LABORATORY MEASUREMENTS OF THE REDUCTION OF TRANSMITTED IMPACT NOISE PANETTI OVERLAID BY CONCRETE FLOORING

Similar documents
LABORATORY MEASUREMENTS OF THE SOUND ABSORPTION COEFFICIENTS OF OSCAR EVO-PANELS

Measurement of Acoustic Properties of light weight concrete SL-Deck

TFI Report Sound Absorption Impact Sound Insulation

TFI Report Sound Absorption Impact Sound Insulation

TFI Report Sound Absorption Impact Sound Insulation

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 7MM TESTED WITH A 20MM AIR GAP IN A REVERBERATION ROOM.

TFI Report Sound Absorption Impact Sound Insulation

LABORATORY MEASUREMENTS OF THE SOUND ABSORPTION OF CLASSICTONE 700 ASTM C Type E Mounting. Test Number 2

Consultancy Report Ref: 9383-R01

Test Report. RI Acoustic Lab. Measurement of Sound Absorption Coefficient for RockDelta NoiStop Noise Barrier. 20 Feb. 07

TFI Report Impact Sound Insulation

MEASUREMENTS OF SOUND ABSORPTION TIMBERCRETE

A L I O N Technical Center. Test Report. Port Coquitlam, British Columbia, Canada

Testing Procedure: AS ISO

TFI Report Impact Sound Insulation

RIVERBANK ACOUSTICAL LABORATORIES

Yalıtım Kontrol Koruma. Insulation Control Protection

Technical Report. Project. The Laboratory Determination of The Random Incidence sound Absorption Coefficient of VertiQ Panels.

A L I O N Technical Center. Test Report

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 24MM TESTED WITH NO AIR GAP MEASURED IN A REVERBERATION ROOM.

RIVERBANK ACOUSTICAL LABORATORIES

DELTA Test Report. DANAK TEST Reg. no Measurement of Sound Absorption Coefficient for Kvadrat Soft Cells Wall Panel Type Time

Measurement of sound absorption coefficient for Fraster felt SpaceCover

DELTA Test Report. Measurement of sound absorption coefficient for 15 mm Fraster felt Plus acoustic panels with mounting depth 45 mm

ISO INTERNATIONAL STANDARD

1238. Relation between reduction of weighted impact sound pressure level and shape of small size specimen of floating floor construction

DELTA Test Report. Measurement of Sound Absorption for AqFlex ON, one Sample as a discrete Object. Performed for Flex Acoustics

Laboratory for Acoustics. Determination of the sound insulation of sliding door constructions, manufactured by Metaflex

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6266/ARL-SA6274 Revision 0 ARL

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

Fabric Dazzle 6086 Manufacturer Carnegie Fabrics

Renolit stretch ceilings

ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6712/ARL-SA6713 Revision 0 ARL

Fabric XPRESS + PU-foam Manufacturer Gabriel A/S

REPORT N CR

R & D AKUSTIKA * SIA. Test Report of laboratory Sound Insulation measurements Nr. 569 / 2011 AL 8.4. CUSTOMER: AEROC AS (Estonia)

Fabric REFLECTACOUSTIC

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6986/ARL-SA6987 Revision 0 ARL

Fabric ALEX. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/09

Fabric Sport. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/02

Fabric VELOS STRATO. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/10

stylegreen Iceland Moss / Reindeer Moss of the company FlowerArt

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6956 Revision 1 ARL

Fabric UDINE. Measurement of sound absorption according to EN ISO 354. Test Report No. M102794/32

Fabric Zetacoustic. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/07

An examination of some aspects of the use of ISO 140 Part 4 and 7 in field measurements.

Fabric TWIST MELANGE Manufacturer Gabriel A/S

Roller blind fabric PRIMACOUSTIC R

Acoustic response in non-diffuse rooms

Fabric Medley Manufacturer Gabriel A/S

Fabric Umbria III R. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/13

Paseo Recoletos, nº Madrid TEST REPORT

Fabric STREAMER pro. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M111250/04

LABORATORY MEASUREMENT OF SOUND ABSORPTION OF SONOGLASS SPRAY-ON TREATMENT IN THREE CONFIGURATIONS

Laboratory for Acoustics

Curtain fabric type Ace Manufacturer Kvadrat A/S

Calcul des coefficients d'absorption alpha sabine

Laboratory for Acoustics. Determination of the sound absorption (reverberation room method) of Airpanel, manufacturer Texdecor

ISO INTERNATIONAL STANDARD

Report. Laboratory for Acoustics

ENVIRONMENTAL NOISE IMPACT ASSESSMENT

Fabric Corsica. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M111250/16

Development of a small-scale reverberation room

Report. Laboratory for Acoustics Determination of the sound absorption (reverberation room method) of different wired mats, manufacturer Rockwool

Evaluation of standards for transmission loss tests

Laboratory for Acoustics. Determination of the sound absorption (reverberation room method) of curtains, manufacturer Vescom BV

Standard ECMA-108 3rd Edition - December Measurement of High-frequency Noise emitted by Information Technology and Telecommunications Equipment

Report. Laboratory for Acoustics

Report. Draft. Laboratory for Acoustics

Page 1 of 10 pages Appendix, 5 pages Report no.: P Glostrup, October 12th 2012 Project: Claimant:

Laboratory for Acoustics

INVESTIGATIONS INTO THE PERFORMANCE OF THE REVERBERATION CHAMBER OF THE INTEGRATED ACOUSTICS LABORATORY. A Thesis Presented to The Academic Faculty

Acoustic design of lightweight cabin walls for cruise ships

Report. P.O. Box 70 NL 5700 AB Deurne The Netherlands Report number: A E-RA Date: 12 februari 2014 TS/TS/JW/A E-RA

ISO 354 INTERNATIONAL STANDARD. Acoustics Measurement of sound absorption in a reverberation room

Study of Wenger Audience Seating Chair Absorption. Ron Freiheit

Laser scanning vibrometry measurements on a light weight building element

Using an ambisonic microphone for measurement of the diffuse state in a reverberant room

REPORT. Client. Test object. Date of testt. Results. Rönnåsgatan 5B Ulricehamn. (7 appendices) content of the

Sound radiation and sound insulation

The information included in the following report presents the results of sound pressure and sound power testing.

Summary. The basic principles of the simulation technique SERT

Determination of sound absorption coefficient in impedance tubes according to ISO (2 appendices)

Product Data. Brüel & Kjær B. Sound Intensity Calibrator Type 3541

MAC Aura XB Acoustic Test Report

SIMPLE APPLICATION OF STI-METHOD IN PREDICTING SPEECH TRANSMISSION IN CLASSROOMS. Jukka Keränen, Petra Larm, Valtteri Hongisto

Part 2: Methods for special reverberation test rooms

ASSOCIATION POUR LA CERTIFICATION DES MATERIAUX ISOLANTS

Sound power level determinations at laboratory and field environments: An experimental comparison

Certificate Sound reduction of building elements

Acoustics - Measurements on silencers in situ (ISO 11820:1996) Akustik - Ljuddämpare - Fältmätningar (ISO 11820:1996)

EUROVENT 8/12 SOUND TEST METHOD FOR DUCTED FAN COIL UNITS. FCP 2008 testing procedures FCP acoustical test method pag. 1

Document No 10/6298/001/GLA/O/R/001 Issue : B2. Kingspan Renewables Ltd. Kingspan KW6 Wind Turbine Noise Performance Test

Technical Note. Measurement of Sound Absorption for Flex Acoustics AqTube. Performed for Flex Acoustics. TC Project no.: T Page 1 of 7

EXPERIMENTAL VERIFICATION OF THE EUROPEAN METHODOLOGY FOR TESTING NOISE BARRIERS IN SITU: SOUND REFLECTION

Available online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015

ISO INTERNATIONAL STANDARD. Acoustics Acoustic insulation for pipes, valves and flanges

Accuracy of speech transmission index predictions based on the reverberation time and signal-to-noise ratio Galbrun, Laurent; Kitapci, Kivanc

ISO 3741 INTERNATIONAL STANDARD

Transcription:

Report No. L/3194 Page 1 of 8 for EA Mimarlik Insaat Teknolojileri San.ve. Tic.Ltd.Sti 1420/3 Sokak NO. 22 Kizilkanat Silesi D Blok D.12 Alsancak Izmir Turkey Dated: 18 July 2011 LABORATORY MEASUREMENTS OF THE REDUCTION OF TRANSMITTED IMPACT NOISE BY PANETTI OVERLAID BY CONCRETE FLOORING Report Author: M Sawyer MIOA ACOUSTICAL INVESTIGATION & RESEARCH ORGANISATION LTD Duxons Turn Maylands Avenue Hemel Hempstead Hertfordshire HP2 4SB Telephone: 01442 247146

LABORATORY MEASUREMENTS OF THE REDUCTION OF TRANSMITTED IMPACT NOISE BY PANETTI OVERLAID BY CONCRETE FLOORING 1. INTRODUCTION This report presents the results of measurements made in the AIRO Acoustics Laboratory of the reduction of transmitted impact noise by 5 mm and 8 mm thick Panetti when overlaid by concrete flooring. The measurements were made on 6 July 2011 for EA Mimarlik Insaat Teknolojileri San.ve. Tic.Ltd.Sti. Measurements of the reduction of transmitted impact noise, Reduction of Impact Sound Pressure Level ( L), were conducted in accordance with British Standard BS EN ISO 140 (ref 1) (see Appendix A1). Single figure ratings of the reduction of impact noise, known as the Weighted Reduction of Impact Sound Pressure Level ( L w ) and the Spectrum Adaptation Term (C I, ), are derived from these measurements in accordance with British Standard BS EN ISO 717 (ref 2). AIRO is a UKAS accredited testing laboratory No. 0483 and measurements to the above British Standards are included on our schedule of accreditation. UKAS is the United Kingdom Accreditation Service. 2. SUMMARY OF RESULTS The results of the measurements presented in this report are summarised in the following table: AIRO Test No. Test Specimen L w db L/3194/1 5 mm Panetti overlaid by concrete flooring 21 L/3194/2 8 mm Panetti overlaid by concrete flooring 22 Approved by: D L Watts Eur Ing D L Watts BEng CEng FIOA Principal Consultant Report Author: M Sawyer M Sawyer MIOA Laboratory Supervisor Page 2 of 8

3. TEST SPECIMEN DETAILS AND CONDITIONS 3.1 5 mm Panetti overlaid by concrete flooring AIRO Test No. L/3194/1 The test specimen comprised 5 mm thick Panetti polyethylene-based polymeric foam (100 kg/m³) which was supplied as a 1250 mm wide roll and laid with tightly butted edges to cover the 3.80 m x 3.70 m Standard Floor. The test specimen was overlaid by a 75 mm thick precast concrete slab of area 1.2 m x 1.2 m to simulate a floating screed. The measured mass of the 5 mm Panetti and nominal mass of the precast concrete slab are 0.5 kg/m² and 150 kg/m² respectively. 3.2 8 mm Panetti overlaid by concrete flooring AIRO Test No. L/3194/2 The test specimen comprised 8 mm thick Panetti polyethylene-based polymeric foam (100 kg/m³) which was supplied as a 1250 mm wide roll and laid with tightly butted edges to cover the 3.80 m x 3.70 m Standard Floor. The test specimen was overlaid by a 75 mm thick precast concrete slab of area 1.2 m x 1.2 m to simulate a floating screed. The measured mass of the 8 mm Panetti and nominal mass of the precast concrete slab are 0.8 kg/m² and 150 kg/m² respectively. Page 3 of 8

Reduction of Impact Sound Pressure Level according to BS EN ISO 140-8:1998 Test No. L/3194/1 Date of Test: 6 July 2011 Client: EA Mimarlik Insaat Teknolojileri San.ve. Tic.Ltd.Sti. Specimen: 5 mm Panetti overlaid by concrete flooring Installed by: AIRO Receive Chamber volume: 208 m³ Source Chamber air temperature: 22 C Source Chamber relative humidity: 80% Mass per unit area: 0.5 kg/m² Frequency (Hz) ÀL (db) L n,0 (db) 60 50 63 80 100 4.8 62.4 125 4.4 66.5 160 2.6 66.9 200 4.5 70.1 250 3.9 70.5 315 6.2 71.8 400 13.2 70.8 C 500 11.6 74.1 630 18.2 73.1 800 19.0 73.8 1000 18.7 74.2 1250 22.3 74.8 1600 23.8 75.4 2000 27.4 75.7 2500 31.0 76.0 3150 32.3 75.3 4000 34.0 74.2 5000 37.2 72.1 6300 8000 10000 Measured result Reduction of Impact Sound Pressure Level, ÀL (db) 50 40 30 20 10 0 50 80 125 200 315 500 800 1250 2000 3150 5000 Frequency (Hz) Rating according to BS EN ISO 717-2:1997 L n,r,0,w = 78 db C I,r,0 = -11 db L w = 21 db C I, = -11 db L n,r,w = 57 db C I,r = 0 db These results are based on test made with an artificial source under laboratory conditions (engineering method) Approved by: D L Watts Eur Ing D L Watts BEng CEng FIOA Principal Consultant Report Author: M Sawyer M Sawyer MIOA Laboratory Supervisor Page 4 of 8

Reduction of Impact Sound Pressure Level according to BS EN ISO 140-8:1998 Test No. L/3194/2 Date of Test: 6 July 2011 Client: EA Mimarlik Insaat Teknolojileri San.ve. Tic.Ltd.Sti. Specimen: 8 mm Panetti overlaid by concrete flooring Installed by: AIRO Receive Chamber volume: 208 m³ Source Chamber air temperature: 22 C Source Chamber relative humidity: 80% Mass per unit area: 0.8 kg/m² Frequency (Hz) ÀL (db) L n,0 (db) 60 50 63 80 100 3.6 62.4 125 3.4 66.5 160 3.7 66.9 200 4.2 70.1 250 7.6 70.5 315 11.0 71.8 400 17.6 70.8 C 500 14.6 74.1 630 21.1 73.1 800 23.2 73.8 1000 21.5 74.2 1250 24.7 74.8 1600 27.3 75.4 2000 31.8 75.7 2500 32.5 76.0 3150 31.1 75.3 4000 33.5 74.2 5000 38.1 72.1 6300 8000 10000 Measured result Reduction of Impact Sound Pressure Level, ÀL (db) 50 40 30 20 10 0 50 80 125 200 315 500 800 1250 2000 3150 5000 Frequency (Hz) Rating according to BS EN ISO 717-2:1997 L n,r,0,w = 78 db C I,r,0 = -11 db L w = 22 db C I, = -11 db L n,r,w = 56 db C I,r = 0 db These results are based on test made with an artificial source under laboratory conditions (engineering method) Approved by: D L Watts Eur Ing D L Watts BEng CEng FIOA Principal Consultant Report Author: M Sawyer M Sawyer MIOA Laboratory Supervisor Page 5 of 8

APPENDIX A1 - METHOD OF MEASUREMENT TO BS EN ISO 140-8:1998 The reduction of impact noise due to a floor covering is measured by use of an artificial source of impact sound, known as a tapping machine, which has a mass of approximately 18 kg and is supported on three legs. A Standard Floor comprising 150 mm thick reinforced concrete and area 11.2 square metres when viewed from the underside is suspended in an aperture between two vertically adjacent reverberant chambers, both constructed of 215 mm brick with reinforced concrete floors and ceilings. The lower chamber, used as the receiving chamber, rests on resilient mountings to give good acoustic isolation from the source chamber above it and the building exterior. To improve the diffusion of the sound fields both chambers are irregularly shaped and contain several reflecting diffuser panels. A standard tapping machine is used as the impact source which is located sequentially in five positions over the floor. Measurements are made in the receiving chamber at the one-third octave intervals from 100 Hz to 5000 Hz as prescribed in the Standard (ref 1). The measurements are made with a microphone attached to a rotating microphone boom to obtain a good average of the transmitted sound pressure levels. The process is carried out with the tapping machine placed on the floor covering over the Standard Floor and also in the absence of the floor covering. Measurements are also made of the noise level in the absence of the tapping machine in order that corrections for background noise may be made if appropriate. The Normalized Impact Sound Pressure Level (NISPL) in decibels (db) is calculated in each frequency band using the equation: A L n,0 or L L 10 lg n i + A 0 = db Equation (i) where: L n,0 is the NISPL of the Standard Floor (db) L n L i A is the NISPL of the sample on the Standard Floor (db) is the measured sound pressure level in the receiving chamber (db re 20μPa) is the equivalent absorption area in the receiving chamber (m²) A 0 is the reference absorption areas, equal to 10 m² The equivalent absorption area in the receiving chamber is determined from twelve sets of reverberation time measurements using a microphone connected to a rotating microphone boom. The measurements are made in accordance with International Standard ISO 354:2003 (ref 3) and the value of 'A' determined using Sabine's formula: A = 0.16V m² Equation (ii) T where: V is the volume of the receiving chamber (m³) T is the reverberation time of the receiving chamber (seconds) Page 6 of 8

The Reduction of Impact Sound Pressure Level (RISPL) is then: Δ L = L - L db Equation (iii) n,0 n To obtain a repeatable single figure rating of the sample's performance, the method prescribed in BS EN ISO 717-2:1997 is followed. This method applies the measured RISPL figures to a set of specified NISPL figures for an idealized 'Reference Floor' in order that the Weighted Reduction of Impact Sound Pressure Level ( L w ) in decibels (db) and the related Spectrum Adaptation Term (C I, ), also in decibels, may be calculated. The calibration of all equipment is traceable via an unbroken chain to National Standards. Deviations from BS EN ISO 140-8:1998 Methodology BS EN ISO 140-8:1998 requires that the resilient layer and concrete floating floor should cover the entire area, or at least 10 m², of the Standard Floor. For this project a 75 mm thick precast concrete slab of area 1.2 m x 1.2 m was laid over the resilient layer which covered the entire area of the Standard Floor. Measurements were made using 5 tapping machine positions on the precast slab which was moved across the resilient layer and Standard Floor in order that a good average may be obtained. APPENDIX A2 - PRACTICAL APPLICATION OF TEST RESULTS It should be noted that the Weighted Reduction of Impact Sound Pressure Level ( L w ) is a property of the floor covering alone and is obtained by comparing Reductions of Impact Sound Pressure Level ( L) measured on a heavy concrete floor with the performance of the idealized Reference Floor. In buildings, when the floor covering forms part of a floor the resultant transmitted impact sound will depend upon the performance of the base floor and additional factors such as the relative surface areas involved and the nature and acoustic characteristics of the receiving space. Page 7 of 8

APPENDIX A3 - REFERENCES 1. British Standard BS EN ISO 140 Acoustics - Measurement of sound insulation in buildings and of building elements BS EN ISO 140-8:1998 Laboratory measurements of the reduction of transmitted impact noise by floor coverings on a heavyweight standard floor 2. British Standard BS EN ISO 717 Acoustics - Rating of sound insulation in buildings and of building elements BS EN ISO 717-1:1997 Impact sound insulation 3. International Standard ISO 354:2003 Acoustics - Measurement of sound absorption in a reverberation room APPENDIX A4 - SCHEDULE OF EQUIPMENT Use Type Serial No. Noise Source B&K 3204 Tapping Machine 351719 Measuring Norsonic 840 Real Time Analyzer 16009 System B&K 4165 ½" Condenser Microphone 1471398 B&K 2669 Microphone Pre-Amplifier 1856926 NEAS 212 Rotating Microphone Boom 12172 Calibration B&K 4228 Pistonphone 1756569 Page 8 of 8