Dynamic simulation of DH house stations

Similar documents
Control Concepts for DH Compact Stations

How to avoid pressure oscillations in district heating systems

Stability Performance Dilemma in Hydronic Radiators with TRV

Model of a heat meter in a district heating substation under dynamic load

Heat Transfer From the Evaporator Outlet to the Charge of Thermostatic Expansion Valves

Multifunctional Thermostatic Circulation Valve MTCV

SECTION 1 - WHAT IS A BTU METER? BTU's = Flow x ΔT Any ISTEC BTU Meter System consists of the following main components:

Thermal Analysis of an HVAC System with TRV Controlled Hydronic Radiator

Eliminating Oscillations in TRV-Controlled Hydronic Radiators

REDUCING PROCESS VARIABLITY BY USING FASTER RESPONDING FLOWMETERS IN FLOW CONTROL

VD1 CLC. Small Valves DIN-range with a higher k v -value

Lecture 9 Thermal Analysis

Experiment # 5 5. Coupled Water Tanks

WeatherWatcher ACP. Astronomers Control Panel (V4 or >) Ambient Virtual Weather Station (Pro or Internet editions) ASCOM platform v4.

Dynamic performance of a district heating system in Madumvej, Denmark

VDN2.. VEN2.. VUN2.. Radiator valves. Building Technologies HVAC Products ACVATIX TM. NF norm, for 2-pipe heating systems

Investigations of hot water temperature changes at the pipe outflow

Water terminal control solutions

Contents... 1 Intro... 1 Giving guarantees... 2

6 Securing of the delivery and acceptance

I, THERMAL ANALYSIS OF BUS-BAR FOR SWITCH BOARD

Mathematical Modelling Using SimScape (Electrical Systems)

YTÜ Mechanical Engineering Department

Educational laboratory setup of DC motor cascade control based on dspace1104 platform

Physical Modelling with Simscape Rick Hyde

Thermal Analysis. inspiration

EUROMASTER HYDRAULIC PRESSBRAKES

SOLIDWORKS Simulation Time Based Thermal Stress

JOHNDEERE MOBILE WEATHER VALUE AND WALK AROUND GUIDE CLICK THE ARROW TO GET STARTED

Validation of DNS techniques for dynamic combined indoor air and constructions simulations using an experimental scale model

AN AUTOMATED GONIOPHOTOMETER FOR LUMINAIRE CHARACTERIZATION

Last updated: Copyright

IRMS. perspective. Isotope Ratio Mass Spectrometry.

BOXA-II ON-STREAM X-RAY FLUORESCENCE ANALYZER. Technical Description Version 2 BGRIMM AUTOMATION

Pipex px SUSTAINABLE SYSTEMS

Lab 1a Wind Tunnel Testing Principles & Drag Coefficients of Golf balls

Lentis Pai/Associate Director/Wiwynn

PRO-CLEAN STRATIFIED TANK

RECORD AND ANALYSE THE PRESSURE-ENTHALPY DIAGRAM FOR A COMPRESSION HEAT PUMP

DYNAMIC VAPOR SORPTION ANALYZER FULLY AUTOMATED COMPACT BENCH-TOP DVS ANALYZER, FOR FAST AND ACCURATE SORPTION MEASUREMENTS.

Double Inverted Pendulum (DBIP)

Lightcloud Application

This is the third of 3 parts detailing my experience of auto guiding for astrophotography.

A. Solar Walls. B. Prototype I

Radial piston pump type R and RG

XHDU Cassette type fan-coils for double/four pipe connections 1,98-14 kw HYDRONIC TERMINALS

Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid

Calculation of the heat power consumption in the heat exchanger using artificial neural network

SIMULATION SUITE CHEMCAD SOFTWARE PROCESS CONTROL SYSTEMS PROCESS CONTROL SYSTEMS COURSE WITH CHEMCAD MODELS. Application > Design > Adjustment

ES205 Analysis and Design of Engineering Systems: Lab 1: An Introductory Tutorial: Getting Started with SIMULINK

Thermal System Closed-Loop Temperature Control

Documentation of the Solutions to the SFPE Heat Transfer Verification Cases

Electronic pressure-independent characterised control valve EPIV

PERSPECTIVE STABLE ISOTOPE RATIO MS

A Simple Method for Thermal Characterization of Low-Melting Temperature Phase Change Materials (PCMs)

Thermal Analysis of Fairchild Dornier 728Jet Wing/Fuselage Interface using MSC.Patran Thermal. Paper number D. Konopka, J. Hyer, A.

Multiphysics Modeling

LABOTRON EXTRACTION & SYNTHESIS 2450 MHz

Kjeltec 2300 Analyzer Unit

473 Dew Point Hygrometer

PARAMETRIC ANALYSIS OF AUTOMOTIVE MECHATRONIC SYSTEMS

A Hybrid Approach For Air Conditioning Control System With Fuzzy Logic Controller

Thermostatic expansion valves TUA/TUAE

A Reconfigurable Quantum Computer

Temperature Control of an External Cleaning Unit

Computer Evaluation of Results by Room Thermal Stability Testing

405 Compact Orifice Series and 1595 Conditioning Orifice Plate Flow Test Data Book and Flow Handbook

Introduction to Heat Transfer Analysis

Thermal Analysis & Design Improvement of an Internal Air-Cooled Electric Machine Dr. James R. Dorris Application Specialist, CD-adapco

Cooling Water Flow Regulator

Analysis of Electric DC Drive Using Matlab Simulink and SimPower Systems

Atomic and nuclear physics

COMPARISON OF MEASURED AND ANALYTICAL PERFORMANCE OF SHELL-AND-TUBE HEAT EXCHANGERS COOLING AND HEATING SUPERCRITICAL CARBON DIOXIDE

Residual Chlorine Monitor

IMPROVEMENTS OF THE VARIABLE THERMAL RESISTANCE

DEVELOPMENT OF THE MEASURING SYSTEM FOR ANALYSING THE THERMAL PROPERTIES OF CLOTHING

Edgetech Instruments Inc.

Lecture 10 Multistep Analysis

Solar Flat Plate Thermal Collector

Automation of the radiochemical procedures for the sequential separation of radionuclides

CHAPTER 5 CONVECTIVE HEAT TRANSFER COEFFICIENT

VMS-GeoMil. Background

MotiveWave Hurst Cycles Guide Version: 1.0

Compact Titration. Compact Titrator G20. One Click Titration Simple & Dependable

Simplified Collector Performance Model

Michigan State University College of Engineering East Lansing, MI

Water & Vapor Sorption

If there is convective heat transfer from outer surface to fluid maintained at T W.

Automated Switching Between 1D-LC and Comprehensive 2D-LC Analysis

ENHANCEMENT MAXIMUM POWER POINT TRACKING OF PV SYSTEMS USING DIFFERENT ALGORITHMS

FRAM V5.2. Plutonium and Uranium Isotopic Analysis Software

405 Compact Orifice Series and 1595 Conditioning Orifice Plate Flow Test Data Book and Flow Handbook

Rotary Motion Servo Plant: SRV02. Rotary Experiment #01: Modeling. SRV02 Modeling using QuaRC. Student Manual

SRV02-Series Rotary Experiment # 1. Position Control. Student Handout

SITRANS F flowmeters. SITRANS F US System information SITRANS F US Ultrasonic flowmeters 4/181

EPIV electronic pressure-independent characterised control valve EPIV

PERSPECTIVE STABLE ISOTOPE RATIO MS

405 Compact Orifice Series and 1595 Conditioning Orifice Plate Flow Test Data Book and Flow Handbook

YTÜ Mechanical Engineering Department

Transcription:

Article Dynamic simulation of DH house stations Jan Eric Thorsen, Director, DHS Application Centre, Danfoss A/S www.danfoss.com

Jan Eric Thorsen, Director, DHS Application Centre, Danfoss A/S Presented by 7. Dresdner Fernwärme-Kolloquium 9/2002 Published in Euro Heat & Power 6/2003 Dynamic simulation of DH house stations Danfoss proceeds on developing simulation models of HVAC components including control equipment that the company produces for central and district heating systems. In this paper some examples are given. The example of a simulated domestic hot water service station is presented. Some of the model components included are described, and the link between mathematical model and simulation model is shown. Two simulation results are included representing different component specifications (thermal time constant for a temperature sensor). Furthermore, an example of hardware in the loop simulation is presented. In this case a domestic heating system is built up in the laboratory by hardware components connected with real time simulations. This system forms the basis for test and evaluation of new control strategies. The Software used for modelling and simulations Simulink 1 is a software package for modelling, simulating and analysing dynamic systems. For modelling Simulink provides a graphical user interface for building models as block diagrams using click-and-drag mouse operations. This is an improvement in user-friendliness compared to former versions of simulation packages requiring formulated differential equations and difference equations in a language or program. Simulink includes a comprehensive block library including linear and non-linear components. Furthermore it is possible to create custom blocks. A Simulink block diagram is a pictorial model of a dynamic system. It consists of a set of symbols called blocks interconnected by lines. Each block represents an elementary sub system that produces an output based on the inputs, states and time. The lines represent connections of block inputs to block outputs. A block comprises of one or more of the following: a set of inputs, a set of states, and a set of outputs, see fig. 1. When a model contains a number of built-up blocks it can be grouped and hidden behind a new block with a suitable number of inputs and outputs. In this way models containing different components or subsystems can be built up one by one. These component models, e.g. a temperature sensor can be connected to form the desired system and is represented in a block diagram representing the main components connected by a number of lines. Menus are accessible for each icon and facilitate the selection of different parameters, e.g. dimensions. It is very easy to reorganise and adjust the model, such as adding or replacement of individual parts of the system. Displays and scopes may be added to watch the simulation during execution. (1). Component model examples Example of a temperature sensor model: The temperature sensor is often described by a first order differential equation (2). Assuming the sensor is represented by a finite mass with uniform temperature distribution during the transient process, the heat flux to this mass may be described by: (see abbreviation table). q sensor = (T ambient T sensor )ha s (1) The change of sensor temperature is dependent on the heat flux described by: q sensor = cvρ dt sensor (2) dt Combining equation (1) and (2) yields (T ambient T sensor ) ha s dt = sensor (3) cvρ dt where the thermal time constant τ [sec] is expressed by: τ = cvρ ha s (4) The step input for the system, T ambient is stepping from 20 to 60 at simulation time = 5 sec. The system output is shown in figure 3. This simple example shows the link between the mathematical equations and the Simulink model. Example of a valve model: This model example describes the static relation between the position of the spindle, differential pressure across the valve and the flow rate through the valve. The k v value as a function of the spindle position is included in a lookup table. The lookup table includes the valve characteristic, performing linear interpolation between the measured data points. The flow rate through the valve follows the well known relation: Q Q = k v 2 p (5) The Simulink model for the Danfoss VS2 motorised valve can be modelled as in figure 4. 2 Danfoss Heating VF.HB.K3.02 Danfoss

The plate heat exchanger model: The modelling of heat exchangers is typically based on dividing the heat exchanger into a number of elements, and set up the differential equations describing the temperature in each element (lumped model). The method has proven quite successful in FIGURE 1: Graphical Simulink presentation of a dynamic block Danfoss Heating VF.HB.K3.02 Danfoss 3

compiling a good description of the dynamics of the heat exchanger. The model is described by geometrical data like number of plates, distance between plates, plate size, plate weight, number of passes etc. However, the model still requires more than geometrical data, since the influence of various plate forms on the heat transfer coefficient has not been explained. In the same way, in principle, Simulink has also been used to set up a general model of plate heat exchangers which can be adapted to most types of exchangers. The geometrical data are keyed into a menu. The model has been verified using measured data from experiments on several types of plate heat exchangers in the range 50 400 kw. Experience shows that the model is able to simulate all types with high accuracy, but also that it is necessary to use a scaling factor to adapt the heat coefficient to different plate forms. 1/5 1 s T ambient Step input Gain Integrator Tensor Output Scope FIGURE 2: Simulink model of first order temperature sensor = 5 sec. System simulation One of the areas where the simulation tool has been utilised is heat exchanger control. A common application for domestic hot water supply, as shown in figure 5, is an example of this. Each component itself may be simple to model and understand. The interconnection of components, as shown on figure 5, makes it far more challenging to see the connections between output, input, and component parameters. The simulation system gives a tool for a better understanding of these. The related Simulink model can be modelled as shown in figure 6. Based on the models as shown in figure 6 different combinations of differential pressure, temperatures and loads, and different combinations of control parameters, e.g. sensor time constant, sensor placing, control algorithm, actuator speed, valve characteristics, valve control ratio, etc. are investigated. In the development of products for heat exchanger control, simulation models have thus been used to analyse which product design can be expected to give the best results when considering a broad spectrum of operating conditions. Prototypes FIGURE 3: Output from the temperature sensor model 1 Valve position Input 2 Differential pressure Input s Look-up table VS2 s-kv relation dp FIGURE 4: Simple static Simulink model of the Danfoss linear VS2 motorised valve Mux f(u) Q calculation 1 Q Output 4 Danfoss Heating VF.HB.K3.02 Danfoss

and results that have been verified by laboratory experiments do confirm that the simulation results are reliable. As an example figures 7 and 8 show the output from a simulation based on the system shown in figure 5/6. In this case the subject was to investigate the influence of different time constants for the temperature sensor. System specifications: Dimensioning of heat exchanger 65/30 55/10 C. Actuator speed: 7 sec/mm. Control valve: linear valve with K vs = 1.0 and stroke = 4 mm. P across control valve = 0.7 bar constant. No circulation flow. The PI controller parameters are tuned for optimum dynamic controller performance. Temperature set point = 55 C. In general, practical tests and simulations have shown that the following factors in controlling equipment are important if the control system has to perform well: Low sensor time constant Sensor placing in the system Suitable combination of valve characteristic (stroke) and actuator speed and actuator resolution Motor valve characteristic and control ratio Suitable settings for electronic PI-controller Also lifetime improvement by influences of number of actuations and direction shifts are investigated by simulations. T 11 T 12 M Q 1 Q 2 FIGURE 5: A schematic diagram of the hot service water system to be simulated FIGURE 6: The model as presented in the Simulink graphical user interface T T 22 Tap Water T 21 Cold Water supply Valve pos dp M ON +/- temperature Differential pressure Valve Tap Water flow Q2 Q1 Q prim Q sec Valve motor 100 T11 10 T21 ECL PI controller Heat Exchanger Sensor T12 T22 Danfoss Heating VF.HB.K3.02 Danfoss 5

100 90 80 Simulation results / Temperatures and flows T11 T12 T22 T21 Q1 Q2 Temp [ C] / Flow [l/h] 10 70 60 50 40 30 20 10 100 200 300 400 500 600 700 800 time [sec] FIGURE 7: Simulation results for τ = 1.0 sec. 100 90 80 Simulation results / Temperatures and flows T11 T12 T22 T21 Q1 Q2 Temp [ C] / Flow [l/h] 10 70 60 50 40 30 20 10 100 200 300 400 500 600 700 800 time [sec] FIGURE 8: Simulation results for τ = 6.0 sec. 6 Danfoss Heating VF.HB.K3.02 Danfoss

Test and verification of controller code against simulated environments At the time projects are running with the purpose to implement new functionality to the Danfoss ECL controller. For testing and evaluation a system as shown in figure 9 is built in the laboratory. First step was to build up the model, as presented in figure 9, in Simulink. Hereby it is possible to test the controller code (new functionality) up against a dynamic model of theenvironment including rooms, radiators, pumps, heat exchanger etc. The ECL controller code is programmed in the ANSI C program language. For the simulation model the feature of integrating externally compiled ANSI C program code is used. This code compatibility gives a comprehensive tool for rapid code prototyping. Furthermore prior to code implementation in the ECL controller, it is possible to perform hardware in the loop simulations. By this, the system, as shown in figure 9, is partly simulated and partly represented by real components. Communication between the processor and hardware is provided by an IO-board. During the simulation the system is running in real time. In this case it is obvious that components like buildings, influence T 11 T 12 M ECL Controller T 22 T 21 T Pos A Pos B FIGURE 9: The two pipes indirectly connected in the heating system. Each radiator line is equipped with a thermostatic valve. The grey area is further detailed in figure 10 of surroundings (ambient temperature, sun radiation, secondary heat etc.) and radiators are simulated. Components like piping, heat exchanger, temperature sensor, actuators, valves and pump are included as hardware. The control loop for one of the thermostatic radiator valves in this system is shown in figure 10. Finally, after code implementation in the ECL, the controller replaces the ANSI C program code block in the simulation model. Now the ECL controller can be tested up against the same environments as mentioned above before implementing it in field tests. By using the real time hardware in the loop simulation tool some of the needed full-scale test activities are moved into the laboratory; especially regarding heating systems, where weather conditions have a major influence on the test results. Here it is essential to test and compare several control strategies under the same conditions. Simulations have a good feature here since it is a question of keying the desired values into a menu. The hardware components are very useful in regard to estimating measuring accuracy of flow and pressure signals provided by the hardware components. Further examples of ECL functionality developed by support of simulations Pos A Temp. (measured) Amb. Temp. Flowmeter (Hardware) Flow rate Radiator Water temp. in Heat output from radiator Room Heat load on room Room temperature Thermostat Radiator Valve (Hardware) Actuator (Hardware) Water temp. out Spindle position Pos B FIGURE 10: Control loop for thermostatic radiator valve. Grey boxes represents simulated components. Pos A and Pos B are related to figure 9 Danfoss Heating VF.HB.K3.02 Danfoss 7

FIGURE 11: Left, picture of hardware components (pipes, heat exchangers, pump, valves, actuators, temperature sensor and flowmeters). Right, real time processor (below table) and PC for data acquisition and system control. is the flow switch function and the Auto Tuning function both to be used in hot service water systems involving heat exchanger control. The flow switch function detects tapping flow (on-off), in hot service water stations by means of a switch mounted into the secondary supply pipe. Hereby the primary flow is held on zero at idle, and furthermore this feed forward signal is used at tapping start and tapping end. The Auto Tuning function automatically sets the PI controller parameters and secures a stable idle control (motor protection). By systematically reducing the proportional factor for the controller, oscillations will occur at a certain point. By increasing this proportional value by a factor, oscillations are avoided. The Integral value is calculated by means of the critical time period for the oscillations. /3/ Conclusion Experience from the last 10 years of using dynamic simulation as a link in the development of controls for central and district heating systems has been positive. It has been shown that simulation can be used with advantage, not only to test particular design ideas, but also, just as important to gain a better overview and greater understanding of the inter-relationship between the parameters that influence how a heating or domestic hot waterservice system works. 8 Danfoss Heating VF.HB.K3.02 Danfoss

Danfoss Heating VF.HB.K3.02 Danfoss 9

Abbreviations q Heat transfer rate [W] T sensor Temperature of sensor matrerial, assumed to be uniform [ C] T ambient Temperature of external medium passing the temperature sensor [ C] c Specific heat capacity [j/kg K] h Heat transfer coefficient [W/ C m 2 ] ρ Density of sensor material [kg/m 3 ] V Volume of sensor [m 3 ] A S Submerged sensor area [m 2 ] t Q 1 Q 2 Time [sec] Flow - primary side [l/h] Flow - secondary side [l/h] References More articles [1] Simulink, Dynamic System Simulation for MATLAB, Version 4, Users Guide. The Math Works, Inc. 2000. [2] Introduction to Heat Transfer, Frank P. Incropera, David P. De Witt, Second Edition John Wiley & Sons, 1990. [3] Poul Erik Hansen, Danfoss A/S; H. Poulsen, Danish Technological Institute: Consumer Substations Automatically Tuned, EUROHEAT & POWER no. 4 April 2001. [4] Benonysson, A., Danfoss A/S; Boysen, H, Danfoss A/S: Optimal Control of Heat Exchangers. 5th International Symposium on Automation of District Heating Systems, Finland, August 1995. [5] Benonysson, A., Danfoss A/S; Boysen, H, Danfoss A/S: Valve characteristics for motorized valves in district heating substations. EUROHEAT & POWER 7-8/1999. [6] IT ENERGY, Centre for IT tools within the field of Energy. www.itenergy.dk [1] Valve characteristics for motorized valves in district heating substations, by Atli Benonysson and Herman Boysen [2] Optimum control of heat exchangers, by Atli Benonysson and Herman Boysen [3] Auto tuning and motor protection as part of the pre-setting procedure in a heating system, by Herman Boysen [4] Differential pressure controllers as a tool for optimization of heating systems, by Herman Boysen [5] District heating house substations and selection of regulating valves, by Herman Boysen [6] kv: What, Why, How, Whence?, by Herman Boysen [7] Pilot controlled valve without auxiliary energy for heating and cooling system, by Martin Hochmuth [8] Pressure oscillation in district heating installation, by Bjarne Stræde More information Find more information on Danfoss District Energy products and applications on our homepage: www.heating.danfoss.com VF.HB.K3.02 Copyright Danfoss DHS-SMCT/PL 2017.04