An Experimental Study On Condensation Of R134a In A Multi-Port Extruded Tube

Similar documents
Boiling Heat Transfer and Pressure Drop of R1234ze(E) inside a Small-Diameter 2.5 mm Microfin Tube

Condensation Heat Transfer of Pure Refrigerants in Microfin Tubes

Experimental investigation on up-flow boiling of R1234yf in aluminum multi-port extruded tubes

Characteristics of Flow Boiling Heat Transfer of Sub-Critical CO2 in Mini-Channels With Micro- Fins

Heat Transfer of Condensation in Smooth Round Tube from Superheated Vapor

Uncertainty Analysis on Prediction of Heat Transfer Coefficient and Pressure Drop in Heat Exchangers Due to Refrigerant Property Prediction Error

R32 Heat Transfer Coefficient During Condensation In A Mini-Channel Multiport Tube

Experimental Study on Liquid Film Thickness of Annular Flow in Microchannels

Pressure Distribution of Refrigerant Flow in an Adiabatic Capillary Tube

Investigations Of Heat Transfer And Components Efficiencies In Two-Phase Isobutane Injector

Two-Phase Refrigerant Distribution in a Micro- Channel Manifold

Characteristics of CO2 Transcritical Expansion Process

R134a Flow Boiling inside a 4.3 mm ID Microfin Tube

An experimental investigation on condensation of R134a refrigerant in microchannel heat exchanger

Innovative Minichannel Condensers and Evaporators for Air Conditioning Equipment

A Numerical Study of Convective Heat Transfer in the Compression Chambers of Scroll Compressors

Frictional Characteristics of Thrust Bearing in Scroll Compressor

Boiling Heat Transfer and Pressure Drop of a Refrigerant Flowing in a Vertical Small Diameter Tube

Investigation of Thermal-Hydraulic Characteristics of Pillow Plate Heat Exchangers Using CFD

DETERMINATION OF R134A S CONVECTIVE HEAT TRANSFER COEFFICIENT IN HORIZONTAL EVAPORATORS HAVING SMOOTH AND CORRUGATED TUBES

An experimental study of flow boiling characteristics of carbon dioxide in multiport mini channels

Minhhung Doan, Thanhtrung Dang

ME 402 GRADUATE PROJECT REPORT ACTIVE BATTERY COOLING SYSTEM FOR ALL-ELECTRIC VEHICLES JINGWEI ZHU

THE EXPERIMENTAL STUDY OF THE EFFECT OF ADDING HIGH-MOLECULAR POLYMERS ON HEAT TRANSFER CHARACTERISTICS OF NANOFLUIDS

Semi-Empirical 3D Rectangular Channel Air Flow Heat Transfer and Friction Factor Correlations

Heat transfer coefficient of near boiling single phase flow with propane in horizontal circular micro channel

Theoretical and Experimental Studies on Transient Heat Transfer for Forced Convection Flow of Helium Gas over a Horizontal Cylinder

Condensation and Evaporation Characteristics of Flows Inside Three Dimensional Vipertex Enhanced Heat Transfer Tubes

Two Phase Pressure Drop of CO2, Ammonia, and R245fa in Multiport Aluminum Microchannel Tubes

IHTC DRAFT MEASUREMENT OF LIQUID FILM THICKNESS IN MICRO TUBE ANNULAR FLOW

THE EFFECT OF LIQUID FILM EVAPORATION ON FLOW BOILING HEAT TRANSFER IN A MICRO TUBE

EFFECT OF LIQUID REYNOLDS NUMBER ON PRESSURE DROP OF EVAPORATIVE R-290 IN 500µm CIRCULAR TUBE

Heat Transfer Correlations for Small Closed End Heat Pipe with Special Vapor Chamber

THE CHARACTERISTICS OF BRAZED PLATE HEAT EXCHANGERS WITH DIFFERENT CHEVRON ANGLES

Optimization of Peripheral Finned-Tube Evaporators Using Entropy Generation Minimization

Forced Convective Boiling Heat Transfer in Microtubes at Low Mass and Heat Fluxes

Technological design and off-design behavior of heat exchangers 26

CHME 302 CHEMICAL ENGINEERING LABOATORY-I EXPERIMENT 302-V FREE AND FORCED CONVECTION

Experimental and Numerical Investigation of Two- Phase Flow through Enlarging Singularity

Piping Systems and Flow Analysis (Chapter 3)

Evaporation Heat Transfer and Pressure Drop of Refrigerant R-410A Flow in a Vertical Plate Heat Exchanger

RELATION BETWEEN HEAT TRANSFER AND FRICTIONAL PRESSURE DROP OF GAS-LIQUID TWO-PHASE FLOW IN SMALL BORE TUBES

Flow Boiling Pressure Drop of R134a in Micro Diameter Tubes: Experimental Results and Assessment of Correlations

Title Process of Ethanol in Activated Car. Citation Physics Procedia (2015), 69:

Mathematical Modelling for Refrigerant Flow in Diabatic Capillary Tube

a. Key Laboratory of Efficient Utilization of Low and Medium Grade Energy, MOE, Tianjin University, Tianjin , China

Evaporation Heat Transfer Coefficients Of R-446A And R-1234ze(E)

Analysis Of Void Fraction In Microchannels

Variable Speed Tri-Rotor Screw Compression Technology

NUMERICAL SIMULATION OF CONJUGATE HEAT TRANSFER FROM MULTIPLE ELECTRONIC MODULE PACKAGES COOLED BY AIR

Tutorial 1. Where Nu=(hl/k); Reynolds number Re=(Vlρ/µ) and Prandtl number Pr=(µCp/k)

The Effect Of Volute Tongue And Passage Configuration On The Performance Of Centrifugal Fan

Conjugate heat transfer from an electronic module package cooled by air in a rectangular duct

Heat Transfer Characteristics of Square Micro Pin Fins under Natural Convection

Fall 2014 Qualifying Exam Thermodynamics Closed Book

Developing Mist-Annular Flow of R134a/PAG 46 Oil on Inclined Tubes at Compressor Discharge

FIELD STUDY OF FLOW AND HEAT TRANSFER IN TUBE MICROPHONE

Experimental Investigation of Single-Phase Friction Factor and Heat Transfer inside the Horizontal Internally Micro-Fin Tubes.

In Tube Evaporation Heat Transfer of Refrigerant Mixtures

FLOW BOILING HEAT-TRANSFER IN PLATE MICRO- CHANNEL HEAT SINK

FE Fluids Review March 23, 2012 Steve Burian (Civil & Environmental Engineering)

Thermodynamic Properties of Low-GWP Refrigerant for Centrifugal Chiller

INVESTIGATION OF VAPOR GENERATION INTO CAPILLARY STRUCTURES OF MINIATURE LOOP HEAT PIPES

Three-Dimension Numerical Simulation of Discharge Flow in a Scroll Air Compressor

GRAVITY EFFECT ON THE DISTRIBUTION OF REFRIGERANT FLOW IN A MULTI-CIRCUITED CONDENSER

Heat Transfer Characteristics for Condensation of R134a in a Vertical Smooth Tube

InterPACKICNMM

HFO1234ze(E) And HFC134a Flow Boiling Inside a 4mm Horizontal Smooth Tube

CFD Simulation and Experimental Study on Airside Performance for MCHX

Condensation of refrigerant R407C in multiport minichannel section

CONDENSATION HEAT TRANSFER COEFFICIENT CORRELATION BASED ON SLIP RATIO MODEL IN A HORIZONTAL HEAT EXCHANGER

Heat Transfer During In-Tube Condensation of CFC-113 with Downflow in Vertical, Internally- Enhanced Tubes

Performance evaluation of heat transfer enhancement for internal flow based on exergy analysis. S.A. Abdel-Moneim and R.K. Ali*

NATURAL CONVECTION HEAT TRANSFER CHARACTERISTICS OF KUR FUEL ASSEMBLY DURING LOSS OF COOLANT ACCIDENT

Department of Mechanical Engineering, VTU, Basveshwar Engineering college, Bagalkot, Karnataka, India

Convection Workshop. Academic Resource Center

LIQUID FILM THICKNESS OF OSCILLATING FLOW IN A MICRO TUBE

Convective Mass Transfer

Energy and Exergy Analyses of the Scroll Compressor

Correlation of Evaporative Heat Transfer Coefficients for Refrigerant Mixtures

Two-phase frictional pressure gradient of R236ea, R134a and R410A inside multi-port mini-channels

Thermo-Fluid Performance of a Vapor- Chamber Finned Heat Sink

The Effect of Bubble Acceleration on the Liquid Film Thickness in Micro Tubes

Study on Flow Characteristics of Oil Viscosity Pump for Refrigerant Compressors

Oil Retention and Pressure Drop of R134a, R1234yf and R410A with POE 100 in Suction Lines

The Effects of Friction Factors on Capillary Tube Length

TankExampleNov2016. Table of contents. Layout

Numerical Study on the Condensation Length of Binary Zeotropic Mixtures

Fluid Flow and Heat Transfer of Combined Forced-Natural Convection around Vertical Plate Placed in Vertical Downward Flow of Water

CFD-Based Correlation Development for Air Side Performance of Wavy Fin Tube Heat Exchangers using Small Diameter Tubes

Influence of the Heat Transfer on the Pressure Field in Radial Diffusers Flows

A VAPOR-PRESSURE-DRIVEN HEAT PIPE FOR SIDEWARD LONG-DISTANCE HEAT TRANSPORT

An Experimental Study on Convective Condensation of Steam in a Horizontal Tube at Low Pressure with Twisted Tape Inserts

A Novel Model Considered Mass and Energy Conservation for Both Liquid and Vapor in Adsorption Refrigeration System.

Takaki OHKOUCHI Hiroyuki OSAKABE Toshihide NINAGAWA Kiyoshi KAWAGUCHI

Gradient-Based Estimation of Air Flow and Geometry Configurations in a Building Using Fluid Dynamic Adjoint Equations

Level 7 Post Graduate Diploma in Engineering Heat and mass transfer

International Journal of Heat and Mass Transfer

International Journal of Multiphase Flow

VOID FRACTION CHARACTERISTICS OF ONE-COMPONENT GAS LIQUID TWO-PHASE FLOW IN SMALL DIAMETER TUBES

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2 An Experimental Study On Condensation Of R134a In A Multi-Port Extruded Tube S. Koyama Denso Corporation K. Kuwahara Denso Corporation K. Yamamoto Denso Corporation K. Nakashita Kyushu University Follow this and additional works at: http://docs.lib.purdue.edu/iracc Koyama, S.; Kuwahara, K.; Yamamoto, K.; and Nakashita, K., "An Experimental Study On Condensation Of R134a In A Multi-Port Extruded Tube" (2). International Refrigeration and Air Conditioning Conference. Paper 552. http://docs.lib.purdue.edu/iracc/552 This document has been made available through Purdue e-pubs, a service of the Purdue University ibraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick aboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

R6-2 AN EXPERIMENTA STUDY ON CONDENSATION of R134a IN A MUTI-PORT EXTRUDED TUBE * Shigeru Koyama, Dr. Eng., Professor, Institute of Advanced Material Study, Kyushu University, 6-1 Kasuga-kohen, Kasuga 816-8580, Japan; Tel: 81-92-583-7831, Fax: 81-92-583-7833 E-mail: koyama@cm.kyushu-u.ac.jp *Author for Correspondence Ken Kuwahara, Assistant Professor, Institute of Advanced Material Study, Kyushu University, 6-1 Kasuga-kohen, Kasuga 816-8580, Japan; Tel: 81-92-583-7269, Fax: 81-92-583-7833 E-mail: kenk@cm.kyushu-u.ac.jp Koichi Nakashita, Interdisciplinary Graduate School of Engineering Sciences, Kyushu University, 6-1 Kasuga-kohen, Kasuga 816-8580, Japan; Tel: 81-92-583-7269, Fax: 81-92-583-7833 Ken Yamamoto, Director, Air-Conditioning R&D Depart. 2, Denso Corporation, Kariya, Aichi 448-8661, Japan ABSTRACT In the present study, the local characteristics of pressure drop and heat transfer are investigated experimentally for the condensation of a pure refrigerant R134a in multi-port extruded tubes of 8 channels in 1.36mm hydraulic diameter and 19 channels in 0.80mm hydraulic diameter. The experimental data of frictional pressure drop (F.P.D.) and condensation heat transfer coefficient (H.T.C.) are compared with previous correlations, most of which are proposed for the condensation of pure refrigerant in a relatively large diameter tube. Considering the effects of surface tension and kinematic viscosity, new correlation of F.P.D. is developed based on the Mishima-Hibiki correlation. New correlation of H.T.C. is also developed modifying the effect of diameter in the correlation of Haraguchi et al. A : heat transfer surface of tube Bo : Bond number Cp : isobaric specific heat d : hydraulic diameter G : mass velocity g : gravitational acceleration Ga : Galileo number H : width of tube H () ξ : function of void fraction Nu : Nusselt number P : pressure Ph : phase change number Pr : Prandtl number q : heat flux Re : Reynolds number S : wetted perimeter length T : temperature α : heat transfer coefficient h : latent heat of condensation P : pressure drop NOMENCATURE P f : frictional pressure drop P m : pressure drop due to momentum change λ : thermal conductivity µ : viscosity ν : kinematic viscosity ξ : void fraction ρ : density σ : surface tension Φ : two-phase multiplier factor Χ tt : ockhart-martinelli parameter Subscripts B : free convection condensation term cal : prediction exp : experiment F : forced convection condensation term : liquid R : refrigerant S : heat sink (cooling water) : vapor wi : inside surface wo : outside surface

INTRODUCTION From the viewpoint of global environment protection, it is urgently necessary to introduce environmentally acceptable new refrigerants and improve further the performance in the refrigeration and air-conditioning systems. As one of the methods for improving the system performance, the reduction of the diameter of heat transfer tubes is taken an interest in. There are a few previous studies on the condensation heat transfer of refrigerants in small diameter tubes. Katsuta (1994) carried out experiments of R134a in several multi-port extruded tubes, and compared the local heat transfer characteristics with several correlations proposed for relatively large diameter tubes. Yang and Webb (1996) carried out experiments on the heat transfer of R12 in a horizontal multi-port extruded tube of 2.64 mm in hydraulic diameter and a horizontal multi-port extruded microfin tube of 1.56 mm in hydraulic diameter. Moser et al. (1998) proposed a correlation using the equivalent Reynolds number model, based on experimental data of heat transfer in many horizontal tubes of 4.57-12.7 mm I.D. However, it is very difficult to measure accurately the local heat transfer characteristics in a small diameter tube using the traditional methods such as the water calorimetric method, the Wilson-plot method. Accordingly, more research efforts are required to clarify the condensation process in a small diameter tube. In the present study, local characteristics of pressure drop and heat transfer are investigated experimentally for the condensation of pure refrigerant R134a in two kinds of multi-port extruded tubes made of aluminum. The present experimental results are compared with previous correlations proposed for relatively large diameter tubes. Then, based on the present experimental data, new correlations are proposed for the frictional pressure drop and heat transfer coefficient of pure refrigerant condensing in a small diameter tube. EXPERIMENTA APPRUTUS Figure 1 shows the schematic view of the experimental apparatus. The refrigerant liquid discharged from a gear pump (1) flows into an evaporator (4) through a mass flow meter (3). The refrigerant vapor generated at the evaporator flows into a test section (5). The refrigerant condensed in the test section returns to the pump through a subcooler (6) and a liquid receiver (7). Figure 2 shows the test section, which is composed of an inlet mixing chamber, a multi-port extruded tube, and an outlet mixing chamber. Two types of multi-port extruded tubes, dimensions of which are listed in Table 1, are tested. Each test tube is 865 mm in total length and mm in effective cooling length. Eight cooling water jackets are attached on both upside and downside surfaces of the test tube; the length of each jacket is 150 mm. Sixteen heat flux sensors are inserted in between the water jackets and the test tube; the length of each sensor is 75 mm. The heat flux measured with each sensor is considered as local value in the present study. The refrigerant temperature is measured with two φ 0.5 mm K-type sheathed thermocouples inserted in the inlet and outlet mixing chambers. The outer wall temperature of the test tube is measured with 16 T-type thermocouples of φ 75 µ m O.D. (11) (7) (12) (10) (6) (2) (8) (5) (1) (2) (3) (4) ( 1) Refrigerant Pump ( 2) Flow Control alve ( 3) Mass Flow Meter ( 4) Evaporator ( 5) Test Section ( 6) Subcooler ( 7) iquid Receiver ( 8) Filter ( 9) Constant Temperature Water Bath (10) Coolant Pump (11) olume Flow Meter (12) Cooling Unit (9) (9) (9) Figure 1: Schematic view of experimental apparatus.

P R T R T W Pressure port Heat flux sensor Water jacket Mixing chamber Figure 2: Schematic view of test section. Table 1. Dimension of multi-port extruded tube Tube Type Type A Type B Channel Number 8 19 Wetted Perimeter ength [mm] 43.59 54.00 Cross Sectional Area [mm 2 ] 12.14 10.90 Hydraulic Diameter [mm] 1.114 0.807 Tube ength [mm] 865.0 865.0 Table 2. Experimental ranges Tube Type A and B Refrigerant R134a G [kg/m 2 s] P Rin [MPa] 1.7 T Rin [K] 340 T S [K] 265,280, buried in the test tube at central points of every heat flux sensor. The inlet refrigerant pressure in the inlet mixing chamber is measured by an absolute pressure gauge. The local pressure distribution from the inlet mixing chamber to the outlet mixing chamber is measured through 8 pressure measuring ports using a differential pressure transducer Pure refrigerant R134a is used as a test fluid. The experimental ranges are summarized in Table 2. The following assumptions are employed in the data reduction process: (1) In the vapor single-phase region, the pressure change is estimated using the Colburn equation; this assumption is employed to estimate the total pressure drop in the vapor single-phase region and determine the starting point of condensation. (2) In the two-phase region, the pressure drop due to the momentum change is estimated using the separated flow model; subtracting this pressure drop from the measured pressure drop leads to the frictional pressure drop. (3) In a subsection where the condensation starts, the heat flux is assumed to be uniform in the refrigerant flow direction; this assumption is employed to explore the starting point of condensation. (4) In the determination of the ending point of condensation, the heat flux is also assumed to be uniform in a subsection where the condensation terminates. (5) The representative temperature at the inner wall of the test tube is estimated assuming the one dimensional heat conduction in the tube wall. By solving the energy balance equation in each subsection successively in the refrigerant flow direction along with measured data of the refrigerant flow rate, the wall heat flux and the pressure, the quality change in each subsection is calculated. The local heat transfer coefficient α and local Nusselt number Nu are obtained as, A q H q α = =, A ( T T ) S ( T T ) wo 2 wi R wi R wi α d Nu = (1), (2) λ where A wo is the outer cooling area of the test tube, A wi is the inner cooling area of the test tube, q is the wall heat flux over a subsection, H is the width of the test tube, S is the wetted perimeter length of the test tube, T R is the arithmetic mean of refrigerant temperature at the inlet and the outlet of a subsection, T wi is the inner wall temperature of the test tube, d is the hydraulic diameter of the test tube, and λ is the thermal conductivity of refrigerant liquid. The frictional pressure drop between the neighboring pressure measuring ports, Pf, is obtained by subtracting the effect of momentum change from the measured pressure drop as,

2 2 ( 1 x) ( ) 1 ξ ρ Pf P Pm 2 2 Pm G x G =, = + (3), (4) ξ ρ where P is the measured pressure drop, Pm is the pressure drop due to momentum change, ξ is the void fraction, z is the distance between the neighboring pressure measuring ports, and ρ and ρ are the densities of refrigerant liquid and vapor, respectively. The void fraction is estimated by the Smith equation (Smith 1971) as, Then, the two-phase multiplier factor 1 x + 0. 4 x ψ = 1 + 0 4 0 6. +. ρ x 1 x (5) ρ 1 x Φ is obtained as, ρ ρ 1 + 0. 4 x 1 Pf Φ = (6) P where P is the pressure drop when only the vapor component flows in the test tube, which is estimated by the Colburn equation. Thermophysical properties in data reduction of each experiment are calculated using the REFPROP ersion 6.0 (Mcinden et al. 1998). RESUTS AND DISCUSSION Figure 3 shows the relation between the two-phase multiplier factor φ and the ockhart-martinelli parameter Χ tt, where Figs. 3(a) and (b) are the results for test tubes of Type A and Type B, respectively. In both figures, correlations proposed by Mishima-Hibiki (1995), Chisholm-aird (1958), Soliman et al. (1968), and Haraguchi et al. (1994a) are represented by a dashed line, a solid line, a chain line and a double-dotted chain line, respectively. Both correlations of Chisholm-aird and Soliman et al. overpredict the experimental data, and the correlation of Haraguchi et al. shows completely different trend toward the experimental data. The main reason of these discrepancies is due to neglecting the effect of tube diameter in their correlations. On the other hand, Mishima- Hibiki correlation, in which the effect of tube diameter is considered, shows the same trend as the experimental data. Φ G TS[K] [kg/sm 2 ] 265 280 G=[kg/m 2 s] G=[kg/m 2 s] Φ G TS[K] [kg/sm 2 ] 265 280 G=[kg/m 2 s] G=[kg/m 2 s] 10 0 Correlation of Mishima-Hibiki Correlation of Chisholm-aid Correlation of Soliman Correlation of Haraguchi et al. 10-2 10-1 10 0 Χtt 10 0 Correlation of Mishima-Hibiki Correlation of Chisholm-aid Correlation of Soliman Correlation of Haraguchi et al. 10-2 10-1 10 0 Χtt Figure 3: Relation between Φ and Χ tt.

p p p p p p p p 10 4 [kg/m 2 s] 24 25 5-10 10 4 [kg/m 2 s] 25 5-10 P exp [Pa] 10 3 +40% P exp [Pa] 10 3-20% 10 3 10 4 10 3 10 4 P cal [Pa] P cal [Pa] Figure 4: Comparison between measured and predicted pressure drop by equation (7). Table 3: Correlations of frictional pressure drop and heat transfer Frictional pressure drop: Φ Heat Transfer Correlation: 6 2 ( ) 0. Bo e Χ tt + 0. 17 2 ν = 1 + 13. 17 1 Χ tt ν (7) 2 2 ( Nu ) 1 2 F Nu 1.37 0.7 where Nu 0. Pr ( Φ / Χ ) Re F 0112 Nu = + (8) B 0 85 = tt, NuB = 0. 725( 1 e ). Bo H() ξ Ph Ga Pr 1 4 (note) 2 2 3 d g( ρ ρ ) g ρ d Bo =, 2 σ µ µ Cp Pr =, Re λ H., 0 1 Ga =, () ξ = ξ + [ 10(1 ξ) 8. 9] ξ ( 1 ξ ) ( 1 x) G d =, X µ tt 1 x = x 0. 9 ρ ρ 0. 5 µ µ 0. 1 Ph Cp ( T T R wi =, h ) The Mishima-Hibiki correlation is based on the experimental data of air-water adiabatic two-phase flow. Therefore, in the present study, new collation, listed in Table 3, is proposed taking an account of the surface tension effect based on the Mishima-Hibiki equation. The comparison between the measured pressure drop and the pressure drop predicted using equation (7) is shown in Figure 4. The values of the predicted pressure drop agree well with measured ones. Figure 5 shows the comparison between experimental data of local heat transfer and the correlation of Moser et al. (1998), which is proposed for the in-tube condensation heat transfer coefficient based on the data of relatively large diameter tubes of 4.57-12.7 mm I.D. It is noted that the experimental data cannot be compared with the correlation of Moser et al. originally because it is out of range. In the cases of high mass velocity, G = -

p p +% +% +50% [kg/m 2 s] 45 25 5-10 [kg/m 2 s] 25 5-10 Figure 5: Comparison between experimental data and correlation of Moser et al. g p p g p p [kg/m 2 s] 45 25 5-10 -70% [kg/m 2 s] 45 25 5-10 +50% -75% Figure 6: Comparison between experimental data and correlation of Haraguchi et al. [kg/m 2 s], most of the present data agree with the correlation within an error of ± 30%. However, in the cases of low mass velocity, G = and [kg/m 2 s], the data of are higher than the predicted values. The reason is mainly due to neglecting the free convection effect in their correlation. Figure 6 shows the comparison between the present experimental data and correlation of Haraguchi et al. (1994b). This correlation is proposed for in-tube condensation heat transfer coefficient based on the data of a relatively large diameter tube of 8.4 mm I.D; in this correlation, both effects of the forced convection and free convection are taken into account. The present data,, are lower than the predicted values,, and there is a different trend between the experimental data and the predicted values. The main reason of this difference is caused

p p p p [kg/m 2 s] 45 25 5-10 [kg/m 2 s] 25 5-10 Figure 7: Comparison between experimental data and equation (8) by the estimation of the forced convection term in their correlation. In the correlation of Haraguchi et al. (1994b), the forced convection term is calculated based on the frictional pressure drop correlation of Haraguchi et al. (1994a). However, their correlation for frictional pressure drop overpredicts the present experimental data extremely. In consequence, their correlation for heat transfer coefficient overpredicts the present experimental data. Therefore, in the present study, new heat transfer correlation, listed in Table 3, is proposed by modifying the effect of tube diameter in the correlation of Haraguchi et al. Figure 7 shows the comparison between experimental data and prediction by equation (8). The agreement between the experiment and the prediction is fairly good. CONCUSIONS The characteristics of pressure drop and heat transfer are experimentally investigated on the condensing twophase flow of pure refrigerant R134a in two kinds of horizontal multi-port extruded tubes. The conclusions are as follows: (1) The trend of the present experimental data of frictional pressure drop is the same as the Mishima-Hibiki correlation. However, correlations of Chisholm-aird, Soliman et al. and Haraguchi et al. overpredict the experimental data. This result suggests that the effect of tube diameter should be included in the correlation of frictional pressure drop. (2) The present experimental data except for cases of low mass velocity are relatively in good agreement with the heat transfer correlation of Moser et al., although it is proposed for the in-tube forced convective condensation based on the data of relatively large diameter tubes. It is inferred from this result that the effect of gravitational acceleration should be considered in the case of low mass velocity. The present experimental data were also compared with the heat transfer correlation of Haraguchi et al., in which both effects of the forced convection and the free convection are taken into account. However, the agreement between the experiment and the prediction is not so good. This reason may be caused mainly by the estimation of the forced convection term in their correlation. (3) Considering the effects of surface tension and kinematic viscosity, new correlation of frictional pressure drop is developed based on the Mishima-Hibiki correlation. New correlation of heat transfer coefficient is also developed modifying the effect of diameter in the correlation of Haraguchi et al. REFERENCES Chisholm, D. and aird, A. D. K., Two-phase flow in rough tubes, Trans. ASME, 80-2, pp. 227-286, 1958.

Haraguchi, H., Koyama, S. and Fujii, T., Condensation of Refrigerants HCFC22, HFC134a and HCFC123 in a Horizontal Smooth Tube (1st Report, Proposal of Empirical Expressions for the ocal Frictional Pressure Drop), Trans. JSME, (B), 60-574, pp. 239-244, 1994a, (in Japanese). Haraguchi, H., Koyama, S. and Fujii, T., Condensation of Refrigerants HCFC22, HFC134a and HCFC123 in a Horizontal Smooth Tube (2nd Report, Proposal of Empirical Expressions for the ocal Heat Transfer Coefficient), Trans. JSME, (B), 60-574, pp. 245-252, 1994b, (in Japanese). Katsuta, M., The Effect of a Cross-Sectional Geometry on the Condensation Heat Transfer Inside Multi-Pass Tube, Proc. WTPF, POSTECH, ol.2, pp. 146-157, 1994. Mcinden, M. O., Klein, S. A., emmon, E. W. and Peskin, A. P., NIST thermodynamic properties of refrigerants and refrigerant mixtures database (REFPROP), er. 6.0, 1998. Mishima, K. and Hibiki, T., Effect of inner diameter on some characteristics of air-water two-phase flows in capillary tubes, Trans. JSME, (B), 61-589, pp. 99-106, 1995, (in Japanese). Moser, K. W., Webb, R.. and Na, B., A New Equivalent Reynolds Number Model for Condensation in Smooth Tubes, ASME J. Heat Transfer, ol.120, pp. 410-417, 1998. Smith, S.., oid Fraction in Two-Phase Flow: A Correlation Based upon an Equal elocity Heated Model, Heat and Fluid Flow, ol.1, pp. 22-37, 1971. Soliman, M., Schuster, J. R. & Berenson, P. J., A general heat transfer correlation for annular flow condensation, Trans. ASME, Ser. C, 90-2, pp. 267-276, 1968. Yang, C-Y. and Webb, R.., Condensation of R-12 in Small Hydraulic Diameter Extruded Aluminum Tubes with and without Micro-Fins, Int. J. Heat Mass Transfer, ol.39, pp. 791-800, 1996.