TESTING GUIDANCE FOR PROVIDERS OF FIRM FREQUENCY RESPONSE BALANCING SERVICE

Similar documents
Bringing Renewables to the Grid. John Dumas Director Wholesale Market Operations ERCOT

EUROPEAN COMMISSION. Brussels, XXX D046374/04 [ ](2016) XXX draft ANNEX 1 ANNEX

Job Description. 1) To provide a range of meteorological services, including a forecaster consultancy service.

EUROPEAN COMMISSION. Brussels, XXX [ ](2015) XXX draft ANNEX 1 ANNEX

DS3 System Services Scalar Design RECOMMENDATIONS PAPER. DS3 System Services Implementation Project

DEMAND FORECASTING PROTOCOL

TATA CHEMICALS MAGADI LIMITED (Mining Section) TRONA CRUSHING PLANT AND PREWASH TANK FACILITY PROJECT

2018 Annual Review of Availability Assessment Hours

Drexel Woods Homeowner s Association, Inc Baltimore National Pike, Box 158 Catonsville, MD 21228

While entry is at the discretion of the centre, candidates would normally be expected to have attained one of the following, or equivalent:

Procurement Plan Mozambique: P Greater Maputo Water Supply Expansion Project

EBS IT Meeting July 2016

High-Speed Environmental Analysis Using the Agilent 7500cx with Integrated Sample Introduction System Discrete Sampling (ISIS DS)

Peterborough Distribution Inc Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5

Dual 3-channel analog multiplexer/demultiplexer with supplementary switches

ISO defines the Rockwell superficial hardness value, HRN, as:

15 March 2010 Re: Draft Native Vegetation of the Sydney Metropolitan Catchment Management Authority Area GIS layers and explanatory reports

Modelling of Primary Frequency Control and Effect Analyses of Governing System Parameters on the Grid Frequency. Zhixin Sun

MEETING OF THE METEOROLOGY PANEL (METP) WORKING GROUP MOG (WAFS)

This Unit may form part of an National Qualification Group Award or may be offered on a freestanding

Expedited Filing Draft August 22, 2017

Guide to Registration Requirements for Active Substance Manufacturers, Importers and Distributors in Ireland

Town of Taos Request for Proposal Historic Preservation GIS Geodatabase Project April 2007

Adding the METAR service to the CNS/ATM-1 FIS Application

LUXEON UV U1. Highest power density, superior efficiency, powered by leading Chip Scale Package (CSP) technology ILLUMINATION

Competencies for Aeronautical Meteorological Personnel (AMP) Developed by Chair WMO CAeM ET-ET

BUK9Y53-100B. N-channel TrenchMOS logic level FET. Table 1. Pinning Pin Description Simplified outline Symbol 1, 2, 3 source (S) 4 gate (G)

In data sheets and application notes which still contain NXP or Philips Semiconductors references, use the references to Nexperia, as shown below.

PPA PROCUREMENT PLAN (Textual Part)

N-channel TrenchMOS logic level FET

This Unit may form part of a National Qualification Group Award or may be offered on a free standing basis.

Derogation Criteria for the Requirements for Generators Network Code

Maritime Weather Information: Automatic Reporting, A New Paradigm

METEOROLOGICAL WARNINGS STUDY GROUP (METWSG)

PSMN006-20K. N-channel TrenchMOS SiliconMAX ultra low level FET

Outage Coordination and Business Practices

PHB108NQ03LT. N-channel TrenchMOS logic level FET

N-channel TrenchMOS logic level FET

BUK A. N-channel TrenchMOS standard level FET

PHD/PHP36N03LT. 1. Product profile. 2. Pinning information. N-channel TrenchMOS logic level FET. 1.1 General description. 1.

N-channel enhancement mode Field-Effect Transistor (FET) in a small SOT23 (TO-236AB) Surface-Mounted Device (SMD) plastic package using

Passivated ultra sensitive gate thyristor in a SOT54 plastic package. Earth leakage circuit breakers or Ground Fault Circuit Interrupters (GFCI)

OFFSHORE INTEGRATION STUDY. Analysis, benchmark and mitigation of storm and ramping risks from offshore wind power in Belgium 05/02/2018

74HC2G16; 74HCT2G16. The 74HC2G16; 74HCT2G16 is a high-speed Si-gate CMOS device. The 74HC2G16; 74HCT2G16 provides two buffers.

Ministry of Health and Long-Term Care Geographic Information System (GIS) Strategy An Overview of the Strategy Implementation Plan November 2009

In data sheets and application notes which still contain NXP or Philips Semiconductors references, use the references to Nexperia, as shown below.

International Workshop on Wind Energy Development Cairo, Egypt. ERCOT Wind Experience

60 V, 0.3 A N-channel Trench MOSFET

Request for Empanelment

MAIN CIVIL WORKS CONTRACT SCHEDULE 3 ROLES AND REPRESENTATIVES TABLE OF CONTENTS

2017/18 Wider Cancellation Charge Statement. Version 1. Effective from 1 st April Based Upon: User Commitment Methodology.

2018/19 Wider Cancellation Charge Statement. Version 2.0. Effective from 1 st April Based Upon: User Commitment Methodology.

Green Procurement Standards

Unit title: Fundamental Chemistry: An Introduction (SCQF level 6)

N-channel TrenchMOS standard level FET. High noise immunity due to high gate threshold voltage

Low-power dual Schmitt trigger inverter

Forecast User Manual FORECAST. User Manual. Version P a g e

The 74AUP2G34 provides two low-power, low-voltage buffers.

This Unit may form part of a National Qualifications Group Award or may be offered on a freestanding

2018 North Carolina Residential Code Prescriptive Tables for Selection of Support Elements for Beams, Girders, and Headers: Example Problems

Internal Audit Report

Renewables and the Smart Grid. Trip Doggett President & CEO Electric Reliability Council of Texas

DESIGN BULLETIN No. 39/2006 (Revised June 2007) June 2007 Amendment to Design Bulletin #39/2006

SNOW REMOVAL - REQUEST FOR PROPOSAL. Snow Removal/Clearing and Sanding/Salting for Winter Fundy Ocean Research Center for Energy

Key Indicators for Territorial Cohesion & Spatial Planning Stakeholder Workshop - Project Update. 13 th December 2012 San Sebastián, Basque Country

Unit title: Fundamental Chemistry: An Introduction (SCQF level 6)

XC7SET General description. 2. Features. 3. Applications. Ordering information. Inverting Schmitt trigger

PSEG Long Island LLC 111 Eighth Avenue, 13th Floor New York, NY 10011

Report on System-Level Estimation of Demand Response Program Impact

R E A D : E S S E N T I A L S C R U M : A P R A C T I C A L G U I D E T O T H E M O S T P O P U L A R A G I L E P R O C E S S. C H.

REQUEST FOR QUOTATION (RFQ) FOR PROCUREMENT OF THERMO HYGROMETER -UNDP GLOBAL FUND

Technical Requirements. Version No. 1.0 Effective Date 10/1/2008

PHP110NQ08T. N-channel TrenchMOS standard level FET

The Service Pipe A Forgotten Asset in Leak Detection

This Unit may form part of a National Qualification Group Award or may be offered on a freestanding

PPA PROCUREMENT PLAN (Textual Part)

Unit certificate for solar inverters

Cree XLamp XP-G LEDs Data Sheet

5-stage Johnson decade counter

STANDARD MICROCIRCUIT DRAWING MICROCIRCUIT, LINEAR, PRECISION TIMER, MONOLITHIC SILICON

RFP # Attachment 5 Revised Proposal Evaluation Form Attachment 5 PROPOSAL EVALUATION FORM All proposals will be reviewed for responsiven

NOAA s Climate Normals. Pre-release Webcast presented by NOAA s National Climatic Data Center June 13, 2011

BUK B. N-channel TrenchMOS logic level FET

PSMN013-80YS. N-channel LFPAK 80 V 12.9 mω standard level MOSFET

PSMN4R3-30PL. N-channel 30 V 4.3 mω logic level MOSFET. High efficiency due to low switching and conduction losses

4-bit magnitude comparator

The 74AXP1G04 is a single inverting buffer.

Advisory Circular. U.S. Department of Transportation Federal Aviation Administration

Is Your GIS Ready For Grid Modernization? A State-of-the Industry Report

N-channel TrenchMOS logic level FET

PPA PROCUREMENT PLAN (Textual Part)

Procurement Plan for Eth Expressway Project ( P148850)

Centralized Forecasting Registration and Communication Requirements for Distribution Connected Variable Generators. IESO Training

PSMN8R3-40YS. N-channel LFPAK 40 V 8.6 mω standard level MOSFET

Demand Estimation Sub-Committee MOD330 Phase 1 and 2. 7 th November 2012

PSMN2R6-40YS. N-channel LFPAK 40 V 2.8 mω standard level MOSFET

Pursuant to Section 205 of the Federal Power Act ( FPA ) 1 and the Commission s

HOUSING FUND PROSPECTUS

FORECAST ACCURACY REPORT 2017 FOR THE 2016 NATIONAL ELECTRICITY FORECASTING REPORT

Seamless Data-Processing and Forecasting System (SDPFS)

Transcription:

TESTING GUIDANCE FOR PROVIDERS OF FIRM FREQUENCY RESPONSE BALANCING SERVICE Authors Published Version Update Summary Kevin Smethurst Vicci Walsh May 2017 D1 Kevin Smethurst Vicci Walsh Draft 2/6/17 D6 Kevin Smethurst Honor Hynes Otis Rook-Grignon Draft 7/7/17 D10 Vicci Walsh Kevin Smethurst Honor Hynes Otis Rook-Grignon Vicci Walsh November 2017 D11 Honor Hynes July 2018 12 Tolerance values in Tables 3.7 and 3.8 amended to correctly reflect tolerance bands shown in Figures 3.8, 3.9, 3.10 and 3.11. Non-Dynamic References to High/Primary for Non-Dynamic removed. Secondary timescales only. 1Hz Sample Rate for Nondynamic testing. Dynamic In Test 1 pass criteria, 2.5% standard deviation has been replaced with overshoot limit. Test 4 (system frequency) replaced with injection profile of a real frequency event. Appendix B Test data format examples Appendix C Test request form 1

Table of Contents 1 Introduction... 3 1.1 Purpose... 3 1.2 Overview- FFR (Firm Frequency Response)... 3 2 Non-Dynamic Firm Frequency Response Testing... 6 3 Dynamic Firm Frequency Response Testing... 8 3.1 Test 1- Step Tests... 8 3.2 Test 2- Frequency Sweep Tests... 11 3.3 Test 3- Duration Tests... 17 3.4 Test 4- Frequency Event Test... 18 Appendix A Test Data and Test Signals... 19 Appendix B Format of Test Results... 20 Appendix C Test Request Form... 22 2

1 Introduction 1.1 Purpose This document aims to provide guidance to Firm Frequency Response (FFR) providers to National Grid. This document covers the testing requirements for pre-qualification assessment and reproving of this service. The tests outlined in the document are to verify that the requirements of the service specified in contract documents can be met. For any further enquires or questions, contact your Account Manager or: E-mail commercial.operation@nationalgrid.com Telephone +44 (0) 1926 654611 1.2 Overview- FFR (Firm Frequency Response) FFR is the change in active power delivered as a response to a change in system frequency. This change in active power could either be from its initial state or a predicted demand level (baseline). It is available in two variants: Non-Dynamic (also referred to as Static): Contracted Response Delivery timescale Secondary timescale 30s 30min Table 1.1 Response Timescale for a Non-Dynamic Service Dynamic: Contracted Response Delivery timescale Primary timescale 10s 30s 2 Secondary timescale 30s 30min High Frequency timescale 10s 30min (minimum) Table 1.2 Response Timescales for a Dynamic Service With Non-Dynamic response, the change in active power is a specified value which is triggered when the frequency falls through 49.7Hz. See Figure 1.1 below. 3

49.7Hz Figure 1.1 Example of a Non-Dynamic Response to a Varying Frequency In Dynamic response the change in active power is proportional to the change in frequency as shown in Figure 1.2. There are 2 services: Low Frequency o Primary and Secondary Response High Frequency Response 4

Frequency Active Power Theoretical Response from Demand Theoretical Response from Generation K-factor, dynamic delay Dynamic Delay (Up to 2 Seconds) 50.00Hz Figure 1.2 Example of a Dynamic Response to a Varying Frequency 5

2 Non-Dynamic Firm Frequency Response Testing The non-dynamic low frequency test aims to monitor the capability of the provider to deliver the minimum contracted level of response. The frequency profile can be injected either at site or remotely. The sample rate for this test is 1Hz. Pass criteria for test: An acceptable frequency injection profile is used (see Figure 2.1). The relay (or equivalent) operating point of the plant/unit(s) occurs at the correct contracted trigger frequency and within the permitted tolerance (±0.01Hz). Sustain the response for the 30 minutes. The standard deviation of active power error over a 30 minute period must not exceed 2.5% of the contracted active power change. 6

Parameter Point A B C D E F G H J K L M N P Q R D T Time (s) 0.0 30.0 40.0 80.0 90.0 120.0 420.0 450.0 750.0 780.0 1080.0 1110.0 1410.0 1440.0 1740.0 1770.0 2070.0 2100.0 Freq (Hz) 50.000 50.000 49.720 49.720 50.000 49.500 49.500 49.800 49.800 49.600 49.600 50.200 50.200 50.400 50.400 50.000 50.000 50.000 Table 2.1 Injected Frequency against Time for Low Frequency Non-Dynamic Response Testing Non-Dynamic Low Frequency Response Injection Profile Figure 2.1 Injection Profile for Low Frequency Non-Dynamic Response Testing a) The injected frequency profile used in testing is shown in Figures 2.1 above. This shows a trigger frequency of 49.7Hz. b) The length of the test is approximately 2100s in the case where the providers are providing an 1800s response. If the agreed response time is longer or shorter than 1800s, the test may be proportionately increased or decreased as required. 7

3 Dynamic Firm Frequency Response Testing The dynamic frequency tests assess the capability of the service provider to deliver dynamic response. The frequency profiles can be injected either at site or remotely. 3.1 Test 1- Step Tests This test is designed to ensure the system responds when the frequency moves outside of the +/- 0.015Hz deadband. The step injections are shown in Figure 3.1 with corresponding values in Table 3.1. Each step is sustained for 180 seconds to verify the response. The frequency will then be returned to 50Hz for a minimum of 30 seconds, or until the output is stable, before the next injection is applied. The injections and expected responses for each test are shown in Table 3.2. Tests 1.1 and 1.2 are designed to ensure a change in active power when the frequency moves outside the deadband. Pass criteria for test: For Tests 1.1 and 1.2 a noticeable change in power in the correct direction is observed. Delay in response of active power due to a change in frequency is no greater than 2 seconds. Minimum of the sampled values of active power response within primary, secondary and high frequency timescales are within the allowable tolerances given in Table 3.2 and shown graphically in Figures 3.2 and 3.3. progressively change to its contracted output. Any overshoot shall not exceed 10% of the steady state change in output for the duration of the test. The output should have attained the steady state value within 10s of the application of the frequency step. Test Parameter Values Time (s) 0 30 30 210 210 240 1.1 Frequency (Hz) 50 50 50.02 50.02 50 50 1.2 Frequency (Hz) 50 50 49.98 49.98 50 50 1.3 Frequency (Hz) 50 50 50.1 50.1 50 50 1.4 Frequency (Hz) 50 50 49.9 49.9 50 50 1.5 Frequency (Hz) 50 50 50.2 50.2 50 50 1.6 Frequency (Hz) 50 50 49.8 49.8 50 50 1.7 Frequency (Hz) 50 50 50.3 50.3 50 50 1.8 Frequency (Hz) 50 50 49.7 49.7 50 50 1.9 Frequency (Hz) 50 50 50.4 50.4 50 50 1.10 Frequency (Hz) 50 50 49.6 49.6 50 50 1.11 Frequency (Hz) 50 50 50.5 50.5 50 50 1.12 Frequency (Hz) 50 50 49.5 49.5 50 50 Table 3.1 Test 1 Frequency Injection Table Corresponding with Times 8

Figure 3.1 Test 1 Injection Profile Test Number Frequency Step (Hz) Expected Response Allowable Power Tolerance 1.1 50.02 >0% n/a 1.2 49.98 >0% n/a 1.3 50.1 20% 5%/-4% 1.4 49.9 20% 5%/-4% 1.5 50.2 40% 5%/-3% 1.6 49.8 40% 5%/-3% 1.7 50.3 60% 5%/-2% 1.8 49.7 60% 5%/-2% 1.9 50.4 80% 5%/-1% 1.10 49.6 80% 5%/-1% 1.11 50.5 100% 5%/-0% 1.12 49.5 100% 5%/-0% Table 3.2 - Frequency Injection and Expected Response values 9

Percentage Active Power Response Percentage Active Power Response 150 100 50 0-0.8-0.6-0.4-0.2 0 0.2 0.4 0.6 0.8-50 -100-150 Frequency Deviation from 50Hz (Hz) Contracted Active Power Response Allowable Active Power Tolerance Figure 3.2 - Allowable Power Tolerance for a Negative Gradient Active Power Response 150 100 50 0-0.8-0.6-0.4-0.2 0 0.2 0.4 0.6 0.8-50 -100-150 Frequency Deviation from 50Hz Contracted Active Power Response Allowable Active Power Tolerance Figure 3.3 - Allowable Power Tolerance for a Positive Gradient Active Power Response 10

3.2 Test 2- Frequency Sweep Tests These tests comprise of frequency ramps from 50.6Hz to 49.4Hz and from 49.4Hz to 50.6Hz, in order to examine the system s entire performance envelope. The ramps will be injected over 30 seconds (Test 2.1, 2.2) and 90 seconds (Tests 2.3, 2.4). The injection profiles are shown in Tables 3.3 to 3.6 and Figures 3.4 to 3.7. The test will verify: At key data points the ability of the service to provide the correct active power response in accordance with the injected frequency. The active power as the frequency passes through the dead band. The 2 frequency ramp rates used enable assessment where primary and secondary contract values are different. Pass criteria for test: Delay in response of active power due to a change in frequency is no greater than 2 seconds. Active power response is within the tolerances given in Tables 3.7 and 3.8 which are shown graphically in Figures 3.8, 3.9, 3.10 and 3.11. Note: where the contract table has different values for primary and secondary response, the tolerance bands shown will not be applicable for either Test 2.2 (where primary < secondary) or Test 2.4 (where primary > secondary). 11

Frequency (Hz) Frequency (Hz) Test 2.1 Frequency Injection Table Time (s) 0 30 30 80 110 160 160 190 Frequency (Hz) 50 50 50.6 50.6 49.4 49.4 50 50 Table 3.3 Test 2.1 Frequency Injection Table Corresponding with Times 50.8 50.6 50.4 50.2 50 49.8 49.6 49.4 49.2 0 50 100 150 200 Time (s) Figure 3.4 - Test 2.1 Injection Profile Test 2.2 Frequency Injection Table Time (s) 0 30 30 80 110 160 160 190 Frequency (Hz) 50 50 49.4 49.4 50.6 50.6 50 50 Table 3.4 Test 2.2 Frequency Injection Table Corresponding with Times 50.8 50.6 50.4 50.2 50 49.8 49.6 49.4 49.2 0 50 100 150 200 Time (s) Figure 3.5 Test 2.2 Injection Profile 12

Frequency (Hz) Frequency (Hz) Test 2.3 Frequency Injection Table Time (s) 0 30 30 80 170 220 220 250 Frequency (Hz) 50 50 50.6 50.6 49.4 49.4 50 50 Table 3.5 Test 2.3 Frequency Injection Table Corresponding with Times 50.8 50.6 50.4 50.2 50 49.8 49.6 49.4 49.2 0 50 100 150 200 250 Time (s) Figure 3.6 Test 2.3 Injection Profile Test 2.4 Frequency Injection Table Time (s) 0 30 30 80 170 220 220 250 Frequency (Hz) 50 50 49.4 49.4 50.6 50.6 50 50 Table 3.6 Test 2.4 Frequency Injection Table Corresponding with Times 50.8 50.6 50.4 50.2 50 49.8 49.6 49.4 49.2 0 50 100 150 200 250 Time (s) Figure 3.7 Test 2.4 Injection Profile 13

Test 2.1 and 2.2 Negative Active Power Gradient Positive Active Power Gradient Time Expected Percentage Tolerance Expected Percentage Tolerance Active Power Response Active Power Response 82.5 100-0%/+5% -100-5%/+0% 84.5 84-0.8%/+21% -84-21%/+0.7% 85 80-1%/+21% -80-21%/+1% 87.5 60-2%/+21% -60-21%/+2% 90 40-3%/+21% -40-21%/+3% 92.5 20-4%/+21% -20-21%/+4% 95 0-5%/+21% 0-21%/+5% 97.5-20 -5%/+20.2% 20-20.2%/+5% 100-40 -5%/+19.3% 40-19.3%/+5% 102.5-60 -5%/+18.4% 60-18.5%/+5% 105-80 -5%/+17.6% 80-17.6%/+5% 107.5-100 -5%/+16.7% 100-16.7%/+5% 109.5-100 -5%/+0% 100-0%/+5% Table 3.7-30 Second Sweep Test Tolerances Test 2.3 and 2.4 Negative Active Power Gradient Positive Active Power Gradient Time Expected Percentage Tolerance Expected Percentage Tolerance Active Power Response Active Power Response 87.5 100-0%/+5% -100-5%/+0% 89.5 94.67-0.3%/+10.4% -94.67-10.4%/+0.3% 95 80-1%/+10.4% -80-10.4%/+1% 102.5 60-2%/+10.4% -60-10.4%/+2% 110 40-3%/+10.4% -40-10.4%/+3% 117.5 20-4%/+10.4% -20-10.4%/+4% 125 0-5%/+10.4% 0-10.4%/+5% 132.5-20 -5%/+9.4% 20-9.4%/+5% 140-40 -5%/+8.5% 40-8.5%/+5% 147.5-60 -5%/+7.5% 60-7.5%/+5% 155-80 -5%/+6.6% 80-6.6%/+5% 162.5-100 -5%/+5.6% 100-5.6%/+5% 164.5-100 -5%/+0% 100-0%/+5% Table 3.8-90 Second Sweep Test Tolerances 14

Percentage Active Power Response Percentage Active Power Response 150 100 50 0 75 80 85 90 95 100 105 110 115-50 -100-150 Time (s) Contracted Active Power Response Allowable Active Power Tolerance Figure 3.8 - Negative Active Power Gradient Tolerance Band 150 100 50 0 75 80 85 90 95 100 105 110 115-50 -100-150 Time (s) Contracted Active Power Response Allowable Active Power Tolerance Figure 3.9 - Positive Active Power Gradient Tolerance Band 15

Percentage Active Power Response Percentage Active Power Response 150 100 50 0 75 85 95 105 115 125 135 145 155 165 175-50 -100-150 Time (s) Contracted Active Power Tolerance Allowable Active Power Tolerance Figure 3.10 - Negative Active Power Gradient Tolerance Band 150 100 50 0 75 85 95 105 115 125 135 145 155 165 175-50 -100-150 Time (s) Contracted Active Power Response Allowable Active Power Tolerance Figure 3.11 - Positive Active Power Gradient Tolerance Band 16

3.3 Test 3- Duration Tests FFR duration tests require the service provider to be able to respond at full output for 30 minutes. Operation will be tested at ±100% of capability to ensure the system is compliant. This is carried out by a frequency step of ±0.6Hz onto the system for 30 minutes. The frequency will then be stepped back to 50Hz. The frequency injection profiles are shown in Tables 3.9 and 3.10 and Figures 3.12 and 3.13. Pass criteria for test: The standard deviation of load error at steady state over a 30 minute period must not exceed 2.5% of the maximum contracted active power response. For Test 3.1 and 3.2, standard deviation is assessed from 10 seconds until 30 minutes after the frequency step, unless the contracted values for primary and secondary are different. In this case, standard deviation for Test 3.2 is assessed from 30 seconds until 30 minutes after the frequency step. Sustain response for 30 minutes. Test 3.1 Frequency Injection Table Time (s) 0 30 30 1830 1830 1860 Frequency (Hz) 50 50 50.6 50.6 50 50 Table 3.9 Test 3.1 Frequency Injection Table Corresponding with Times Figure 3.12 - Test 3.1 Injection Profile Test 3.2 Frequency Injection Table Time (s) 0 30 30 1830 1830 1860 Frequency (Hz) 50 50 49.4 49.4 50 50 Table 3.10 Test 3.2 Frequency Injection Table Corresponding with Times 17

Figure 3.13 - Test 3.2 Injection Profile 3.4 Test 4- Frequency Event Test This test assesses the system s performance using an injected frequency profile from a real frequency event which will be provided by National Grid. Pass criteria for test: Provide an active power response consistent with the contracted performance within Primary, Secondary and/or High frequency response timescales. Sample Frequency Profile to be included here Figure 3.14 - Test 4 (Frequency profile/s to be confirmed in final version) 18

Appendix A Test Data and Test Signals The limits of error and minimum sample rates for testing are shown below in Tables A.1 for Non- Dynamic and A.2 for Dynamic. All success criteria are subject to the stated limit of error/accuracy threshold. Limit of error/ Accuracy threshold Minimum Sample rate Frequency (Hz) ±0.01 Hz 1Hz Active Power (MW) Please see pass criteria 1Hz Table A.1- Limits of error and minimum sample rates for Non-Dynamic Service Testing Limit of error/ Accuracy threshold Minimum Sample rate Frequency (Hz) ±0.01 Hz 10Hz Active Power (MW) Please see pass criteria 10Hz Table A.2- Limits of error and minimum sample rates for Dynamic Service Testing Simulations / simulated tests are not permitted. Each test submitted must record real time data from the plant and sites under test: The test data submitted must come from the specific site to be contracted; substituted data will not be accepted. Test results much not be changed before submission for analysis. Test Signals In ALL cases, the data should record ALL required signals for at least 30 seconds BEFORE the application of the frequency injection signal and for at least 30 seconds AFTER the completion of the test. For ALL services, the data for the following signals will need to be provided a) Time b) Active Power c) System Frequency or Injected frequency as appropriate d) Any other relevant signals that may affect the success criteria. Examples of such signals include State of Charge, Control signals and Relay Logics. 19

Appendix B Format of Test Results Test data needs to be in a format compatible with Microsoft Excel. The data should be clear and concise with no ambiguities for the recipient of the data. The Test Data should be submitted with a completed Non BM Frequency Response Testing Request form. See Appendix C below. Each test will need to be recorded on an individual worksheet and include: Identification of the asset/group The location Provider s company name Date of the test Associated test number Service being provided (Low Frequency Non Dynamic, Low/High Frequency Dynamic, etc.) Example Test Results Figure B.1- One Site Non-Dynamic Provider Company Name Date xx-xx-xxxx Test 1 Service Low Frequency Non-Dynamic Secondary Response Location AA Site/Group/Plant A Time Injected Frequency Baseline Power Measured Power (Hz) (MW) (MW) Relay 0 50.00 0.00 0.00 0 0.1 50.00 0.00 0.00 0 0.2 50.00 0.00 0.00 0 0.3 50.00 0.00 0.00 0 0.4 50.00 0.00 0.00 0 0.5 50.00 0.00 0.00 0 0.6 50.00 0.00 0.00 0 0.7 50.00 0.00 0.00 0 0.8 50.00 0.00 0.00 0 0.9 50.00 0.00 0.00 0 1 50.00 0.00 0.00 0 1.1 50.00 0.00 0.00 0 1.2 50.00 0.00 0.00 0 1.3 50.00 0.00 0.00 0 1.4 50.00 0.00 0.00 0 1.5 50.00 0.00 0.00 0 1.6 50.00 0.00 0.00 0 20

Figure B.2- Multiple Sites Non-Dynamic Provider Company Name Date xx-xx-xxxx Test 1 Service Low Frequency Non-Dynamic Secondary Response Location AA AB Site/Group/Plant A B Time Injected Baseline Power Measured Power Injected Baseline Power Measured Power Frequency (Hz) (MW) (MW) Relay Time Frequency (Hz) (MW) (MW) Relay 0 50.00 0.00 0.00 0 0 50.00 0.00 0.00 0 0.1 50.00 0.00 0.00 0 0.1 50.00 0.00 0.00 0 0.2 50.00 0.00 0.00 0 0.2 50.00 0.00 0.00 0 0.3 50.00 0.00 0.00 0 0.3 50.00 0.00 0.00 0 0.4 50.00 0.00 0.00 0 0.4 50.00 0.00 0.00 0 0.5 50.00 0.00 0.00 0 0.5 50.00 0.00 0.00 0 0.6 50.00 0.00 0.00 0 0.6 50.00 0.00 0.00 0 0.7 50.00 0.00 0.00 0 0.7 50.00 0.00 0.00 0 0.8 50.00 0.00 0.00 0 0.8 50.00 0.00 0.00 0 0.9 50.00 0.00 0.00 0 0.9 50.00 0.00 0.00 0 1 50.00 0.00 0.00 0 1 50.00 0.00 0.00 0 1.1 50.00 0.00 0.00 0 1.1 50.00 0.00 0.00 0 1.2 50.00 0.00 0.00 0 1.2 50.00 0.00 0.00 0 1.3 50.00 0.00 0.00 0 1.3 50.00 0.00 0.00 0 1.4 50.00 0.00 0.00 0 1.4 50.00 0.00 0.00 0 1.5 50.00 0.00 0.00 0 1.5 50.00 0.00 0.00 0 1.6 50.00 0.00 0.00 0 1.6 50.00 0.00 0.00 0 Figure B.3- Dynamic Provider Company Name Date xx-xx-xxxx Test 1 Service Low/High Frequency Dynamic Response Location AA Site/Group/Plant A Time Injected Baseline Measured Test Frequency (Hz) Power (MW) Power (MW) Number 0 50.00 0.00 0.00 1.1 0.1 50.00 0.00 0.00 1.1 0.2 50.00 0.00 0.00 1.1 0.3 50.00 0.00 0.00 1.1 0.4 50.00 0.00 0.00 1.1 0.5 50.00 0.00 0.00 1.1 0.6 50.00 0.00 0.00 1.1 0.7 50.00 0.00 0.00 1.1 0.8 50.00 0.00 0.00 1.1 0.9 50.00 0.00 0.00 1.1 1 50.00 0.00 0.00 1.1 1.1 50.00 0.00 0.00 1.1 1.2 50.00 0.00 0.00 1.1 1.3 50.00 0.00 0.00 1.1 1.4 50.00 0.00 0.00 1.1 1.5 50.00 0.00 0.00 1.1 1.6 50.00 0.00 0.00 1.1 21

Appendix C Test Request Form Non BM Frequency Response Testing Request Purpose This form should provide all the information needed by the Electricity Connections Compliance Team (ECC) for the efficient planning and implementation of contracted firm frequency response testing. It should be noted that currently ECC are not mandated to undertake non-bm testing. Any test data review and validation is subject to their workload prioritisation and can take up to 4 weeks. Testing All testing is based on the default set of tests documented within the Testing Guidance for Providers of Firm Frequency Response Balancing Service (link) and modified as necessary based on the information contained below. Contract company details Contracted company Primary contact Contact number Email address High level contracted service details Contract Log Number Service type, e.g. Non-Dynamic or Dynamic Asset type, e.g. diesel generator, battery etc Unit make up, e.g. single or aggregated Aggregation methodology (if appropriate) Unit location / ID Contract signed date Service start date Test date Detailed service parameters Please complete one of the following tables. Non-Dynamic service details Contracted MW Contracted initiation time, e.g. 2 seconds, 10 seconds etc Contracted response time Contracted duration Trigger frequency setting Any relevant special conditions the Compliance Team should be aware of? 22

Dynamic service details Deadband Primary response MW Secondary response MW High response MW Any relevant special conditions the Compliance Team should be aware of? Frequency Deviation (Hz) -0.1 Primary Response (MW) Secondary Response (MW) Frequency Deviation (Hz) 0.1 High Response (MW) -0.2 0.2-0.3 0.3-0.4 0.4-0.5 0.5 23