Improving the Control System for Pumped Storage Hydro Plant

Similar documents
EVALUATION OF NEURAL PDF CONTROL STRATEGY APPLIED TO A NONLINEAR MODEL OF A PUMPED-STORAGE HYDROELECTRIC POWER STATION

Simulation of hydroelectric system control. Dewi Jones

Engraving Machine Example

Modeling of Hydraulic Turbine and Governor for Dynamic Studies of HPP

Lecture 5 Classical Control Overview III. Dr. Radhakant Padhi Asst. Professor Dept. of Aerospace Engineering Indian Institute of Science - Bangalore

QFT Framework for Robust Tuning of Power System Stabilizers

LOAD FREQUENCY CONTROL WITH THERMAL AND NUCLEAR INTERCONNECTED POWER SYSTEM USING PID CONTROLLER

Accurate and Estimation Methods for Frequency Response Calculations of Hydroelectric Power Plant

YTÜ Mechanical Engineering Department

CHAPTER 2 MODELING OF POWER SYSTEM

6.1 Sketch the z-domain root locus and find the critical gain for the following systems K., the closed-loop characteristic equation is K + z 0.

Dynamic Behavior of a 2 Variable Speed Pump- Turbine Power Plant

Outline. Classical Control. Lecture 1

YTÜ Mechanical Engineering Department

LFC of an Interconnected Power System with Thyristor Controlled Phase Shifter in the Tie Line

ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 4 Active Power and Frequency Control

Turbines and speed governors

Relationships between Load, Speed Regulation and Frequency. Slope= -R

HYDRO power plant (HPP) turbine governing has been studied extensively in the

Quantitative Feedback Theory based Controller Design of an Unstable System

(b) A unity feedback system is characterized by the transfer function. Design a suitable compensator to meet the following specifications:

Positioning Servo Design Example

AN INTRODUCTION TO THE CONTROL THEORY

Steam-Hydraulic Turbines Load Frequency Controller Based on Fuzzy Logic Control

PID controllers. Laith Batarseh. PID controllers

Robust Tuning of Power System Stabilizers Using Coefficient Diagram Method

VALLIAMMAI ENGINEERING COLLEGE SRM Nagar, Kattankulathur

CHAPTER 2 MATHEMATICAL MODELLING OF AN ISOLATED HYBRID POWER SYSTEM FOR LFC AND BPC

Bangladesh University of Engineering and Technology. EEE 402: Control System I Laboratory

80DB A 40DB 0DB DB

Topic # Feedback Control Systems

EC CONTROL SYSTEM UNIT I- CONTROL SYSTEM MODELING

SAMPLE SOLUTION TO EXAM in MAS501 Control Systems 2 Autumn 2015

Systems Analysis and Control

ME 475/591 Control Systems Final Exam Fall '99

Index. Index. More information. in this web service Cambridge University Press

D(s) G(s) A control system design definition

Feedback Control of Linear SISO systems. Process Dynamics and Control

Wind Turbine Control

Outline. Classical Control. Lecture 5

IMPROVED TECHNIQUE OF MULTI-STAGE COMPENSATION. K. M. Yanev A. Obok Opok

Chapter 9: Transient Stability

Analysis of Coupling Dynamics for Power Systems with Iterative Discrete Decision Making Architectures

Dr Ian R. Manchester Dr Ian R. Manchester AMME 3500 : Root Locus

Application of Model Based Predictive Control to a Pumped Storage Hydroelectric Plant

Dynamic Compensation using root locus method

Load Frequency Control of Multi-Area Power System

Mech 6091 Flight Control System Course Project. Team Member: Bai, Jing Cui, Yi Wang, Xiaoli

ECE317 : Feedback and Control

Introduction to Feedback Control

Economic Operation of Power Systems

ECSE 4962 Control Systems Design. A Brief Tutorial on Control Design

CYBER EXPLORATION LABORATORY EXPERIMENTS

POWER SYSTEM STABILITY

LABORATORY INSTRUCTION MANUAL CONTROL SYSTEM II LAB EE 693

Spontaneous Speed Reversals in Stepper Motors

Exercises for lectures 13 Design using frequency methods

Due Wednesday, February 6th EE/MFS 599 HW #5

FATIMA MICHAEL COLLEGE OF ENGINEERING & TECHNOLOGY

Acceleration Feedback

Department of Electrical and Computer Engineering. EE461: Digital Control - Lab Manual

Electromechanical Oscillations in Hydro- Dominant Power Systems: An Application to the Colombian Power System

Study of Sampled Data Analysis of Dynamic Responses of an Interconnected Hydro Thermal System

Frequency-Bias Tie-Line Control of Hydroelectric Generating Stations for Long Distances

Today (10/23/01) Today. Reading Assignment: 6.3. Gain/phase margin lead/lag compensator Ref. 6.4, 6.7, 6.10

ECE 585 Power System Stability

Research Article. World Journal of Engineering Research and Technology WJERT.

(a) Find the transfer function of the amplifier. Ans.: G(s) =

Frequency Response Techniques

Homework 7 - Solutions

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Type-2 Fuzzy Logic Control of Continuous Stirred Tank Reactor

LABORATORY INSTRUCTION MANUAL CONTROL SYSTEM I LAB EE 593

ROBUSTNESS COMPARISON OF CONTROL SYSTEMS FOR A NUCLEAR POWER PLANT

Dr Ian R. Manchester

Automatic Control 2. Loop shaping. Prof. Alberto Bemporad. University of Trento. Academic year

Stability of CL System

Lecture 12. Upcoming labs: Final Exam on 12/21/2015 (Monday)10:30-12:30

LOAD FREQUENCY CONTROL IN A SINGLE AREA POWER SYSTEM

Control of Electromechanical Systems

CHAPTER 7 STEADY-STATE RESPONSE ANALYSES

9. Two-Degrees-of-Freedom Design

Contents. PART I METHODS AND CONCEPTS 2. Transfer Function Approach Frequency Domain Representations... 42

DYNAMIC RESPONSE OF A GROUP OF SYNCHRONOUS GENERATORS FOLLOWING DISTURBANCES IN DISTRIBUTION GRID

CHAPTER 3 QUARTER AIRCRAFT MODELING

Design and Tuning of Fractional-order PID Controllers for Time-delayed Processes

Topic # Feedback Control. State-Space Systems Closed-loop control using estimators and regulators. Dynamics output feedback

MULTIVARIABLE PROPORTIONAL-INTEGRAL-PLUS (PIP) CONTROL OF THE ALSTOM NONLINEAR GASIFIER MODEL

UNIT-I Economic Operation of Power Systems -1

Digital Control Systems

-MASTER THESIS- ADVANCED ACTIVE POWER AND FREQUENCY CONTROL OF WIND POWER PLANTS

EE 4443/5329. LAB 3: Control of Industrial Systems. Simulation and Hardware Control (PID Design) The Torsion Disks. (ECP Systems-Model: 205)

Dr Ian R. Manchester Dr Ian R. Manchester AMME 3500 : Review

Problem Value Score Total 100/105

Classify a transfer function to see which order or ramp it can follow and with which expected error.

AMME3500: System Dynamics & Control

Control of Manufacturing Processes

Table of Laplacetransform

Modelling the Dynamics of Flight Control Surfaces Under Actuation Compliances and Losses

CDS 101/110a: Lecture 8-1 Frequency Domain Design

Transcription:

011 International Conference on Computer Communication and Management Proc.of CSIT vol.5 (011) (011) IACSIT Press, Singapore Improving the Control System for Pumped Storage Hydro Plant 1 Sa ad. P. Mansoor University of Wales, Bangor Gwynedd LL57 1UT, U.K. Abstract. The operational flexibility of pump storage hydro-stations means that they are often used on a power system (grid) as a means of controlling system frequency and for load management. When used in this role, the response of the generator is determined by the behaviour of its control system (governor). The basic function of a governor is to control frequency variation of the grid where its droop characteristics ensure equitable load sharing between generating units in order to ensure satisfactory and stable operation. The governor setting and in particular the loop gains, are therefore critical to achieving optimum levels of performance. In this paper, a step-by-step procedure taken to construct the new governor is presented. The most relevant results on the evaluation of the governor are shown and its performance advantages compared to the current governor are highlighted. Keywords: governor, pump storage, control 1. Introduction The role of a governor is to control frequency variation of the grid due to dynamic load changes and produce stable operation. A normally governor consists of two feedback loops, a frequency control loop which has the frequency error as input and a power control loop in which the error between the set point and measured power is operated on by the 'droop' gain [1]. The governor output is then used to set the guide vane position []. Since the grid s unknown parameters such as the stiffness and the inertia are part of the frequency feedback loop, it is difficult to achieve optimum gain settings for all operating conditions with the current governor. The proposed scheme utilises the frequency error signal and the unit droop characteristics to determine the amount of power the unit needs to pick up or shed (this is called power target). Adopting such an arrangement separates the feedback loops and a single feedback loop to regulate the power target is implemented. An advantage of the scheme is that the grid unknowns (inertia and stiffness) are not included in the power control loop. The grid characteristics (effects) are embedded within the grid frequency signal, which is used to determine the power target signal. Therefore, it is feasible to optimise the governor performance for all operating conditions. In the present study, the root-locus technique was used to design a new PI control system. The result shows that the actuator rate limits influence the unit response and should be included at the design stage. For this purpose the Matlab nonlinear control blockset was used to re-evaluate the system loop gain for different operating conditions.. System model As stated earlier, the unit governor consists of two feedback loops. During frequency control operation the unit will share load according to its droop characteristics. The droop gain is used to trim the frequency error signal in order to determine how much power the unit will pick up (power target). Hence, it is possible to calculate the amount of power that the unit is required to pick up or shed, depending on the frequency error signal. Fig. 1 shows the proposed control system where the power target is the only variable being 1 Dr Sa ad Mansoor. Tel: + (018)38716; fax: + (018) E-mail address: s.mansoor@bangor.ac.uk 669

controlled. The droop characteristics determine the amount of power the unit will share and this can be calculated as [3]: ( o ) unit _ rating targ et grid droop% fo P = f f P (1) where: P target = Power target; P unit_rating = Unit rated power MW; droop= Droop setting; f grid = Grid frequency and f o = Nominal frequency (50Hz). Power target + _ Controller Guide vane Hydraulic system Y(s) G(s) Power generated Power transducer Fig. 1: System block diagram During the investigation the guide vane dynamics were modelled as a two-stage actuator with an internal feedback loop using the transfer function of equation(), which relates the desired and the actual positions. Gs () 1 = Ys () ( Ts+ 1)( Ts+ 1) 1 () The time constants T1 & T are determined by the pressure/flow characteristics of the guide vane and its actuator servomotors. A step response test was carried out on the guide vane to identify the system time constants. The result shows that T1 = 0.19 and T =0.. The penstock-turbine is modelled using the mathematical relationship of equation (3), which relates the turbine power increment to the guide vane position increment []. T 1 w tanh( T ) ΔP () e m s T = e ΔGs () T 1+ 0.5 w tanh( T e ) T e (3) Where: P m is the power generated; G is the guide vane position; T w is the water starting time; T e is the wave travelling time and s is the Laplace operator. Forming the lumped parameter approximation modifies the representation of equation(3), 1 e tanh by expanding ( x ) x the transfer function into the general nth-order model, using the relationship; = 1 + e, which leads to the finite approximation [5]. x tanh( Ts) = e n= ste ste 1 + n= 1 nπ = ste 1 + (n 1) π n n= 1 () For n=1 equation () can be written in the form of an equation which represents an elastic water column. For most power system stability studies the approximate transfer function (5) is adequate. 670

TT w e 3 e ΔP () 1 w m s Ts+ Ts s = π π ΔGs () 1+ 0.5Ts w + Ts + 0.5 s π π TT w e 3 e (5) The root-locus of Fig. a shows how changes in the system s characteristics influence the closed loop pole locations, which largely determine its time response. Matlab software [6] was used to plot the root locus for the system based on single unit operation. Plotting the system root locus for variable loop gain reveals that increasing the system gain (Kloop) causes the root to cross over to the right hand side of the s-plane (unstable region). Thus, there is a limit to how much the gain can be increased before the system becomes unstable. The design criterion was to set the system damping to 0.7 and that is achieved by setting the gain to 0.0. The corresponding Nichols chart is used to plot the system closed loop frequency response and is shown in Fig. b. For this gain value, the gain margin is 11.dB and the phase margin is 6.0, which are within the stability limits. 8 0.5 0.16 0.08 Root Locus Editor (C) 7 Single Unit Open-Loop Nichols Editor (C) 0 db 6 0.36 6 30 0.5 db 5 0.5 db 0.8 0 1 db Imag Axis 0-0.6 0.78 0.9 0.9 0.78 3 1 1 Open-Loop Gain (db) 10 0-10 3 db 6 db 0.6 3-0 - 0.8 5-30 -6 0.36 0.5 0.16 0.08 6 7-0 G.M.: 11. db @ 0.903 rad/sec P.M.: 6. deg @ 0.9 rad/sec Stable loop - -1 0 1 3 Real A xis -70-5 -180-135 -90-5 Open-Loop Phase (deg) (a) Root locus (b) Nichols chart Fig. : Control system design for a single Unit Because the Dinorwig plant that was used as a case study consists of six units and each has its own penstock, which is connected to the upper reservoir by a single tunnel. Consequently, the water inertia will change according to the number of units on line. Hence, it is necessary to investigate the effect of changes in water inertia on the performance of the new governor. As before, the root locus technique was used to establish the loop gain for different operating points: two units, three units active and so on. Table 1 shows the loop gain and gain margins for each operational condition. 671

Table 1 system loop gain and margins Units on line Loop gain (K loop ) Gain margin (db) Phase margin (deg.) One 0.0 11. 6. Two 0.017 11.7 66.8 Three 0.015 10.6 6.3 Four 0.015 10.5 6. Five 0.011 10. 63.5 Six 0.01 10.8 65.3 It can be seen that, as predicted, the required loop gain depends on the operating condition (water inertia) and to comply with the design criterion the loop gain must be reduced as the number of units on line increased..1. Matlab nonlinear control design blockset The plant has a rate limit on the main actuator and the rate limit has a large influence on the unit response it is crucial to include it in the design process. Fortunately, Matlab software has a non-linear control blockset, which can be used for this purpose. The tool provides a time-domain-based optimisation approach to system design. It is designed for use with Simulink block diagrams and automatically tunes parameters, based on user-defined time-domain performance constraints. The Blockset provides an interactive GUI for modifying system parameters and specifying performance constraints. The Simulink system, time-domain constraints, tuneable variables and parameter uncertainty are formulated as a constrained optimisation problem. The optimisation performs successive simulations on the Simulink system and changes the tuneable variables in an attempt to better meet the time response specifications. As before, the investigation involved tuning the loop gain at different operating conditions. The maximum power target considered during system tuning was 150MW to minimise the power variations (between minimum 0MW and maximum 150MW in this case). This is justifiable because the maximum amount of power that any unit can pick up during frequency control is 150MW (this occurs only during extreme circumstances such as losing a large generating unit on the grid). The aim is to minimise the error between the output and the input signal for all time steps, thus producing a multiobjective function (one function for each time step). The tuneable variable for optimisation, the loop gain (Kloop) should ensure that the closed loop system meets or exceeds the following performance specifications: The maximum percent of overshoot is 5%. The maximum rise time is 10 second. The maximum settling time within 1% is less than 5 second. The results of the optimisation are shown in Table. Compared to the gains obtained previously (Table 1) it is evident that reductions in the gain values are required, even when operating with a light hydraulic system (small water starting time). However, the results as previously indicate that a gain-scheduling regime should be implemented to achieve an optimum response for all operating conditions. Table : System loop gain Number of Units on line Loop gain (K loop ) Number of Units on line Loop gain (K loop ) One 0.016 Four 0.015 Two 0.0138 Five 0.011 Three 0.018 Six 0.01 67

3. Performance of the new control system In this section the response of the new governor is determined for two relevant conditions, variation of Grid parameters and part load response. 3.1. Grid parameters The effects of power system parameters, specifically the Grid inertia and stiffness, on the stability of the new governor as depicted in Fig. 1 (with the rate limit included) are investigated. The grid inertia M corresponds to the total inertia of rotating machines on the Grid (which includes the inertia constant of the generators and the load). Therefore the inertia constant is large when the number of generating units is high. To investigate the stability of the new governor scheme (tuned using the nonlinear blockset) to changes in the Grid inertia, simulation tests were conducted using two units responding to load deviation on the Grid. Both units were operating with 1% droop the first unit was controlled using the new governor (Kp=10 Ki=1 and Kloop=0.016) while the current governor (Kp=10 Ki=1 and Kd=) controlled the second unit.. The first test was conducted using an inertia constant of M = 10 MWs on a 30GVA base, and then the test MVA. was repeated for M = 5 MWs on a 30GVA base. MVA The results shown in Fig. 3, illustrate that the inertia constant will influence the speed at which the unit picks up the load. For both governors, low inertia results in the unit responding faster and the reason for that is the higher rate of frequency change due to low grid inertia. It can be seen that the new governor performance is stable as predicted and is superior to the current governor in both cases. For the case of inertia equal to 5, it can be seen that the unit picks up an extra 1MW after 10s compared with the current governor. Moreover at high inertia (M = 10) the new governor once again picks up an extra 1MW after 10s. It is clear that the new governor scheme will enhance the unit response regardless of grid inertia. 195 190 Unit responses to a step load of 300MW New governor Current governor 0 30 Unit responses to a step load of 300MW New governor B=100 MW/Hz 185 0 Current governor 180 M =5 10 Power (MW ) 175 170 165 M =10 Power (MW) 00 190 180 B=3600 MW/Hz 160 170 155 160 0 5 10 15 0 5 30 35 Time (sec) 150 0 5 10 15 0 5 30 35 0 Time (sec) Fig. 3: The effect of changes the grid inertia (M) on unit response Fig. : The effect of changes the gird stiffness (β) on unit response The second parameter to be examined was the power system frequency response characteristic β which is referred to as the stiffness. The physical significance of β can be stated as follows: if a power system was subject to a step load change, it would experience a static frequency drop inversely proportional to its stiffness. The smaller the change in frequency for a given load change the stiffer the system. In this context, an experiment was carried out to compare the responses of both governors using a grid operated with β = 100 MW, and then repeated using a stiffer grid β = 3600 MW. The test was conducted Hz Hz by applying a step load of 300MW on the system, while the grid inertia was set to M. = 10 MWs on a MVA 673

30GVA base. Fig., shows the results, which, as expected, show that the load has less impact when operating on a stiff grid. Both units pick up the extra load of 50MW in steady state but once again the unit operating with the new governor picks up the load much faster than the unit operating with the current governor. This is also true for the lighter grid where both units pick up an extra load of 85 MW, but the new governor achieves this in 10s while the current governor requires up to 5s to do so.. Conclusions A new control scheme is developed to enhance the performance of the Dinorwig plant. Adopting such a scheme enables us, to discard the unknown parameters in the power system during the design stages, because they are not part of the control loop. However, their effects are embedded in the Grid frequency signal, which is used to determine the power target signal. The results of the simulations suggest that there are significant possibilities for improved performance based on the introduction of a revised governor for the Dinorwig plant. The new governor scheme responds to variation of grid parameters in a stable manner and the results demonstrate the advantage of the new scheme, as the plant is more responsive to frequency variation on the grid. The study has highlighted that the plant is nonlinear and that operating with a fixed gain governor is not the way forward because conservative gain settings are chosen to cover the whole operating range. Gain scheduling accommodates all operating conditions, which results in better-tuned governor.. References [1]. Mansoor, S. P., Jones, D. I., Bradley, D. A., Aris, C., and Jones, G., Reproducing oscillatory behaviour of a hydroelectric power station by computer simulation, Control Engineering Practice, 8, 161-17, 000. []. Mansoor, S. P., Jones, D. I., Bradley, D. A., Aris, C., and Jones, G., Stability of a Pump Storage Hydro-Power Station Connected to a Power System, IEEE power Winter Meeting 1999, New York, vol. pp. 66-650,1999. [3]. Mansoor, S. P., Behaviour and Operation of Pumped Storage Hydro Plants, PhD Thesis University of Wales, 000. []. Working Group on Prime Mover and Energy Supply Models for System Dynamic Performance Studies, Hydraulic Turbine and Turbine Control Models for System Dynamic Studies, IEEE Transaction on Power Systems, vol. 7, pp. 167-179, 199. [5]. Goodson, R. E., Distributed System Simulation Using Infinite Product Expansions, Simulation, vol. 15, pp. 55-63, 1970. [6]. MATLAB System Toolbox User's Guide, MA, USA: The Math Works Inc., 010. 67