VERIFICATION TEST AND EARTHQUAKE RESPONSE OBSERVATION OF A BASE ISOLATED BUILDING WITH ECCENTRIC ROLLER BEARINGS

Similar documents
Special edition paper

SAFETY EVALUATION OF SEISMICALLY ISOLATED HOUSES WITH DISPLACEMENT RESTRAINT DEVICES UNDER SEVERE EARTHQUAKE MOTIONS

DEVELOPMENT OF SEISMIC ISOLATION TABLE COMPOSED OF AN X-Y TABLE AND WIRE ROPE ISOLATORS

Development of Spherical Sliding Bearing

Title. Author(s)DONG, Q.; OKAZAKI, T.; MIDORIKAWA, M.; RYAN, K.; SAT. Issue Date Doc URL. Type. Note. File Information BEARINGS

RESPONSE ANALYSIS STUDY OF A BASE-ISOLATED BUILDING BASED

STATIC AND DYNAMIC LOADING TESTS OF BRACKET COMPLEXES USED IN TRADITIONAL TIMBER STRUCTURES IN JAPAN

Preliminary Examination in Dynamics

A STUDY AND DEVELOPMENT OF SEMI-ACTIVE CONTROL METHOD BY MAGNETORHEOLOGICAL FLUID DAMPER IN BASE ISOLATED STRUCTURES

Application of Capacity Spectrum Method to timber houses considering shear deformation of horizontal frames

Effects of Damping Ratio of Restoring force Device on Response of a Structure Resting on Sliding Supports with Restoring Force Device

Preliminary Examination - Dynamics

INFLUENCE OF FRICTION PENDULUM SYSTEM ON THE RESPONSE OF BASE ISOLATED STRUCTURES

RESIDUAL STORY-DRIFT OF WEAK-BEAM PORTAL FRAME WITH SLIP-TYPE RESTORING FORCE CHARACTERISTICS OF COLUMN-BASE SUBJECTED TO GROUND MOTION

2.003 Engineering Dynamics Problem Set 10 with answer to the concept questions

Vibration Control Effects of Tuned Cradle Damped Mass Damper

AN EXPERIMENTAL STUDY OF THE DYNAMIC CHARACTERISTICS OF VISCOUS FLUID DAMPERS FOR BASE ISOLATED BUILDING

Effect of Dynamic Interaction between Train Vehicle and Structure on Seismic Response of Structure

Fundamental study on simple quantitative approach of damping performance for semi-active damper

Junya Yazawa 1 Seiya Shimada 2 and Takumi Ito 3 ABSTRACT 1. INTRODUCTION

Analysis Of Seismic Performance Of Fps Base Isolated Structures Subjected To Near Fault Events

SHAKING TABLE DEMONSTRATION OF DYNAMIC RESPONSE OF BASE-ISOLATED BUILDINGS ***** Instructor Manual *****

TABLE OF CONTENTS SECTION TITLE PAGE 2 PRINCIPLES OF SEISMIC ISOLATION OF BRIDGES 3

SHAKING TABLE TESTS ON SEISMIC RESPONSE REDUCTION EFFECTS OF ROCKING BUILDING STRUCTURAL SYSTEMS

NON-LINEAR SEISMIC RESPNSE OF A PWR-TYPE REACTOR BUILDING SIMULATED BY A 3-D FEM MODEL

THE PENNSYLVANIA STATE UNIVERSITY SCHREYER HONORS COLLEGE SCHOOL OF ENGINEERING

ASEISMIC DESIGN OF TALL STRUCTURES USING VARIABLE FREQUENCY PENDULUM OSCILLATOR

REAL-TIME HYBRID EXPERIMENTAL SIMULATION SYSTEM USING COUPLED CONTROL OF SHAKE TABLE AND HYDRAULIC ACTUATOR


EARTHQUAKE SIMULATION TESTS OF BRIDGE COLUMN MODELS DAMAGED DURING 1995 KOBE EARTHQUAKE

On The Ultimate Strength of RC Shear Wall under Multi-Axes Seismic Loading Condition

EARTHQUAKE OBSERVATION OF A LOW-RISE BUILDING

Lubrication and Journal Bearings

Dynamic analysis of a reinforced concrete shear wall with strain rate effect. Synopsis. Introduction

RELATIONSHIP OF SEISMIC RESPONSES AND STRENGTH INDEXES OF GROUND MOTIONS FOR NPP STRUCTURES

Experimental Studies of Free-Standing Spent Fuel Storage Cask subjected to Strong Earthquakes

SHAKING TABLE TEST FOR FRICTIONAL ISOLATED BRIDGES AND TRIBOLOGICAL NUMERICAL MODEL OF FRICTIONAL ISOLATOR

midas Civil Dynamic Analysis

ON THE PREDICTION OF EXPERIMENTAL RESULTS FROM TWO PILE TESTS UNDER FORCED VIBRATIONS

AN EXPERIMENTAL STUDY ON INELASTIC BEHAVIOR AND RESTORING FORCE CHARACTERISTICS OF VIBRATION CONTROL DEVICE AS STEEL SCALING-FRAME

R-Plus System Frontespizio_R_PlusSystem.indd 1 11/06/ :32:02

RAPID PLATE LOAD TESTS ON BEARING STRATUM OF A BUILDING FOUNDATION

DEVELOPMENT OF A LARGE SCALE HYBRID SHAKE TABLE AND APPLICATION TO TESTING A FRICTION SLIDER ISOLATED SYSTEM

PROTECTING PRECISION MACHINERY USING GUIDEWAY SLIDING ISOLATOR WITH GAP SPRING AND DAMPERS

Structural Dynamics Lecture 4. Outline of Lecture 4. Multi-Degree-of-Freedom Systems. Formulation of Equations of Motions. Undamped Eigenvibrations.

BI-DIRECTIONAL SEISMIC ANALYSIS AND DESIGN OF BRIDGE STEEL TRUSS PIERS ALLOWING A CONTROLLED ROCKING RESPONSE

Seismic Response Analysis of Structure Supported by Piles Subjected to Very Large Earthquake Based on 3D-FEM

RESIDUAL DISPLACEMENT PREDICTION OF R/C BUILDING STRUCTURES USING EARTHQUAKE RESPONSE SPECTRA

SHAKING TABLE TEST OF STEEL FRAME STRUCTURES SUBJECTED TO NEAR-FAULT GROUND MOTIONS

Experimental investigation on monotonic performance of steel curved knee braces for weld-free beam-to-column connections

Case Study On The Soft-First-Story Buildings Strengthened By Confined Concrete Columns

Safety Margin Ratio-Based Design of Isolation Gap Size for Base-isolated Structures

Earthquake response analysis of rock-fall models by discontinuous deformation analysis

Seismic Retrofitting, Base Isolation, Dynamical Testing and System Identification: A Case Study in Sicily

SEISMIC BASE ISOLATION

Seismic design of bridges

A Modified Response Spectrum Analysis Procedure (MRSA) to Determine the Nonlinear Seismic Demands of Tall Buildings

Response characteristics of R/C buildings considering impulsive force of tsunami drifting objects

Boundary Nonlinear Dynamic Analysis

Mechatronics. MANE 4490 Fall 2002 Assignment # 1

A STUDY ON EARTHQUAKE RESPONSES OF ACTUAL ROCK-FILL DAM AND NUMERICAL ANALYSES

Evaluating the effects of near-field earthquakes on the behavior of moment resisting frames

Lectures Chapter 10 (Cutnell & Johnson, Physics 7 th edition)

1/7. 4-1) Introduction

A Sloping Surface Roller Bearing and its lateral Stiffness Measurement

Study of Rupture Directivity in a Foam Rubber Physical Model

TOPIC E: OSCILLATIONS EXAMPLES SPRING Q1. Find general solutions for the following differential equations:

SEISMIC PERFORMANCE ESTIMATION OF ASYMMETRIC BUILDINGS BASED ON THE CAPACITY SPECTRUM METHOD

Estimation Method of Seismic Response Based on Momentary Input Energy Considering Hysteresis Shapes of a Building Structure

PERFORMANCE BASED DESIGN OF SEISMICALLY ISOLATED BUILDINGS IN JAPAN

Simulated Earthquake Ground Motion for Structural Design"

SAMCEF For ROTORS. Chapter 1 : Physical Aspects of rotor dynamics. This document is the property of SAMTECH S.A. MEF A, Page 1

APPLICATION OF RESPONSE SPECTRUM METHOD TO PASSIVELY DAMPED DOME STRUCTURE WITH HIGH DAMPING AND HIGH FREQUENCY MODES

Step 1: Mathematical Modeling

Force, Mass, and Acceleration

Sabah Shawkat Cabinet of Structural Engineering Walls carrying vertical loads should be designed as columns. Basically walls are designed in

Experimental Investigation of the Performances of a WRS-BTU Seismic Isolator

ON THE REVISION OF WIND-RESISTANT DESIGN MANUAL FOR HIGHWAY BRIDGES

WORK SHEET FOR MEP311

Simulation of Nonlinear Behavior of Wall-Frame Structure during Earthquakes

REPRODUCTION OF A LARGE-SCALE 1G TEST ON UNSATURATED SAND DEPOSITS AND PILE FOUNDATIONS USING CENTRIFUGE MODELING

PRACTICAL THREE-DIMENSIONAL EFFECTIVE STRESS ANALYSIS CONSIDERING CYCLIC MOBILITY BEHAVIOR

Apex Grammar School O & A Level Evening Classes. Physics EVALUATION TEST PAPER. REAL EXAMINATION QUESTIONS for Secondary 4

Study on Dynamic Properties of Rock Discontinuity using Dynamic Direct Shear Test Machine

Centrifuge Shaking Table Tests and FEM Analyses of RC Pile Foundation and Underground Structure

A new seismic testing method E. Kausel Professor of Civil and Environmental Engineering, Massachusetts 7-277, OamWd^e, ^ 027 JP,

Seismic Base Isolation Analysis for the Control of Structural Nonlinear Vibration

CHAPTER 5. T a = 0.03 (180) 0.75 = 1.47 sec 5.12 Steel moment frame. h n = = 260 ft. T a = (260) 0.80 = 2.39 sec. Question No.

Real-Time Hybrid Simulation of Single and Multiple Tuned Liquid Column Dampers for Controlling Seismic-Induced Response

STUDIES ON SEVARAL COUNTERMEASURES AGAINST LIQUEFACTION-INDUCED FLOW AND AN APPLIVATION OF A MEASURE TO EXISTING BRIDGES IN TOKYO

Introduction to structural dynamics

SLOPE STABILITY EVALUATION AND ACCEPTANCE STANDARDS

Software Verification

7 SEISMIC LOADS. 7.1 Estimation of Seismic Loads. 7.2 Calculation of Seismic Loads

Codal Provisions IS 1893 (Part 1) 2002

Author(s) Sawamura, Yasuo; Kishida, Kiyoshi;

DUCTILITY BEHAVIOR OF A STEEL PLATE SHEAR WALL BY EXPLICIT DYNAMIC ANALYZING

Calculating Mechanical Transfer Functions with COMSOL Multiphysics. Yoichi Aso Department of Physics, University of Tokyo

HYSTERETIC PERFORMANCE OF SHEAR PANEL DAMPERS OF ULTRA LOW- YIELD-STRENGTH STEEL FOR SEISMIC RESPONSE CONTROL OF BUILDINGS

International Journal of Advance Engineering and Research Development

Transcription:

VERIFICATION TEST AND EARTHQUAKE RESPONSE OBSERVATION OF A BASE ISOLATED BUILDING WITH ECCENTRIC ROLLER BEARINGS Akihiko NAKAE 1, Susumu OTSUKA 2, Nobuyasu KAWAI 3, Isao AOKI 4, Toru NAGAOKA, Ikuo SHIMODA 6 And Sumio KAWAGUCHI 7 SUMMARY Eccentric roller bearing is a base isolation device made of stainless steel and its restoring force is produced by the gravity like a pendulum. This bearing consists of two size of eccentric roller of large and small radii with eccentric distance. Because the natural period is independent of mass of superstructure, this bearing makes it possible to achieve the long effective natural periods for a wide range of structures. Two story RC building supported by these bearings with viscous dampers is completed. Through the verification tests and the earthquake response observations, the validity of the developed base isolation device and the response reduction effect against earthquakes are confirmed. INTRODUCTION A seismic isolation device for buildings using stainless steel eccentric rollers utilizing the gravity to produce a restoring force was developed ten-odd years ago. After the Great Hanshin-Awaji Earthquake in 199, this type of isolation systems started to be applied to exhibition cases, floors and then buildings. This paper reports the results of performance verification tests and the earthquake response observation of the eccentric roller bearing isolation system carried out on a building. OUTLINE OF BASE ISOLATED BUILDING The base-isolated building is the two-story RC-structured laboratory belonging to Housing and Urban Development Corporation. Designed total floor area is 23 m 2 and the weight is 36.9 tf. In June of 1997, the eccentric roller bearing was installed on the foundation of the building. Figure 1 shows the isolated building and the plan of isolated layer. Figure 2 shows the eccentric roller bearing and the viscous damper employed in this building. The eccentric roller base isolation device supporting the superstructure consists of two stages of the isolated layers, each comprising four eccentric roller bearings forming a XY-motion mechanism, and separated by an intermediate plate. The specifications of the eccentric roller bearings used in this system are shown in Table 1. Since the eccentric roller bearing has no damping capacity, four shearing type viscous dampers are used. Table 2 shows the specifications of the viscous damper. 1 2 3 4 6 7 Building Design & Planning Dept. Okumura Corp. Tokyo, Japan Email:oku767@gm.okumuragumi.co.jp Building Design & Planning Dept. Okumura Corp. Tokyo, Japan Email:oku767@gm.okumuragumi.co.jp Building Design & Planning Dept. Okumura Corp. Tokyo, Japan Email:oku767@gm.okumuragumi.co.jp Head Office of Engineering, TENOX Corp., Tokyo, Japan Saitama Regional Branch, Housing & Urban Development Corp., Saitama, Japan Technical Dept., OILES Corp., Tokyo, Japan Technical Dept., OILES Corp., Tokyo, Japan

Figure 1: View of base-isolated building and plan of isolated layer View of eccentric roller bearing View of viscous damper Figure 2: View of base isolation device Table 1: Specifications of eccentric roller bearing (per unit) Item External dimensions Maximum applicable load Radii of large & small rollers Eccentric distance Maximum relative displacement Specification 1 W 1 D H cm 2tf 6. cm,. cm.2 cm ±34.6 cm Table 2: Specifications of viscous damper (per unit) Item Specification External dimensions 1 W 1 D 3 H cm Viscous material Butanoic polymer Area of the resistance plate 3848.4 cm 2 Shear clearance 1. cm MECHANISM OF BASE ISOLATION DEVICE The eccentric roller bearings have 6 cm radius in the thick portions, cm radius in the thin portions and.2 cm eccentric distance. There are rails arranged in parallel above and under the eccentric roller bearings. The thick portions of the rollers touch the upper rails and the thin portions sit on the lower rails. When the superstructure 2

moves in earthquake, the eccentric roller rolls, the superstructure is slightly lifted up in accordance with its horizontal displacement. The relations between the rotational angle of the rollers and the horizontal and vertical displacements are shown in Equations (1) and (2). y = ( r1 + r2 ) d sin d( 1 cos ) z = (2) where r 1 and r 2 are the radii of thin and thick portions of the roller respectively (cm), d is the eccentric distance (cm), is the rotational angle of the roller (radian), and y and z are the horizontal and vertical displacements respectively (cm). (1) State with no rolling of a eccentric roller State with rolling of a eccentric roller Figure 3: Operation of the isolation device The variation in the displacement y and z in relation to the rotational angle ( ) indicates the locus of the superstructure. When the rotational angle ( ) changes from degree to ±18 degree, the superstructure moves from the origin (,) to the point [±2(r 1 +r 2 )π, 2d ]. Since the tangential gradient leans toward the origin when the rotational angles are between ±18 degree, a restoring force is applied to the superstructure. The restoring force, Q (tf), produced in the horizontal direction can be expressed by following equation. d sin Q = m ( g + z ) (3) r1 + r2 d cos where m is the mass of the superstructure supported by the eccentric rollers (t), z is the vertical input acceleration and g is the gravity acceleration. Equation (3) shows how the eccentric roller converts the vertical inertia force including the gravity to the horizontal restoring force as shown in Figure 4. The restoring force has the non linearity and it starts to decrease as the rotational angle of the roller exceeds ±9 degree (±17.3 cm). The potential energy of the superstructure will continue to increase with the rotational angles between ±18 degree (±34.6 cm) maintaining the superstructure stable. The relationship between the rotational angle and the potential energy of the roller are analogous to the locus of the superstructure. Although the maximum rotational angle of the eccentric roller is 18 degree, in view of the horizontal installation accuracy and the motion of the foundation during earthquake, 3

the allowable horizontal displacement for the design was set to 32 cm, which corresponds to a rotational angle of 16 degree of the eccentric roller.. Vertical displacement Restoring forc.2. 1- -4-3 -2-1 1 2 3 4 1 - -1-1 - -4-3 -2-1 1 2 3 4 Horizontaldisplacem ent (cm ) Figure 4: Locus of superstructure and displacement restoring force curve The natural period of the eccentric roller is irrespective of weight it supports and determined only by the shape of the roller. The smaller the horizontal displacement (the rotational angle of the roller), the shorter the natural period. And when the horizontal displacement becomes greater, the natural period becomes longer. When the amplitude of the rotational angle is the smallest, the natural period T is expressed by Equation (4). ( r + r d ) 2π 1 2 T = (4) gd This eccentric roller bearing isolation system exhibits a natural period of 4.31 seconds when the amplitude is minimal. When the horizontal displacement exceeds 17 cm (maximum amplitude angle 9 degree), the natural period starts to lengthened sharply and becomes infinite when the horizontal displacement reaches 34 cm (maximum amplitude angle 18 degree ). (Refer to Figure ) 1 Natural perio 1 1 2 3 4 Horizontaldisplacem ent(cm ) Figure : Relationship between natural period and maximum displacement The roller bearing is made of special stainless steel of high weather resistance and its surface is hardened. The element test results certify that frictional coefficient is below 1/1. The eccentric roller bearing isolation system are equipped with a rack and pinion mechanism for prevention of roller slippage and a sliding type lifting prevention mechanism. 4

The eccentric roller bearing has no damping capacity, then the shearing type viscous dampers are applied to this seismic isolation system. When an earthquake occurs, the disk type resistance plate fixed to the superstructure moves in the viscous material contained in the compartment fixed on the base structure. Thus, a resisting force is generated in response to the relative velocity between the foundation and the superstructure. The shearing resisting force, Q (kgf), of the damper is expressed by Equation (). V.9 y.43t Q =.42 V e S () d where T is the temperature of the viscous material ( ), S is the area of the resistance plate (cm 2 ), d is the clearance between the resisting plate and the base plate, and y is the relative velocity (cm/s). SEISMIC RESPONSE ANALYSIS Preliminary evaluation of the base-isolated performance of the building was conducted using geometric nonlinear models of the eccentric roller bearings. Weight of the superstructure for analytical models were 36.9 tf. The results of the analyses for the long side of the building are reported below. In the analyses, equation (1) and (2) expressing the horizontal and vertical displacements with the rotational angle were used. Whether the eccentric rollers roll or not due to the friction were determined step by step. As an input earthquake ground motion for the response analyses, the NS and UD components of El Centro (194) were used. The maximum acceleration were set to 766.2 cm/s 2 for NS, maximum velocity of 7 cm/s, and 462 cm/s 2 for UD as an input motion level for confirmation of the safety margin. Figure 6 shows the response acceleration time histories at the first floor and the relative displacement for the base-isolated layer. The results of the analyses clearly indicates that the analyzed eccentric roller bearing isolation system has exhibited smaller response acceleration compared with that of the conventional systems and the response displacement are also smaller. It has also become clear that the framework of the isolated building has a sufficient margin against the cracking displacement. ( cm 8 4-4 -8 1 - -1 3 1-1 -3 Input acceleration Maximum :766.2 cm /s 2 Response acceleration 1 2 3 4 Maximum :88. cm /s 2 Response displacem 1 ent 2 Maximum :22. 3 cm 4 1 2 3 4 Figure 6: Response time histories (Simulated) VERIFICATION TEST After the completion of the building, the static force application and free vibration tests were conducted for confirmation of the fundamental characteristics of the eccentric roller bearings. In the static force application

test, center hole jack was set on the pedestal located on the foundation and steel wire were fixed to the pedestal on the first floor. A relative displacement of 32 cm (critical design displacement) was applied to the isolated layer by pulling the wire with the jack. In the free vibration test, hydraulic releasing devices were installed between the jack and wire. After application of the design displacement of 32 cm, the wire were released to apply free vibration to the building. The verification test were performed both on the longer and shorter sides of the building. This paper reports the results on the longer side of the building. Figure 7 shows the relations between the restoring force and the horizontal displacement. The non-linearity inherent to the eccentric rollers as shown in Figure 4 was confirmed by the test. The restoring forces of the eccentric rollers are determined only by the supporting weight and the shapes of the rollers as indicated by Equation (3). Because of the dimensional accuracy of the rollers, the weight of the building can be estimated using the restoring force obtained in the experiment. The weight of the building was estimated to be 46 tf. The restoring forces for this weight are plotted in the figure with dashed lines and are very similar to the experiment results. restoring forc 1 1 - -1 restring force of the building weight being 46tf -1-4 -2 2 4 displacem ent i ƒ j Figure 7: Restoring force - displacement curve (Experiment) Using the results of the free vibration tests as explained earlier, this paper now examines the dynamic characteristics of the eccentric roller base isolation device. The tests were conducted for the eccentric roller bearings without damper operation. Figure 8 shows the response acceleration of the first floor of the building and the relative displacement response time histories. Free vibrations continued for more than 2 seconds. This indicates the superior movability of the rollers with very small friction. As the acceleration time histories in Figure 8 represent, each peak of about 23 cm/s 2 splits into two parts in about 4 seconds after the release of the force. During this period, the maximum horizontal displacements exceed 17 cm. In the free vibrations without damper operation, the inertia force is considered to balance with the restoring force when the small friction is neglected. As seen in Figure 7, peak acceleration of 23 cm/s 2 is corresponds to maximum restoring force and the split occurs due to the decrease of the restoring force. (cm) Acceleration 3 2 1-1 -2-3 Displacem 4ent 8 12 16 2 24 28 4 Time(s) 2-2 -4 4 8 12 16 2 24 28 Time(s) Figure 8: Time histories in free vibration test 6

Using the displacement time histories in this figure, the relations between the maximum displacement amplitude and the vibration period in each cycle were evaluated. Figure 9 shows the relationship between the natural period and amplitude. The vibration period exceeded 8 seconds when the horizontal displacement was 3 cm, while it was 4 second on the small amplitude level. The theoretical relationship between the natural period and maximum displacement as shown in Figure is also shown in Figure 9. As seen in Figure 9, the natural period and the maximum amplitude of the experiments are very similar to the theoretical relationship. This superior aseismatic performance has been proved in the experiments for the comparatively light weight structure. 16 vibration peri 12 8 4 Theory Test results 1 1 2 2 3 3 maximum displacem ent am plitude (cm ) Figure 9: Relationship between natural period and maximum displacement (Experiment ) EARTHQUAKE OBSERVATIONS After the completion of the building, the earthquake response observation is continuously carried out. Several earthquake responses have been observed, and they are shown in Table 3. The observed earthquakes were medium or small classes. Table 3: Observed earthquakes Name Maximum acceleration Displacement (mm) Direction Specifications Basement 1st floor Roof floor Base-isolated layer East Off Izu Peninsula NS 6..94 1.38.26 1998..3, Mj.4 EW 6. 1.2 1.31.4 South Chiba NS 19.7 2. 2.81.6 1998..16, Mj4.9 EW 11.6 1.6 1.7.32 East Off Chiba NS 3.6 1.44 1..9 1998.6.14, Mj.6 EW 3.63 1. 1.6.46 Tokyo Bay NS 2.3 3. 7.7 1.28 1998.8.29, Mj.1 EW 23.94 4.63 6.6 1.96 Tokyo Bay NS 2.34 2.32 3.67.41 1998.11.8, Mj4.9 EW 18.12 2.17 2.6.74 Tokyo Bay Earthquake (August 29, 1998) is the largest one and maximum ground acceleration is about 2 cm/s 2 in EW-direction. Thought the maximum displacement of the bearings is very small from.2 mm to 2. mm, the maximum response acceleration of the superstructure is reduced into from 1/3 to 1/8 of that of ground motion. In order to verify the adequacy of the analytical model regarding the non-linearity of eccentric roller bearings and viscous dampers, simulation analyses of the earthquake response observations were carried out. The models were the same as those used in the preliminary evaluation, however, the building weight was revised to 46 tf, a re-estimated weight based on the test results. In the simulation analysis, friction coefficient of 1/1 in the smaller displacement levels and viscous material temperature of 2.6 o C were used. The resisting force of dampers are reduce to 1/2 of the evaluated value by Equation (), because the response was quite smaller than the design revel. The simulated results are shown in Figure 1 in comparison with observed time histories. It is confirmed that the numerical results well describes the observed response data of the building during actual 7

earthquake. (mm) BasementAcceleration (Observed) 3 1-1 -3 1st floor Acceleration 2 (Observed) 4 6 8 6 3-3 -6 Displacem ent 2 (Observed) 4 6 8 2 1-1 -2 2 4 6 8 Figure 1: Time histories of observed and simulated results (mm) 1stfloor Acceleration(Simulated) 6 3-3 -6 Displacem2 ent (Sim ulated) 4 6 8 2 1-1 -2 2 4 6 8 CONCLUSIONS The eccentric roller bearing isolation system can effectively prolongs the natural periods by changing the shape of the eccentric rollers. It is a superior isolation system because the natural period will be longer according to the increment of the displacement. By conducting the performance verification tests including free vibration tests, the fundamental properties and performance have been confirmed. Through the earthquake response observations, it is also verified that this system is sufficiently applicable to the actual buildings. In addition, the numerical simulation of the earthquake response is performed with a geometric non-linear model of this bearing. It is also confirmed that the non-linear model well describes the response of the building during actual earthquake. ACKNOWLEGMENTS This study was conducted jointly by Housing and Urban Development Corporation, Okumura Corporation and OILES Corporation. In conclusion, we would like to give our sincere thanks to Dr. Takafumi Fujita, Professor of Institute of Industrial Science, University of Tokyo, for his adequate guidance. REFERENCES Shimoda, I. (1994), Study of High Viscous damper (Modelling of Viscoelasticity and proposition of design method), Transactions of the Japan Society of Mechanical Engineers, 6, 7, pp112-117. (in Japanese) Otsuka, S. et al. (1998), Verification Test and Simulation on Isolated Building by Eccentric Roller Bearings, The 1th Earthquake Engineering Symposium proceedings, pp2693-2698 (in Japanese) 8