Model of a heat meter in a district heating substation under dynamic load

Similar documents
Reducing the Flow Measurement Error Caused by Pulsations in Flows

Dynamic simulation of DH house stations

Detection of pulsating flows in an ultrasonic flow meter

Ultrasonic Flow Metering Errors due to Pulsating Flow

Mechanical thermal expansion correction design for an ultrasonic flow meter

How to avoid pressure oscillations in district heating systems

Dynamic performance of a district heating system in Madumvej, Denmark

The Expansibility Factor Equations in ISO and ISO : Do They Deliver What They Promise?

Installation effects on an ultrasonic flow meter with implications for self diagnostics

Energy flows and modelling approaches

Finite-Element Evaluation of Thermal Response Tests Performed on U-Tube Borehole Heat Exchangers

dq = λa T Direction of heat flow dq = λa T h T c

Homework 6 Solar PV Energy MAE 119 W2017 Professor G.R. Tynan

Lecture 39. PHYC 161 Fall 2016

HOTTEST SPOT AND LIFE EVALUATION OF POWER TRANSFORMER DESIGN USING FINITE ELEMENT METHOD

Guidelines for the Selection and Operation of Provers with Micro Motion ELITE Coriolis Flow Meters

Estimation of the Capacity of Multipath Infrared Channels

11. ELECTRIC CURRENT. Questions and Answers between the forces F e and F c. 3. Write the difference between potential difference and emf. A.

Thermal System Closed-Loop Temperature Control

Digital two-parametric processing of the output data from radiation detectors

Practical Analysis Of Turbulent Flow In A Pipe Using Computational Fluid Dynamics

NTE74HC109 Integrated Circuit TTL High Speed CMOS, Dual J K Positive Edge Triggered Flip Flop w/set & Reset

Excerpt from the Proceedings of the COMSOL Conference 2010 Boston

Today s menu. Last lecture. Measurement of volume flow rate. Measurement of volume flow rate (cont d...) Differential pressure flow meters

New frequency counting principle improves resolution

Sławomir Grzelak, Jarosław Czoków, Marcin Kowalski, Marek Zieliński

Switching characteristics of lateral-type and vertical-type SiC JFETs depending on their internal parasitic capacitances

Building heat system sizing

Correlation between temperatures of air, heat carrier liquid and seabed sediment in renewable low energy network

CSE140L: Components and Design Techniques for Digital Systems Lab. Power Consumption in Digital Circuits. Pietro Mercati

Downloaded from

BISTABILITY IN NbN HEB MIXER DEVICES

Simulation and verification of a plate heat exchanger with a built-in tap water accumulator

CSE140L: Components and Design Techniques for Digital Systems Lab. FSMs. Instructor: Mohsen Imani. Slides from Tajana Simunic Rosing

ITTC Recommended Procedures

Question Bank. Electric Energy, Power and Household Circuits

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study.

Multivariate Regression Model Results

Lesson 7: Thermal and Mechanical Element Math Models in Control Systems. 1 lesson7et438a.pptx. After this presentation you will be able to:

EAS327 Environmental Instrumentation Mid-term 13 Feb,2003

A Brief Description of the Construction and Function of Common Electric Matches

World Academy of Science, Engineering and Technology International Journal of Computer and Systems Engineering Vol:7, No:12, 2013

LDE/LME/LMI pressure sensors in bypass configuration for gas flowmeters

Increasing Transmission Capacities with Dynamic Monitoring Systems

Phase Control Thyristor Types N2500VC120 to N2500VC160

EXPERIMENT NO. 4 CALIBRATION OF AN ORIFICE PLATE FLOWMETER MECHANICAL ENGINEERING DEPARTMENT KING SAUD UNIVERSITY RIYADH

Operation of an Electromagnetic Trigger with a Short-circuit Ring

Temperature Control of an External Cleaning Unit

A MEASUREMENT ASSURANCE PROGRAM FOR LOW FLOW CALIBRATION BY THE TRANSFER METHOD CS20

MCE380: Measurements and Instrumentation Lab

1. Nusselt number and Biot number are computed in a similar manner (=hd/k). What are the differences between them? When and why are each of them used?

Current and Resistance

Name: Answers. Mean: 83, Standard Deviation: 12 Q1 Q2 Q3 Q4 Q5 Q6 Total. ESE370 Fall 2015

Optimization of the Air Gap Spacing In a Solar Water Heater with Double Glass Cover

Finite Element Modeling of Ultrasonic Transducers for Polymer Characterization

Comparison of Finite Element Analysis to IEC for Predicting Underground Cable Ampacity

6 INCH W X 5-3/4 INCH D X 8-3/8 INCH H

P-Channel Enhancement Mode Mosfet

Capacitor investigations

CHAPTER 5 CONVECTIVE HEAT TRANSFER COEFFICIENT

ELG4112. Electromechanical Systems and Mechatronics

Phase Control Thyristor Types N3533Z#140 to N3533Z#220 Old Type No.: N1400CH02-20

5SDD 36K5000 Old part no. DV 889B

Lab-Report Control Engineering. Proportional Control of a Liquid Level System

SECONDARY SCHOOL ANNUAL EXAMINATIONS 2002 Educational Assessment Unit - Education Division

Detection range and accuracy specs.

Safety Precautions WARNING If critical situations that could lead to user s death or serious injury is assumed by mishandling of the product.

8. Electric circuit: The closed path along which electric current flows is called an electric circuit.

PowerApps Optimal Power Flow Formulation

Phase Control Thyristor Type SKT552/16E

Heat Sinks and Component Temperature Control

SGB02N120. Fast IGBT in NPT-technology. Power Semiconductors 1 Rev. 2_3 Jan 07

Investigation of Flow Profile in Open Channels using CFD

Basic Electricity. Unit 2 Basic Instrumentation

PC Control / Touch Control

IXYS. Thyristor/Diode Modules MC#500. Date: 13 th Mar Data Sheet Issue: 1. Absolute Maximum Ratings V RRM V DRM [V] MAXIMUM LIMITS

SYSTEMS OF UNITS. 1 st Class Basic of Electrical Engineering. Current and Voltage

Experimentation. Third Edition. Wheeler. Ahmad R. Ganji. School of Engineering. With Third Edition contributions by. V. V. Krishnan. Brian S.

MATLAB SIMULINK Based Transient Exploration of RL Circuit

Interconnect Lifetime Prediction for Temperature-Aware Design

Electrical Engineering Fundamentals for Non-Electrical Engineers

57:020 Mechanics of Fluids and Transfer Processes OVERVIEW OF UNCERTAINTY ANALYSIS

Solar Flat Plate Thermal Collector

IXYS. Thyristor/Diode Modules MC#650. Date: 13 th Mar Data Sheet Issue: 1. Absolute Maximum Ratings V RRM V DRM [V] MAXIMUM LIMITS

Experiences in an Undergraduate Laboratory Using Uncertainty Analysis to Validate Engineering Models with Experimental Data

PHYSICS MC 17 P 1 23

Modelling and Simulation of Direct Self-Control Systems*

On the energy demands of small appliances in homes

Better Weather Data Equals Better Results: The Proof is in EE and DR!

MEASUREMENT OF THE THERMAL DIFFUSIVITY OF BUILDING MATERIALS

of the heat is dissipated as a result of the flow of electrical current in various conductors. In order to predict temperatures

Electrical Power Cables Part 2 Cable Rating Calculations

Dynamic Response in a Pipe String during Drop-Catch in a Wellbore

Mathematical Modelling of an 3 Phase Induction Motor Using MATLAB/Simulink

INTRODUCTION TO THE SIMULATION OF ENERGY AND STORAGE SYSTEMS

Modelling the Temperature Changes of a Hot Plate and Water in a Proportional, Integral, Derivative Control System

SIMULINK MODEL FOR A HEAT-EXCHANGER

Figure 1: Representative strip. = = 3.70 m. min. per unit length of the selected strip: Own weight of slab = = 0.

Electromagnetic Flowmeter

405 Compact Orifice Series and 1595 Conditioning Orifice Plate Flow Test Data Book and Flow Handbook

Transcription:

Model of a heat meter in a district heating substation under dynamic load Yassin Jomni, Jan van Deventer, Jerker Delsing EISLAB, CSEE, Luleå University of Technology, Luleå, Sweden, {yassin,deventer,jerker.delsing }@sm.luth.se Abstract Measurement errors generated by heat meters cause a substantial revenue loss in the district heating industry. The focus of previous works has mainly been treating improvements of heat energy measurement at steady state conditions. We have investigated how dynamic events affect the energy measurements. A simulation model comprised of a heat meter and a district heating substation has been developed. The model was implemented with the software package Simulink of MathWorks. This simulation model is used to show the impact of a dynamic load on the heat energy measurement. We see that the dynamic tap water load imposed on the system has an impact on the accuracy of the heat meter, especially when the flow increases rapidly from a low value to a higher value. The mean heat measurement error is approximatively 4% of the real heat energy transfered. Introduction District heating is a technology used to deliver heat energy from a central production facility to city districts or whole cities through a distribution network. This technology was introduced in the USA around 870-80 []. Water is commonly used as an energy carrier in such networks. The transfer of heat energy between the district heating network and a building occurs in a district heating substation through heat exchangers. It is at these substations that heat meters are located. The energy consumption can be divided into space heating and tap water usage. The tap water consumption varies as users consume hot water when they, for example, take a hot shower, wash hands etc. A typical heat meter consists of a set of two resistance temperature sensors, usually Pt500 sensors, a volume-flow meter and an integrating unit, which estimates the energy consumed by the household []. The aim of this work has been to create a computer model of a commonly used heat meter as part of a Simulink model of a district heating substation and a household [5], taking in account the dynamics of the system. The impact of the domestic hot water dynamic load on heat metering was then investigated using this model.

Heat metering theory The district heating substation, which connects the district heating network and house, also separates their circuits. The district heating circuit is refered to as the primary circuit while the household circuits are the secondary circuits. The heat meter estimates how much energy was transfered from the primary circuit to the secondary circuits. It is commonly comprised of a volume-flow meter, two resistance temperature sensors and a computing unit. The temperature sensors measure the supply and return temperatures in the primary circuit. The flow meter measures the flow rate of the primary circuit. The heat energy consumed by the household Q [J] during a period of time t is given by the following continuous time integral [] where Q = t t ṁc p (T r, T s ) T dt = V k(t r, T s ) T dt, () t t k(t r, T s ) = ρ(t r )c p (T r, T s ), () T = T s T r, () V = ṁ ρ, (4) t = t t. (5) and Ts = the measured supply temperature [ o C] T r = the measured return temperature [ o C] k(t r, T s ) = the heat coefficient [J/ o Cm ] ṁ = the mass-flow rate [kg/s] V = the volume-flow rate [m /s] ρ(t r ) = the fluid density at T r [kg/m ] c p (T r, T s ) = the average specific heat capacity at T r and T s [J/ o Ckg]. Heat meters do not compute continuous events, they use the following discrete approximation of equation () to compute the heat energy consumed by the household N Q = V i k i T i t i. (6) i=0 where t i is the time elapsed between two consecutive measurements. The flow meter emits a pulse when a certain volume of water has passed through it. The time between two consecultive pulses is often called the integration time and is flow dependent. When a pulse is emitted, the integration unit measures the return and supply temperatures and the integration time []. The average flow rate during the integration time V i, temperature difference T i and the heat coefficient k i (T ri, T si ) are then computed by the heat integrator unit using equations () to (4) and multiplied to get the value of the heat energy consumed for each iteration i. The obtained value is then added to the one computed in the previous iteration to get the total heat energy consumed according to equation (6).

Method The heat meter model presented in this paper is used as part of a larger Simulink model of a district heating substation [5] having the outside environment temperature and the domestic hot water consumption as inputs. The outside temperature is modeled by a sine wave where the daily temperature fluctuations are also modeled in the same manner. Nordic winter temperatures ( o C T o C) have been modeled in this simulation. Rectangular tap water pulses with a duration of 50 s, a period of 50 s and an amplitude of 0.8 l/s were used in this simulation to simulate the dynamics of the system. The simulated duration is hour. Real flow Real Trr Real Trs Real Flow. Meas. Flow Error in flowmeter Return Hot Water Primary circuit Real Temp.Meas. Temp Temp sensor Return Hot Water Primary circuit Real Temp.Meas. Temp Temp sensor Supply Hot Water Primary circuit Product Flowmeter pulses Flow FLOWMETER Heat Real Meas. flow Measured Tr Ts Meas. Tr Flowmeter Pulses Measured heat energy INTEGRATING UNIT Measured flow Measured Tr Measured heat Figure : Simulink model of the heat meter The inputs of the heat meter model, shown in figure (), are the real supply and return temperatures T rs and T rr and the real flow of the primary circuit which are simulated by the district heating substation model. The heat meter model s outputs, over the simulated period, are the measured return temperatures T r, the measured flow of the primary circuit and the measured heat energy consumed by the household. Flow s Integrator Water volume rem If Vol. is multiple of int. vol (reminder) If reminder small enough set to 0 Flowmeter pulses The volume of water to wait for (intg. Vol) Figure : Simulink model of a volume-flow meter Each component of the heat meter have been modeled separately with its

associated systematic and random uncertainties. Random uncertainties have been modeled by adding a Gaussian distribution with mean 0 and variance []. The response time due to material coatings and encapsulation around resistance temperature sensors has been modeled using the following first order transfer function [] G(s) = τs +, where τ is the time constant. We have used τ = in this simulation. The volume-flow meter and the integrating unit, shown in figures () and () respectively, have been modeled as explained in section. 4 Flowmeter Pulses 5 Clock Measured Tr Time pulse time Measures the time of each pulse Transport Delay Time Diff. Meas. Tr Read time diff Read Tr Measure the integration time and triggers temp. measurement Div Switch Meas. flow Meas. Tr Heat Real z Unit Delay INTEGRATOR (real=magenta) Measured heat energy Ts Product z Unit Delay f(u) Fcn INTEGRATOR: Heat error (%) Figure : Simulink model of an integrating unit 4 Results and discussion We show in figure (4) the error in heat energy estimation. The mean measurement error is approximately 4% of the real heat energy transfered estimated using equation (). Each sensor in a district heating substation has an associated uncertainty at a given confidence level whether they are used for control or for the measurement of the transferred heat. A standard error analysis is very useful to 4

0 0 00 90 Heat measurement error (%) 80 70 60 50 40 0 0 0 0 500 000 500 000 500 000 500 Time (Seconds) Figure 4: The error in heat measurement assess the contribution of the uncertainty of each error as it propagates to the transferred heat measurement. But this only considers set and static conditions [4]. Considering dynamic effects of the heat exchanger and sensors explains the source of dynamic errors. In this paper, we combine the sensor uncertainties and the dynamics of the systems to illustrate that the total error is considerable. One of the many problems the heat integrator faces, when computing the heat transfer equation (6), is that the supply and return temperatures are assumed to be constant by the heat integrator during the integration time. This is far from reality since the return temperature, but also the supply temperature to a lesser extent, fluctuates during the integration time. This problem is not noticeable at night and in summer since the heat consumption is then quasiconstant and do not fluctuate drastically during the integration time, but once the heat consumption is dynamic the heat integrator fails to give us an accurate value of the consumed heat energy since the return and supply temperatures fluctuate considerably under the integration time. One possible error source in the temperature sensors is the time constant τ, which affects the response time needed before the sensor can accurately measure the water temperature. If the integration time is shorter than the response time of the sensor accuracy problems in temperature measurements will occur. Other sources of error also need to be taken in account, like the choice of encapsulation materials, etc.. The measurement error of the flow meter is more difficult to predict since it depends on many factors. One of the major problems is that the volume-flow meter only enables us to estimate an average flow rate under the integration 5

time. The real flow rate may drastically vary during the integration time without being detected by the integrating unit. An other problem is the length of the integration time. If it is too short then the flow measurement error will drastically increase. Other error sources need also to be taken in account like the fact that the pipes do expand when hot water flows through them. This could affect the dimensioning of our system and give us errors. We conclude that heatmeters using volume-flow meters have bad accuracy when exposed to a dynamic heat energy consumption especially when the flow rate in the primary circuit is low. New energy metering methods are to be proposed if one wants more accurate energy measurements. A balance between heat measurement accuracy and power consumption is to be taken in account since these devices are often powered by batteries. References [] John P. Bentley. Principles of Measurement Systems. Pearson Education Ltd., rd edition, 995. [] S. Frederiksen and S. Werner. Fjärrvärme Teori, teknik och funktion. Studentlitteratur, 99. [] W. Glenn Steele Hugh W. Coleman. Experimentation and Uncertainty Analysis for Engeneers. John Wiley & Sons, INC, second edition, 998. [4] Varaday P. Moczar G., Csubak T. Distributed measurement system for heat metering and control. Instrumentation and measurement, IEEE transactions, Vol. 5, Issue 4:Pages 69 694, Aug 00. [5] T. Persson. Tappvarmvatten reglering i fjärrvärmecentraler för småhus. Licentiate thesis, Dept. of Heat and Power Engineering, Lund Institute of Technology, Box 8, 00, Lund, Sweden, October 00. 6