Effect of rib height on heat transfer and friction factor in a square channel roughened by inclined ribs with a gap

Similar documents
Augmented Heat Transfer in Square ducts with Transverse and Inclined Ribs with and without a gap

Thermo-Hydraulic Performance of a Roughened Square Duct Having Inclined Ribs with a Gap on Two Opposite Walls

Heat Transfer Enhancement of Solar Air Heater By Using Artificial Roughness double inclined ribs

W-Discrete Rib for Enhancing the Thermal Performance of Solar Air Heater

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 06, 2015 ISSN (online):

Effect of roughness shape on heat transfer and flow friction characteristics of solar air heater with roughened absorber plate

ARTICLE IN PRESS. K.R. Aharwal a,, B.K. Gandhi b, J.S. Saini b

Exergy Analysis of Solar Air Collector Having W Shaped Artificial Roughness

Numerical Investigation of Heat Transfer and Fluid Flow Characteristics of Roughened Solar Air Heater Duct

Comparative study of Different Geometry of Ribs for roughness on absorber plate of Solar Air Heater -A Review

Department of Mechanical Engineering, Indian Institute of Technology, Mumbai , Bombay Powai, India

COMPUTATIONAL FLUID DYNAMICS ANALYSIS OF A V-RIB WITH GAP ROUGHENED SOLAR AIR HEATER

EFFECT OF BAFFLES GEOMETRY ON HEAT TRANSFER ENHANCEMENT INSIDE CORRUGATED DUCT

Thermo Hydraulic Performance of Solar Air Heater by Using Double Inclined Discrete Rib Roughened Absorber Plate

Computational Fluid Dynamics Based Analysis of Angled Rib Roughened Solar Air Heater Duct

A Computational Fluid Dynamics Investigation of Solar Air Heater Duct Provided with Inclined Circular Ribs as Artificial Roughness

Empirical study of heat transfer at input area of turbojet blades

Empirical assessment of heat transmission and pressure loss in turbojet blades

Theoretical prediction of performance of Single and Double pass solar air heaters with artificial roughened absorber plates

International Communications in Heat and Mass Transfer

Convective Heat Transfer and Thermal Performance in a Circular Tube Heat Exchanger Inserted with U-Shaped Baffle

Experimental Heat transfer study of Turbulent Square duct flow through V type turbulators

NUMERICAL HEAT TRANSFER ENHANCEMENT IN SQUARE DUCT WITH INTERNAL RIB

Numerical and Experimental Investigation of Heat Transfer Using Discrete Ribs

"Experimental investigation of heat transfer enhancement by u-shaped Turbulator"

HEAT TRANSFER AND FRICTION FACTOR CHARACTERISTICS OF COMPOUND TURBULATORS IN RECTANGULAR DUCTS OF SOLAR AIR HEATER

Performance evaluations of two pass solar air heater using 60⁰ inclinedvshaped ribs on absorber plate

EFFECT OF STAGGERED RIB LENGTH ON PERFORMANCE OF SOLAR AIR HEATER USING V-RIB WITH SYMMETRICAL GAP AND STAGGERED RIB

Department of Mechanical Engineering, M.A.C.T. (R.E.C.), Bhopal , India b. Received 15 December 2000; accepted 15 January 2001

Experimental Validation of Heat Transfer Enhancement in plate Heat Exchanger with Non Conventional Shapes of Rib

Numerical Investigation of Heat Transfer and Fluid Flow Characteristics of Square Type Tabulator Roughness Solar Air Heater

FLOW AND HEAT TRANSFER ANALYSIS OF VARIOUS RIBS FOR FORCED CONVECTION HEAT TRANSFER

Numerical Heat Transfer Study of Turbulent Square Duct Flow through W-Type Turbulators

EXPERIMENTAL STUDY OF DEVELOPING TURBULENT FLOW AND HEAT TRANSFER IN RIBBED CONVERGENT/DIVERGENT RECTANGULAR DUCTS

Forced Convection Heat Transfer Augmentation from Ribbed Surface

INTERNATIONAL JOURNAL OF SCIENTIFIC & TECHNOLOGY RESEARCH VOLUME 5, ISSUE 09, SEPTEMBER 2016 ISSN

CFD Analysis for Thermal Behavior of Turbulent Channel Flow of Different Geometry of Bottom Plate

CFD analysis of solar air heater having absorber plate roughened with compound turbulators

A CFD Analysis Of A Solar Air Heater Having Triangular Rib Roughness On The Absorber Plate

EXPERIMENTAL STUDY OF HEAT TRANSFER AND PRESSURE LOSS IN CHANNELS WITH MINIATURE V RIB-DIMPLE HYBRID STRUCTURE

TURBULENCE AND PRESSURE DROP BEHAVIORS AROUND SEMICIRCULAR RIBS IN A RECTANGULAR CHANNEL

ENERGY PERFORMANCE IMPROVEMENT, FLOW BEHAVIOR AND HEAT TRANSFER INVESTIGATION IN A CIRCULAR TUBE WITH V-DOWNSTREAM DISCRETE BAFFLES

Flow and Heat Transfer Profiles in a Square Channel with 45 V-Downstream Orifices

Abstract 1. INTRODUCTION

EXPERIMENTAL STUDY OF DEVELOPING TURBULENT FLOW AND HEAT TRANSFER IN RIBBED CONVERGENT / DIVERGENT RECTANGULAR DUCTS by

International Journal of Advanced Engineering Technology E-ISSN

Performance Investigation of Artificially Roughened Duct used in Solar Air Heaters

Experimental analysis of heat transfer performance on different ribs shapes in forced convection

Department of Mechanical Engineering, VTU, Basveshwar Engineering college, Bagalkot, Karnataka, India

Heat transfer characteristics in forced convection through a rectangular channel with 60 tilted staggered ribs

Numerical Investigation on Turbulent Forced Convection in Heating Channel Inserted with Discrete V-Shaped Baffles

3D Numerical Study on Laminar Forced Convection in V-Baffled Square Channel

International Journal of Engineering, Business and Enterprise Applications (IJEBEA)

Analysis of Heat Transfer in Pipe with Twisted Tape Inserts

Numerical Investigation of Fluid Flow and Heat Transfer in a Two-Pass Channel with Perforated Ribs

Laminar Forced Convection and Heat Transfer Characteristics in a Square Channel Equipped with V-Wavy Surface

ASPECT RATIO EFFECT ON HEAT TRANSFER IN ROTATING TWO-PASS RECTANGULAR CHANNELS WITH SMOOTH WALLS AND RIBBED WALLS. A Dissertation WEN-LUNG FU

CFD based flow and heat transfer analysis of various ribs in solar air heater duct by continuous ribs on absorber plate

Transitional Flow and Heat Transfer Characteristics in a Rectangular Duct with Stagger-arrayed Short Pin Fins

Second law optimization of a solar air heater having chamfered rib groove roughness on absorber plate

Heat Augmentation Using Non-metallic Flow Divider Type Inserts in Forced Convection

Heat transfer and fluid flow analysis of roughness ribin solar air heater duct by computational fluid dynamics (CFD)

EFFECT OF DIFFERENT PARAMETERS ON THE PERFORMANCE OF RIB ROUGHNESS SOLAR DUCT

Experimental Investigations on the Local Distribution of wall static pressure coefficient Due To an Impinging Slot Air Jet on a Confined Rough Surface

International Journal of Scientific & Engineering Research, Volume 6, Issue 5, May ISSN

Experimental Investigation of Forced Convection Heat Transfer Augmentation from a Dimpled Surface

Flow and heat transfer in the wake of a surface-mounted rib with a slit

CFD Analysis of Forced Convection Flow and Heat Transfer in Semi-Circular Cross-Sectioned Micro-Channel

Experimental Analysis of Heat Transfer Enhancement over Dimpled Surface on One Side of Plate

Sarbendu Roy, Manvendra Tiwari and Sujoy Kumar Saha 1. Mechanical Engineering Department, IIEST, Shibpur, Howrah , West Bengal, INDIA

NUMERICAL SIMULATION OF FLOW THROUGH TURBINE BLADE INTERNAL COOLING CHANNEL USING COMSOL MULTIPHYSICS

Heat Transfer Enhancement of a Gas Turbine Blade-Tip Wall

Experimental Study of the Holes Density Effect on Film Cooling Performance

Chapter 3 NATURAL CONVECTION

Heat transfer enhancement on a flat surface with axisymmetric detached ribs by normal impingement of circular air jet

EXPERIMENTAL AND NUMERICAL INVESTIGATION OF IMPINGEMENT ON A RIB-ROUGHENED LEADING-EDGE WALL by

Heat Transfer Correlations for Gas Turbine Cooling LITH-IKP-EX--05/2313--SE. Jenny Sundberg

Numerical Study on Heat Transfer Enhancement in a Rectangular Duct with V-Shaped Ribs

Investigation of Heat Transfer on Smooth and Enhanced Tube in Heat Exchanger

CFD Analysis & Experimental Investigation to improve Heat Transfer Enhancement in flat plate with W Ribs

ENHANCEMENT OF HEAT TRANSFER FOR AIR FLOW THROUGH A DUCT WITH VARIOUS RIBS

Heat Transfer Enhancement in Turbines using Dimples- A CFD Study Nitish Kumar Jain 1 Dr.U.S. Mallikarjun 2

Study on the Performance of a Sirocco Fan (Flow Around the Runner Blade)

CFD Analysis of Heat Transfer through Artificially Roughened Solar Duct

Comparative Analysis of Heat Transfer and Friction Characteristics in a Corrugated Tube

Review of Roughness Enhancement of Solar Air Heaters having Different Rib Roughness Geometries on Absorber Plate

Heat Transfer Enhancement with Different Square Jagged Twisted Tapes and CuO Nano fluid

An Experimental Study on Heat Transfer Enhancement of Flat Plates Using Dimples

Effect of V-Shape Twisted Jaw Turbulators on Thermal Performance of Tube heat exchanger: An Experimental Study

A study of Heat Transfer Enhancement on a Tilted Rectangular Stainless Steel Plate

NUMERICAL SIMULATION OF FLOW AND HEAT TRANSFER OF INTERNAL COOLING PASSAGE IN GAS TURBINE BLADE. A Dissertation GUOGUANG SU

PARTICLE IMAGE VELOCIMETRY AND PROPER ORTHOGONAL DECOMPOSITION ANALYSIS OF THE CHANNEL FLOW EQUIPPED WITH CYLINDRICAL RIBS.

Experimental Investigation of Adiabatic Film Cooling Effectiveness and Heat Transfer Coefficients over a Gas Turbine Blade Leading Edge Configuration

Experimentation and Performance Evaluation of Heat Exchanger Using Z-Ribs

Investigation of Jet Impingement on Flat Plate Using Triangular and Trapezoid Vortex Generators

Experimental Investigation of Heat Transfer Analysis of Ribbed Duct for Thermal Performance Enhancement

NUMERICAL SIMULATION ON RECTANGULAR CONVERGENT AND DIVERGENT RIBBED CHANNELS

Heat Transfer Analysis of Helical Strip Insert with Regularly Spaced Cut Sections Placed Inside a Circular Pipe

EFFECT OF HEAT FLOW RATE Q ON CONVECTIVE HEAT TRANSFER H OF FLUID JET IMPINGEMENT COOLING ON HOT PLATE.

ENHANCEMENT OF THE HEAT TRANSFER RATE IN FREE CONVECTION SOLAR AIR HEATER USING PIN SHAPED ARTIFICIAL ROUGHNESS ON ABSORBER PLATE

Transcription:

International Journal of Thermal Technologies E-ISSN 2277 4114 2017 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Effect of rib height on heat transfer and friction factor in a square channel roughened by inclined ribs with a gap Aditi Neekhara 1#, Pooja Tiwari 2 and Shailesh Gupta 3* 1,2 Department of Mechanical Engineering, SRIT, Jabalpur - 482002, India 3 Department of Mechanical Engineering, Hitkarini College of Engineering & Technology, Jabalpur - 482005, India Received 10 Oct, Accepted 15 Dec 2017, Available online 18 Dec 2017, Vol.7, No.4 (Dec 2017) Abstract This work concentrates on experimental investigation of forced convection heat transfer and friction factor (pressure drop) characteristics of a rib-roughened surface with varying rib height of discrete inclined ribs. The test section of the square duct (AR=1) is roughened on its top and bottom wall with Inclined square ribs having a gap on its length. Reynolds number (Re) based on duct hydraulic diameter varied from 5,000 to 40,000, relative roughness pitch (p/e) is 10, relative gap width (g/e) is 1 and relative gap position (d/w) is taken as 1/3. The rib attack angle (α) is taken as 60 0.The effects of five rib height to hydraulic diameter ratios (e/d h) of 0.047, 0.060, 0.074, 0.087 and 0.10 on heat transfer in terms of Nusselt number and friction loss in the form of friction factor are experimentally investigated. The results show that there is significant effect on the Nusselt number and friction factor when (e/d h) has changed. It is observed that the heat transfer augmentation in the channel increase with decrease in the rib height to hydraulic diameter ratio (e/d h) (from 0.10 to 0.060) but only at the cost of the pressure drop across the test section. Maximum heat transfer enhancement is associated with ribs of (e/d h) = 0.060 which also produces the maximum pressure drop penalty in the range of parameters investigated. The thermal hydraulic performance for all (e/d h) ratios is also presented. The thermal hydraulic performance of ribs with (e/d h) = 0.060 has found maximum and is about 2.18. Keywords: Nusselt number, Friction factor, Rib height to hydraulic diameter ratio, Reynold s number, thermal performance 1. Introduction 1 Generally gas turbine cooling is achieved by bleeding some relatively cool air from the compressor and using it inside the gas turbine blades to remove heat transferred into the blade from the hot mainstream. The cooling air flows through internal cooling passages inside the blade, these passages are specifically designed to maximize the heat transfer. Rib turbulators are the most frequently used method to enhance the heat transfer in the cooling passages. Roughened internal blade passage is one of the popular ways to enhance the heat transfer through the blade surface and effectively used in the design of internal cooling passage of turbine blade. The blade surfaces roughened with the ribs cause extra flow resistances. The performance of the heat transfer surface with ribs depends significantly on the Rib parameters, flow parameters as well as the area of the surface. Many investigators have investigated fluid flow and heat transfer distributions in rib roughened channels. *Corresponding author Dr Shailesh Gupta is working as Professor in Mechanical Engineering, Phone: +91-0761-2600222; # Aditi Neekhara is Research Scholar Various geometrical parameters such as channel aspect ratio (AR), rib height-to-passage hydraulic diameter ratio (e/d h), rib attack angle (α), rib pitch-to-height ratio (p/e), rib shape, discretization of ribs and the manner in which the ribs are positioned relative to one another have considerable effects on heat transfer coefficient and friction factor of the passage [Han et al, 2001]. Chandra and Alexander, 2003, presented results of experimental studies on heat transfer and pressure drop in a square channel with continuous ribs on one, two, three and four walls. Experiments were conducted for a rib to hydraulic diameter ratio of 0.0625, pitch to rib height ratio of 8 and Reynolds number ranging from 12,000 to 72,000. It was observed that with increasing Reynolds number, the heat transfer augmentation decreased and the friction factor augmentation increased. It was also observed that the heat transfer augmentation and the friction factor increased with the increase in the number of ribbed walls. Rau et al, 1998, presented local heat transfer distribution in a square channel for various pitch to rib height (p/e) ratios with ribs on one wall. Liquid crystal thermography technique was used for determining local temperature field. Different pitch to rib height (p/e) ratios covered were 6, 8, 9, 10, 12, 223 International Journal of Thermal Technologies, Vol.7, No.4 (Dec 2017)

Aditi Neekhara et al 14 and 16 with a rib height to hydraulic diameter (e/d h) ratio of 0.1. It was observed that the heat transfer augmentation was highest for (p/e) ratios of 9 and 12 compared to all other (p/e) ratios studied. Liou and Hwang, 1992, presented both local and average heat transfer distributions along with friction factor variations in rectangular channel with two opposite rib roughened walls. Reynolds number varied from 5000 to 50,000 and the rib to hydraulic diameter ratios (e/d h) of 0.063, 0.081 and 0.106. Laser holographic interferometry technique was used for local heat transfer measurement and thermocouples were used for average heat transfer measurement. They concluded that the average Nusselt number increased by 2.2- to 2.9-folds that of a smooth channel for an (e/d h) variation from 0.063 to 0.106. Han et al, 1991, presented experimental results on pressure drop and heat transfer in a square channel with ribs on two walls for nine different rib configurations. Regionally averaged heat transfer and friction factor were reported for rib pitch-to-height ratio (p/e) of 10 and the rib height to hydraulic diameter ratio (e/d h) of 0.0625. They concluded that the angled ribs and V ribs provide higher heat transfer augmentation compared to continuous ribs. It was observed that the heat transfer augmentations and the friction factor were highest for the 60 0 orientation compared to 45 0 and 90 0 orientation amongst the angled ribs. Han and Zhang, 1992, reported results of heat transfer and pressure drop in a square channel with seven different configurations of broken ribs and shows that generally broken ribs give better heat transfer performance than corresponding continuous ribs. Liou et al, 1998, investigated the effect of rib height and pitch on the thermal performance of passage with detached solid ribs in a rectangular channel of aspect ratio 4. The rib to duct height ratio was varied from 0.13 to 0.26 and the pitch to rib height ratio (p/e) from 7 to 13. The clearance ratio was fixed at 0.38. Amongst the three rib heights investigated, they found that detached rib with rib to duct height ratio of 0.17 with (p/e) of 10 has highest thermal performance. Also they reported that the vortex shedding was the main controlling mechanism for the observed trend of heat transfer distribution observed in case of detached ribs. Kiml et al, 2001, reported that the thermal performance of rib arrangements with α = 60 0 is better than that of 45 0. Han and Park, 1998, studied heat transfer and pressure losses with 90, 60, 45, and 30 angle ribs in square and rectangular channels. The Reynolds number was from 10000 to 60000. They concluded that the higher thermal performance in the square channel was 30 rib angle and the higher thermal performance in the rectangular channel was 45 rib angle. The higher heat transfer with higher pressure drop in the square channel was 60 rib angle. The square channel in their study showed a larger increase in heat transfer performance than the wide aspect ratio channels. Lau et al, 1991, observed that the replacement of continuous transverse ribs by inclined ribs in a square duct results in higher turbulence at the ribbed wall due to interaction of the primary and secondary flows. Liou and D. Hwang, 1992, studied the heat transfer and flow field in the ribbed channels. They found that the (p/e) of 10 resulted in the best heat transfer; the heat transfer showed a periodic behavior between consecutive ribs; and both heat transfer and friction factor increased with decreasing rib spacing. Liou and J. Hwang, 1993, conducted experiments to measure the local as well as average heat transfer coefficients to compare the performance of square, triangular and semi-circular ribs and found that the square ribs give best heat transfer performance. Taslim et al, 1996, studied the effect of e/d h on the heat transfer and friction losses with 90 0, 45 0 and V-shaped ribs. The Reynolds number was from 5000 to 30000. The (e/d h) was 0.085, 0.125 and 0.167, (p/e) was 10. For (e/d h) = 0.085, the V-shape ribs shows the highest thermal performance and for (e/d h) equal to 0.125 and 0.165, the 45 0 angled ribs have the highest thermal performance. Taslim et al, 1997 and 1998, investigated the effect of (p/e) and (e/d h) on the heat transfer and friction losses with 90 0 sharp angle ribs and 90 0 around angle ribs in a square channel. The (e/d h) was 0.133, 0.167 and 0.25 and p/e was 5, 7, 8.5, and 10. The Relative roughness pitch of 8.5 and 10 reported the highest thermal performance. The thermal performance increases as (e/d h) increases. Sriharsha et al, 2009, studied the effect of (e/d h) on the local heat transfer distributions in a double wall ribbed square channel with 90 0 continuous and 60 0 V-broken ribs. It was observed that the enhancement caused by 60 0 V-broken ribs are higher than those of 90 0 continuous attached ribs and also results in lower pressure drop. But, with increase in (e/d h), the enhancements are found to decrease in the channel with broken ribs. Saha, 2010, concluded that Nusselt number and friction factor increase by increasing flow turbulator height and Reynolds number in square, rectangular and circular channels with ribs inserted in opposite walls. Thianpong et al, 2009, reported the heat transfer and friction loss behaviors of different heights of triangular ribs with three e/h ratios (e/h =0.13, 0.2 and 0.26) and aspect ratio 10 using data acquisition system (fluke 2650B). They observed that the uniform rib height performs better than the corresponding nonuniform one. Casarsa et al, 2002, showed that in their square channel with (e/d h) = 0.30 a strong acceleration of the flow over ribs occurred due to the reduced crosssection. Bailey and Bunker, 2003, considered an aspect ratio of 1:2.5 with three blockage ratios of 0.193, 0.263, and 0.333. They showed that heat transfer enhancement and friction increases with the blockage ratio. It is evident from the literature that there is scant data available on effect of rib height on heat transfer 224 International Journal of Thermal Technologies, Vol.7, No.4 (Dec 2017)

Aditi Neekhara et al distributions at higher (e/d h) ratios, particularly in broken rib configurations. Thus the role of rib s height seems to need more investigations. Hence, the present work focuses on the effect of the rib s height in the two opposite side s roughened square channel having discrete inclined ribs. The optimum value of (e/d h) have been obtained and discussed. 2. Experimental set-up and Roughness Geometry A schematic diagram of the experimental set-up including the test section is shown in Fig.1, which was previously used by Gupta et al, 2013 and Chaube et al, 2014. The flow duct consists of an entrance section, a test section and an exit section of length 1500 mm (20Dh), 1500 mm (20D h) and 750 mm (10D h) respectively. The dimension of wooden duct was 3750 mm x 75 mm x 75 mm (L x W x H) (inner dimensions of duct). G. I. pipe having internal diameter of 81 mm was connected to the exit end of the duct with a calibrated orifice plate (to measure flow rate) through a square to circular transition piece. The outside of entire set-up from inlet to the orifice plate, were covered with 25 mm thick thermocole sheet, to minimize the heat losses from the test section. Fig.1 Schematic diagram of experimental set-up Fig.2 Schematic of roughness geometry 225 International Journal of Thermal Technologies, Vol.7, No.4 (Dec 2017)

Nusselt Number Ratio (Nu r /Nu o ) Nusselt Number (Nu r ) Aditi Neekhara et al 3. Data Reduction 5. Results and Discussion The values of useful parameters were calculated as follows: The Reynolds number based on the channel hydraulic diameter, D h, is given by ρavdh Re (1) μ a The mass flow rate, m, of air through the duct has been calculated from pressure drop measurement across the orifice plate.. 0.5 2.ρa ΔP o m Cd.Ao. 4 (2) 1 β The average heat transfer coefficient, h, is evaluated from the measured temperatures and heat inputs as below: Q u = m C p (T o T i) (3) Qu h (4) A T T ) p( p f The average value of plate temperature (T p) is calculated as a weighted mean of the plate temperature measured at different locations and mean bulk air temperature (T f ) is calculated from the following equations. T f Ti To (5) 2 20 Tn T p (6) 20 n 1 Then, average Nusselt number, Nu, is written as hdh Nu (7) k a The friction factor is determined from the measured values of pressure drop, (ΔP) d across the test section length, between the two points located 1.2 m apart. 2( P) d Dh f (8) 2 4 ρ L V a f Figure 3 and Fig. 4 shows the values of Nusselt number, and Nusselt number ratio for discrete inclined ribs respectively. It is shown in the figures that the Nusselt number increases as Reynolds number increases and maximum heat transfer enhancement is about 4.1 times that of smooth duct. The increased turbulence at higher Reynolds numbers produces much more increase in heat transfer for ribbed duct as compared to increase in heat transfer for smooth duct. It is expected that the flow travels along the ribs from side wall and generate secondary flows and the swirling motion created by the secondary flow helped to generate a high overall average heat transfer coefficient. 400.0 350.0 300.0 250.0 200.0 150.0 100.0 5.0 4.0 3.0 2.0 50.0 0.0 e/dh=0.047 e/dh=0.060 e/dh=0.074 e/dh=0.087 e/dh=0.10 Fig. 3. Nusselt number as a function of Reynolds number for different values of e/d h e/dh=0.047 e/dh=0.060 e/dh=0.074 e/dh=0.087 e/dh=0.10 The thermo-hydraulic performance can be calculated by η=[(nu r/nu o)/(f r/f o) 1/3 ] (9) From the analysis of the uncertainties in the measurement by various instruments [Holman, 2004, Bhatti and Shah, 1987], the maximum uncertainties in the calculated values of various parameters are within ±10%. 1.0 Fig 4. Variation of Nusselt number ratio with Reynolds for different values of e/d h The effect of relative roughness height e/d h on Nusselt number is depicted in Figures 3 and 5. It can be observed that the increase in relative roughness height results in a decrease in heat transfer coefficient for the 226 International Journal of Thermal Technologies, Vol.7, No.4 (Dec 2017)

Friction factor (f r ) Friction factor (f r ) Nusselt Number (Nu r ) Friction factor Ratio (f r /f o ) Aditi Neekhara et al range of parameters investigated in the study. The augmentations are found to decrease with increase in the rib height. This may be due to the reason that with an increase in the rib height, the effect of inclination of the rib is not distinctly observed. Hence, it acts as a discrete transverse rib resulting in lower augmentations. The maximum enhancement in Nusselt number is observed for e/d h= 0.060 which is about 4.1 times that of smooth duct. 400.0 350.0 300.0 250.0 200.0 150.0 100.0 50.0 0.0 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11 Relative Roughness Height (e/d h ) Fig.5 Nusselt number as a function of e/d h Ratio for different Reynolds number Figure 6 and Fig. 7 shows the effect of Reynold number on friction factor and friction factor ratio for Inclined ribs with a gap respectively. In general, friction factor decreases with an increase of Reynolds number as expected. However, the values of friction factor are distinctly different as compared to those obtained for smooth plate due to distinct change in the fluid flow characteristics as a result of roughness that causes flow separation, reattachment and the generation of secondary flows. 0.080 0.070 0.060 0.050 0.040 0.030 0.020 0.010 Re=5000 Re=20000 Re=30000 Re=40000 e/dh=0.047 e/dh=0.060 e/dh=0.074 e/dh=0.087 e/dh=0.10 The maximum enhancement in friction factor was found to be 7.4 times that of smooth duct for e/d h= 0.060. Fig. 8 shows that by increasing the relative roughness height friction factor decreases. It is also seen that the rate of decrease of Nusselt number is lower than that of the friction factor. 11.0 10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0 2.0 1.0 0.0 Fig.7 Variation of Nusselt number ratio with Reynolds for different values of e/d h It has been found that artificial roughness results in considerable enhancement of heat transfer which is accompanied by a substantial increase in friction factor. Therefore, to select the best rib geometry, the heat transfer and friction characteristics should be considered simultaneously. A parameter that facilitates the simultaneous consideration of thermal and hydraulic performance known as thermo-hydraulic performance [Lewis, 1975] is evaluated for both the cases and plotted as in Figure 9 and 10. 0.080 0.070 0.060 0.050 0.040 0.030 0.020 0.010 0.000 e/dh=0.047 e/dh=0.060 e/dh=0.074 e/dh=0.087 e/dh=0.10 Re=5000 Re=20000 Re=30000 Re=40000 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0.11 Relative Roughness Height (e/d h ) 0.000 Fig.6 Nusselt number as a function of Reynolds number for different values of e/d h Fig.8 Friction factor as a function of e/d h Ratio for different Reynolds number It is observed from the figures that, in general, the thermo hydraulic performance improves with decreasing values of relative roughness height and 227 International Journal of Thermal Technologies, Vol.7, No.4 (Dec 2017)

Thermal Hydraulic Performance(η) Aditi Neekhara et al absolute maxima occurs with relative roughness height of 0.060 which is about 1.9 times that of smooth duct, in the range of values investigated in the present study. (Nu r /Nu o )/(f r /f o ) 1/3 2.6 2.4 2.2 2.0 1.8 1.6 1.4 1.2 1.0 e/dh=0.047 e/dh=0.06 e/dh=0.074 e/dh=0.087 e/dh=0.10 Fig.9 Variation of Thermo hydraulic performance with Reynolds number Reynolds for different values of e/d h (2) The Nusselt number enhancement decreases when the Reynolds number increases. The friction factor ratio is found to increases as Reynolds number increases and becomes constant at high Reynolds numbers. (3) It was observed that the rate of increase of Nusselt number with an increase in Reynolds number is lower than the rate of increase of friction factor. (4) The relative roughness height plays an important role for desirable fluid flow characteristics. The maximum value of Nusselt number is obtained for relative roughness height of 0.060. Nusselt number ratio at this relative roughness height was 4.1 times that of smooth duct for the range of parameters investigated due to stronger and optimum secondary flow. (5) The maximum enhancement in Nusselt number and friction factor values compared to smooth duct are of the order of 4.1 and 7.4 respectively. (6) The thermal performance decreases when the Reynolds number increases. The discrete inclined rib with relative roughness height of 0.060 gives the highest thermal hydraulic performance. References Conclusions Fig.10 Variation of Thermo hydraulic performance with e/d h for different values of Reynolds number The following conclusions can be drawn from the present work: (1) In general, Nusselt number increases and friction factor decreases with an increase of Reynolds number. Nusselt number and friction factor are significantly higher as compared to those obtained for smooth duct. This is due to the distinct change in the fluid flow characteristics as a result of discrete inclined ribs that causes flow separations, reattachments and the generation of secondary flows. J. C. Han, S. Dutta, and S. V. Ekkad, (2001), Gas Turbine Heat Transfer and Cooling Technology, Taylor & Francis, Inc., New York. P.R. Chandra, C.R. Alexander, (2003), J.C. Han, Heat transfer and friction behavior in rectangular channels with varying number of ribbed walls, International Journal of Heat and Mass Transfer, 46, 481 495. G. Rau, M. Cakan, D. Moeller, T. Arts, (1998), The effect of periodic ribs on the local aerodynamic and heat transfer performance of a straight cooling channel, Trans. of ASME, Journal of Turbomachinery, 120, 368 375. T. M. Liou, J. J. Hwang, (1992), Turbulent heat transfer augmentation and friction in periodically fully developed channel flows, Transactions of ASME, Journal of Heat Transfer, 114, 56 64. J.C. Han, Y.M. Zhang, C.P. Lee, (1991), Augmented heat transfer in square channels with parallel, crossed and V- shaped angled ribs, Transactions of ASME, Journal of Heat Transfer, 113, 590 596. J.C. Han, Y.M. Zhang, (1992), High performance heat transfer ducts with parallel broken and V-shaped broken ribs, International Journal of Heat and Mass Transfer, 35, 513 523. T.M. Liou, W.J. Shuy, Y.H. Tsao, (1998), Effect of rib height and pitch on the thermal performance of a passage disturbed by detached solid ribs, Transactions of ASME, Journal of Turbomachinery, 120, 581 588. R. Kiml, S. Mochizuki, A. Murata, (2001), Effects of rib arrangements on heat transfer and flow behavior in a rectangular rib roughened passage, Journal of heat transfer, 123, 675-681. J. C. Han and J. S. Park, (1988), Developing Heat Transfer in Rectangular Channels with Rib Turbulators, Int. Journal of Heat and Mass Transfer, 31, 183-195. 228 International Journal of Thermal Technologies, Vol.7, No.4 (Dec 2017)

Aditi Neekhara et al S. C. Lau, R. D. McMillin and J. C. Han, (1991), Heat Transfer characteristics of turbulent flow in a square channel with angled rib, Journal of Turbomachinery, 113, 367-374. T. Liou and D. Hwang, (1992), Turbulent Heat Transfer Augmentation and Friction in Periodic Fully Developed Channel Flows, J. of Heat Transfer, 114, 56-64. T.M. Liou, J.J. Hwang, (1993), Effect of ridge shapes on turbulent heat transfer and friction in a rectangular channel, Int. Journal of Heat and Mass Transfer, 36, 931 940. Taslim, M. E., Li, T., and Kercher, D. M., (1996) Experimental Heat Transfer and Friction in Channels Roughed with Angled, V-Shaped, and Discrete Ribs on Two Opposite Walls, Journal of Turbomachinery, Vol. 118 (1), 20-28,. Taslim, M. E., and Wadsworth, C. M.,(1997), An experimental investigation of rib surface-average Heat Transfer Coefficient in Rib-Roughened Square Passage, Journal of Turbo machinery, Vol. 119, 381-389. Taslim, M. E., and Korotky, G. J., (1998), Low-aspect-ratio rib heat transfer coefficient measurements in square channel, ASME Journal of Turbomachinery, Vol. 120, 831-838. Sri Harsha, V., Prabhu, S. V. and Vedula, R. P., (2009), Influence of rib height on the local heat transfer distribution and pressure drop in a square channel with 90o continuous and 60 0 V-broken ribs, Journal of Applied Thermal Engineering, Vol. 29, 2444-2459. S. K. Saha, (2010), Thermal and friction characteristics of turbulent flow through rectangular and square ducts with transverse ribs and wire-coil inserts, Exp. Therm. Fluid Sci., 34, 575 589. Thianpong. C., Chompookham. S. Skullong, Promvonge. P., (2009), Thermal characterization of turbulent flow in a channel with isosceles triangular ribs, International Communications in Heat and Mass Transfer Vol.37, 712-717. Casarsa, L., Cakan, M., Arts, T., (2002), Characterization of the Velocity and Heat Transfer Fields in an Internal Cooling Channel with High Blockage Ratio, ASME Paper No. GT2002-30207. Bailey, J.C, Bunker, R.S., (2003), Heat Transfer and Friction with Very High Blockage 45 deg Staggered Turbulators, ASME Paper No. GT2003-38611. S. Gupta, A. Chaube and P. Verma, (2013), Augmented Heat Transfer in Square ducts with Transverse and Inclined Ribs with and without a gap, International Journal of Current Engineering and Technology, 3(2), 688-694. A. Chaube, S. Gupta and P. Verma, (2014), Heat transfer and friction factor enhancement in a square channel having integral inclined discrete ribs on two opposite walls, Journal of Mechanical Science and Technology, 28 (5), 1927-1937. J. P. Holman, (2004), Experimental methods for engineers, Tata Mcgraw Hills, New Delhi. M. S. Bhatti, R. K. shah, (1987), Turbulent and transition flow convective heat transfer, Handbook of Single-phase Convective Heat Transfer, Wiley, New York. M. J. Lewis, (1975), Optimizing the thermo-hydraulic performance of rough surfaces, international Journal of Heat and Mass transfer, 18, 1243-1248. 229 International Journal of Thermal Technologies, Vol.7, No.4 (Dec 2017)