technical bulletin Installation Instructions: Wall-Mount Dewpoint Probe ( )

Similar documents
Installation Instructions: ICON Anti-Condensate Controller

Remote Display Unit. Installers Handbook Copyright 2001 AirSense Technology Ltd. LM Remote Display Unit Installers Handbook Issue 1.

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

E2T0 DVP

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER

Minute Impulse Clock Controller I01DN

Operating Instructions for Digital Manometer. Model: MAN-SD

Secured Series Front End Reader Installation Instructions Proximity Reader (ProxPro, ProxPro w/keypad, MiniPro, Thinline II)

S Sapling INSTALLATION MANUAL FOR FIELD SELECTABLE ANALOG CLOCKS SAA SERIES SPECIFICATIONS. advanced time and control systems

Route and retain the clinometer cable so that it does not interfere with moving parts where the unit is mounted.

MODEL HMP45C TEMPERATURE AND RELATIVE HUMIDITY PROBE INSTRUCTION MANUAL

400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL

Installation Instructions

iweathar EDGE V Installation Guide Copyright 2012 iweathar. All rights reserved.

POINTS OF CAUTION BEFORE USE...

WE RE HERE TO HELP: 1 (844) LIGHTCLOUD

Pressure Display Controller

ISSPRO 3 3/8 Programmable Tachometer High Performance EV Line Part Numbers R5535M, R6535M

W 30 Photoelectric proximity switches: Clear signals even with low remission

SPECIFICATION SHEET : FHS2-UNV-36L

473-SHX Dew Point Mirror

WARRANTY AND ASSISTANCE

Aluminum Capacitors Power Printed Wiring Style

BEFORE USE... POINTS OF CAUTION COMPONENT IDENTIFICATION INSTRUCTION MANUAL MODEL R7K4DH-1-DAC32D R7K4DH-1-DAC32D

MODEL 107 TEMPERATURE PROBE INSTRUCTION MANUAL

Installation and Operation Manual. AllSync Plus Wired Clocks

Power Resistor for Mounting onto a Heatsink Thick Film Technology

ph electrode Instruction Manual For use with the RAH-210 & RPH-250

Today s Weather 24 Hour Forecaster

Installation guide 862 MIT / MIR

16 Input AC Block I/O Module

HD2016. [ GB ] Weighing rain gauge. Rain PART OF G H M GROUP TELEMETRIE & AUTOMATION TELEMETRIE & AUTOMATION

STATIC GAS MONITOR Type SGM/DEW Revision A of 20 aprile 2016

Safety Precautions WARNING If critical situations that could lead to user s death or serious injury is assumed by mishandling of the product.

Amphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH

Filter Inductors, High Current, Radial Leaded

Small Gage Pressure Sensor

NOVALYNX CORPORATION MODEL 110-WS-16BP BAROMETRIC PRESSURE SENSOR INSTRUCTION MANUAL

Flexitest Switch Assemblies Type FT-19R and FT-19RX Supersedes DB March 2008

MKIII -MB USER S GUIDE 09/18/18. Rev. 3

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

MET ONE RAIN GAGE MODELS 380, 385, 380M, 385M

Ruggedized Electrical Double Layer Energy Storage Capacitors

Electrical Double Layer Energy Storage Capacitors Up to 3 V Operating Voltage

Small, Gauge Pressure Sensor

w w w. i n t e l l i g e n t a c t u a t o r. d e

OEM Silicon Pressure Die

User Manual VX4750 Function Generator Module

INSTALLATION INSTRUCTIONS ATV Plow Blade Part Number: (50 ), (54 ), or (60 ) Application: All Terrain Vehicles

Multi-function, economical instrument with 4 functions in the same casing. Accessibility and safety: large-dimension terminals Insulated circuits

Pressure Measurement. Transmitters for basic requirements SITRANS P MPS (submersible sensor) Transmitter for hydrostatic level 2/27

M2 SERIES THERMOSTATS 0 F to 240 F, Narrow Differential, Hermetically Sealed ½

SECTION 1 - WHAT IS A BTU METER? BTU's = Flow x ΔT Any ISTEC BTU Meter System consists of the following main components:

Integrated Suppression Module

PHOENIX CONTACT - 04/2016. Features

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008

SSi Super Systems Inc.

Aluminum Electrolytic Capacitors Power Long Life Snap-In

Assembly and Operation Manual. April 2016

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Digital Multi-Day Max/ Min/Current Air and Soil Temperatures Protocol

Power Resistors for Mounting Onto a Heatsink Thick Film Technology

PTA-427 BAROMETRIC PRESSURE TRANSDUCER OPERATOR S MANUAL

GS110. IR Thermal Imaging System for Low-Emissivity Glass with Automatic Emissivity Correction. Manual Addendum

Small Absolute Pressure Sensor

32 Input AC Block I/O Module

Quick Reference. Daily Cleaning Procedures Pages 3-8 Stopping Conditions & Recovery Steps Pages 9-20

Model: WT-3181PL Instruction Manual DC: Indoor/Outdoor Atomic Wall Clock. Get Started

DIM. A (+ 0,05 0,51) .135 ±.015 (3,43 ± 0,38) COMMON LUG INTEGRAL ASSEMBLY NUT, DO NOT REMOVE 1/4-32 UNEF-2A THREAD

SM98A Harsh Media Backside Absolute Pressure Series

Transmitters for basic requirements SITRANS P MPS (submersible sensor) Transmitter for hydrostatic level

Field Pro Operation and Installation Manual

Medium Pressure Sensor Analog Output

Aluminum Electrolytic Capacitors Power Standard Miniature Snap-In

Operating Instructions Validation Tool Kit, KT2 For use with USP Apparatus #1 & #2

Rain Collector (# 7852 & 7852M)

Water terminal control solutions

2mm Hard Metric Connectors

Common Lightcloud Wiring Applications. Wiring Diagrams. Overview Controller Dimmer Gateway Integrator Sensor Touch. Lightcloud

OPERATION MANUAL. Acceleration, Velocity RMS measurement, Metric & Imperial unit PEN VIBRATION METER Model : PVB-820

User s Manual: MODEL 904-T CLINOMETER PAK


Conductive Polymer Aluminum Capacitors SMD (Chip), Low Impedance

ph Probe ReallyEasyData com

SPECIFICATION SHEET : FHS2-UNV-36L

SC125MS. Data Sheet and Instruction Manual. ! Warning! Salem Controls Inc. Stepper Motor Driver. Last Updated 12/14/2004

Amphenol. Amphenol-Tuchel Electronics GmbH. Circular Connectors C 091 A/B/D Series

Aluminum Electrolytic Capacitors Power Economic Printed Wiring

Lead (Pb)-Free Thick Film, Rectangular High Value Chip Resistor

473 Dew Point Hygrometer

Product Manual (Revision D) Original Instructions. Speed Switch and Integrated Speed Switch. Installation and Operation Manual

Lead (Pb)-Bearing Thick Film, Rectangular High Value Chip Resistor

The Ordering Code for various standard model Recorders with an AC supply and without any additional options are as follows:

Series FEATURES AND BENEFITS INTRODUCTION. Figure 1 Power Derating Curve. Table 1 Tolerance and TCR vs. Resistance

CTC 155 / 350 / 660 Dry-block calibrator

MODE button MAX/MIN button CHANNEL button / C/ F / RCC button SNOOZE / LIGHT button Battery compartment A/C in-jack 3. 4.

Advanced Sensor Technologies, Inc. TEL: TOLL FREE: WOW-ASTI ( ) FAX:

Power Resistor for Mounting onto a Heatsink Thick Film Technology

HYGRASGARD KFF KFTF HYGRASGARD AFF AFTF HYGRASGARD AFF - LC AFTF - LC

Infrared Thermometer Model CA879

Transcription:

Installation Instructions: Wall-Mount Dewpoint Probe (809-2011) The HMW90 Wall-Mount Dewpoint Probe (P/N 809-2011) HMW90 measures dewpoint for indoor applications such as anti-sweat heater control and HVAC dehumidification. The probe s linear 0-5VDC output makes the probe compatible with the E2 site controller and all legacy CPC site control products that use MultiFlex and 16AI input boards. Note that the HMW90 dewpoint probe model is shipped factory-configured. Do not adjust dip switch settings or configuration loss may occur to the unit. The model number can be identified by checking the label located on the side of the unit (Figure 1). HMW90 Specifications Property Description/Value Property Description/Value Operating Temperature -5 C to +55 C (+23 F to +131 F) Relative Humidity Range 0-90% RH 90-100% RH Storage Temperature -20 C to +60 C (-4 F to +140 F) Accuracy +/- 1.7% RH +/- 2.5% RH Supply Voltage 18-35VDC or 24VAC * Output Voltage 2 x 0-5v or 2 x 0-10v Current consumption 12mA External Load 10k min. *May be powered with MultiFlex or 16AI, 12 VDC output, if optional relay is not used. Mounting Mount the dewpoint probe enclosure against a flat surface (such as a wall or riser) or junction box. Remove the front cover, and remove the two screws that attach the probe s circuit board to the rear mounting plate (Figure 2). Attach the mounting plate to the mounting surface (Figure 1), then reattach the circuit board and snap the cover back in place. Document Part # 026-4837 Rev 0 21-SEP-2012

Enclosure Mounting Label-side of probe with part number Figure 1 - Enclosure Dimensions and Mounting Plate Opening for cable from top UP RELAY _ ON OFF 1 2 3 4 5 6 7 8 To secure cable with zip tie Cable opening Figure 2 - Circuit Board Document Part # 026-4837 Rev 0 21-SEP-2012 Page 2 of 6

Power and Input Wiring To wire the dewpoint probe to a MultiFlex or 16AI input point, use Belden #8771 three-conductor shielded 22AWG wire (or equivalent) Figure 3 shows the connection point on the dewpoint probe and where to connect the wires to the probe as well as the MultiFlex input point. The probe is powered by the +12VDC power supply terminal on the MultiFlex or 16AI input boards. Connect the SHIELD wire on the MultiFlex end of the cable to a separate earth ground near the board. Cut Shield RELAY - T + - Td + UP _ RUN CABLE THROUGH WALL OR CONDUIT AND FEED END THROUGH HOLE IN MOUNTING PLATE CABLE (BELDEN #8771) WHITE (SIG) JUMPER BLACK RED (12VDC) CABLE (BELDEN #8771) SHIELD BLACK WHITE 1 2 3 4 5 6 7 8 Relay - T + - Td + VS 0...5V 0...5V - + ~ CIRCUIT BOARD, FRONT VIEW (COVER REMOVED) Figure 3 - Dewpoint Probe Wiring If you are replacing a faulty HMW93 dewpoint probe, it is recommended that the mounting plate be replaced. The wiring of the HMW90 dewpoint probe signal wire has been moved. The white signal wire will now connect to terminal 6, and the jumper wire will now connect from terminal 7 to terminal 5 on the back mounting plate (see Figure 3). The input type dip switch on the MultiFlex or 16AI input board must be set to the DOWN or OFF position. Input type dip switches for points #1 through #8 are located on switch bank S1, while points #9 through #16 are located on switch bank S2. Dewpoint dip switches are factory set: 1. Non-metric: for Degrees F 2. Td: (dewpoint) for dewpoint linear output on RH terminals. 3. 0...5V: 0 to 5V linear output for MultiFlex inputs. Document Part # 026-4837 Rev 0 21-SEP-2012 Page 3 of 6

Note that the linear ranges on the label-side of the HMW90 dewpoint probe box are for reading dewpoint. Dewpoint probe dip switches are factory set and should be not be changed. Td (0...100 F) or (-18...38 C). Document Part # 026-4837 Rev 0 21-SEP-2012 Page 4 of 6

AOUT 1 0...5V Td( F) 0...100 F AOUT 2 0...5V T( F) 0...100.0 F E2 Input Setup NOTE: Do NOT set up this probe with a sensor type of Dewpoint ; this setting only works for old-style CPC Dewpoint Probes (P/N 203-1902). This probe must be set up with a sensor type of Linear. Figure 4 - HMW90 Power Up Screen 1. Log into the E2 and press (Input Summary). 2. Highlight the input point the Dewpoint Probe is connected to, and press (Setup). 3. When prompted to select the data type, press (Analog). Figure 5 - E2 Input Setup Document Part # 026-4837 Rev 0 21-SEP-2012 Page 5 of 6

4. In the Analog Input setup screen, enter the following information in the fields listed below: Name: A description of the sensor s function and/or location (e.g., INDOOR DEWPT). Sensor Type: Linear Eng. Unit: DF Low Eng Units: 0 High Eng Units: 100 5. Press to save changes and exit the Analog Input setup screen. Note: If you are using Degrees C, set Eng. Unit: DC, Low Eng. Units: -18.0 and High Eng. Units: 38. The E2 controller can be set to display degrees Celsius, but the dewpoint probe only displays in degrees Fahrenheit. Calibration The dewpoint probe is factory calibrated and should not need to be recalibrated. If the dewpoint probe is out of calibration, DO NOT use the E2 input offsets. The calibration must be adjusted on the dewpoint probe itself. If the dewpoint probe needs calibration, contact your Emerson Retail Solutions sales representative for more information 770-425-2724. Troubleshooting 1. If the dewpoint is not reading correctly on the E2, verify that the Low and High Engineering Units are set correctly. The dewpoint probe s linear range can be seen on the second screen during power up. This range is normally 0...100 F but some earlier HMW93 units have a range of -4...131 F. 2. If the dewpoint probe is not reading correctly, verify that the signal wire on the dewpoint probe is connected to the correct terminal location on the HMW unit. Document Part # 026-4837 Rev 0 21-SEP-2012 Page 6 of 6 This document may be photocopied for personal use. The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or the ir use or applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively Emerson ), reserves the right to modify the designs or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user. 026-4837 21-SEP-2012 Emerson is a trademark of Emerson Electric Co. 2012 Emerson Climate Technologies Retail Solutions, Inc. All rights reserved.