Boiling Heat Transfer and Pressure Drop of R1234ze(E) inside a Small-Diameter 2.5 mm Microfin Tube

Similar documents
Uncertainty Analysis on Prediction of Heat Transfer Coefficient and Pressure Drop in Heat Exchangers Due to Refrigerant Property Prediction Error

Experimental investigation on up-flow boiling of R1234yf in aluminum multi-port extruded tubes

R134a Flow Boiling inside a 4.3 mm ID Microfin Tube

An Experimental Study On Condensation Of R134a In A Multi-Port Extruded Tube

Condensation and Evaporation Characteristics of Flows Inside Three Dimensional Vipertex Enhanced Heat Transfer Tubes

Heat Transfer of Condensation in Smooth Round Tube from Superheated Vapor

Characteristics of Flow Boiling Heat Transfer of Sub-Critical CO2 in Mini-Channels With Micro- Fins

Characteristics of CO2 Transcritical Expansion Process

Condensation Heat Transfer of Pure Refrigerants in Microfin Tubes

Evaporation Heat Transfer Coefficients Of R-446A And R-1234ze(E)

R1233zd(E) and R245fa Flow Boiling Heat Transfer and Pressure Drop inside a 4.2 mm ID Microfin Tube

a. Key Laboratory of Efficient Utilization of Low and Medium Grade Energy, MOE, Tianjin University, Tianjin , China

HFO1234ze(E) And HFC134a Flow Boiling Inside a 4mm Horizontal Smooth Tube

Two-Phase Refrigerant Distribution in a Micro- Channel Manifold

Flow boiling heat transfer of a non-azeotropic mixture inside a single microchannel

R32 Heat Transfer Coefficient During Condensation In A Mini-Channel Multiport Tube

Effect of Oil on Flow Boiling Heat Transfer and Flow Patterns of CO2 in 11.2 mm Horizontal Smooth and Enhanced Tube

Innovative Minichannel Condensers and Evaporators for Air Conditioning Equipment

HFO1234yf Condensation Inside A Brazed Plate Heat Exchanger

Oil Retention and Pressure Drop of R134a, R1234yf and R410A with POE 100 in Suction Lines

A Novel Model Considered Mass and Energy Conservation for Both Liquid and Vapor in Adsorption Refrigeration System.

DETERMINATION OF R134A S CONVECTIVE HEAT TRANSFER COEFFICIENT IN HORIZONTAL EVAPORATORS HAVING SMOOTH AND CORRUGATED TUBES

Heat Transfer Characteristics for Condensation of R134a in a Vertical Smooth Tube

Experimental Study on Liquid Film Thickness of Annular Flow in Microchannels

EXPERIMENTAL STUDY OF R-134A VAPORIZATION IN MINICHANNELS

Experimental Heat Transfer Coe±cient and Pressure Drop during Condensation of R-134a and R-410A in Horizontal Micro- n Tubes

Pratik Shashikant Deokar Auburn University, Department of Mechanical Engineering, Auburn, AL, USA,

Investigations Of Heat Transfer And Components Efficiencies In Two-Phase Isobutane Injector

Boiling of R-134a in Horizontal Mini Tube

Condensation and Evaporation of R744/R32/ R1234ze(E) Flow in Horizontal Microfin Tubes

Forced Convective Boiling Heat Transfer in Microtubes at Low Mass and Heat Fluxes

IHTC DRAFT MEASUREMENT OF LIQUID FILM THICKNESS IN MICRO TUBE ANNULAR FLOW

Boiling Heat Transfer and Pressure Drop of a Refrigerant Flowing in a Vertical Small Diameter Tube

Thermodynamic Properties of Low-GWP Refrigerant for Centrifugal Chiller

THE EFFECT OF LIQUID FILM EVAPORATION ON FLOW BOILING HEAT TRANSFER IN A MICRO TUBE

Condensation of refrigerant R407C in multiport minichannel section

A STUDY OF IN-TUBE EVAPORATION HEAT TRANSFER OF CARBON DIOXIDE

An experimental investigation on condensation of R134a refrigerant in microchannel heat exchanger

FORCE FED BOILING AND CONDENSATION FOR HIGH HEAT FLUX APPLICATIONS

EXPERIMENTAL ANALYSIS OF R-134a FLOW CONDENSATION IN A SMOOTH TUBE

InterPACKICNMM

Measurements of Thermodynamic Properties for R1123 and R1123+R32 Mixture

EFFECT OF LIQUID REYNOLDS NUMBER ON PRESSURE DROP OF EVAPORATIVE R-290 IN 500µm CIRCULAR TUBE

EXPERIMENTAL INVESTIGATION OF FLOW BOILING HEAT TRANSFER OF HFO1234YF AND R32 REFRIGERANT MIXTURE IN A SMOOTH HORIZONTAL TUBE

In Tube Evaporation Heat Transfer of Refrigerant Mixtures

Gradient-Based Estimation of Air Flow and Geometry Configurations in a Building Using Fluid Dynamic Adjoint Equations

CONDENSATION HEAT TRANSFER COEFFICIENT CORRELATION BASED ON SLIP RATIO MODEL IN A HORIZONTAL HEAT EXCHANGER

THE CHARACTERISTICS OF BRAZED PLATE HEAT EXCHANGERS WITH DIFFERENT CHEVRON ANGLES

Heat transfer and pressure drop experimentation inside single minichannels

General Correlation For Heat Transfer During Condensation in Plain Tubes: Further Development and Verification

Evaporation Heat Transfer and Pressure Drop of Refrigerant R-410A Flow in a Vertical Plate Heat Exchanger

Correlation of Evaporative Heat Transfer Coefficients for Refrigerant Mixtures

EVAPORATIVE CO 2 HEAT TRANSFER MEASUREMENTS FOR COOLING SYSTEMS OF PARTICLE PHYSICS DETECTORS

Pressure drop during condensation of refrigerants in pipe minichannels

A Study on High Efficiency Wing-Vane Compressor - Part.2: Lubrication Characteristic of The Partial Arc Guide Bearing -

Numerical Study on the Condensation Length of Binary Zeotropic Mixtures

Supersonic air and wet steam jet using simplified de Laval nozzle

CALCULATION METHOD FOR FLOW BOILING AND FLOW CONDENSATION OF R134A AND R1234YF IN CONVENTIONAL AND SMALL DIAMETER CHANNELS

TWO-PHASE FLOW FRICTIONAL PRESSURE DROP OF FC-14 IN HORIZONTAL TUBES

Performance Investigation on Electrochemical Compressor with Ammonia

Heat transfer coefficient of near boiling single phase flow with propane in horizontal circular micro channel

Experimental Thermal and Fluid Science

Energy and Exergy Analyses of the Scroll Compressor

Variable Speed Tri-Rotor Screw Compression Technology

Transient pressure drop correlation between parallel minichannels during flow boiling of R134a

Continuous vs. pulsating flow boiling. Part 2: Statistical comparison using response surface methodology

FIELD STUDY OF FLOW AND HEAT TRANSFER IN TUBE MICROPHONE

Effects Of Leakage Flow Model On The Thermodynamic Performance Of A Scroll Compressor

Onset of Flow Instability in a Rectangular Channel Under Transversely Uniform and Non-uniform Heating

Three-Dimension Numerical Simulation of Discharge Flow in a Scroll Air Compressor

Investigations on Performance of an Auto-Cascade Absorption Refrigeration System Operating with Mixed Refrigerants

Developing Two-Phase R134a Flow after an Expansion Valve in an 8.7mm Tube

FLOW BOILING OF ETHANOL IN SMALL DIAMETER TUBES

Nucleate pool boiling heat transfer from small horizontal smooth tube bundles

Heat Transfer From the Evaporator Outlet to the Charge of Thermostatic Expansion Valves

An experimental study of flow pattern and pressure drop for flow boiling inside microfinned helically coiled tube

FLOW BOILING HEAT-TRANSFER IN PLATE MICRO- CHANNEL HEAT SINK

Frictional Characteristics of Thrust Bearing in Scroll Compressor

Helium two-phase flow in a thermosiphon open loop

Isentropic Efficiency in Engineering Thermodynamics

Nucleate boiling heat transfer coefficients of halogenated refrigerants up to critical heat fluxes

Experimental Heat Transfer Coefficients and Pressure Drop During Refrigerant Vaporisation Inside Plate Heat Exchangers

Heat Transfer of Refrigerant Mixtures

International Journal of Heat and Mass Transfer

GRAVITY EFFECT ON THE DISTRIBUTION OF REFRIGERANT FLOW IN A MULTI-CIRCUITED CONDENSER

VOID FRACTION CHARACTERISTICS OF ONE-COMPONENT GAS LIQUID TWO-PHASE FLOW IN SMALL DIAMETER TUBES

In-Situ Measurement of Absorption Rates in Horizontal-Tube Falling-Film Ammonia-Water Absorbers: Part II Heat and Mass Transfer Coefficients

The Effect Of Volute Tongue And Passage Configuration On The Performance Of Centrifugal Fan

Study on Flow Characteristics of Oil Viscosity Pump for Refrigerant Compressors

A New Numerical Approach for Predicting the Two- Phase Flow of Refrigerants during Evaporation and Condensation

Experimental and Numerical Investigation of Two- Phase Flow through Enlarging Singularity

JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (JMET)

IHTC DRAFT: HEAT TRANSFER CHARACTERISTICS OF FLOW BOILING OF R134A IN UNIFORMLY HEATED HORIZONTAL CIRCULAR MICROTUBES

An experimental study of flow boiling characteristics of carbon dioxide in multiport mini channels

SEM-2017(03HI MECHANICAL ENGINEERING. Paper II. Please read each of the following instructions carefully before attempting questions.

Stratified Flow Condensation of CO 2 in a Tube at Low Temperatures Pei-hua Li 1, a, Joe Deans 2,b and Stuart Norris 3,c

THE EFFECT OF THE CROSS-SECTIONAL GEOMETRY ON SATURATED FLOW BOILING HEAT TRANSFER IN HORIZONTAL MICRO-SCALE CHANNELS

Comparison of pool boiling heat transfer for different tunnel-pore surfaces

Y.; Kobayashi, H.; Inatani, Y. Citation Physics Procedia (2015), 67: Right article under the CC BY-NC-ND

HFO1234ze(Z) saturated vapour condensation inside a brazed plate heat exchanger

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 208 Boiling Heat Transfer and Pressure Drop of inside a Small-Diameter 2.5 mm Microfin Tube Daisuke Jige Tokyo University of Marine Science and Technology, Japan, djige00@kaiyodai.ac.jp Shota Iizuka Graduate School of Marine Science and Technology, Tokyo University of Marine Science and Technology (2--6 Etchujima, Koto-ku, Tokyo, 35-8533, Japan), m64003@edu.kaiyodai.ac.jp Norihiro Inoue Tokyo University of Marine Science and Technology, Japan, inoue@kaiyodai.ac.jp Follow this and additional works at: https://docs.lib.purdue.edu/iracc Jige, Daisuke; Iizuka, Shota; and Inoue, Norihiro, "Boiling Heat Transfer and Pressure Drop of inside a Small-Diameter 2.5 mm Microfin Tube" (208). International Refrigeration and Air Conditioning Conference. Paper 20. https://docs.lib.purdue.edu/iracc/20 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2542, Page Boiling Heat Transfer and Pressure Drop of Inside a Small-Diameter 2.5 mm Microfin Tube Daisuke JIGE *, Shota IIZUKA 2, Norihiro INOUE Tokyo University of Marine Science and Technology, Etchujima, Koto-ku, Tokyo, Japan Phone number: +8-3-5245-7479, Fax number: +8-3-5245-7479 E-mail address: djige00@kaiyodai.ac.jp, inoue@kaiyodai.ac.jp 2 Graduate School of Marine Science and Technology, Tokyo University of Marine Science and Technology, Etchujima, Koto-ku, Tokyo, Japan * Corresponding Author ABSTRACT This study experimentally investigated the flow boiling heat transfer and pressure drop of in a horizontal small-diameter microfin tube with an outer diameter of 2.5 mm and equivalent diameter of 2. mm. The boiling heat transfer and pressure drop were measured in the mass velocity range of 0 400 kg/(m 2 s) and in the heat flux range of 5 20 kw/m 2 at a saturation temperature of 5 C. The heat transfer coefficient increased as the quality increased because of increasing the forced convection in the pre-dryout region. The heat transfer coefficient increased as the heat flux increased in the low-quality region, but decreased when the heat flux increased past a certain point because the thin liquid film at the fin tips had dried. The heat transfer coefficient increased as the mass velocity increased and exhibited the highest value at a mass velocity of 200 kg/(m 2 s). The measured heat transfer coefficient agreed well with previous correlations only in the dominant region of the forced convection evaporation. The frictional pressure drop increased as the mass velocity and vapor quality increased, and the measured values agreed well with previously reported correlations for conventional-diameter microfin tubes.. INTRODUCTION The development of high-performance and compact heat exchangers with small-diameter microfin tubes, whose tube diameter is less than 5 mm, is needed to improve the performance of the heat exchanger and reduce the refrigerant charge for air-conditioning systems. The effects of surface tension and shear stress on the boiling heat transfer and flow characteristics become dominant, in comparison to the gravity effect, as the tube diameter decreases. Moreover, the flow boiling characteristics are different from those in conventional-diameter tubes. Many studies have been conducted on boiling heat transfer, pressure drop, and flow characteristics inside conventionaldiameter microfin tubes and have clarified these characteristics. Several studies have investigated the boiling heat transfer and pressure drop of small-diameter microfin tubes with an inner diameter of less than 4 mm, in comparison to conventional-diameter microfin tubes. Dang et al. (20) investigated the boiling heat transfer of CO 2 inside a microfin tube with a mean inner diameter of 2.0 mm, and reported that the heat transfer was significantly affected by heat flux, and that it increased with increasing heat flux because of enhancing the nucleate boiling. Mancin et al. (205) investigated the boiling heat transfer and pressure drop of R34a inside a microfin tube with a fin-tip diameter of 3.4 mm and reported that the heat transfer was controlled by nucleate boiling and forced convection. Inoue et al. (206) carried out experiments regarding the boiling heat transfer and pressure drop of R32 inside two microfin tubes with equivalent diameters of 3.5 mm and 3.7 mm and investigated the effect of fin geometry on the flow boiling characteristics. Jige et al. (206) investigated the boiling heat transfer and pressure drop of R32 inside a microfin tube with an equivalent diameter of 2.6 mm and reported that the tube diameter influenced the boiling heat transfer, and that the heat transfer coefficient in the 2.6 mm microfin tube was.3.6 times larger in comparison to that of the 3.7 mm microfin tube. Moreover, HFO refrigerants are perceived as refrigerants with a low global

2542, Page 2 warming potential and are expected to replace conventional HFC refrigerants because of worldwide refrigerant regulations. However, few studies have been conducted on the boiling heat transfer and pressure drop of HFO refrigerants in small-diameter microfin tubes with a tube diameter smaller than 5 mm. Diani et al. (204) conducted experiments with inside a microfin tube with a fin-tip diameter of 3.4 mm and an outer diameter of 4 mm in the mass velocity range of 90 940 kg/(m 2 s) and at a saturation temperature of 30 C. They proposed two prediction correlations for heat transfer and pressure drop in a small-diameter microfin tube. Diani et al. (205) also experimented with R234yf inside a microfin tube with a fin-tip diameter of 3.4 mm and reported that the heat transfer coefficient increased with increasing heat flux, while the forced convection heat transfer became more effective in the high-quality region. To facilitate the design of evaporators with small-diameter microfin tubes, it is necessary to acquire the measurement data of the boiling heat transfer and pressure drop under a wide range of experimental conditions. This study experimentally investigated the flow boiling heat transfer and pressure drop characteristics of inside a horizontal small-diameter microfin tube with an outer diameter of 2.5 mm and equivalent diameter of 2. mm. The experiments were carried out in the mass velocity range of 0 400 kg/(m 2 s), with a heat flux range of 5 20 kw/m 2, and a saturation temperature of 5 C. The effects of mass velocity, heat flux, and quality on the flow boiling characteristics were clarified, and the measured heat transfer and pressure drop were compared to previously reported correlations. 2. EXPERIMENTAL APPARATUS AND METHOD 2.. Experimental Apparatus and Procedure Figure shows a schematic of the experimental apparatus used in this study. The test apparatus consisted of a pump, water preheater, electric preheater, test section, condenser, receiver, and subcooler. The liquid refrigerant discharged from the gear pump and flowed into the water heat exchanger and electric heater. The electric heater heated the refrigerant to obtain the desired quality at the inlet to the test section. The subcooled liquid refrigerant returned to the pump through the condenser, receiver, and subcooler. The mass flow rate of the refrigerant was measured by a mass flow meter with an accuracy of ±0.5%. The refrigerant flow rate was controlled by the flow control valves in the main and bypass loops. Figure 2 shows the details of the test section. The test tube was heated by Joule heating with an AC power supply unit. The tube wall temperatures were measured by T-type thermocouples attached onto the test tube wall, separated by mm intervals, and with a measuring accuracy of ±0.05 K. The absolute pressure transducer measured the refrigerant pressure at the inlet of the measuring section with an accuracy of ±.4 kpa. The pressure drop between the inlet and outlet of the measuring section was measured by differential pressure transducers. The measuring lengths of the heat transfer and pressure drop were 0 and 3 mm, respectively. (6) (5) (4) (7) () (6) (8) (9) () Gear pump (2) Flow control valve (3) Mass flow meter (4) Water heat exchanger (5) Electric preheater (6) Mixing chamber (7) Test section (8) Condenser (9) Receiver () Subcooler (3) (2) () Figure : Schematic of experimental apparatus

2542, Page 3 Absolute pressure transducer P P Pressure port Flow Differential pressure transducer AC source Tw Tw3 Tw5 Tw2 Tw4 Tw6 25 25 25 25 200 0 Figure 2: Details of test section Table : Specifications of test microfin tubes hf Figure 3: Cross-sectional view of test microfin tube Outer diameter, D o [mm] 2.5 Equivalent diameter, D eq [mm] 2. Fin height, h f [mm] 0. Number of fins, n f [-] 25 Helix angle, [ ] Surface enlargement ratio, [-].5 Figure 3 shows the cross-sectional view of the test microfin tube. Table gives the specifications of the test microfin tube, which was a small-diameter microfin tube with an outer diameter of 2.5 mm and equivalent diameter of 2. mm. The parameters of the test microfin tube were as follows: fin number of 25, helix angle of, fin height of 0. mm, and an enlargement surface area of.5. The equivalent inner diameter means the inner diameter of a smooth tube with the same internal free flow area as that of the test microfin tube. The enlargement surface area is defined as the ratio of the actual heat transfer area to the surface area of a smooth tube with the same equivalent diameter. The experiments were carried out using as the test refrigerant under a saturation temperature of 5 C at the inlet to the test section. The heat transfer coefficient and pressure drop were measured in the mass velocity range of 0 400 kg/(m 2 s) and in the heat flux range of 5 40 kw/m 2. 2.2. Data Reduction The bulk specific enthalpy at the inlet of the test section (h TS,in ) was calculated by the following heat balance equation: h h Q / m, () TS,in E,in E where h E,in is the specific enthalpy at the inlet of the electric preheater, Q E is the heat transfer rate in the electric preheater, and m is the flow rate of the test refrigerant. The distribution of heat equilibrium quality in the test section was calculated by the distributions of the refrigerant pressure, while the specific enthalpy was calculated by the heat transfer rate in the heating section. The heat transfer coefficient was calculated by the following equation: QTS, (2) D L( T T ) eq w S

2542, Page 4 where Q TS is the heat transfer rate, D eq is the equivalent inner diameter, L is the effective heating length, is the surface enlargement ratio calculated by the actual and nominal heat transfer areas, T w is the inner wall temperature, and T R is the saturation temperature of the refrigerant. The tube wall temperature is the average temperature of the top and bottom side of the tube. For most of the data, the uncertainty of the boiling heat transfer coefficient calculated based on the calculation procedure given by Jige et al. (207) was estimated to be within ±%. The maximum uncertainty was evaluated at 25% with a heat flux of 5 kw/m 2, mass velocity of 200 kg/(m 2 s), and quality of 0.7. The frictional pressure drop PF of the boiling flow was calculated by the following equation: ΔP ΔP ΔP, (3) F mes A where P mes is the measured pressure drop between the inlet and the outlet of the test tube, and P A is the acceleration pressure drop in the measured section. The acceleration pressure drop was estimated from the following equation. 2 2 2 2 ( ) Δ A Δ Gx G P x V L (4) The void fraction was estimated by the correlation for microfin tube (Kondou et al., 2008). The properties of were calculated by NIST REFPROP (Lemmon et al., 203). 3. EXPERIMENTAL RESULTS 3.. Boiling Heat Transfer Figures 4 (a) and (b) show the effect of heat flux on the measured heat transfer coefficient in the microfin tube with an equivalent diameter of 2.6 mm at constant mass velocities of 200 and 400 kg/(m 2 s). The horizontal and vertical axes represent the quality and heat transfer coefficient, respectively. The heat transfer coefficient of both mass velocities increased with increasing quality because the forced convection heat transfer was enhanced under any heat flux condition. In particular, at a mass velocity of 200 kg/(m 2 s) and heat flux of 5 kw/m 2, the heat transfer coefficient increased rapidly as the quality increased at x=0.3. For microfin tubes, the heat transfer was enhanced by the extremely thin liquid film that was formed in the grooves; namely, the meniscus liquid film. It is thought that 30 20 (a) G = 200 kg/(m 2 s) q = 5 kw/m 2 q = kw/m 2 q = 20 kw/m 2 30 20 (b) G = 400 kg/(m 2 s) Microfin tube T s = 5 o C 0 q = 20 kw/m 2 q = 40 kw/m 2 0 Figure 4: Effect of heat flux on heat transfer coefficient at mass velocities of 200 and 400 kg/(m 2 s).

2542, Page 5 30 20 Microfin tube T s = 5 o C q = 5 kw/m 2 G = 0 kg/(m 2 s) G = 200 kg/(m 2 s) G = 400 kg/(m 2 s) 0 Figure 5: Effect of mass velocity on heat transfer coefficient at heat flux of 5 kw/m 2 this heat transfer enhancement was caused by the flow pattern transitioning to annular flow with a liquid meniscus film. The heat transfer coefficient of both mass velocities increased as the heat flux increased with a quality less than 0.3, because of enhanced nucleate boiling. In contrast, the mass velocity heat transfer coefficient of 200 kg/(m 2 s) decreased as the heat flux increased in the higher quality region. It is thought that the liquid film thickness decreased as the quality increased, and that the liquid film at the fin tips dried because of the heat flux increasing. However, the effect of the heat flux on the heat transfer coefficient was small at G = 400 kg/(m 2 s) and with higher quality. At the mass velocity of 400 kg/(m 2 s) in the higher-quality region, the flow pattern estimated the annular flow with a uniform liquid film thickness, and the liquid film flowed across the microfins. Therefore, the deterioration of the heat transfer because of the dryness at the fin tips was suppressed because a liquid meniscus did not exist. Similar trends, which were the effects of the quality and heat flux on the heat transfer characteristics, have been reported by a previous study using R32 as the test refrigerant inside a microfin tube with an equivalent diameter of 2.6 mm (Jige et al., 206). Figure 5 shows the effect of mass velocity on the heat transfer coefficient at a heat flux of 5 kw/m 2. The effect of the mass velocity on heat transfer was small with a quality of less than 0.2. The heat transfer coefficient for the mass velocities of 0, 200, and 400 kg/(m 2 s) increased dramatically as the quality increased at x = 0.5, 0.3, and 0., respectively. This heat transfer enhancement was caused by the flow pattern that transitioning to annular flow with a liquid meniscus in the grooves. The heat transfer coefficient increased as the mass velocity increased, under 200 kg/(m 2 s), because of increasing the vapor shear stress, but it decreased with the further increase of the mass velocity because the circumferential liquid film thickness became uniform and the liquid flowed across the microfins. Therefore, the highest value of the heat transfer coefficient was observed at G = 200 kg/(m 2 s) in a higher quality region. Figures 6 (a) and (b) show the heat transfer coefficient differs at the top and bottom sides of the microfin tube at the mass velocities of 0 and 400 kg/(m 2 s). For a mass velocity of 400 kg/(m 2 s), there was no difference in the heat transfer coefficients at the top and bottom sides of the tube. Therefore, it was thought that the flow pattern was the annular flow and that the circumferential liquid film thickness was uniform. Moreover, for a mass velocity of 0 kg/(m 2 s), the heat transfer coefficient at the top side of the tube indicated a higher value, in comparison to the bottom side in the lower quality region. This difference in the heat transfer coefficient suggested that the liquid film thickness at the bottom side was thick, in comparison to the upper side, owing to the effect of gravity. Additionally, the influence of gravity could be confirmed even in a 2. mm microfin tube with lower mass velocity and quality. However, the influence of gravity was not observed at a higher vapor velocity.

2542, Page 6 5 Microfin tube T s = 5 o C G = 0 kg/(m 2 s) q = 5 kw/m 2 5 Microfin tube T s = 5 o C G = 400 kg/(m 2 s) q = 20 kw/m 2 Top Bottom Top Bottom Figure 6: Difference of heat transfer coefficient between top and bottom sides of microfin tube at mass velocities of 0 and 400 kg/(m 2 s) (a) Cavallini et al. (b) Diani et al. cal [kw/(m 2 K)] 5 + 30% -30% Exp. data Exp. data -30% 0.5 0.5 0.5 5 0.5 5 exp [kw/(m 2 K)] exp [kw/(m 2 K)] Figure 7: Comparison between measured heat transfer coefficient and predicted values calculated by correlations (Cavallini et al., 999: Diani et al., 204) cal [kw/(m 2 K)] 5 + 30% Figures 7 (a) and (b) show a comparison between the measured heat transfer coefficient and the predicted values calculated using the correlations for the microfin tubes (Cavallini et al., 999, Diani et al., 204). The correlation of Diani et al., which was proposed for a small-diameter microfin tube, slightly underpredicted the data obtained in this study. However, the correlation of Cavallini et al., which was proposed for conventional-diameter microfin tubes, was in good agreement with the data obtained in this study inside the 2. mm microfin tube. 3.2. Frictional Pressure Drop Figure 8 shows the frictional pressure drop inside the microfin tube with a 2. mm equivalent diameter on the boiling flow and within the heat flux range of 5 kw/m 2. In this comparison, the quality change in the measured section was within 0.05. The measured frictional pressure drop increased with increasing quality and mass velocity because of increasing the vapor shear stress. The frictional pressure drop at a mass velocity of 400 kg/(m 2 s) was four times that of G = 200 kg/(m 2 s) with the same quality. The measured frictional pressure drop was compared to the correlations of Filho et al. (2004) regarding conventional-diameter microfin tubes, and to those of Diani et al. (204)

2542, Page 7 PF / Z [kpam - ] 300 0 T s = 5 C q = 5- kw/m 2 G = 400 kg/(m 2 s) G = 200 kg/(m 2 s) Diani et al. Filho et al. Figure 8: Frictional pressure drop at mass velocities of 200 and 400 kg/(m 2 s) regarding small-diameter microfin tubes, as shown in Figure 8. The Diani et al. correlation agreed well with the data obtained in this study in the higher quality region, but slightly overpredicted the results obtained in the low-quality region. The Filho et al. correlation was proposed based on the data of a microfin tube with an inner diameter of 6.4 8.9 mm and using R34a. This correlation agreed well with the measured pressure drop of inside the 2. mm microfin tube. 4. CONCLUSIONS This study experimentally investigated the boiling heat transfer and pressure drop characteristics of inside a horizontal small-diameter microfin tube with an equivalent diameter of 2. mm and outer diameter of 2.5 mm. The main conclusions drawn from this investigation are summarized as follows: () The heat transfer coefficient increased with increasing heat flux in the low-quality region because of the enhanced nucleate boiling. However, it decreased as the heat flux increased at a lower mass velocity and in a higher quality region because the thin liquid film at the fin tips had dried. This dryness at the fin tips was suppressed by increasing the mass velocity. (2) The heat transfer coefficient increased rapidly as the quality increased at certain quality values, as a result of the flow pattern transitioning to annular flow with a meniscus. This flow pattern transition could be confirmed based on the measured heat transfer coefficients at the top and bottom sides of the tube. (3) The heat transfer coefficient increased with the mass velocity under a mass velocity of 200 kg/(m 2 s), while it decreased as the mass velocity increased further because the circumferential liquid film thickness became uniform and the liquid flowed across the microfins as the vapor shear stress increased. (4) The correlation of Cavallini et al. (999) for conventional-diameter microfin tubes agreed well with the present data of the heat transfer coefficient inside the 2. mm microfin tube. (5) The measured frictional pressure drop increased with the quality and mass velocity because of increasing the vapor shear stress. The data obtained in this study were predicted using the frictional pressure drop correlation of Filho et al. (2004). NOMENCLATURE D diameter (m) G mass velocity (kg/(m 2 s)) h f fin height (m) h specific enthalpy (J/kg) L heat transfer length (m) n Number of fins (-)

2542, Page 8 q heat flux (W/m 2 ) Q heat transfer rate (W) T temperature (K) T s saturation temperature (K) x vapor quality (-) heat transfer coefficient (W/(m 2 K)) P Z pressure drop gradient (Pa/m) surface enlargement ratio (-) helix angle ( ) Subscripts A Bottom cal E eq exp f F in mes Top TS w acceleration bottom side calculation value pre-heater equivalent experimental value fin friction inlet measured top side test section tube wall REFERENCES Cavallini A, Del Col D, Doretti L, Longo GA, Rossetto L. 999, Refrigerant vaporization inside enhanced tubes: a heat transfer model. Heat Technology. 7, 29 36. Dang C, Haraguchi N, Hihara E. 20, Flow boiling heat transfer of carbon dioxide inside a small-sized microfin tube. Int. J. Refrigeration, 33, 655 663. Diani A, Mancin S, Rossetto L. 204, R234ze (E) flow boiling inside a 3.4 mm ID microfin tube, Int. J. Refrig. 47:5 9. Diani A, Mancin S, Rossetto L. 205, Flow boiling heat transfer of R234yf inside a 3.4 mm ID microfin tube, Experimental Thermal and Fluid Science.66:27-36. Filho EPB, Jabardo JMS, Barbieri PEL. 2004, Convective boiling pressure drop of refrigerant R-34a in horizontal smooth and microfin tubes, Int. J. Refrig. 27: 895 903. Inoue N, Jige D, Sagawa K. 206, Evaporation heat transfer and pressure drop of R32 inside small-diameter 4.0 mm tubes, International Refrigeration and Air Conditioning Conference, Paper 2394. Jige D, Sagawa K, Inoue N. 206, Flow boiling heat transfer characteristics of R32 inside a horizontal smalldiameter microfin tube, International Refrigeration and Air Conditioning Conference, Paper 237. Jige, D., Sagawa, K., Inoue, N., 207, Effect of tube diameter on boiling heat transfer and flow characteristic of refrigerant R32 in horizontal small-diameter tubes, Int. J. Refrig. 76: 206 28. Kondou C, Kuwahara K, Koyama S, 2008, An experimental study on void fraction of CO 2 flow boiling in a horizontal micro-fin tube, International Refrigeration and Air Conditioning Conference, Paper 985. Lemmon EW, Huber ML, McLinden MO. 203, Reference Fluid Thermodynamic and Transport Properties- REFPROP, Version 9., National Institute of Standards and Technology (NIST), Standard Reference Data Program, Gaithersburg. Mancin S, Diani A, Rossetto L. 205, Experimental measurements of R34a flow boiling inside a 3.4 mm ID microfin tube. Heat Transf. Eng., 36, 28 229. ACKNOWLEDGEMENT We would like to express our gratitude to the Japan Copper Development Association for partially supporting this study.