QIRT th International Conference on Quantitative InfraRed Thermography

Similar documents
METHOD OF IN-SITU MEASUREMENT OF THERMAL INSULATION PERFORMANCE OF BUILDING ELEMENTS USING INFRARED CAMERA

Determining of Thermal Conductivity Coefficient of Pressed Straw (Name of test)

Determination of installed thermal resistance into a roof of TRISO-SUPER 12 BOOST R

Publ. No. T Rev. a326 ENGLISH (EN) March 6,

THERMAL TRANSMITTANCE OF MULTI-LAYER GLAZING WITH ULTRATHIN INTERNAL PARTITIONS. Agnieszka A. Lechowska 1, Jacek A. Schnotale 1

Vincent Barraud SOPREMA BASICS OF THERMAL INSULATION

Reflow Soldering Processes Development Using Infrared Thermography

In situ quantitative diagnosis of insulated building walls using passive infrared thermography

Initial study - draft

5. AN INTRODUCTION TO BUILDING PHYSICS


WUFI Workshop NBI / SINTEF 2008 Radiation Effects On Exterior Surfaces

THERMAL ANALYSIS OF OVERGROUND BOUND CONSTRUCTIONS

Standard Test Method for Measuring the Steady-State Thermal Transmittance of Fenestration Systems Using Hot Box Methods 1

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NORTH EAST WINDOWS USA, INC.

NUMERICAL ANALYSIS OF HEAT STORAGE AND HEAT CONDUCTIVITY IN THE CONCRETE HOLLOW CORE DECK ELEMENT

Thermal mass vs. thermal response factors: determining optimal geometrical properties and envelope assemblies of building materials

/qirt The influence of air humidity on effectiveness of heat sink work. by M. Kopeć*, R. Olbrycht*

Analysis of Thermal Diffusivity of Metals using Lock-in Thermography

TREES Training for Renovated Energy Efficient Social housing

THERMAL DYNAMIC BEHAVIOR OF SINGLE COMPONENT: EXPERIMENTAL ANALYSIS AND NUMERICAL MODELING

Determination of thermal transmittance of window (test title)

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NU VISTA WD, INC. SERIES/MODEL: Malibu 250 T TYPE: Fixed

Report No: NCTL NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 12/14/15

AIR-INS inc. 1320, boul. Lionel-Boulet, Varennes (Quebec) J3X 1P7 Tél. : (450) Fax : (450)

Chapter 2 Experimental Studies on Hygrothermal Behaviour of ETICS

Test Results: Results of the test period on 06/19/16 using the Equivalent CTS Method: Thermal transmittance at test conditions (U s ):

Inverse Heat Flux Evaluation using Conjugate Gradient Methods from Infrared Imaging

Assessing The Thermal Performance of Building Enclosure Materials Using A Medium-Size Hot Box Chamber Summer Meeting Torkan Fazli

Response function method

Div. 1 Div. 2 Div. 3 Div.4 8:30 am 9:30 pm 12:30 pm 3:30 pm Han Xu Ruan Pan

Fig 1. Power Tower during Operation

LP PYRA Installation and Mounting of the Pyranometer for the Measurement of Global Radiation:

A quantitative infrared thermography method for the assessment of windows thermal transmittance

Double-Skin Facade in Low-Latitude: Study on the Absorptance, Reflectance, and Transmittance of Direct Solar Radiation

Physics 326 Lab 6 10/18/04 DAMPED SIMPLE HARMONIC MOTION

Characterisation of Deposits on Membrane Walls of Steam Generators by Heat Flux Density Measurement

Report No: NCTL S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 07/14/15. Test Specimen

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC.

NFRC THERMAL TEST SUMMARY REPORT January 27, 1999 Test Specimen

Preliminary Experimental Study on Heat Transfer Characteristics of Wall with Automatic Adjustment of Heat Transfer Coefficient

Quality Assurance of Automated Measuring Systems: practical implementation of pren 14181:2001. Results of field experience at two Italian plants.

Calculating the heat transfer coefficient of frame profiles with internal cavities

Calculation of the heat power consumption in the heat exchanger using artificial neural network

Towards a Quantitative Prediction of Ice Forming at the Surface of Airport Runways

THERMAL PERFORMANCE OF COOL FACADES. EVALUATION BY INFRARED THERMOGRAPHY

Radiation Effects On Exterior Surfaces

PERFORMANCE EVALUATION OF REFLECTIVE COATINGS ON ROOFTOP UNITS

Weather Cloud Detection. Measuring infrared temperature from the environment to characterize the current weather

Write Down Your NAME. Circle Your DIVISION. Div. 1 Div. 2 Div. 3 Div.4 8:30 am 9:30 pm 12:30 pm 3:30 pm Han Xu Ruan Pan

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

DETAILED MODELING OF SOLAR FLAT-PLATE COLLECTORS WITH DESIGN TOOL KOLEKTOR 2.2

Use of Matlab package for external local calibration of IR camera with microbolometric FPA detector

DIAGNOSIS OF INSULATED BUILDING WALLS USING PASSIVE INFRARED THERMOGRAPHY AND NUMERICAL SIMULATIONS

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Energy flows and modelling approaches

Building and Environment

NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 03/31/06

3D UNSTEADY STATE ANALYSIS OF THERMAL PERFORMANCE OF DIFFERENTLY INSULATED FLOORS IN CONTACT WITH THE GROUND

Use of Infrared Thermography for Building Inspection

Uncertainty Workshop: Overview of uncertainty factors in HTGHPs

Defect detection with thermal imaging and phase shifting methods in lock-in thermography

HEAT LOSS MEASUREMENTS ON PARABOLIC TROUGH RECEIVERS

Comparing 2-D Conduction Experiments with Simulation

AN INTERNATIONAL SOLAR IRRADIANCE DATA INGEST SYSTEM FOR FORECASTING SOLAR POWER AND AGRICULTURAL CROP YIELDS

ISO INTERNATIONAL STANDARD

STUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION

Practical Experiences in Climatic Testing

Confirmation of Heat Generation during Hydrogenation of Oil

R E V I E W R E P O R T

Building physics. Reinforced concrete/reinforced concrete. Steel/reinforced concrete. Timber/reinforced concrete. Steel/steel.

Mathematical Modelling of Ceramic Block Heat Transfer Properties

TEST METHOD FOR MEASURING INSULATION VALUES OF CRYOGENIC PIPES

INVESTIGATING GLAZING SYSTEM SIMULATED RESULTS WITH REAL MEASUREMENTS

Determination of moisture surface transfer coefficients under transient conditions

OIML R 141 RECOMMENDATION. Edition 2008 (E) ORGANISATION INTERNATIONALE INTERNATIONAL ORGANIZATION

Surrounding Effects on Temperature and Emissivity Measurement of Equipment in Electrical Distribution System

SIMULATION OF FRAME CAVITY HEAT TRANSFER USING BISCO v10w

Examination Heat Transfer

Solar Flat Plate Thermal Collector

ISO INTERNATIONAL STANDARD. Thermal performance of windows, doors and shutters Calculation of thermal transmittance Part 1: Simplified method

Thermal Performance Characterization of Embedded Pulsating Heat Pipe Radiators by Infrared Thermography

THERMAL PERFORMANCE TEST REPORT

SHANGHAI MYLCH WINDOWS & DOORS THERMAL PERFORMANCE TEST REPORT

LaserComp, Inc., DESCRIPTION OF THE INSTRUMENT

TB [103 marks] The damping of the system is now increased. Which describes the change in ƒ 0 and the change in A 0?

INFLUENCE OF SURFACE EMISSIVITY AND OF LOW EMISSIVITY SHIELDS ON THE THERMAL PROPERTIES OF LOW DENSITY INSULATING MATERIALS

THE EFFECTS OF CALORIMETER TILT ON THE INWARD-FLOWING FRACTION OF ABSORBED SOLAR RADIATION IN A VENETIAN BLIND

CHAPTER 5 CONVECTIVE HEAT TRANSFER COEFFICIENT

Computational Modelling of the Impact of Solar Irradiance on Chemical Degradation of Painted Wall Hangings in an Historic Interior

Testing the performance of a green wall system on an experimental building in the summer

TEST METHOD FOR THERMAL TRANSMITTANCE AND AIR INFILTRATION OF GARAGE DOORS

Heat transfer coefficient distribution over the inconel plate cooled from high temperature by the array of water jets

Thermal Imaging Best Practices: The Measuring Object. Page 2

LP NET. 1 About LP NET. 2 Working Principle. TEL r.a. FAX

TIR100-2 Measurement of Thermal Emissivity

Analytical Design of Isolations for Cryogenic Tankers

Liquid water is one of the

Real Temperature Distribution on the Surface of Underfloor Heating

USER MANUAL HFP01 & HFP03

Transcription:

10 th International Conference on Quantitative InfraRed Thermography July 27-30, 2010, Québec (Canada) Quantitative infrared wall inspection *CE Dept., Cracow University of Technology, Kraków, Poland, tkisilew@pk.edu.pl ** MSaEE Dept., AGH University of Science and Technology, Kraków, Poland, alibel@agh.edu.pl by T. Kisilewicz*, A. Wróbel** Abstract Energy performance certification of an existing building should be based on a reliable analysis of the wall thermal characteristics. In the simplest case it may rely on the building plans, if they exist and are available. Since those plans may reflect designer s intention rather than the reality, it is suggested that the final reliable assessment should be based only on experimental testing, e.g. an infrared inspection [1]. A well insulated wall was tested in laboratory climatic chamber, initially under stationary and then under non-stationary conditions. Data gathered simultaneously by means of heat flow meter and infrared camera allowed to determine thermal characteristic of the wall in different ways. The results of the comparative measurements are presented in this paper. 1. Introduction Infrared inspection of the existing buildings is very often aimed not only at answering the question whether a continuous thermal insulation is present, but also at determining the extent of expected thermal losses. Such an approach means turning from qualitative, as in the standard [1], to quantitative thermographic assessment of the building. For this purpose, general conditions of the inspection assuring reliable and sufficient data acquisition should be specified. Subsequently, common criteria of the objective thermal image evaluation should be precisely stated. The main difficulty with field inspection of the building shell in real internal and external conditions, so called "in-situ" examination [2], is related to non-stationary boundary conditions. Due to continuous changes in the environmental temperatures, not only thermal conductivity but also specific heat and density of the materials significantly influence heat transfer through a building component. Instantaneous temperature distribution, recorded during a quick thermographic survey does not correspond with the stationary heat flow conditions and, usually, is not a good basis for reliable calculation of the overall heat transmission coefficient value. The best way to overcome temperature and heat fluctuations in real conditions is to collect data for a sufficiently long period (respectively to component thermal capacity) and use mean values to calculate thermal resistance [2]. Influence of the non-stationary conditions on the results of inspection may be to some extent limited when the inspection is carried out during a carefully selected period with limited and repeating air temperature fluctuations. Other factors having impact on success of the thermographic inspection, like solar radiation, precipitation and intensive air movement, relative humidity, distance, sky and environmental radiation etc., are relatively well researched and known by now. 2. Experimental testing in the climatic chamber The testing facility of the Cracow Technical University (CUT), Figure 1, contains the warm and cold chambers, which allow investigating a sample of maximum size 1.9 x 1.9 m. The wall tested in the climatic chamber consisted of two layers: the silica structural brickwork and insulation of 12 cm thick foamed polystyrene coated with 5 mm reinforced plaster, as in ETICS (External Thermal Insulation Compound System). Temperatures of air and wall surfaces were simultaneously measured by means of the T-type thermocouples and thermal camera Therma CAM S60 PAL with 20 o lens, Figure 2. A sheet of paper mounted on the tripod within the camera field of view was used to allow air temperature observation. Thermal images were recorded at 30 minute intervals. Temperature measured on the thermal image was in ThermaCAM Reasearcher Pro2.8, averaged across selected areas, as shown in Figure 2 with accuracy 0.1 K. Heat flow density was measured on the warm surface of the wall by the heat flow transducer Ahlborn W 150-2 (50 cm x 50 cm) with calibration uncertainty of 5%.

Fig. 1. Full scale climate chamber facility at Cracow University of Technology, cold chamber on the left, warm chamber on the right side. 31,0 C AR03 AR02 AR01 30 28 26 24 22 21,0 C Object parameter Value Emissivity 0,95 Object distance 1,5 m Ambient temperature 30,0 C Label Value AR01 : avg 29,2 C AR02 : avg 23,4 C AR03 : avg 22,6 C Fig. 2. Warm chamber of the testing facility. On the left: a view of the sample wall with the thermocouples, heat flow transducer and the thermal camera, on the right: thermal image of the sample, tripod with paper sheet and the areas selected for temperature averaging Heat transfer at the interior surface of a wall is usually described by a Newton s boundary condition, Eq. (1): where: h si heat transfer coefficient at the internal wall surface, W/(m 2 K) T i ambient air temperature, o C, T si internal surface temperature, o C. q = h ( T T ) (1) si si i si

Modeling A moderate forced convection was observed in the warm chamber. On the cold side, intensive forced convection conditions matched average exterior conditions as in the European standard EN 6946 [4]. Average velocity of the forced air flow in the warm chamber was ca. 0.3 m/s. Surface heat transfer coefficient h si, calculated according to the European standard EN 6946 [4] as the sum of forced convection and radiation coefficients, was equal to 10.33 W/(m 2 K). 80,0 heat flow density, W/m 2 70,0 60,0 50,0 40,0 30,0 20,0 10,0 R 2 = 0,9976 0,0 0 2 4 6 8 temperature difference, K Fig. 3. Correlation of the measured heat flux density and recorded by the thermal camera temperature difference of air and wall surface in the warm chamber Heat flux density data, measured by means of the transducer and recorded by the thermal camera temperature difference of air and wall surface in the warm chamber, are plotted in figure 3. A very strong correlation may be easily observed: correlation coefficient is greater than 0.99 with standard deviation of 0.45 W/m 2. It proves that the thermal camera measurement accuracy should be sufficient for quantitative assessment of the wall. According to Eq. (1), the slope of the approximating line can be regarded as the surface heat transfer coefficient h si. In our case, the slope resulting from the measurements equal to 10,28 W/(m 2 K) was practically the same as the above calculated value [5]. 3. Testing results The standard testing procedure in the climate chamber is usually based on stationary heat flow conditions, i.e. constant temperature in both chambers. Thermal resistance of the wall was measured in the stationary boundary conditions: T i = +30,20 o C and T e = +2,05 o C. Thermal resistance of the insulated wall in these conditions R λ,stat was equal to 2,68 m 2 K/W. It was regarded later as a point of reference. 19 17 15 13 11 9 7 5 3 1-1 -3 time [h] 10.01.2009 11:39:00 11.01.2009 04:19:00 11.01.2009 20:59:00 12.01.2009 13:39:00 13.01.2009 06:19:00 temperature [ o C] 30 29 28 27 26 25 24 23 22 Fig. 4. Quasi-periodic temperature fluctuations in the cold chamber for iinsulated silica brickwork: temperature fluctuations at the interior wall surface (upper curve and right axis), between insulation and brickwork (middle curve, right axis) and ambient air in the cold chamber (bottom curve and left axis).

Subsequently non-stationary testing courses were started. The temperature control system of the chamber allows not only to maintain steady state conditions but also to follow the stepwise programmed temperature schedule. This feature of the testing facility was used to simulate non-stationary conditions in the cold chamber. A test that was designed to model sinusoidal ambient air temperature schedule is shown in figure 4. In fact, although the temperature controlling unit had been programmed to follow the stepwise procedure, due to the steering process logic and chamber thermal capacity, the cold air temperature course was partially smoothed. It was assumed that the periodic temperature oscillations were the closest match to real day and night temperature changes. Due to the quasi-sinusoidal ambient air temperature fluctuations, the mathematical solution of the heat transfer in harmonic boundary conditions was commonly used to determine the dynamic characteristics of the building walls as in the standard EN 13786 [3]. The diagrams in figure 4 (cold and warm surface temperature) show thermal response of the he sample wall to the stepwise programmed temperature controller. Maximum ambient air temperature was +8 o C and minimum -2,5 o C. In order to show clearly the fluctuations of the well damped temperature wave, two different temperature ranges (and axes) were used in Figure 4. The cold surface temperature amplitude is 10.17 K with mean value of 2.64 o C. The amplitude of the temperature fluctuations under the insulation is reduced to 0.58 K and the interior surface temperature amplitude is, at the same time, equal to 0.27 K. The damping factor of the insulated wall was 0.027. A quasi-sinusoidal 24 h period was applied to simulate the random external climate conditions. Instantaneous heat flux densities measured by the heat flow transducer and calculated using the thermal images and Eq. (1) is shown in figure 5. Due to the high sensitivity of the heat flow sensor to the air turbulences and electrical noise data recorded by the camera show a close fit to the physical variability of the heat flow. thermal camera transducer 10,5 heat flow density [W/m 2 K] 10 9,5 9 8,5 8 0 2 4 6 8 10 12 14 16 18 20 22 24 time [h] Fig. 5. Quasi-periodic temperature fluctuations. Heat flux at the internal wall surface measured by the heat flow transducer and thermal camera. So called "in-situ" examination of the existing building shell is always connected with non-stationary boundary conditions. However, instantaneous temperature distribution, recorded during a quick thermographic survey (as it often happens in a common practice) is not a good basis for reliable calculation of the wall thermal resistance value. The possible results of the instantaneous measurements are shown in figure 6 as the separate points. Under the non-stationary conditions such a quick, momentary survey could become a source of the completely false results. The thermal resistance of the wall measured in this way would be in the range of 2.07 to 3.84 m 2 K/W while the proper value is 2.68 m 2 K/W. In real circumstances, the best way to overcome temperature and heat flow fluctuations in real conditions is to collect data for a sufficiently long period and use mean values to calculate the thermal resistance. According to the draft standard pren 12494 [2], an analysis shall be carried out over a period which is an integer multiple of 24 hours. In our case data recorded by the infrared camera during the regular quasi-sinusoidal 24 and 48 h periods were used to calculate wall thermal resistance.

Modeling The mean heat flux q mean,si was calculated as the product of the surface heat transfer coefficient and mean temperature drop at the internal surface, Eq. (2): where: = h ( T T (2) mean, si si i si mean q ) index mean is 24 or 48 h mean value of the heat flux and surface temperature drop The thermal resistance of the wall R λ was calculated as a ratio of the mean temperature difference of the interior and exteriorl wall surfaces and the above calculated heat flux, Eq. (3): where: ( T T ) R = si se mean λ q mean, si T se momentary exterior wall surface temperature, o C. (3) R λ,24 as calculated by Eq. (3) was equal to 2,86 m 2 K/W, i.e. 6,7 % greater than that measured under stationary conditions. The period extended to 48 hours improved accuracy of the calculations: R λ,48 was equal to 2,73 m 2 K/W, i.e. 1,7 % greater than that measured under stationary conditions. It all means that the infrared imaging may be successfully used for quantitative assessment of the building external shell. Any increased uncertainty of the measurements is likely a result of the chosen method and boundary conditions rather than a fault of the tool (camera). accumulated instantaneous thermal resistance [m 2 K/W] 4 3,8 3,6 3,4 3,2 3 2,8 2,6 2,4 2,2 2 0 2 4 6 8 10 12 14 16 18 20 22 24 hour Fig. 6. Quasi-periodic temperature fluctuations in the cold chamber. Instantaneous and accumulated for 24 h thermal resistance of the wall. Black horizontal line refers to the stationary conditions value. As it was mentioned above, the thermal analysis under real weather non-stationary conditions should be carried out over a period which is an integer multiple of 24 hours [2] i.e. a full period of the harmonic temperature wave. Special importance of this condition is shown in figures 6 and 7. A curve connecting black dots represents so called accumulated thermal resistance value. Every point of this curve was calculated as per Eq. (3), but the number of the applied averaged data was gradually increasing. In case of the full two cycles (48 h) i.e. sufficiently long period of calculations the thermal resistance of the tested wall would become about equal to that calculated under stationary conditions.

4 3,8 accumulated resistance momentary resistance thermal resistance [m 2 K/W] 3,6 3,4 3,2 3 2,8 2,6 2,4 4. Conclusions Fig. 7. Quasi-periodic temperature fluctuations in the cold chamber. Instantaneous and accumulated for 48 h thermal resistance of the wall. Black horizontal line refers to the stationary conditions value. It was shown that a transfer from qualitative to quantitative thermographic assessment of the building shell quality is justified. If the surface heat transfer value is correctly evaluated (e.g. according to the ISO standard procedures), the thermal camera measurement accuracy shall be sufficient for quantitative assessment of the wall. In real climatic conditions sufficiently long period of data averaging and integer multiple of the 24 h period, i.e. the typical measures applied in testing of the building components under non-stationary conditions, would allow to achieve good results also in case of the infrared thermal inspection. Acknowledgements 2,2 2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 hour This work was carried out within the framework of the research grant: NN526119133 financed by the Polish Ministry of Science and Higher Education from 2007 to 2010. REFERENCES [1] EN 13187 Thermal performance of buildings Qualitative detection of thermal irregularities in building envelopes Infrared method. [2] pren 12494 Building components and elements - In-situ measurement of the surface-to-surface thermal resistance [3] EN 13786, 2007. Thermal performance of building components Dynamic thermal characteristics Calculation methods. [4] EN ISO 6946 Building components and building element - Thermal resistance and thermal transmittance - Calculation method. [5] Kisilewicz T., Wróbel A. 2008. Detection of thermal bridges - aims, possibilities and conditions. QUIRT 2008 Proceedings 9-th International Conference on Quantitative Infrared Thermography, July 2-5, Krakow (Poland), p. 227-232, 2008. [6] Kisilewicz T., Thermal resistance of a wall determined in non-stationary boundary conditions, paper accepted for the I Central European Symposium on Building Physics, September 13-15, Krakow (Poland), 2010