw) 2 + (kvar) 2 (ii) Power factor, cos φ = OA active power = OB apparent power = kw kva Thus the power factor of a circuit may also be defined as the ratio of active power to the apparent power. (iii) The lagging reactive power is responsible for the low power factor. It is clear from the power triangle that smaller the reactive power component, the higher is the power factor of the circuit. kvar = kva sin φ = kw cos φ sin φ kvar = kw tan φ 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 4
(iv) For leading currents, the power triangle becomes reversed. This fact provides a key to the power factor improvement. If a device taking leading reactive power (e.g. capacitor) is connected in parallel with the load, then: The lagging reactive power of the load will be partly neutralized, thus Improving the power factor of the load. (v) The power factor of a circuit can be defined in one of the following three ways: (a) Power factor = cos φ = cosine of angle between V and I (b) Power factor = R Z = Resistance Impedance (c) Power factor = VIcosφ Active power VI = Apparent Power (vi) The reactive power is neither consumed in the circuit nor it does any useful work. 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 5
6.4 Causes of Low Power Factor Low power factor is undesirable from economic point of view. The following are the causes of low power factor: (i) AC 1-φ and 3-φ induction motors operate at low lagging power factor specially at light load. (ii) Lamps and industrial heating furnaces operate at low lagging power factor. (iii) The load on the power system is varying results in decreasing power factor. 6.5 Power Factor Improvement The low power factor is mainly due to the fact that most of the power loads are inductive and, therefore, take lagging currents. In order to improve the power factor, some device taking leading power should be connected in parallel with the load, such device can be a capacitor. The capacitor draws a leading current and partly or completely neutralizes the lagging reactive component of load current. This raises the power factor of the load. 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 6
Illustration. To illustrate the power factor improvement by a capacitor, consider a single phase load taking lagging current I at a power factor cosφ 1 as shown in Fig. 6.3. The capacitor C is connected in parallel with the load. The capacitor draws current I C which leads the supply voltage by 90 o. The resulting line current I is the phasor sum of I and I C and its angle of lag is φ 2 as shown in the phasor diagram of Fig. 6.3. (iii). 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 7
It is clear that φ 2 is less than φ 1, so that cos φ 2 is greater than cos φ 1. Hence, the power factor of the load is improved. 6.6 Power Factor Improvement Equipment Normally, the power factor of the whole load on a large generating station is in the region of 0 8 to 0 9. However, sometimes it is lower and in such cases it is generally desirable to take special steps to improve the power factor. This can be achieved by the following equipment : 1. Static capacitors. 2. Synchronous condenser. 3. Phase advancers. 1. Static capacitor. The power factor can be improved by connecting capacitors in parallel with the equipment operating at lagging power factor. The capacitor (generally known as static capacitor) draws a leading current and partly or completely neutralizes the lagging reactive component of load current, thus improving the power factor. 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 8
For three-phase loads, the capacitors can be connected in delta or star as shown in Fig. 6.4. 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 9
2. Synchronous condenser. A synchronous motor takes a leading current when overexcited and, therefore, behaves as a capacitor. An over-excited synchronous motor running on no load is known as synchronous condenser. When such a machine is connected in parallel with the supply, as shown in Fig. 6.5, it takes a leading current which partly neutralizes the lagging reactive component of the load. Thus the power factor is improved. 3. Phase advancers. Phase advancers are used to improve the power factor of induction motors. The phase advancer is simply an a.c. exciter. 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 10
6.7 Calculations of Power Factor Correction Consider an inductive load taking a lagging current I at a power factor cos φ 1. In order to improve the power factor of this circuit, one of the power factor improvement equipments given in section 6.6 can be connected in parallel with the load which takes a leading reactive component. Fig. 6.6 (i) shows a capacitor connected across the load. 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 11
The capacitor takes a current I C which leads the supply voltage V by 90 o. The current I C partly cancels the lagging reactive component of the load current as shown in the phasor diagram in Fig. 6.6 (ii). The resultant circuit current becomes I and its angle of lag is φ 2. It is clear that φ 2 is less than φ 1 so that new power factor cos φ 2 is more than the previous power factor cos φ 1. Power triangle. The power factor correction can also be illustrated from power triangle. Thus referring to Fig. 6.7, the power triangle OAB is for the power factor cos φ 1, whereas power triangle OAC is for the improved power factor cos φ 2. 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 12
It may be seen that active power (OA) does not change with power factor improvement. However, the lagging kvar of the load is reduced by the pf correction equipment, thus improving the pf to cos φ 2. Leading kvar supplied by pf correction equipment = BC = AB AC = kvar 1 kvar 2 = OA (tan φ 1 tan φ 2 ) = kw (tan φ 1 tan φ 2 ) Knowing the leading kvar supplied by the pf correction equipment, the desired results can be obtained. 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 13
3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 14
3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 15
3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 16
3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 17
3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 18
3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 19
Pb 1: Assignment Number Three Pb.2 Pb. 3 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 20
6.8 Importance of Power Factor Improvement The improvement of power factor is very important for both consumers and generating stations as discussed below : (i) For consumers. A consumer has to pay electricity charges for his maximum demand in kva plus the units consumed. If the consumer improves the power factor, then there is a reduction in his maximum kva demand and consequently there will be annual saving due to maximum demand charges. Although power factor improvement involves extra annual expenditure on account of p.f. correction equipment, yet improvement of p.f. to a proper value results in the net annual saving for the consumer. 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 21
(ii) For generating stations. A generating station is as much concerned with power factor improvement as the consumer. The generators in a power station are rated in kva but the useful output depends upon kw output. As station output is kw = kva cos φ, therefore, number of units supplied by it depends upon the power factor. The greater the power factor of the generating station, the higher is the kwh it delivers to the system. This leads to the conclusion that improved power factor increases the earning capacity of the power station 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 22
6.9 Most Economical Power Factor (Week No 6) If a consumer improves the power factor, there is reduction in his maximum kva demand and hence there will be annual saving over the maximum demand charges. However, when power factor is improved, it involves capital investment on the power factor correction equipment. The consumer will suffer expenditure every year in the shape of annual interest and depreciation on the investment made over the p.f. correction equipment. Therefore, the net annual saving will be equal to the annual saving in maximum demand charges minus annual expenditure incurred on p.f. correction equipment. The value to which the power factor should be improved so as to have maximum net annual saving is known as the most economical power factor. 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 23
Consider a consumer taking a peak load of P kw at a power factor of cosφ 1 and charged at a rate of Rs x per kva of maximum demand per annum. Suppose the consumer improves the power factor to cos φ 2 by installing p.f. correction equipment. Let costs acquired on the p.f. correction equipment be Rs y per kvar per annum. The power triangle at the original p.f. cos φ 1 is OAB and for the improved p.f. cos φ 2, it is OAC [See Fig. 6.13]. kva max. demand at cos φ 1, kva 1 = P/cos φ 1 = P sec φ 1 kva max. demand at cos φ 2, kva 2 = P/cos φ 2 = P sec φ 2 Annual saving in maximum demand charges = Rs x (kva 1 kva 2 ) = Rs x (P sec φ 1 P sec φ 2 ) = Rs x P (sec φ 1 sec φ 2 )...(i) 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 24
Reactive power at cos φ 1, kvar 1 = P tan φ 1 Reactive power at cos φ 2, kvar 2 = P tan φ 2 Leading kvar taken by p.f. correction equipment = P (tan φ 1 tan φ 2 ) Annual cost of p.f. correction equipment = Rs Py (tan φ 1 tan φ 2 )...(ii) Net annual saving, S = exp. (i) exp. (ii) = xp (sec φ 1 sec φ 2 ) yp (tan φ 1 tan φ 2 ) In this expression, only φ 2 is variable while all other quantities are fixed. Therefore, the net annual saving will be maximum if differentiation of above expression w.r.t. φ 2 is zero i.e. d(s) dφ 2 = 0 Most economical power factor, It may be noted that the most economical power factor (cos φ 2 ) depends upon the relative costs of supply and p.f. correction equipment but is independent of the original p.f. cos φ 1. 3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 25
3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 26
3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 27
3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 28
3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 29
3/11/2014 Principle of Power System/ Dr. Ramzi A. Abdul-Halem 30