Operating instructions Magnetic-inductive flow meter SM6x04 SM7x04 SM8x04

Similar documents
Operating instructions Magnetic-inductive flow sensor SM6004 SM7004 SM / / 2014

Operating instructions Magnetic-inductive flow meter. SM6x01 SM7x01 SM8x / / 2015

Operating instructions Magnetic-inductive flow meter SM4x00 SM6x00 SM7x00 SM8x00 SM6x01 SM7x01 SM8x01

Operating instructions Vortex flow meter. SVxxx / / 2015

Operating instructions Magnetic-inductive flow meter SM2001 SM / / 2014

Operating instructions Magnetic-inductive flow sensor SM / / 2010

Operating instructions Compressed air meter SD / / 2013

Operating instructions Compressed air meter SD / / 2013

Operating instructions Volumetric flow sensor SQ / / 2012

Operating instructions Infrared temperature sensor TW20xx TW21xx

Operating instructions Pressure sensor PN / / 2007

Operating instructions Compressed air meter SD / / 2012

Operating instructions Flow rate meter for gases SD / / 2010

Operating Instructions for Digital Manometer. Model: MAN-SD

Compact and low-cost monitoring of conductive liquids. Magnetic-inductive flow metering from ifm.

Installation guide 862 MIT / MIR

Latest generation testo air velocity & IAQ probes with cable handle. Instruction manual

DS 200P. Electronic Pressure Switch. Pressure Ports And Process Connections With Flush Welded Stainless Steel Diaphragm

Solenoid valves Type EVUL

TECHNICAL MANUAL 820 LX / 910 LX / 1300 LX

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

ABB i-bus KNX Analogue Input AE/A 2.1

ED 701 General Industry Pressure Transmitter

DS 300. Electronic Pressure Switch. with IO-Link interface. Stainless Steel Sensor. accuracy according to IEC 60770: 0.35 % FSO.

PHOENIX CONTACT - 04/2016. Features

Kingspan Smart-Lite Kite Luminaire

Field Pro Operation and Installation Manual

Turbine Meter TRZ 03 PRODUCT INFORMATION. Reliable Measurement of Gas

Lamp and Control Panel (Lamp Panel)

AIR PREPARATION. ELECTRONICALLY CONTROLLED PRESSURE REGULATING VALVE (PROPORTIONAL PRESSURE REGULATING VALVE) SERIES control

ph electrode Instruction Manual For use with the RAH-210 & RPH-250

Low Drop Voltage Regulator TLE

AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER

Direct-operated 2/2-way solenoid valves Type EV210B

VOLUMEC. Valve Position Indicator 5

Cooling Water Flow Regulator

Digital Controller Operation

M O D U L E - 3A Model A10V0 Piston Pump Manual A10V0 PUMP. Features

PTF30 Series. Features. Ordering information. G 6 N N F8 (0 to 5 kgf/cm 2 ) PTF30

- compressed air plants (refrigerating/adsorption dryers) - granulate dryers - medical gases - non-corrosive gases, e. g. nitrogen

PRODUCT CATALOGUE PREssURE switch

E 094 E 103 E 143. Tank top mounting Connection up to G1 Nominal flow rate up to 135 l/min e

Cooler-Bypass Thermostat Valve, Size 10

FLT5A FLT5A. abc. abc. Thermometer User Guide. Thermometer User Guide. Internet:

Low Drop Voltage Regulator TLE 4296

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity

Power Resistor for Mounting onto a Heatsink Thick Film Technology

VD1 CLC. Small Valves DIN-range with a higher k v -value

OPERATING MANUAL. EIB-Kombisensor AS 315 N

Pressure Measurement. Transmitters for basic requirements SITRANS P MPS (submersible sensor) Transmitter for hydrostatic level 2/27

Dimensional drawing face mount flange radial. R = bending radius min. 40 mm. Dimensional drawing face mount flange axial

Power Resistor for Mounting onto a Heatsink Thick Film Technology

Solenoid valve Types CSV 2 - CSV 22 (NC) and solenoid coil

Doc No. KF08-002D. Portable Ultrasonic Flowmeter UFP-20. Installation & Operation Manual

ISEmax CAM40/CAS40. Technical Information

R a t i o n a l i s e d B r a k e A c t u a t o r s

Sitting height... 6 Back tilt and back height... 6 Armrest... 7 Brakes... 7 Charging VELA Tango 300E... 7

DMP 331Pi. Precision Pressure Transmitter. pressure ports and process connections with flush welded stainless steel diaphragm

SECTION 1 - WHAT IS A BTU METER? BTU's = Flow x ΔT Any ISTEC BTU Meter System consists of the following main components:

Power Resistor for Mounting onto a Heatsink Thick Film Technology

DRS 61: Incremental encoders, number of lines and zero pulse width freely programmable DRS 60: Incremental Encoders with Zero-Pulse-Teach

MODE button MAX/MIN button CHANNEL button / C/ F / RCC button SNOOZE / LIGHT button Battery compartment A/C in-jack 3. 4.

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

DMP 331Pi. Precision Pressure Transmitter. pressure ports and process connections with flush welded stainless steel diaphragm

DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor

5-V Low Drop Fixed Voltage Regulator TLE 4279

VK2 volume flow controller Overview

/2 way valves (solenoid actuated diaphragm with forced lifting) 1/4... 2

Power Resistor for Mounting onto a Heatsink Thick Film Technology

5 V/10 V Low Drop Voltage Regulator TLE 4266

Thermal-Magnetic Circuit Breaker 2210-T2...

TPM(A) Quick Startup Guide SIEMENS SINAMICS S120

Vet Photometer DP 700 Operating Manual. Version V5.9

Suntracer KNX-GPS. Weather Station. Technical specifications and installation instructions Item number 3093

Amphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH

PHS-25CW/3BW Benchtop ph Meter Instruction Manual

Drive electronics pq12

Installation and Operation Manual. AllSync Plus Wired Clocks

PAA-ANALYZERS PRINCIPLE OF OPERATION

Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals.

Druglizer LE5 Drug Tester User Manual

Oberebenestrasse Bremgarten Switzerland Tel Fax

Commercial Generator Parts Catalog. PROTEC Series

Sensors for pressure control OsiSense XMLR

Product Description. Further highlights. Outstanding features. 4 Bosch Rexroth Corporation Miniature Linear Modules R310A 2418 (2009.

LED light engine / OLED LED compact. Module DLE G4 ADV Modules DLE

Circular Motion and Centripetal Force

Periodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018

PHASED OUT. FL ballasts Electronic dimming. PCA TC BASIC Y II, W BASIC compact

Power Resistor for Mounting onto a Heatsink Thick Film Technology

Power Resistor for Mounting onto a Heatsink Thick Film Technology

Power Resistor Thick Film Technology

SITRANS F flowmeters. SITRANS F US System information SITRANS F US Ultrasonic flowmeters 4/181

N) manual. Biomaster Operating manual

Operating Manual. Turb 355 IR/T. Portable turbidimeter. ba75454e03 09/

WE RE HERE TO HELP: 1 (844) LIGHTCLOUD

LED light engines LED compact. Module SLE G7 ADV Modules SLE ADVANCED

5-V Low Drop Fixed Voltage Regulator TLE

5-V Low Drop Fixed Voltage Regulator TLE 4275

Transcription:

Operating instructions Magnetic-inductive flow meter SM6x04 SM7x04 SM8x04 UK 80223776 / 00 11 / 2018

Contents 1 Preliminary note...3 2 Safety instructions...4 3 Functions and features...4 4 Function...5 4.1 Processing of the measured signals...5 4.2 Direction of flow...5 4.3 Analogue function...6 4.4 Measured value damping (dap)...7 5 Mounting...8 5.1 Recommended installation position...8 5.2 Not recommended installation position...9 5.3 Grounding...10 5.4 Installation in pipes... 11 6 Electrical connection...12 7 Operating and display elements...13 8 Menu...14 9 Set-up...16 10 Parameter setting...16 10.1 Parameter setting in general...17 10.1.1 Change to the menu "Extended functions"...17 10.1.2 Locking / Unlocking...17 10.1.3 Timeout...18 10.2 Scaling of the analogue value for temperature (OUT1)...18 10.3 Scaling of the analogue value for volumetric flow (OUT2)...18 10.4 User settings (optional)...18 10.4.1 Determine the standard unit of measurement for volumetric flow...18 10.4.2 Determine the standard unit of measurement for temperature...18 10.4.3 Standard display...18 10.4.4 Measured value damping...18 10.4.5 Error behaviour of the outputs...19 10.5 Service functions...19 10.5.1 Read min/max values...19 2

10.5.2 Restoring the factory settings...19 11 Operation...19 11.1 Reading the process value...19 11.2 Changing the process value display in the RUN mode...20 11.3 Reading the set parameters...20 12 Troubleshooting...21 13 Technical data...21 14 Factory setting...22 UK 1 Preliminary note Instructions > Reaction, result [ ] Designation of keys, buttons or indications Cross-reference Important note Non-compliance may result in malfunction or interference. Information Supplementary note. CAUTION Warning of personal injury. Slight reversible injuries may result. 3

2 Safety instructions The device described is a subcomponent for integration into a system. -- The manufacturer of the system is responsible for the safety of the system. -- The system manufacturer undertakes to perform a risk assessment and to create a documentation in accordance with legal and normative requirements to be provided to the operator and user of the system. This documentation must contain all necessary information and safety instructions for the operator, the user and, if applicable, for any service personnel authorised by the manufacturer of the system. Please read this document prior to set-up of the unit. Ensure that the product is suitable for your application without any restrictions. If the operating instructions or the technical data are not adhered to, personal injury and/or damage to property can occur. Improper or non-intended use may lead to malfunctions of the unit or to unwanted effects in your application. That is why installation, electrical connection, set-up, operation and maintenance of the unit must only be carried out by qualified personnel authorised by the machine operator. In order to guarantee the correct condition of the device for the operating time it is necessary to use the device only for media to which the wetted materials are sufficiently resistant ( Technical data). The responsibility whether the measurement devices are suitable for the respective application lies with the operator. The manufacturer assumes no liability for consequences of misuse by the operator. Improper installation and use of the devices result in a loss of the warranty claims. 3 Functions and features The unit monitors liquid media. It detects the 2 process categories volumetric flow and medium temperature. Pressure Equipment Directive (PED) The units comply with the Pressure Equipment Directive and are designed and manufactured for group 2 fluids in accordance with the sound engineering practice. Use of group 1 fluids on request. Application area Conductive liquids with the following properties: 4

Conductivity: 20 µs/cm Viscosity: < 70 mm 2 /s at 40 C; < 70 cst at 104 F 4 Function The unit detects the flow based on the magnetic-inductive volumetric flow measuring principle. The unit also detects the medium temperature. The unit displays the current process value. 4.1 Processing of the measured signals The unit generates 2 output signals according to the parameter settings: UK OUT1: Parameter setting --Analogue signal for temperature 10.2 OUT2: Parameter setting --Analogue signal for volumetric flow quantity 10.3 4.2 Direction of flow In addition to the flow velocity and the volumetric flow quantity, the unit also detects the direction of flow. An arrow with the text "flow direction" on the unit indicates the positive flow direction. Flow... corresponds to the marked flow direction against the marked flow direction Process value display + (positive) - (negative) Only positive process values are processed for the signal output. 5

4.3 Analogue function The unit provides an analogue signal that is proportional to the volumetric flow quantity and the medium temperature. Within the measuring range the analogue signal is 4...20 ma. If the measured value is outside the measuring range or in the event of an internal error, the current signals indicated in Figure 1 are provided. The measuring range is scalable: [ASP] determines at which measured value the output signal is 4 ma. [AEP] determines at which measured value the output signal is 20 ma. Minimum distance between [ASP] and [AEP] = 20 % of the final value of the measuring range. MAW Initial value of the measuring range For non-scaled measuring range MEW Final value of the measuring range (= factory setting) ASP AEP Table 1: Definitions Analogue start point Analogue end point For scaled measuring range 1 [ma] FOU=On 22 21,5 20 3 4 5 6 4 FOU=OFF 3,5 Q MAW ASP 5* 6* MEW Figure 1: Characteristics of the analogue output according to the standard IEC 60947-5-7. 6 AEP Err UL OL Err -130-120 0 100 120 130 [% MEW] T -50-40 -20 80 100 110-58 -40-4 176 212 230 2 [ C] [ F]

Q: Flow (a negative flow value means flow against the marked flow direction) T: Temperature UL: Below the display range OL: Above the display range Err: The unit is in the error state FOU=On: Default setting at which the analogue signal goes to the upper final value in case of an error. FOU=OFF: Default setting at which the analogue signal goes to the lower final value in case of an error. 1 Analogue signal 2 Measured value (flow or temperature) 3 Detection zone 4 Display range 5 Measuring range 5* Analogue signal in the measuring range with factory setting 6 Scaled measuring range 6* Analogue signal for scaled measuring range UK 4.4 Measured value damping (dap) The damping time allows to set after how many seconds the output signal has reached 63 % of the final value if the flow value changes suddenly. The set damping time stabilises the outputs and the display. The signals [UL] and [OL] ( 12) are defined under consideration of the damping time. 7

5 Mounting CAUTION If the medium temperature is above 50 C (122 F) parts of the housing can increase in temperature to over 65 C (149 F). > > Risk of burns. Protect the housing against contact with flammable substances and unintentional contact. Attach the supplied warning label to the sensor cable. Ensure that the system is free of pressure during installation. Ensure that no media can leak at the mounting location during installation. Avoid deposits, accumulated gas and air in the pipe system. The unit can be installed independently of the orientation if the following is ensured: -- No air bubbles can form in the pipe system. --The pipes are always completely filled. 5.1 Recommended installation position Install the unit so that the measuring pipe is always completely filled. Arrange for inlet and outlet pipe lengths. Disturbances caused by bends, valves, reductions, etc. are compensated for. It applies in particular: no shut-off and control devices are allowed directly in front of the unit. 3 x D F 1 x D S S S = disturbance (e.g. shut-off / control device, pump, bends) D = pipe diameter F = direction of flow 8

Install in front of or in a rising pipe. F F UK 5.2 Not recommended installation position Avoid the following installation positions: F F Directly in front of a falling pipe. In a falling pipe. 9

F F Directly in front of the spout of the pipe. On the suction side of a pump. F At the highest point of the pipe system. F = flow direction 5.3 Grounding If installed in an ungrounded pipe system (e.g. plastic pipes), the unit must be grounded (functional earth). Ground brackets for the M12 connector are available as accessories www.ifm.com. 10

5.4 Installation in pipes The units with a G thread can be installed in the pipes using adapters. Information about the available mounting accessories at www.ifm.com. A correct fit of the unit and ingress resistance of the connection are only ensured using ifm adapters. A B C D D C B A UK 1. Grease the threads of the process connection, adapter and sensor. Use a lubricating paste which is suitable and approved for the application. 2. Screw the adapter (B) into the pipe (A). 3. Place the seals (C) and install the unit according to the marked flow direction. 4. Screw the adapter (B) with the threads (D) until it is hand-tight. 5. Tighten the two adapters in opposite direction (Tightening torque: 30 Nm). After installation air bubbles in the system can affect the measurement. Corrective measures: Rinse the system after installation for ventilation. In case of horizontal installation: As a result of design requirements a small quantity of the medium always remains in the measuring channel after switching off the pump. 11

6 Electrical connection The unit must be connected by a qualified electrician. The national and international regulations for the installation of electrical equipment must be adhered to. Voltage supply according to EN 50178, SELV, PELV. Disconnect power. Connect the unit as follows: 2 1 3 4 BK: black BN: brown BU: blue WH: white 1 2 4 3 BN WH BK BU L+ OUT2 OUT1 L Colours to DIN EN 60947-5-2 Pin 1 L+ Pin 3 L- Pin 4 (OUT1) Analogue signal for temperature Pin 2 (OUT2) Analogue signal for volumetric flow quantity 12

7 Operating and display elements 1-8: Indicator LEDs LEDs 1-6: Unit of the currently represented numerical value 11.1 Reading the process value LED 7-8: not used 9: Alphanumeric display, 4 digits Current volumetric flow quantity with setting [SELd] = FLOW Current medium temperature with setting [SELd] = TEMP Parameters and parameter values 10: [Mode/Enter] button Change from the RUN mode to the main menu Select parameters Acknowledge the set parameter value 11: [Set] button Change parameter values (hold button pressed) Change of the display unit in the normal operating mode (RUN mode) UK 13

8 Menu RUN EF l/min m 3 /h C / F Hi.F gpm gph C / F Lo.F Hi.T ASP1 Lo.T AEP1 FOU1 ASP2 FOU2 dap AEP2 dis EF uni.f uni.t SELd [Mode / Enter] [Set] res 14

Parameters ASP1 AEP1 ASP2 AEP2 EF Hi.F Hi.T Lo.F Lo.T FOU1 FOU2 dap dis uni.f uni.t SELd res Explanation and setting options Analogue start point for temperature on OUT1. Analogue end point for temperature on OUT1. Analogue start point for volumetric flow on OUT2. Analogue end point for volumetric flow on OUT2. Extended functions: opening of the lower menu level. Maximum value memory for volumetric flow. Maximum value memory for temperature. Minimum value memory for volumetric flow. Minimum value memory for temperature. Behaviour of OUT1 in case of an internal fault: OU, On, OFF ( 10.4.5). Behaviour of OUT2 in case of an internal fault: OU, On, OFF ( 10.4.5). Measured value damping: damping constant in seconds. Update rate and orientation of the display: d1...d3, rd1...rd3, OFF ( 10.4.3). Standard unit of measurement for volumetric flow Standard unit of measurement for temperature Standard measured variable of the display: FLOW (volumetric flow value), TEMP (medium temperature). Restoring the factory settings. UK 15

9 Set-up After power on and expiry of the power-on delay time of approx. 5 s the unit is in the RUN mode (= normal operating mode). It carries out its measurement and evaluation functions and generates output signals according to the set parameters. During the power-on delay time the output signal is at 20 ma. 10 Parameter setting Parameters can be set before installation or during operation. If you change parameters during operation, this will influence the function. Ensure that there will be no malfunctions in your plant. During parameter setting the unit remains in the operating mode. It continues to monitor with the existing parameter until the parameter setting has been completed. CAUTION If the medium temperature is above 50 C (122 F) parts of the housing can increase in temperature to over 65 C (149 F). > Risk of burns. Do not touch the device with your hands. Use another object (e.g. a ballpoint pen) to carry out settings on the unit. 16

10.1 Parameter setting in general 1. Change from the RUN mode to the main menu and selection of the requested parameter 2. Acknowledge the set parameter value [Set] [Mode/Enter] 3. Change the setting mode [Set] > 5 s 4. Modification of the parameter value --incrementally by pressing once --continuously by keeping the button pressed To reduce the value: let the display move to the maximum setting value. Then the cycle starts again at the minimum setting value. [Set] 5. Acknowledge the set parameter value [Mode/Enter] 6. Return to the RUN mode > 30 seconds (timeout) or [Mode/Enter] until the RUN mode is reached. UK 10.1.1 Change to the menu "Extended functions" 1. Change from the RUN mode to the main menu and selection of the parameter EF 2. Change to sub-menu EF [Set] 10.1.2 Locking / Unlocking [Mode/Enter] The unit can be locked electronically to prevent unintentional settings. On delivery: not locked. Locking Unlocking Make sure that the unit is in the normal operating mode. Press [Mode/Enter] and [Set] simultaneously for 10 s until [Loc] is displayed. Make sure that the unit is in the normal operating mode. Press [Mode/Enter] and [Set] simultaneously for 10 s until [uloc] is displayed. 17

10.1.3 Timeout If no button is pressed for 30 s during parameter setting, the unit returns to the operating mode with unchanged values. 10.2 Scaling of the analogue value for temperature (OUT1) Select [ASP1] and set the value at which 4 ma is provided. Select [AEP1] and set the value at which 20 ma is provided. 10.3 Scaling of the analogue value for volumetric flow (OUT2) Select [ASP2] and set the value at which 4 ma is provided. Select [AEP2] and set the value at which 20 ma is provided. 10.4 User settings (optional) 10.4.1 Determine the standard unit of measurement for volumetric flow Select [uni.f] and set the unit of measurement: Lmin, m3h, GPm or GPh. 10.4.2 Determine the standard unit of measurement for temperature Select [uni.t] and set the unit of measurement: C or F. 10.4.3 Standard display Select [SELd] and define the standard unit of measurement FLOW = display shows the current volumetric flow value in the standard unit of measurement. TEMP = display shows the current medium temperature in the standard unit of measurement. Select [dis] and set the update rate and orientation of the display: d1 = update of the measured values every 50 ms. d2 = update of the measured values every 200 ms. d3 = update of the measured values every 600 ms. rd1, rd2, rd3 = display like d1, d2, d3; rotated by 180. OFF = the display is switched off in the operating mode. The LEDs remain active even if the display is deactivated. Error messages are displayed even if the display is deactivated. 10.4.4 Measured value damping Select [dap] and set the damping constant in seconds (τ value 63 %). 18

10.4.5 Error behaviour of the outputs Select [FOUx] and set the value: --On = The analogue signal goes to the upper fault value ( 4.3). --OFF = The analogue value goes to the lower fault value ( 4.3). --OU = The analogue signal corresponds to the measured value. 10.5 Service functions 10.5.1 Read min/max values Read minimum or maximum measured values: Select Hi.x or Lo.x. Hi.F = maximum volumetric flow, Lo.F = minimum volumetric flow Hi.T = maximum temperature, Lo.T = minimum temperature Delete memory: Select Hi.x or Lo.x. Press and hold [Set] until [----] is displayed. Briefly press [Mode/Enter]. It makes sense to delete the memories as soon as the unit operates under normal operating conditions for the first time. UK 10.5.2 Restoring the factory settings Select [res]. Press and hold [Set] until [----] is displayed. Briefly press [Mode/Enter]. 14 Factory setting. We recommend taking down your own settings in that table before carrying out a reset. 11 Operation 11.1 Reading the process value The LEDs 1-6 signal which process value is currently displayed. The process value to be displayed as standard (volumetric flow quantity or temperature) can be preset 10.4.3 Standard display. Moreover, a standard unit of measurement can be defined (volumetric flow 10.4.1 and temperature 10.4.2). 19

11.2 Changing the process value display in the RUN mode Briefly press [Set] in the RUN mode. Press the pushbutton to move to the next display unit. > > The unit displays the current measured value in the selected display unit for approx. 30 s, the corresponding indicator LED lights ( 7). 11.3 Reading the set parameters Briefly press [Mode/Enter] to scroll through the parameters. Briefly press [Set] when the requested parameter is displayed. > > The unit displays the corresponding parameter value. After about 15 s it returns to the RUN mode. 20

12 Troubleshooting The unit has self-diagnostic options. It monitors itself automatically during operation. Warnings and error states are displayed, even when the display is switched off. Display Type Description Fault correction Err Error Unit faulty / malfunction Replace the unit. Err Error Flow value < -130 % MEW or > 130 % MEW. Temperature value < - 50 C (-58 F) or > 110 C (230 F). No display Error Supply voltage too low. Setting [dis] = OFF Loc Warning Setting pushbuttons on the unit locked, parameter change rejected. UL Warning Below the display range. Current value between -130 %... -120 % MEW Temperature value between -50...-40 C (-58...-40 F). OL Warning Display range exceeded. Current value between 120 %... 130 % MEW Temperature value between 100...110 C (212...230 F). Check flow range / temperature range. Check the supply voltage. Change the setting [dis] 10.4.3 Unlock the unit 10.1.2 Check flow range / temperature range. Check flow range / temperature range. UK MEW = final value of the measuring range 13 Technical data Technical data and scale drawing at www.ifm.com. 21

14 Factory setting Parameter Factory setting User setting ASP1 (TEMP) -20 C AEP1 (TEMP) 80 C ASP2 (FLOW) AEP2 (FLOW) FOU1 FOU2 dap dis MAW MEW OFF OFF 3 s d2 uni.f SMxx04 : l/min SMx404 : l/min SMx604 : gpm uni.t SMxx04 : C SMx404 : C SMx604 : F SELd MAW = Initial value of the measuring range MEW = Final value of the measuring range FLOW 22 Technical data, approvals, accessories and further information at www.ifm.com.