Application Note - SolarEdge Inverters, Power Control Options

Similar documents
Application Note - SolarEdge Inverters, Power Control Options

Unit certificate for solar inverters

SuperCELL Data Programmer and ACTiSys IR Programmer User s Guide

OPERATING MANUAL. EIB-Kombisensor AS 315 N

CHV Series Vector Control Inverter Options. Operating Instructions for Tension Control Card

1014/15 R Float Volt - - Voltage, L-L, ave of 3 phases 1016/17 R Float Volt - - Voltage, L-N, ave of 3 phases

Lightcloud Application

Microcare LCD Solar MPPT User Documentation

Analogue Meters CQ2x07 series

Experiment P43: RC Circuit (Power Amplifier, Voltage Sensor)

Rain Watch TM Set up Manual. IC System with Rain Bird IC CONNECT

Three-phase AC Circuits. Measurement of Power in a Three-phase Circuit

Boise State University Department of Electrical and Computer Engineering ECE 212L Circuit Analysis and Design Lab

RC Circuit (Power amplifier, Voltage Sensor)

Measuring the time constant for an RC-Circuit

UMG 96 RM Basic unit Extension UMG 96RM-PN Extension UMG 96RM-P Extension UMG 96RM-CBM Power Analyser

SAFYR7 KAPPABRIDGE CONTROL SOFTWARE. User Manual

The Kestrel Handheld Weather Tracker. 1) If the unit is configured to log data and it is turned off, will it continue to log temperature data?

NorthStar Battery Company DCN: SES DCR: 1038-S07 Date: Page 1 of 12

Old Dominion University Physics 112N/227N/232N Lab Manual, 13 th Edition

St art. rp m. Km /h 1: : : : : : : : : : : : :5 2.5.

Minute Impulse Clock Controller I01DN

Operation Manual Contents subject to change without notice

Connect the Vernier spectrometer to your lap top computer and power the spectrometer if necessary. Start LoggerPro on your computer.

Displaying and Rotating WindNinja-Derived Wind Vectors in ArcMap 10.5

EDSA IEC 909 SHORT CIRCUIT ANALYSIS

Figure 1: Capacitor circuit

Power Factor Improvement

ON SITE SYSTEMS Chemical Safety Assistant

iclicker A metal ball of radius R has a charge q. Charge is changed q -> - 2q. How does it s capacitance changed?

A Determination of Planck s Constant with LED s written by Mark Langella

Precision Circuits Inc

Bright Advance Corporation

MoLE Gas Laws Activities

Review of Basic Electrical and Magnetic Circuit Concepts EE

Digital Controller Operation

MoLE Gas Laws Activities *

Designing a Quilt with GIMP 2011

Lab 1: Numerical Solution of Laplace s Equation

SOTM LAB: P16 OHM S LAW I. TEACHER NOTES & GUIDELINES TITLE OF LAB: Ohm s Law DEVELOPERS OF LAB:

Activity P27: Speed of Sound in Air (Sound Sensor)

GENERATORS AND LOADS MODELS TO INVESTIGATE UNCONTROLLED ISLANDING ON ACTIVE DISTRIBUTION NETWORKS

Performing a Pharmacophore Search using CSD-CrossMiner

Account Setup. STEP 1: Create Enhanced View Account

To order, specify : Types Protection functions Current surge Asymmetry and loss of phase. Operating principle

( ) ( ) = q o. T 12 = τ ln 2. RC Circuits. 1 e t τ. q t

vba vbn vcb van vcn vac Figure 1. Three-phase line and phase voltages

ISSP User Guide CY3207ISSP. Revision C

O P E R A T I N G M A N U A L

MFJ 259/259B Operation & Simplified Calibration

Electric Field PHYS 296

Software BioScout-Calibrator June 2013

Forces and Newton s Second Law

ALPS. Advanced Line Protection System

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers

SRV02-Series Rotary Experiment # 1. Position Control. Student Handout

S Sapling INSTALLATION MANUAL FOR FIELD SELECTABLE ANALOG CLOCKS SAA SERIES SPECIFICATIONS. advanced time and control systems

PHY222 - Lab 7 RC Circuits: Charge Changing in Time Observing the way capacitors in RC circuits charge and discharge.

McIDAS-V Tutorial Displaying Point Observations from ADDE Datasets updated July 2016 (software version 1.6)

WLDS-20 Mk2 MAJOR WATER LEAK DETECTION SYSTEM INSTALLATION & COMMISSIONING

Evaluation copy. Ground Temperature Measurements. computer OBJECTIVES MATERIALS PRE-LAB QUESTIONS

Optics Minimization in LISE ++

Hooke s Law. Equipment. Introduction and Theory

Circular Motion and Centripetal Force

Fault Analysis Power System Representation

Inverted Pendulum System

DigiElch 8 from ElchSoft

EXP. NO. 3 Power on (resistive inductive & capacitive) load Series connection

AC Power Analysis. Chapter Objectives:

B = 8 0 NI/[r (5) 3/2 ],

Operating instructions Vortex flow meter. SVxxx / / 2015

Electrical Machines-I Prof. D. Kastha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

MODELS Number WW4.x For Europe & Others V 50HZ

Urban Canopy Tool User Guide `bo`

General Chemistry Lab Molecular Modeling

Capacitor investigations

OPERATION MANUAL. 3 in 1, IR, Type K/J/R/E/T, Pt 100 ohm THERMOMETER. Model : TM-2000

User Manuel. EurotaxForecast. Version Latest changes ( )

Mathcad Examples. Define units: MVA 1000kW MW MVA kw kvar kw. pu Entering Phasors in Polar Notation

QNET Experiment #05: HVAC System Identification. Heating, Ventilation, and Air Conditioning Trainer (HVACT) Student Manual

Electromagnetic Forces on Parallel Current-

PHASED OUT. FL ballasts Electronic dimming. PCA TC BASIC Y II, W BASIC compact

Inbuilt Modbus Protocol

MOHO PRO 12 Step-by-step demonstration script

Gas Pressure and Temperature Relationships *

Operating instructions Magnetic-inductive flow sensor SM6004 SM7004 SM / / 2014

DigiElch 8 TM from ElchSoft

GENERATOR INTERCONNECTION APPLICATION

Infrared Tire Temperature Sensor, IRTS-V2 - Datasheet

World s First Universal Quantum Computation Simulator. Quantum Computer Simulator. For Windows/Macintosh. User Guide

Current protection I 2 t long-time protection

water work RAIN BUCKET making since 1986 ET2000 (400 SERIES) RAIN BUCKET SETUP

POWER FACTOR IN THE DIGITAL AGE A N E N V I R O N M E N T A L P O T E N T I A L S W H I T E P A P E R. Power Quality For The Digital Age

рн PRO Controller The device is used to control and regulate ph level in hydroponic systems and water preparing units automatically USER MANUAL

Energy Stored in Capacitors

MAN-SGY-012-V11 EC 5195 Fairford Electronics Ltd - Synergy Modbus RTU Programming Manual - 22nd February 2016 Page 1 of 59.

PHY 221 Lab 3 Vectors and Motion in 1 and 2 Dimensions

Operating instructions Compressed air meter SD / / 2013

Creating a Pharmacophore Query from a Reference Molecule & Scaffold Hopping in CSD-CrossMiner

NINE CHOICE SERIAL REACTION TIME TASK

Transcription:

Application Note - SolarEdge Inverters, Power Control Options Contents Introduction... 1 Installation Note for Three Phase Inverters... 1 The Power Control Menu... 2 Energy Manager... 2 RRCR Conf.... 2 Reactive Power Conf.... 3 Active Power Conf.... 4 Phase Balance... 4 Wakeup Conf.... 5 P(f)... 5 Advanced... 5 Load Defaults... 5 Power Control Hierarchy... 6 Reactive Power Control... 6 Active Power Control... 6 The Power Control Status Window... 6 Country Defaults... 7 Germany, Austria, Italy, Belgium, Slovenia... 7 All Other Countries... 8 Appendix A Q Configuration... 9 Example... 10 Appendix B - How to Identify the Inverter s CPU Version... 11 Introduction To improve grid stability, many electric utilities are introducing advanced grid limitations, requiring control of the active and reactive power of the inverter by various mechanisms. All SolarEdge inverters with CPU version 2.337 and later support these requirements. These inverters include default settings per country, based on the specific requirements in that country, as well as the ability to configure these settings (settings may have to be configured according to installation size or utility requirements). This document details the available power control configuration options in the SolarEdge inverters, and explains how to adjust these settings if such changes are required. Installation Note for Three Phase Inverters If power control is enabled, the order of grid lines connection to the inverter is important. A 120deg phase difference between L1 to L2 and between L2 to L3 should be kept (L1-L2-L3 and not, for example L1-L3-L2). If the grid lines are not in this order, the following error will be displayed on the LCD and the inverter will not produce power. E R R O R 1 1 2 W r o n g A C C o n n e c t i o n 1

The Power Control Menu The Power Control menu is accessible from the inverter LCD main menu. Refer to the Inverter User Interface chapter in the SolarEdge installation guide for LCD navigation instructions. The Power Control menu includes the following options: G r i d C o n t r o l < E n > E n e r g y M a n a g e r R R C R C o n f. < E n > R e a c t i v e P w r C o n f A c t i v e P w r C o n f W a k e u p C o n f P h a s e B a l a n c e < E N > P ( f ) A d v a n c e d L o a d D e f a u l t s The Phase Balance option is relevant to single phase inverters only. Grid Control is enabled for Germany and Germany MVGC country settings. The sections below describe the functionality and configuration of each of these menu options. Energy Manager SolarEdge offers the Smart Energy Management solution for increasing the self-consumption of a site. One method used for this purpose is limiting the feed-in power: The inverter dynamically adjusts the PV power production in order to ensure that feed-in power does not exceed a preconfigured limit. To enable this functionality, an energy meter that measures feed-in or consumption must be installed at the site. For details on how to use the Feed-in Limitation feature, refer to the Feed-in Limitation application note at http://www.solaredge.com/files/pdfs/products/feed-in_limitation_application_note.pdf. RRCR Conf. SolarEdge inverters can connect to an external device which can control active and reactive power according to commands sent by the grid operator (for example, an RRCR - Radio Ripple Control Receiver). The RRCR menu includes the following options: R R C R < D i s > S e t V a l u e s 0 0 0 0 - - -, - - -, N 0 0 0 1 0, 1. 0 0, Y 0 0 1 0 3 0, 1. 0 0, Y 0 0 1 1 - - -, - - -, N 0 1 0 0 6 0, 1. 0 0, Y 0 1 0 1 - - -,, N 0 1 1 0 - - -,, N 0 1 1 1 - - -,, N 1 0 0 0 1 0 0, 1. 0 0, Y 1 0 0 1 - - -, - - -, N 1 0 1 0 - - -, - - -, N 1 0 1 1 - - -, - - -, N 1 1 0 0 - - -, - - -, N 1 1 0 1 - - -, - - -, N 1 1 1 0 - - -, - - -, N 1 1 1 1 - - -, - - -, N Use the RRCR Conf. menu to enable this control and to configure up to 16 control states. Each control state is a combination of the following three fields: AC output power limit limits the inverter s output power to a certain percentage of its rated power with the range of 0 to 100 (% of nominal active power). CosPhi sets the ratio of active to reactive power. The Reactive Power Conf. Mode must be set to RRCR when using this control mode. CosPhi range is from 0.8 leading to 0.8 lagging (a negative value indicates a lagging CosPhi) Enable/Disable enables or disables control according to the specific state. 2

To enable/disable RRCR control: Select RRCR Choose Enable or Disable Press Enter Application Note SolarEdge Inverters, Power Control Options 06/2014 In addition to enabling this option, the inverter must be connected to an RRCR. Refer to the Power Reduction Control application note for details: http://www.solaredge.com/files/pdfs/power-reduction-control-application-note.pdf. To enable/disable any of the 16 states: When you select a disabled state, only one line is displayed. After you enable it, three lines are displayed: enable <yes>, pwr reduce and cosphi. Select Set Values Scroll to the relevant state Press Enter Select Enable Choose Yes or No Press Enter Now you can select either cosphi or power reduce and set their value. To set the values of an enabled state: Select Set Values Scroll to the relevant state Press Enter Scroll to the relevant value Input the required setting Press Enter When setting CosPhi values, use the minus symbol (-) for a lagging value. Reactive Power Conf. The Reactive Power menu includes the following options: M o d e < C o s P h i > C o s P h i < 1. 0 0 > C o s P h i ( P ) Q < 0 > Q < U > Q < P > U n o m < 2 3 0 > Mode: C o s P h i C o s P h i ( P ) Q Q ( U ) + Q ( P ) R R C R Use the Reactive Power menu to select one of several reactive power control modes listed below, and to configure the various modes: CosPhi sets a constant CosPhi, regardless of other parameters. Range: from 0.8 leading to 0.8 lagging (a negative value indicates a lagging CosPhi). CosPhi(P) sets a graph of CosPhi to active power (P). CosPhi (P) has a 6-point graph setup. P can be set to any value between 0 and 100 [% of nominal active power] and CosPhi can be set to any value between 0.8 leading to 0.8 lagging (a negative value indicates a lagging CosPhi). Each point includes the following fields: < % of nominal active power, CosPhi >. Q sets constant reactive power (Q); available in three phase inverters only. Range: -100 to 100 (% of nominal reactive power. A negative value indicates a lagging reactive power). Q(U)+Q(P) sets a graph of reactive power (Q) to grid voltage (U) and to active power (P); this mode can be used when Q(U) control is required, by setting Q(P) to zero, and vice versa; available in three phase inverters only. Q(U) and Q(P) have 6-point graph setups. Refer to Appendix A Q Configuration on page 9 for additional configuration instructions. U: 0 to 200 [% of nominal voltage]. P: 0 to 100 [% of nominal active power] RRCR enables CosPhi control through the RRCR. RRCR must be enabled, as described above, when using this control mode. Unom - The Reactive Power menu is also used to set Unom, a reference grid voltage, when required for installation testing. Range: 0 to 500 [V] 3

To select a reactive power control-mode: Enter the Mode menu Scroll to the required mode Press Enter To set the values of a reactive power control-mode: Scroll to the relevant mode Press Enter Input the required setting Press Enter When setting CosPhi or Q values, use the minus symbol ( ) for a lagging value. Active Power Conf. The Active Power menu includes the following options: P o w e r L i m i t < 1 0 0 % > C u r r e n t L i m < 1 5. 7 A > W a k e u p G r a d < E n > G r a d T i m e < x x x x s > Use the Active Power menu to control the inverter active power: Power Limit - limits the inverter maximum output power. The power limit can be set to any value between 0-100 [% of nominal active power]. Current Lim Current Limit: limits the inverter s maximum output current (available from CPU version 2.549). The current limit can be set to any value between 0 and the inverter s max AC current [A] (the LCD will allow setting to a higher value but the inverter will never exceed its maximum AC current). Wakeup Grad Wakeup Gradient: enables gradual power production when it begins operation after a fault or an inverter reset. Grad Time Gradient Time: The wakeup time setting. This line is displayed only if the Wakeup Gradient is enabled. Can be set to any value between 1 and 9999 seconds. To change the power or current limit: Select Power Limit or Current Lim Press Enter Input the required setting Press Enter To set gradual power production: 1 Select Wakeup Gradient Select Enable Press Enter 2 Select Grad Time Press Enter Input the required setting Press Enter Phase Balance Use the Phase Balance menu if balancing the three phases is required when connecting single phase inverters to a three phase grid. This option is available for single phase inverters only. To enable/disable phase balancing of the inverters: Select Phase Balance Select Enable or Disable Press Enter In addition to enabling this option, the inverters that need to be balanced must be inter-wired. Refer to the Phase Balancing Connection Guide for details: http://www.solaredge.com/files/pdfs/phase_balancing_connection_guide.pdf. 4

Wakeup Conf. The Wakeup menu includes the following options: M i n W a k e u p F r e q. M a x W a k e u p F r e q. M i n W a k e u p V g r i d M a x W a k e u p V g r i d. Use the Wakeup menu to set the minimum and maximum grid frequencies and grid voltages between which the inverter can begin power production. This menu does not set the inverter disconnection values, which are pre-set per country. The ranges for Wakeup parameters are: Frequency: 0 to 100 [Hz] Voltage 0 to 500 [V] To change the frequency or voltage values: Scroll to the relevant setting Press Enter Input the required value Press Enter P(f) Use the P(f) menu when frequency-based power reduction is required. This menu defines a linear graph set by two points. The inverter de-rates power according to the defined graph, until the frequency reaches the trip value and the inverter disconnects (the trip point is preset per country therefore does not need to be defined as one of the two points). Each point includes the following fields: <frequency, % of nominal active power>. P 0 < 5 0. 2 0, 1 0 0. 0 > P 1 < 5 1. 2 0, 6 0. 0 0 > The ranges for P(f) parameters are: Frequency: 0 to 100 [Hz] P: 0 to 100 [% of nominal active power]. To change the P or f values: Scroll to the relevant point Press Enter Input the required value Press Enter Advanced Use the Advanced menu to configure the K-Factor for the BDEW-MVGC certification in Germany. It is set to a default value of 2. The range for the FRT-K parameter is 0 to 16. To enable/disable FRT-K: Select Set FRT Select Enable or Disable Press Enter To change the value after enabling the K-Factor: Select FRT-K Input the required value Press Enter Load Defaults Use the Load Defaults menu to restore the default Power Control settings of the country to which the inverter is set, according to the settings detailed below. The only parameter that is not reset when using the Load Defaults option is Active Power Conf. Power Limit. 5

Power Control Hierarchy Reactive Power Control The following describe reactive power control conditions: If RRCR is disabled, and Reactive Pwr. Conf Mode is not set to RRCR, the RRCR points will be ignored. If RRCR is enabled, and Reactive Pwr. Conf Mode is set to RRCR, the RRCR points will control active power and reactive power. If RRCR is enabled, and Reactive Pwr. Conf Mode is not set to RRCR, the RRCR points will control only active power, and reactive power will be controlled by the selected mode. Active Power Control The following modes can control the active output power of the inverter: RRCR Active Power Limit Wakeup Gradient P(f) If several control modes are active, the output power of the inverter will be the minimum power. For example, if an RRCR point is configured to Pwr Reduce=60% and Active Power Conf. Power Limit=70%, the output power will be limited to 60% of Pnom. The Power Control Status Window Short-press the external LCD button at the bottom of the inverter until the following screen appears: P W R C T R L : R E M O T E P W R L i m i t : 1 0. 0 4 k W C o s P h i : 0. 9 P o w e r P r o d : 7 0 0 0 W PWR CTRL: The power control status: REMOTE - Communication with the smart energy manager is confirmed/validated. LOCAL - The power is controlled locally (e.g. by a fixed limit), or this inverter limits the PV power production to its relative portion of the feed-in power limit, as a result of disconnected communication with the smart energy manager. If this status appears, check the communication to the smart energy manager or the communication to the meter. PWR Limit: The inverter maximum output power set by the smart energy manager Cos Phi: The ratio between active to reactive power Power Prod: The power produced by the inverter 6

Country Defaults Germany, Austria, Italy, Belgium, Slovenia RRCR Conf. RRCR Germany MVGC & Austria Germany Italy Belgium Slovenia 1-ph inverters: Disabled 3-ph inverters: Enabled The first value is the power limit [% of nominal power], the second value is CosPhi and Y/N indicates if the point is enabled/disabled: Set values 0 0 0 0 < - - -, - - -, N > 0 0 0 1 < 0, 1. 0 0, Y > 0 0 1 0 < 3 0, 1. 0 0, Y > 0 0 1 1 < - - -, - - -, N > 0 1 0 0 < 6 0, 1. 0 0, Y > 0 1 0 1 < - - -, - - -, N > 0 1 1 0 < - - -, - - -, N > 0 1 1 1 < - - -, - - -, N > 1 0 0 0 < 1 0 0, 1. 0 0, Y > 1 0 0 1 < - - -, - - -, N > 1 0 1 0 < - - -, - - -, N > 1 0 1 1 < - - -, - - -, N > 1 1 0 0 < - - -, - - -, N > 1 1 0 1 < - - -, - - -, N > 1 1 1 0 < - - -, - - -, N > 1 1 1 1 < - - -, - - -, N > Reactive Power Conf. Mode CosPhi CosPhi CosPhi CosPhi 1-ph inverters: CosPhi 3-ph inverters: Q(U)+Q(P) CosPhi 1 1 1 1 1 CosPhi(P) The first value is P [% of nominal power], and the second value is CosPhi: P 0 < 0. 0, 0. 9 0 0 > P 1 < 0. 0, 0. 9 0 0 > P 2 < 0. 0, 0. 9 0 0 > P 3 < 1 0 0. 0, - 0. 9 0 0 > P 4 < 1 0 0. 0, - 0. 9 0 0 > P 5 < 1 0 0. 0, - 0. 9 0 0 > P 0 < 0. 0, 1. 0 0 0 > P 1 < 0. 0, 1. 0 0 0 > P 2 < 5 0. 0 0, 1. 0 0 0 > P 3 < 1 0 0. 0, - 0. 9 5 0 > P 4 < 1 0 0. 0, - 0. 9 5 0 > P 5 < 1 0 0. 0, - 0. 9 5 0 > a Q 0 0 0 0 0 Q(U) The first value is U [% of nominal grid voltage], and the second value is Q [% of nominal Q]. Q/Qnom depends on the AC power of the inverter. The screen below shows the SE12.5k values: P 0 < 9 5. 6 5, - 6. 8 6 9 > P 1 < 9 7. 8 2, - 6. 8 6 9 > P 2 < 9 7. 8 2, - 6. 8 6 9 > P 3 < 1 0 2. 1, 6. 8 6 9 > P 4 < 1 0 2. 1, 6. 8 6 9 > P 5 < 1 0 4. 3, 6. 8 6 9 > P 0 < 8 5. 9 9, - 9 9. 9 9 > P 1 < 8 9. 1 3, - 9 9. 9 9 > P 2 < 8 9. 1 3, - 9 9. 9 9 > P 3 < 1 0 6. 0, 9 9. 9 9 > P 4 < 1 0 6. 0, 9 9. 9 9 > P 5 < 1 0 8. 6, 9 9. 9 9 > Q(P) A The first value is P [% of nominal power], and the second value is Q [% of nominal Q]. Q/Qnom depends on the AC power of the inverter. The screen below shows the SE12.5k values: P 0 < 0. 0, 0. 0 > P 1 < 0. 0, 0. 0 > P 2 < 0. 0, 0. 0 > P 3 < 0. 0, 0. 0 > P 4 < 0. 0, 0. 0 > P 5 < 0. 0, 0. 0 > P 0 < 0. 0, 0. 0 > P 1 < 0. 0, 0. 0 > P 2 < 0. 0, 0. 0 > P 3 < 1 0 0. 0, - 4 9. 9 9 > P 4 < 1 0 0. 0, - 4 9. 9 9 > P 5 < 1 0 0. 0, - 4 9. 9 9 > Unom 230 [V] 230 [V] 230 [V] 230 [V] 230 [V] 7

Germany MVGC & Austria Germany Italy Belgium Slovenia Active Power Conf. Power Limit Current Limit Wakeup Gradient 100 [% of nominal power] 1-ph inverters: 56.5 [A] 3-ph inverters: 117 [A] (Effectively the inverter is limited by its maximum AC current) Enabled Wakeup Gradient Time Phase Balance Phase Balance Wakeup Conf. 10 minutes (i.e. 10% of nominal power per minute) 5 minutes (i.e. 20% of nominal power per minute) 10 minutes (i.e. 10% of nominal power per minute) Disabled Disabled Disabled Disabled Disabled Fmin 47.50 [Hz] 47.50 [Hz] 49.95 [Hz] 47.50 [Hz] 0 [Hz] Fmax 50.04 [Hz] 50.04 [Hz] 50.05 [Hz] 50.04 [Hz] 100 [Hz] Vmin 218 [V] 195 [V] 195.5[V] 0 [V] 0 [V] Vmax 253 [V] 253 [V] 253 [V] 400 [V] 400 [V] P(f) P(f) The first value is the frequency [Hz], and the second value is P [% of nominal power]: P 0 < 5 0. 2 0, 1 0 0. 0 > P 1 < 5 1. 2 0, 6 0. 0 0 > P 0 < 5 0. 2 9, 1 0 0. 0 > P 1 < 5 1. 5 0, 0. 0 > P 0 < 5 0. 2 0, 1 0 0. 0 > P 1 < 5 1. 2 0, 6 0. 0 0 > a a a All Other Countries RRCR Conf. RRCR Set values 1-ph inverters: Disabled 3-ph inverters: Enabled The first value is the power limit [% of nominal power], the second value is CosPhi and Y/N indicates if the point is enabled/disabled: 0 0 0 0 < - - -, - - -, N > 0 0 0 1 < 0, 1. 0 0, Y > 0 0 1 0 < 3 0, 1. 0 0, Y > 0 0 1 1 < - - -, - - -, N > 0 1 0 0 < 6 0, 1. 0 0, Y > 0 1 0 1 < - - -, - - -, N > 0 1 1 0 < - - -, - - -, N > 0 1 1 1 < - - -, - - -, N > 1 0 0 0 < 1 0 0, 1. 0 0, Y > 1 0 0 1 < - - -, - - -, N > 1 0 1 0 < - - -, - - -, N > 1 0 1 1 < - - -, - - -, N > 1 1 0 0 < - - -, - - -, N > 1 1 0 1 < - - -, - - -, N > 1 1 1 0 < - - -, - - -, N > 1 1 1 1 < - - -, - - -, N > Phase Balance Phase Balance Wakeup Conf. Fmin Fmax Vmin Vmax Disabled 0 [Hz] 100 [Hz] 100 [V] 400 [V] 8

Appendix A Q Configuration If the utility requires Q(U) control of the inverter, it will typically provide a linear graph including Umin, Umax, Q(Umin) and Q(Umax) values. If the utility requires Q(U)+Q(P) control of the inverter, it will typically provide a linear Q(U) graph for P=0 and for P=Pnom. To translate this graph into values to be configured in the inverter, follow the definitions and instructions below; Bolded face Q and U are the values that should be set in the inverter: Q max = 0.6 S max NOTE: Q max = sinφ S max = sin (cos 1 P S ) S max ; optimally CosPhi is set to a min/max value of -0.8/0.8 and therefore sin (cos 1 0.8) = 0.6 U min = U min Unom ; U max = U max Unom (between 0 and 200) Q(U min) = Q(U min) Qnom ; Q(U max ) = Q(U max) Qnom NOTE: SolarEdge inverters use the convention of inductive power being positive and capacitive power being negative; since most graphs are supplied with the opposite convention, i.e. with Q decreasing as U increases, the minus sign was inserted into the above definitions. When supplied with a graph where Q increases as U increases, ignore the minus sign. Set the 6 points that create the linear Q(U) graph to the following: P0 Umin Q(Umin) P1 Umin Q(Umin) P2 Umin Q(Umin) P3 Umax Q(Umax) P4 Umax Q(Umax) P5 Umax Q(Umax) NOTE: If the graph comprizes several linear sections, use points 1-4 for the Q(U) values of the break points in the graph. NOTE: Do not enter identical Q(U min ) or Q(U max ) values for different U points. dq = [Q(U, P = P nom) Q(U, P = 0)] See above note regarding the minus sign. Set the 6 points that create the linear Q(P) graph to the following: P0 0 0 P1 0 0 P2 0 0 P3 100 dq/qmax P4 100 dq/qmax P5 100 dq/qmax 9

Q/Qnom [%] Application Note SolarEdge Inverters, Power Control Options 06/2014 Example The following Q(U,P) graph has been provided by the utility: 120 100 80 60 40 20 0-20 -40 85 90 95 100 105 110 115 U/Unom [%] P=Pnom P=0 The inverter being configured is SE10k, which has a maximum AC power of 10kVA. Following the above steps result inthe following values: Q max = 0.6 10 = 6kVAR U min = 90% ; U max = 100% [if U is provided in Volts, divide by Unom to get the percentage value] Q(U min) = 100% ; Q(U max ) = 20% [if Q is provided in kvar, divide by Qnom to obtain the percentage value] Set the 6 points that create the Q(U) graph to the following: P0 90-100 P1 90-100 P2 90-100 P3 100 20 P4 100 20 P5 100 20 dq = [40 ( 20)] = 60% In this case dq is already normalized by Qmax. Therefore the 6 points that create the Q(P) graph should be the following: P0 0 0 P1 0 0 P2 0 0 P3 100-60 P4 100-60 P5 100-60 10

Appendix B - How to Identify the Inverter s CPU Version Application Note SolarEdge Inverters, Power Control Options 06/2014 Once the inverter is connected to the AC grid, the CPU version can be verified by pressing the inverter LCD button several times until the ID Status window appears: I D : # # # # # # # # # # D S P 1 / 2 : x. x x x x / x. x x x x C P U : 0 0 0 2. 7 x x C o u n t r y : X X X X X Most inverters with previous CPU versions can be upgraded to the new version: - All three phase inverters can be upgraded - All single phase inverters with DSP2 version 1.027 and above can be upgraded. For upgrade files please contact support@solaredge.com. For upgrade instructions, refer to the following document: http://www.solaredge.com/files/pdfs/application-note-upgradingsolaredge-inverter-fw.pdf. 11