EXPERIMENTAL INVESTIGATION OF NOISE PARAMETERS IN HVAC SYSTEMS

Similar documents
Some considerations on noise monitoring for air handling equipments

Transmission Matrix Model of a Quarter-Wave-Tube with Gas Temperature Gradients

The diagram below. to the by the. outlet into. calculation. Since TRANSMISSION VIA STRUCTURE. Vibration Via Supports Duct Breakout

Transmission Matrix Model of a Quarter-Wave-Tube with Gas Temperature Gradients

Fan duct noise elimination by the use of helicoidal resonators

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

ISO 5136 INTERNATIONAL STANDARD. Acoustics Determination of sound power radiated into a duct by fans and other air-moving devices In-duct method

PART VIII: ABSORPTIVE SILENCER DESIGN

Wojciech ŁAPKA, Czesław CEMPEL

Addendum to ARI Standard , Air Terminals September 2002

Effect of effective length of the tube on transmission loss of reactive muffler

Ecolibrium. All natural. A new style for supermarkets? THE OFFICIAL JOURNAL OF AIRAH AUGUST 2017 VOLUME 16.7 RRP $14.95

Design of Partial Enclosures. D. W. Herrin, Ph.D., P.E. University of Kentucky Department of Mechanical Engineering

ISO INTERNATIONAL STANDARD

FAN TERMINOLOGY. t = 1.2 kg/m 3 (Standard air density at 20 C and 1013mb. V = duct air velocity, m/s.

Lindab Group We simplify construction

Aeroacoustic simulation of automotive ventilation outlets

Engineering Noise Control

The Corrected Expressions for the Four-Pole Transmission Matrix for a Duct with a Linear Temperature Gradient and an Exponential Temperature Profile

Method of Measuring Machinery Sound Within an Equipment Space

Reactive Silencer Modeling by Transfer Matrix Method and Experimental Study

Acoustic Quantities. LMS Test.Lab. Rev 12A

QUANTIFYING ACOUSTIC SOURCES THROUGH SOUND POWER MEASUREMENTS

Circular duct grille

VK2 volume flow controller Overview

Sound Rating of Ducted Air Moving and Conditioning Equipment

Fundamentals of silencing and their practical application in screw compressor plants

EUROVENT 8/12 SOUND TEST METHOD FOR DUCTED FAN COIL UNITS. FCP 2008 testing procedures FCP acoustical test method pag. 1

Acoustics - Measurements on silencers in situ (ISO 11820:1996) Akustik - Ljuddämpare - Fältmätningar (ISO 11820:1996)

Acoustics of Suction Mufflers in Reciprocating Hermetic Compressors

Experimental study on the aeroacoustic characterization of exhaust mufflers in the presence of mean flow

Transmission Loss Assessment for a Muffler by Boundary Element Method Approach

Comparison of Noise Test Codes when Applied to air Compressors

PREDICTION OF FAN SOUND POWER

ON SOUND POWER MEASUREMENT OF THE ENGINE IN ANECHOIC ROOM WITH IMPERFECTIONS

What s that Noise? Duct System Design Guide. Visit $69.00 value!

Turbines and turbine sets Measurement of emitted airborne noise Engineering/survey method

MAC Aura XB Acoustic Test Report

Standard Test Method for Measuring Acoustical and Airflow Performance of Duct Liner Materials and Prefabricated Silencers 1

ISO 3741 INTERNATIONAL STANDARD

Noise Allocation for Industrial Plant Acoustic Design

CDD/CDR. Circular ceiling diffuser for supply air QUICK FACTS

Available online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015

ONBOARD SHIP NOISE ANALYSIS

Sound power level measurement in diffuse field for not movable sources or emitting prominent discrete tones

AN INTRODUCTION TO NOISE CONTROL IN

CDD/CDR. Single cone ceiling diffusers for supply air. Quick facts. Quick guide CDD/CDR A I R F L O W - S O U N D L E V E L

APPENDIX B. Noise Primer

Active Minimization of Acoustic Energy Density to Attenuate Radiated Noise from Enclosures

VRF Technical Data Book

Basics of Sound and Noise. David Herrin, Ph.D., P.E. University of Kentucky Department of Mechanical Engineering

Introduction to Acoustics Exercises

Circular duct grille. Dimensions. Description. Maintenance The grille should be removed to gain access to the duct.

ECMA Measurement of airborne noise emitted and structure-borne vibration induced by small air-moving devices Part 1: Airborne noise measurement

Assessment & Specifications for Noise Controls

STRUCTURAL ANALYSIS OF THE EXHAUST GAS SILENCER FOR THE FLOW THROUGH PERFORATED AND NON-PERFORATED SILENCER

ISO INTERNATIONAL STANDARD. Acoustics Acoustic insulation for pipes, valves and flanges

Design of Mufflers and Silencers. D. W. Herrin, Ph.D., P.E. University of Kentucky Department of Mechanical Engineering

Analysis of Split Air Conditioner Noise using Sound Intensity Mapping

An Introduction to Noise Control in Buildings (Live Webinar)

Noise Attenuation for Chimney Engineers presented by Steven Reid at the CICIND Conference Lisbon Sept CICIND

DETERMINATION OF AIRBORNE SOUND POWER LEVELS EMITTED BY GEAR UNITS

LINEAR SOURCES WITH NON-LINEAR DISTRIBUTION OF SOUND ENERGY. Miroslav Kučera, Richard Nový, Jiří Bašta

Dominant noise sources identification as cost-effective way in total sound power reduction. Slobodan Jankovic 1, Miodrag Ivkovic 2

Introduction to Building Acoustics and Noise Control

1. Introduction. 2. ISO 3745 and ISO standard comparison

arxiv: v1 [physics.class-ph] 22 Sep 2008

Effect of Length and Porosity on the Acoustic Performance of Concentric Tube Resonators

Estimating Community Sound Levels of Large Industrial Equipment

Nozzles. About Lindab. Comfort and Design. Product overview / symbols. Theory. Ceiling diffusers. Ceiling diffusers - visible.

Cyclical Mutation of Stator and Rotor Designs and Their Impact to the Acoustic Behavior of Induction Motor

IMPROVING THE ACOUSTIC PERFORMANCE OF EXPANSION CHAMBERS BY USING MICROPERFORATED PANEL ABSORBERS

Suction Muffler Optimisation in a Reciprocating Compressor

Chapter 10 Sound in Ducts

University of Kentucky

ALUMINIUM CENTRIFUGAL FANS. 4 x M6 x OUTLET x M6 x 20

ALUMINIUM CENTRIFUGAL FANS x M6 x x M6 x 16

IDENTIFICATION OF SOUND SOURCES EMITTED BY AN AXIAL FAN

DBS315 1-phase SIDE CHANNEL BLOWERS

GRC. Circular egg crate grille for transfer/extract air and wall/ceiling mounting QUICK FACTS

Sound Engineering Test and Analysis

Laser scanning vibrometry measurements on a light weight building element

Noise Testing and Prediction Methods for Multi-Point Ground Flares

ALC. ALBATROSS Supply air terminal for large airflows

NUMERICAL PREDICTION OF PERFORATED TUBE ACOUSTIC IMPEDANCE

ISO INTERNATIONAL STANDARD

Standard Practices for Air Speed Calibration Testing

Sound power qualification of a turbocharger in enclosed environment using an innovating acoustic imaging processing: Generalized Acoustic Holography

Analysis and Control of Noise Emissions of a Small Single Cylinder D.I. Diesel Engine

Study on Acoustically Transparent Test Section of Aeroacoustic Wind Tunnel

In the Psy. Ch., plot point o, r, h r = 51.0 kj/kg, h o = 85 kj/kg

Experimental determination of far field sound power due to panel and vent radiation of a portable diesel generator

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

Modeling and simulation of windows with noise mitigation and natural ventilation

88. Noise control and sound quality evaluation of outdoor unit of split air-conditioner

HVAC Clinic. Duct Design

1 Wind Turbine Acoustics. Wind turbines generate sound by both mechanical and aerodynamic

Consultancy Report Ref: 9383-R01

Understanding & Reducing Air System Noise

Prediction of Transformer Core Noise

Transcription:

The 40 th International Conference on Mechanics of Solids, Acoustics and Vibrations & The 6th International Conference on Advanced Composite Materials Engineering ICMSAV2016& COMAT2016 Brasov, ROMANIA, 24-25 November 2016 EXPERIMENTAL INVESTIGATION OF NOISE PARAMETERS IN HVAC SYSTEMS Marcelin Benchea 1, Carmen Bujoreanu 2 1 Gheorghe Asachi Technical University of Iasi, Romania, marcelin.benchea@tuiasi.ro 2 Gheorghe Asachi Technical University of Iasi, Romania, carmen.bujoreanu@gmail.ro Abstract: Heating, ventilating and air-conditioning (HVAC) systems represent a major source of inside buildings noise with a negative effect on the acoustical environment, so beneficiaries are in particular annoyed by the noise generated from the radiant unit and the air circulating ducts. The technical data presented in manufacturer s catalogues highlight the relations between the air flow, pressure, power-charging and the sound level. The measurements presented in this paper are carried out at different fan s speeds, ranging the power-charge from 30% to % and static air pressure is slowly adjusted between 0 Pa to 500 Pa. Third-octave band analysis of random noise of the handling units is realized in an anechoic room and agrees the requirements of ISO 3744:2011 and ISO 5136:2010 standards. The experimental methodology used in this paper is of real interest for the HVAC manufacturers in order to rate the sound level of their products. Keywords: HVAC systems, sound level, acoustic, air flow, third-octave band analysis. 1. INTRODUCTION HVAC systems are indispensable equipments for the modern buildings in order to ensure the human thermal comfort and admissible air quality. The HVAC system includes air handling unit (AHU), supply and exhaust air ducts, return air path, terminal equipment, spaces served. These components are designed to achieve the raise or decrease of the building temperature and humidity, to add or remove outside air and to provide its proper filtration. Their performances must also agree the imposed noise regulations. The air handling equipment involves any type of HVAC system that contains a fan and it is used to condition and move air through a duct system [2]. The air handling unit is a good example to prove the difficulty in accurate sound data evaluation since there are many possible paths between the noise source and the receiver. In HVAC systems, the source of noise is a combination of different processes, such as mechanical noise from fans, pumps, compressors, motors, control dampers, variable air volume boxes and air outlets such as diffusers, grilles, dampers and registers. Therefore the most significant noise sources are the air handler equipment and the air circulating ducts [4]. The air velocity, the material roughness and the fittings of the ducts significantly increase the friction in the air handler system and obviously the noise generation [3]. Depending on the geometrical inlet/outlet openings configuration of the air handler, the sound passes through the ducts in the direction of airflow or against it. Therefore, these paths together with the air handler radiant unit including fan and dampers provide a complex acoustic situation, difficult to be predicted by theoretical algorithms. Numerical techniques for acoustic propagation in dissipative ducts and radiant unit, such as two-port transfer matrix method [3, 6], finite and boundary elements methods [5, 7] have been developed. There are also algorithms and procedures based on sound power computation [5]. In this paper are investigated two types of commercial air handler units with the same ducts diameters, but different inlet-outlet configuration. Third-octave band analysis of random noise of the handling units is realized, using measurement procedures that agree the requirements of the ISO 3744:2011 and ISO 5136:2010 standards [11, 12]. 2. EXPERIMENTAL TESTS AND PROCEDURES Software predicting the HVAC systems noise may have potential errors as they are using algorithms that calculate the sound level contributions of each element of a system. Generally, the algorithm can be considered 42

an empirical black box that takes an incoming sound power level and characteristic information of the element to produce an output sound power level [7]. Therefore, potential errors may appear and the calculated results could be quiet far from the real situation. The HVAC manufacturers are gathering information about the fan power, duct pressure vs. air flow variation, temperature, sound data and these performance parameters are included in their catalogues [1, 13, 14]. Sound power levels are usually determined in acoustics laboratory, by measuring sound pressure levels in test facilities using some specific procedures [11, 12] in order to realize data compatibility between different manufacturers. 2.1. Terminology HVAC system manufacturers evaluate the sounds in the frequencies between 45 Hz and 11200 Hz. Using the octave bands, this frequency range is separated into eight octave bands with center frequencies of 63, 125, 250, 500, 0, 2000, 4000 and 00 Hz. In terms of sound perception, the human ear is most sensitive in the frequency range 0 Hz to 4000 Hz than at very low or high frequencies. This means that the noise at high or low frequencies will not be as annoying as it would be when its energy is concentrated in the middle frequencies. A higher sound pressure is therefore acceptable at lower and higher frequencies. This knowledge is important in acoustic design and sound measurement [10]. The sound power level SWL, according to ISO 3744:2011, is the sound energy constantly transferred per second from the sound source. A sound source has a constant sound power that does not change if it is placed in a different room environment. Sound power is a theoretical value that is not measurable. p SWL 10 lg (1) p 0 with: measured sound pressure p and the reference sound power level p 0 = 10-12 W. The sound pressure level, SPL is a measurable sound level that depends upon environment. It is expressed in decibels at a specified distance and position [9]. Usually, both sound parameters are calculated and expressed in decibels although they are completely different and should not be confused. Q 4 SPL SWL 10 lg 2 (2) 4 r RC where SWL (db) is the sound power re 10-12 W; SPL (db) is the sound pressure re 2 10-5 Pa; r (m) is the distance from the source; Q is the directivity factor of the source in the direction r; R C (m 2 ) is the room constant of the S W following form: RC with S (m 2 ) total room surface and α W the average absorption coefficient [1]. 1 W Relation (3) is simplified and becomes: SPL = SWL-11 (3) Therefore, in the anechoic room, at r = 1 m distance from the source, Q = 1, the sound pressure level, SPL, is 11 db less than its sound power level, SWL. The measured background noise in our anechoic room is: SWL = 28.9 db or SPL = 17.9 (distance from the source r =1 m). 2.2. Experimental Tests The experimental setup for acoustic measurements [8] consists of: - device for measuring the pressure drop (Fluke 922 pressure differential meter), - the test object (AHU), - the transition elements on either side of the test object (air ducts), - special receiving-sound equipment consisting of: 1) microphone Bruel&Kjaer type 4133 (sensitivity 4-16 mv on N/m 2 ; 0.4-1.6 mv on μbar; 36-150 db(a)), 2) sonometer Bruel&Kjaer type 2209 (amplification: 2 Hz or 10 Hz at khz; standard filters according IEC R179, IEC R179A and ANSI Type 1) connected with the microphone and NIDAQ board, 3) multifunctional external data acquisition board type-nidaqpad-6015 on USB, 4) laptop with LabVIEW soft compatible with National Instruments DAQPad for data processing. The experimental investigation is performed in the anechoic room using a test facility that agrees with ISO 3744:2011 and ISO 5136:2010 [11, 12]. For various fan s speeds, expressed in power-charging variation between 30% and %, the sound level data are acquired. The ducts air flow is slowly adjusted from full closed to full open for each range of charging. There is analyzed the sound level db(a), A weighted, both on radiant unit and the air ducts, using the third-octave 43

analysis with LabVIEW soft, evaluating the pressure levels (dba) for nominal frequencies of 63, 125, 250, 500, 0, 2000, 4000, 00 Hz. Also, the analysis evidenced the equivalent continuous sound level that is an averaged noise in a specified time interval. Figure 1 describes typical air paths of handling unit, namely the ducts, in order to a better understanding of the air travel way and the sound that accompanies it, while figure 2 shows the frequencies and a descriptive terminology at which different types of HVAC components influence the sound spectrum in a room. Figure 1: The sound paths in the air ducts Figure 2: Frequency ranges for HVAC components Figure 3: AHU 1 unit Figure 4: AHU 2 unit The experimental setup is presented in figure 5. Figure 5: Experimental setup 44

3. EXPERIMENTAL RESULTS Figures 6 and 7 represents a comparative evaluation of the total sound level for the tested radiant units running at different air flow pressure from 0 Pa to 500 Pa (the worst case in exploitation) taking int o account of the fan power-charging. AHU 1 radiant unit has the lowest noise level and uniform noise behaviour with charging increase. A very quiet functioning at low charging and 0 Pa air flow pressure can be also noted. AHU 1 sound level values range between 35 45 db and it can be observed that it is a little less noisy than the AHU 2 radiant unit (40 50 db). Radiated unit AHU 1 55 50 45 40 35 30 55 50 45 40 35 30 115 105 95 85 75 65 115 105 95 85 75 65 Figure 6: Sound level for the AHU 1 radiant unit Radiated unit AHU 2 Figure 7: Sound level for the AHU 2 radiant unit Supply air duct AHU 1 Figure 8: Sound level for AHU 1 supply air duct Supply air duct AHU 2 Figure 9: Sound level for AHU 2 supply air duct 45

The HVAC manufacturers are interested in ducts noise in order to optimize their design and efficiency from this point of view. This optimization means the in-duct noise control, generally solved through the silencers use, thus adding adequate attenuation to the system. Therefore, the silencer selection is imposed by the duct noise level. In this regard, the total sound level variation related to the fan power-charging is expressed in figures 8 and 9 for the supply air ducts of the tested AHU 1 and AHU 2 units, ranging the air flow pressure from 0 Pa to 500 Pa. The total sound level values are much higher (65 105 db) than those for the radiant units and the sound increasing tendency with fan power-charging preserved. Also, the supply air duct of AHU 2 has the best performance in sound attenuation and similar to the supply air duct of AHU 1 at 500 Pa air flow pressure. The supply air duct of AHU 1 it is noisier than the supply air duct of AHU 2 at high fan power-charging and low air flow pressure. The same tendency is recorded for the others air ducts (figures 10 to 13). The total sound level is higher in the air ducts of AHU 1 unit at high fan power-charging and low air flow pressure, and it is decreasing at high air flow pressures, similar to the air ducts of AHU 2 unit, where the total sound level doesn t varies very much with the air flow pressure. A possible explanation of the fact that AHU 1 noise level in the air ducts is greater than the sound level of AHU 2 ducts consists in the air paths configuration. Figures 3 and 4 show the difference in the air flow directions through the ducts system, which modify the sound level. The regenerated noise in the AHU 1 air ducts is more intense since there is reverse air flow due to the disposition of the ducts (AHU 1 has the ducts inlet-outlet on the same side). On the other hand, the AHU 1 radiant unit is a little less noisy than the AHU 2 radiant unit, thus the inside attenuation elements do their job more efficient compared to the AHU 2 unit. Exhaust air duct AHU 1 60 60 Figure 10: Sound level for AHU 1 exhaust air duct Exhaust air duct AHU 2 Figure 11: Sound level for AHU 2 exhaust air duct Extract air duct AHU 1 Figure 12: Sound level for the AHU 1 extract air duct 46

Extract air duct AHU 2 Figure 13: Sound level for the AHU 2 extract air duct 4. CONCLUSION The sources of noise in HVAC systems are multiple, but the HVAC beneficiaries are in particular annoyed by the noise generated from the radiant unit and the air circulating ducts, since they are located inside the rooms and buildings. The paper presents the analysis of the equivalent continuous sound level in two commercial air handlers units. The noise level of the radiant unit complies with the standards requirement (NR 35 - NR 40) and the ducts sound level tendency emphasizes the importance of the ducts inlet-outlet mounting. They are influencing the air flow direction and the sound level. The fan power-charging, the air flow pressure, the noise generated in the system constitute acoustic performances of the HVAC systems. In order to optimize their design and efficiency from this point of view it is necessary the in-duct noise control, generally solved through the silencers use, thus adding adequate attenuation to the system. A suitable silencer selection is imposed by the duct noise level. Therefore, the experimental methodology used in the paper is of real interest for the HVAC manufacturers, in order to rate the sound level of their products and to improve the noise attenuation according to the specified standards. REFERENCES [1] Air Change Catalogue - Next-AHU TM Technical Data pp 1-4, 2014. [2] ASHRAE - Handbook-Sound and Vibration Control, chapter 48, pp.279, USA, 2011. [3] Badino A., Borelli D., Gaggero T., Rizzuto E. and Schenone C. Normative framework for ship noise: Present situation and future trends, Noise Control Engineering Journal, 60(6), 740-762, 2012. [4] Bhatia A., HVAC Systems Noise Control, Continuing Education and Development Inc., pp.109, 2014. [5] Bies D.A. and Hansen C.H., Engineering Noise Control-Theory and Practice, Spon Press,NewYork, 2003. [6] Boden, H. and Glav, R., Exhaust and Intake Noise and Acoustical Design of Mufflers and Silencers, Handbook of Noise and Vibration Control, John Wiley & Sons, 2007. [7] Borelli D. and Schenone C., A finite element model to predict sound attenuation in lined and parallel baffle rectangular ducts, HVAC&R Research, 18 (3) pp. 3-405, 2012. [8] Bujoreanu C., Benchea M., Experimental study on HVAC sound parameters, IOP Conference Series: Materials Science and Engineering, vol. 147(1), 012051, 2016. [9] Cory W., Fans & Ventilation: A Practical Guide, Elsevier, pp. 424, 2005. [10] Desmond S.D., Fans in air handling unit, Woods Air Movement Limited UK, pp. 23, 2000. [11] ISO 5136:2010 - Determination of sound power radiated into a duct by fans and other air-moving devices. In-duct method. [12] ISO 3744:2011 - Determination of sound power levels and sound energy levels of noise sources using sound pressure. Engineering methods for an essentially free field over a reflecting plane. [13] Lindab Catalogue - Ventilation Guide, pp. 1-22, 2008. [14] System Air Catalogue - Air Handling Units, pp. 1-138, 2012. [15] Ver I.L., Beranek L.L., Noise and Vibration Control Engineering: Principles and Applications, John Wiley & Sons, 2005. 47