Consultancy Report Ref: 9383-R01
|
|
- Wendy Watts
- 6 years ago
- Views:
Transcription
1 Consultancy Report Ref: 9383-R01 Submitted to: Prepared by: Mr Tim Simmons The Woolley Shepherd Secret Meadow Weekmoor Milverton Taunton TA4 1QE John Fithyan Laboratory Manager Approved for issue by: Andy Varley (MIOA) Senior Consultant Sound absorption tests on a range of sheep s wool based materials February R01 ISVR Consulting, University of Southampton, Highfield Campus, Southampton SO17 1BJ, United Kingdom Tel: +44 (0) Fax: +44 (0) consultancy@isvr.co.uk Web:
2 Contents 1. Introduction Measurement Method Results Ambient Conditions Test results 6 Tables 1 to 6: Sound Absorption Coefficients Figures 1 to 3: Photographs of the test samples inside the reverberation chamber Appendix 1 Appendix 2 Instrumentation and Calibration Acoustic Environment ISVR Consulting Report 9383-R01 / February 2015 Contents
3 1. Introduction ISVR Consulting were engaged by The Woolley Shepherd, to undertake measurements on a range of products to establish their sound absorption coefficient (a S ) or equivalent sound absorption area (A obj m 2 ) depending on the product being tested. The sound absorption measurements were performed in the Reverberant Suite of the Rayleigh Laboratories of the ISVR, University of Southampton. The tests were carried out on the 10 th February The measurements were carried out in accordance with BS EN ISO 354: 2003 Acoustics Measurement of sound absorption in a reverberation room. When a sound source operates in an enclosed space, the level to which reverberant sound builds up, and the subsequent decay of reverberant sound when the source is stopped, are governed by the sound-absorbing characteristics of the boundary surfaces, the air filling the space, and objects within the space. In general, the fraction of the incident sound power absorbed at a surface depends upon the angle of incidence. In order to relate the reverberation time of an auditorium, office, workshop, etc, to the noise reduction that would be effected by an absorbing treatment, knowledge of the sound-absorbing characteristics of the surfaces, usually in the form of a suitable average over all angles of incidence, is required. Since the distribution of sound waves in typical enclosures includes a wide and largely unpredictable range of angles, a uniform distribution is taken as the basic condition for the purposes of standardization. If, in addition, the sound intensity is independent of the location within the space, the sound distribution is called a diffuse sound field, and the sounds reaching a room surface are said to be at random incidence. The sound field in a properly designed reverberation room closely approximates a diffuse field. Hence, sound absorption measured in a reverberation room closely approximates the sound absorption that would be measured under the basic conditions assumed for standardization. ISVR Consulting Report 9383-R01 / February 2015 Page 3 of 20
4 BS EN ISO 354: 2003 Acoustics Measurement of sound absorption in a reverberation room specifies a method of measuring the sound absorption coefficient of acoustical materials used as wall or ceiling treatments, or the equivalent sound absorption area of objects, such as furniture, persons or space absorbers, in a reverberation room. The materials tested were described as follows: Standard wall panel Limpets Clouds The standard wall panels are rectangular panels designed to be mounted onto walls. They can be used individually or combined to cover larger areas of wall. The limpets are a bit like a scalloped rectangle and are designed to be fitted flush onto ceilings. They would normally be installed individually but one ceiling might have multiple limpets fitted. The clouds are similar to the limpets but they are designed to hang from ceilings. The materials were tested as either individual (discrete) absorbers or as plane absorbers depending on their application. The results obtained can be used for comparison purposes and for design calculation with respect to room acoustics and noise control. ISVR Consulting Report 9383-R01 / February 2015 Page 4 of 20
5 2. Measurement Method The averaged reverberation rimes (RT 60 ) in 1/3 octave bands were determined for the empty chamber in the frequency range 100 Hz to 5000 Hz, as described in the standard, using an interrupted broad band noise. Thirty two decays were measured, (eight microphone combinations at each of four sound source locations). The sample of absorbent material was introduced into the chamber and either laid out on the floor or hung from the ceiling in accordance with the guidelines given in the standard. The test arrangement was chosen depending on whether the sample was a discrete absorber or a plane absorber. In the case of the plane absorbers the edges of the sample were covered with metal plate to prevent the edges from absorbing any of the sound waves. Once the sample was positioned in the chamber, the averaged reverberation time spectrum was determined as before. The absorption in the chamber was calculated for the sample and the increase in absorption due to the absorbent material relative to the empty chamber, was found. For the plane absorbers the coefficient of absorption (a S ) in each 1/3 octave band was calculated. The results are shown as a value between 0 and 1 where 1 signifies total absorption and 0 signifies no absorption. NB. In practice the test method can give values greater than 1 which can be confusing. Where a value of greater than 1 is given for a plane absorber it has been caused by edge effects of the test sample. For the discrete absorbers the equivalent sound absorption area (A obj m 2 ) in each 1/3 octave band was calculated. The sound absorption property of discrete objects is quantified by the equivalent sound absorption area expressed as m 2 per object. This is the area of a 100% fictive absorbing surface which would absorb the same amount of sound as the object in question. ISVR Consulting Report 9383-R01 / February 2015 Page 5 of 20
6 3. Results 3.1 Ambient Conditions Barometric pressure kpa Temperature 15.0 C Relative Humidity 44 % 3.2 Test results The results in the tables below are given as either the coefficient of absorption (a S ) or as the equivalent sound absorption area (A obj m 2 ) depending on the type of sample being tested. In the case of the plane absorbers where the results are given as the coefficient of absorption (a S ), BS EN ISO can be used to express the spectrum of results as a sound absorption class. The classes range from A to E where A is the top class. The standard is not applicable to single items, such as the limpets and clouds measured during these tests. NB. There are other standards, namely ASTM C a that can be used to express the sound absorption test spectrum as a single number. ASTM C423 uses the term Noise Reduction Coefficient (NRC) although this is being replaced by Sound Absorption Average (SAA). Both the NRC and SAA terms have values between 0 and 1 where 1 indicates total absorption. ASTM C423 test procedures should be used when calculating the NRC or SAA value. In this report we have used BS EN ISO 354 to determine the sound absorption coefficient. The methods in the two standards differ slightly. However for indication purposes I have used the BS EN ISO 354 values to calculate an NRC and SAA value for the materials we tested. Table 1 shows the results with 20 individual wall panels butted together to form a large rectangle. The outer edges of the rectangle were covered to prevent them absorbing more sound. ISVR Consulting Report 9383-R01 / February 2015 Page 6 of 20
7 Table 2 shows the results with 20 individual wall panels butted together to form a large rectangle. The outer edges of the rectangle were left uncovered and therefore absorbed more sound. Table 3 shows the results when the 20 wall panels were tested as discrete absorbers. The results are given as the equivalent sound absorption area (A obj m 2 ). Table 4 shows the results with 25 individual limpets butted together to form a large sample. The outer edges of the sample were left uncovered and therefore absorbed more sound. Table 5 shows the results when the 25 limpets were tested as discrete absorbers. The results are given as the equivalent sound absorption area (A obj m 2 ). Table 6 shows the results when the 8 clouds were tested as discrete absorbers. The results are given as the equivalent sound absorption area (A obj m 2 ). Figures 1 to 3 show photographs of the samples under test. ISVR Consulting Report 9383-R01 / February 2015 Page 7 of 20
8 Airborne sound absorption measured in a reverberation chamber. BS EN ISO 354:2003 Customer: Woolly Shepherd Construction tested Standard Wall Panel All sample panels butted together. Edges covered Frequency Absorption Hz a s Sound Absorption Coefficient a s Sound absorption coefficient BS EN ISO Sound absorption class = A Frequency, Hz Test Standard: BS EN ISO 354 Project No: 9383 University of Southampton Tested by: J.Fithyan Highfield, Southampton Test date: 27/01/2015 Using the ISO 354 test data above to calculate the ASTM C a descriptors, which is not strictly correct, you would get these values: NRC 0.95 SAA 0.93 Table 1: Standard wall panels butted together with outer edges covered ISVR Consulting Report 9383-R01 / February 2015 Page 8 of 20
9 Airborne sound absorption measured in a reverberation chamber. BS EN ISO 354:2003 Customer: Woolly Shepherd Construction tested Standard Wall Panel All sample panels butted together. Edges left uncovered Frequency Absorption Hz a s Sound Absorption Coefficient a s Sound absorption coefficient BS EN ISO Sound absorption class = A Frequency, Hz Test Standard: BS EN ISO 354 Project No: 9383 University of Southampton Tested by: J.Fithyan Highfield, Southampton Test date: 27/01/2015 Using the ISO 354 test data above to calculate the ASTM C a descriptors, which is not strictly correct, you would get these values: NRC 0.95 SAA 0.97 Table 2: Standard wall panels butted together with outer edges left uncovered ISVR Consulting Report 9383-R01 / February 2015 Page 9 of 20
10 Airborne sound absorption measured in a reverberation chamber. BS EN ISO 354:2003 Customer: Woolly Shepherd Construction tested Standard Wall Panel All sample panels moved apart. Edges left uncovered Frequency Absorption Hz A obj m Equivalent sound absorption per wall panel A obj m 2 Sound absorption coefficient Frequency, Hz Test Standard: BS EN ISO 354 Project No: 9383 University of Southampton Tested by: J.Fithyan Highfield, Southampton Test date: 27/01/2015 Table 3: Twenty individual standard wall panels tested as discrete absorbers ISVR Consulting Report 9383-R01 / February 2015 Page 10 of 20
11 Airborne sound absorption measured in a reverberation chamber. BS EN ISO 354:2003 Customer: Woolly Shepherd Construction tested Limpets All samples butted together. Edges left uncovered Frequency Absorption Hz a s Sound Absorption Coefficient a s Sound absorption coefficient BS EN ISO Sound absorption class = A Frequency, Hz Test Standard: BS EN ISO 354 Project No: 9383 University of Southampton Tested by: J.Fithyan Highfield, Southampton Test date: 27/01/2015 Using the ISO 354 test data above to calculate the ASTM C a descriptors, which is not strictly correct, you would get these values: NRC 1.00 SAA 1.00 Table 4: Limpets butted together with outer edges left uncovered ISVR Consulting Report 9383-R01 / February 2015 Page 11 of 20
12 Airborne sound absorption measured in a reverberation chamber. BS EN ISO 354:2003 Customer: Woolly Shepherd Construction tested Limpets All samples moved apart. Edges left uncovered Frequency Absorption Hz A obj m Equivalent sound absorption per limpet A obj m 2 Sound absorption coefficient Frequency, Hz Test Standard: BS EN ISO 354 Project No: 9383 University of Southampton Tested by: J.Fithyan Highfield, Southampton Test date: 27/01/2015 Table 5: Twenty-five individual limpets tested as discrete absorbers ISVR Consulting Report 9383-R01 / February 2015 Page 12 of 20
13 Airborne sound absorption measured in a reverberation chamber. BS EN ISO 354:2003 Customer: Woolly Shepherd Construction tested Clouds Frequency Absorption Hz A obj m Equivalent sound absorption per cloud A obj m 2 Sound absorption coefficient Frequency, Hz Test Standard: BS EN ISO 354 Project No: 9383 University of Southampton Tested by: J.Fithyan Highfield, Southampton Test date: 27/01/2015 Table 6: Eight individual clouds tested as discrete absorbers ISVR Consulting Report 9383-R01 / February 2015 Page 13 of 20
14 Figure 1: Standard wall panels ISVR Consulting Report 9383-R01 / February 2015 Page 14 of 20
15 Figure 2: Limpets ISVR Consulting Report 9383-R01 / February 2015 Page 15 of 20
16 Figure 3: Clouds ISVR Consulting Report 9383-R01 / February 2015 Page 16 of 20
17 Appendix 1: Instrumentation and Calibration 1.1 Measuring Equipment Noise Generation Instrument Manufacturer Type Ser No Cal Due Amplifier Cambridge Audio A1 V Not required Loudspeaker Not required Noise Measurement Instrument Manufacturer Type Ser No Cal Due Microphone Brüel & Kjær August 15 Microphone Brüel & Kjær August 15 Microphone Brüel & Kjær August 15 Microphone Brüel & Kjær August 15 Microphone Brüel & Kjær August 15 Microphone Brüel & Kjær August 15 Pre-amplifier Brüel & Kjær September 15 Pre-amplifier Brüel & Kjær September 15 Pre-amplifier Brüel & Kjær September 15 Pre-amplifier Brüel & Kjær September 15 Pre-amplifier Brüel & Kjær September 15 Pre-amplifier Brüel & Kjær September 15 Freq Analyser Brüel & Kjær 3560C October 15 Freq Analyser Brüel & Kjær 3560B October 15 Mic Calibrator Brüel & Kjær September System Calibration The noise measuring system was calibrated by applying the microphone calibrator (type 4231) to the transducer and adjusting the analyzer to the reference level at the beginning of the measurement session. The level was also checked at the end of the session to ensure that no drift or fault had occurred. The above equipment is calibrated against the transfer standards below. ISVR Consulting Report 9383-R01 / February 2015 Page 17 of 20
18 1.3 Traceability Microphones and Calibrators Microphones and Calibrators ISVR Consulting hold two transfer standard Microphones, type 4145, serial numbers and The most recent calibration was carried out by Campbell Associates. This is fully documented in Certificates and 17841, dated 22 nd January A transfer standard Pistonphone, type 4220, serial number and a transfer standard calibrator, type 4231, serial number are also held. These were calibrated by Campbell Associates and are documented in certificate numbers and 17842, dated 22 nd January Additional Instrumentation A Digital Voltmeter (Fluke type 8050A) and a Frequency Counter (Marconi type 2430A) are used with these Transfer Standards to calibrate the above equipment. Both instruments were calibrated by Southern Calibration Laboratories and carry certificates numbered and respectively and both are dated 25th November The instrumentation complies with the requirements for a type 1 instrument, as specified in BS EN 61672:2003, BS EN 60942:2003 and BS EN IEC 61260:1996. The Standards are traceable to the National Physical Laboratory, Teddington, England. ISVR Consulting Report 9383-R01 / February 2015 Page 18 of 20
19 Appendix 2: Acoustic Environment 2.1 Large Reverberation Chamber Construction The chamber is constructed of reinforced concrete and is separated from the foundations and neighbouring walls by rubber vibration isolators. It is designed with an inclined ceiling and non-parallel walls to ensure a uniform distribution (with frequency) of the normal acoustic modes of the room Dimensions Mean edge lengths 9.15 m 6.25 m 6.10 m - height Volume 348 m 3 Surface Area 302 m Walls and Ceiling All inside surfaces of the chamber are finished with a hard gloss paint to give a high reflection coefficient. The walls are 305 mm thick, and the ceiling, which is 460 mm thick, includes two removable sections (1.75 m x 0.86 m) which provide access for a chain hoist capable of carrying loads up to 2000 Kg, and an entry for a 4000 Watt siren driven horn. Connections to the equipment in the chamber may be made via any of five cable ports in the walls. A glazed window (305 mm x 305 mm) permits visual observation from the control area Diffusers Ten diffusers are hug from the ceiling of the chamber. These diffusing elements are plywood sheets painted with gloss paint so that they have a low sound absorption. The diffusers, which are of varying sizes are orientated at random and positioned at different heights within the chamber. The total surface area of the diffusers is 43.2 m 2. ISVR Consulting Report 9383-R01 / February 2015 Page 19 of 20
20 2.1.5 Floor Area The floor is 305 mm thick and has a steel vibration isolated pad (2.1 m x 3.6 m) set into it. This pad may be used for mounting test rigs or vibrators without structural vibrations being transmitted to the chamber Doors One set of double doors connects the chamber and the corridor, another set opens into the small reverberation chamber and incorporates removable panels (1.07 m x 1.07 m) for transmission loss measurements. The doorway (2.4 m x 2.0 m) may be used for testing larger panels. The doors (2.56 m x 2.26 m x 130 mm thick) are a sandwich construction of wood wool, wood and steel, and have an average transmission loss in excess of 50 db Ventilation and Lighting At each corner of the floor there is an air inlet vent, and there are four outlet vents situated high up on one wall. With all vents open the air is changed at a rate of 100 m 3 per minute. When not required the vents are covered by steel plates and these have diagonal stiffeners to reduce panel vibrations. The chamber is lit by six sodium discharge lights mounted on the wall at 3 m above the floor. ISVR Consulting Report 9383-R01 / February 2015 Page 20 of 20
MEASUREMENTS OF SOUND ABSORPTION TIMBERCRETE
A.B.N. 73 107 291 494 C O N S U L T I N G A C O U S T I C A L E N G I N E E R S MEASUREMENTS OF SOUND ABSORPTION TIMBERCRETE 100 mm ANCIENT STONE BRICK REPORT NUMBER: 4546-2 PREPARED FOR: Timbercrete Pty
More informationREPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 24MM TESTED WITH NO AIR GAP MEASURED IN A REVERBERATION ROOM.
RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON
More informationREPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 7MM TESTED WITH A 20MM AIR GAP IN A REVERBERATION ROOM.
REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 7MM TESTED WITH A 20MM AIR GAP IN A REVERBERATION ROOM. Testing Procedure: AS ISO 354-2006 Testing Laboratory: Client:
More informationLABORATORY MEASUREMENTS OF THE SOUND ABSORPTION COEFFICIENTS OF OSCAR EVO-PANELS
Report No. L/3237 Page 1 of 8 for Oscar Acoustics Michaels Lane Ash Kent TN15 7HT Dated: 24 July 2012 LABORATORY MEASUREMENTS OF THE SOUND ABSORPTION COEFFICIENTS OF OSCAR EVO-PANELS Report Author: M Sawyer
More informationTesting Procedure: AS ISO
RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON
More informationLABORATORY MEASUREMENTS OF THE SOUND ABSORPTION OF CLASSICTONE 700 ASTM C Type E Mounting. Test Number 2
LABORATORY MEASUREMENTS OF THE SOUND ABSORPTION OF CLASSICTONE 700 ASTM C423-01 Type E Mounting Date of Test: 27/11/2009 Report Author: Mark Simms Test Number 2 Report Number 1644 Report Number 1644 Page
More informationA L I O N Technical Center. Test Report
FOR: Beachwood, OH Sound Absorption CONDUCTED: 2017-10-30 Page 1 of 7 ON: Absorption Sheets TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National Institute
More informationDevelopment of a small-scale reverberation room
Proceedings of ACOUSTICS 2016 9-11 November 2016, Brisbane, Australia Development of a small-scale reverberation room Alexander Rasa Noise Control Research & Development, Pyrotek Pty Ltd, Sydney, Australia
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Atlanta, GA Sound Absorption CONDUCTED: 2016-10-14 Page 1 of 8 ON: D-GIK Panels TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National Institute of
More informationTechnical Report. Project. The Laboratory Determination of The Random Incidence sound Absorption Coefficient of VertiQ Panels.
Technical Report Ref Number C/21387/R01a Date 06 April 2011 Project The Laboratory Determination of The Random Incidence sound Absorption Coefficient of VertiQ Panels Prepared for Rockfon Rockwool A/S
More informationDELTA Test Report. DANAK TEST Reg. no Measurement of Sound Absorption Coefficient for Kvadrat Soft Cells Wall Panel Type Time
We help ideas meet the real world DELTA Test Report DANAK TEST Reg. no. 100 Measurement of Sound Absorption Coefficient for Kvadrat Soft Cells Wall Panel Type Time Client: Kvadrat Soft Cells A/S Page 1
More informationDELTA Test Report. Measurement of Sound Absorption for AqFlex ON, one Sample as a discrete Object. Performed for Flex Acoustics
DELTA Test Report TEST Reg. no. 100 Measurement of Sound Absorption for AqFlex ON, one Sample as a discrete Object Performed for Flex Acoustics Project no.: T202611 Page 1 of 7 21 January 2013 DELTA Venlighedsvej
More informationA L I O N Technical Center. Test Report. Port Coquitlam, British Columbia, Canada
FOR: Port Coquitlam, British Columbia, Canada Sound Absorption CONDUCTED: 2018-03-19 Page 1 of 7 ON: Model F202-2448 - Hercules absorption panels TEST METHOD Riverbank Acoustical Laboratories is accredited
More informationLABORATORY MEASUREMENTS OF THE REDUCTION OF TRANSMITTED IMPACT NOISE PANETTI OVERLAID BY CONCRETE FLOORING
Report No. L/3194 Page 1 of 8 for EA Mimarlik Insaat Teknolojileri San.ve. Tic.Ltd.Sti 1420/3 Sokak NO. 22 Kizilkanat Silesi D Blok D.12 Alsancak Izmir Turkey Dated: 18 July 2011 LABORATORY MEASUREMENTS
More informationMeasurement of Acoustic Properties of light weight concrete SL-Deck
DELTA Test Report TEST Reg. no. 100 Measurement of Acoustic Properties of light weight concrete SL-Deck Performed for Abeo A/S Project no.: I100486 Page 1 of 25 30 June 2014 DELTA Venlighedsvej 4 2970
More informationISO 354 INTERNATIONAL STANDARD. Acoustics Measurement of sound absorption in a reverberation room
INTERNATIONAL STANDARD ISO 354 Second edition 2003-05-15 Acoustics Measurement of sound absorption in a reverberation room Acoustique Mesurage de l'absorption acoustique en salle réverbérante Reference
More informationMeasurement of sound absorption coefficient for Fraster felt SpaceCover
DELTA Test Report TEST Reg. no. 100 Measurement of sound absorption coefficient for Fraster felt SpaceCover Performed for Fraster ApS Project no.: I100645 Page 1 of 9 27 November 2014 DELTA Venlighedsvej
More informationTest Report. RI Acoustic Lab. Measurement of Sound Absorption Coefficient for RockDelta NoiStop Noise Barrier. 20 Feb. 07
Test Report RI Acoustic Lab Measurement of Sound Absorption Coefficient for RockDelta NoiStop Noise Barrier 20 Feb. 07 Title Measurement of Sound Absorption Coefficient for RockDelta NoiStop Noise Barrier
More informationTHE ACOUSTIC IMPEDANCE MEASUREMNET SYSTEM USING TWO MICROPHONES
P-7 THE ACOUSTIC IMPEDANCE MEASUREMNET SYSTEM USING TWO MICROPHONES RYU, YUNSEON BRUEL & KJAER SOUND & VIBRATION MEASUREMENT A/S SKODSBORGVEJ 307 NAERUM 2850 DENMARK TEL : +45 77 41 23 87 FAX : +45 77
More informationDELTA Test Report. Measurement of sound absorption coefficient for 15 mm Fraster felt Plus acoustic panels with mounting depth 45 mm
DELTA Test Report TEST Reg. no. 100 Measurement of sound absorption coefficient for 15 mm Fraster felt Plus acoustic panels with mounting depth 45 mm Performed for Fraster ApS DANAK 100/2275 Project no.:
More informationETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6986/ARL-SA6987 Revision 0 ARL
ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6986/-SA6987 Revision 0 Subject: Sound Absorption Test Date: 01 February 2017 Contents: on Sound Absorption Data, One-third Octave
More informationETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6266/ARL-SA6274 Revision 0 ARL
ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6266/-SA6274 Revision 0 Subject: Sound Absorption Test Date: 17 February 2015 Contents: on Sound Absorption Data, One-third Octave
More informationETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6712/ARL-SA6713 Revision 0 ARL
ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6712/-SA6713 Revision 0 Subject: Sound Absorption Test Date: 17 May 2016 Contents: on Sound Absorption Data, One-third Octave bands
More informationAcoustic response in non-diffuse rooms
Acoustic response in non-diffuse rooms Jack Harvie-Clark Apex Acoustics, Gateshead, United Kingdom. Nicholas Dobinson Apex Acoustics, Gateshead, United Kingdom. Richard Hinton Apex Acoustics, Gateshead,
More informationRIVERBANK ACOUSTICAL LABORATORIES
FOR: Indianapolis, IN. Sound Absorption CONDUCTED: 2015-10-06 Page 1 of 7 ON: LENRD Bass Trap TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National Institute
More informationLaboratory for Acoustics
Laboratory for Acoustics Determination of the sound absorption (reverberation room method) of mineral wool, type MW 35, manufacturer Knauf Insulation B.V. Report number A 3022-5E-RA-001 d.d. 22 maart 2016
More informationinter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE
Copyright SFA - InterNoise 2000 1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 7.2 LABORATORY MEASUREMENT
More informationLABORATORY MEASUREMENT OF SOUND ABSORPTION OF SONOGLASS SPRAY-ON TREATMENT IN THREE CONFIGURATIONS
LABORATORY MEASUREMENT OF SOUND ABSORPTION OF SONOGLASS SPRAY-ON TREATMENT IN THREE CONFIGURATIONS Prepared for: MONOGLASS INC. 922-1200 West 73rd Avenue Vancouver, BC, Canada V6P 6G5 Prepared by: THE
More informationROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT
ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON TEMPE, ROLLER SHADE FABRIC REPORT NUMBER I7375.01-113-11-R0 TEST DATE 08/14/18 ISSUE DATE 09/04/18
More informationAcoustic design of lightweight cabin walls for cruise ships
Acoustic design of lightweight cabin walls for cruise ships A. Treviso 1, M. G. Smith 1 1 ISVR Consulting, University of Southampton University Road, SO17 BJ1, Southampton, United Kingdom e-mail: mgs@isvr.soton.ac.uk
More informationLaboratory for Acoustics. Determination of the sound absorption (reverberation room method) of Airpanel, manufacturer Texdecor
Laboratory for Acoustics Determination of the sound absorption (reverberation room method) of Airpanel, manufacturer Texdecor Report number A 3151-2E-RA-001 d.d. June 1, 2017 Laboratory for Acoustics Determination
More informationTFI Report Sound Absorption Impact Sound Insulation
TFI Report 471194-01 Sound Absorption Impact Sound Insulation Customer egetaepper a/s Industrivej Nord 25 7400 Herning DENMARK Product textile floor covering This report includes 2 pages and 2 annex(es)
More informationETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6956 Revision 1 ARL
ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6956 Revision 1 Subject: Sound Absorption Test Date: 04 January 2017 Contents: on Sound Absorption Data, One-third Octave bands Sound
More informationTFI Report Sound Absorption Impact Sound Insulation
TFI Report 462257-01 Sound Absorption Impact Sound Insulation Customer Desso B.V. Taxandriaweg 15 5142 PA Waalwijk NETHERLANDS Product textile floor covering This report includes 2 pages and 2 annex(es)
More informationLaboratory for Acoustics. Determination of the sound absorption (reverberation room method) of curtains, manufacturer Vescom BV
Laboratory for Acoustics Determination of the sound absorption (reverberation room method) of curtains, manufacturer Vescom BV Report number A 3012-2E-RA-002 d.d. February 4, 2016 Laboratory for Acoustics
More informationCalcul des coefficients d'absorption alpha sabine
Calcul des coefficients d'absorption alpha sabine Selon Norme NFEN 20354 TEST n : 138G04-7 TYPE : Vinyl 340/360 g/m² DATE : 04 février 2005 SUPPORT : Echantillon collé sur plaque de BA13 DONNEES : Température
More informationTFI Report Sound Absorption Impact Sound Insulation
TFI Report 481380-01 Sound Absorption Impact Sound Insulation Customer NEWSPEC CARPET (NINGBO) CO. LTD Cevin Yindong South Road NO. 399 315100 Ningbo CHINA VR Product textile floor covering This report
More informationFabric Dazzle 6086 Manufacturer Carnegie Fabrics
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.de Dipl.-Ing. (FH) Dominik Reif Telephone +49(89)85602 3566 Dominik.Reif@mbbm.com
More informationUsing an ambisonic microphone for measurement of the diffuse state in a reverberant room
Proceedings of 20 th International Congress on Acoustics, ICA 2010 23-27 August 2010, Sydney, Australia Using an ambisonic microphone for measurement of the diffuse state in a reverberant room John Bassett
More informationREPORT N CR
Z Lab Srl Via Pisa, 5/7 37053 Cerea (VR) Italy Tel. +39 0442 410280 Fax +39 0442 418090 info@zeta-lab.it www.zeta-lab.it C.F./P.IVA 02984950788 Cap. Soc. 80.000 i.v. R.E.A. c/o C.C.I.A.A. Verona 376649
More informationRenolit stretch ceilings
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.de Dipl.-Ing. (FH) Eva Müller Telephone +49(89)85602 3206 Eva.Mueller@mbbm.com
More informationCurtain fabric type Ace Manufacturer Kvadrat A/S
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.com M. Eng. Philipp Meistring Telephone +49(89)85602 228 Philipp.Meistring@mbbm.com
More informationFabric REFLECTACOUSTIC
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.com Dipl.-Ing. (FH) Eva Müller Telephone +49(89)85602 3206 Eva.Mueller@mbbm.com
More informationTFI Report Sound Absorption Impact Sound Insulation
TFI Report 480781-01 Sound Absorption Impact Sound Insulation Customer egetaepper a/s Industrivej Nord 25 7400 Herning DENMARK Product textile floor covering This report includes 2 pages and 2 annex(es)
More informationPage 1 of 10 pages Appendix, 5 pages Report no.: P Glostrup, October 12th 2012 Project: Claimant:
TEST REPORT This Test Report may only be reproduced in full. The test results are valid for the tested object only. Fibertex Nonwovens A/S Laboratory measurements of sound absorption coefficient Page 1
More informationFabric Corsica. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M111250/16
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.de M. Eng. Philipp Meistring Telephone +49(89)85602 228 Philipp.Meistring@mbbm.com
More informationFabric ALEX. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/09
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.com Dipl.-Ing. (FH) Eva Müller Telephone +49(89)85602 3206 Eva.Mueller@mbbm.com
More informationFabric Sport. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/02
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Germany Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.de Dipl.-Ing. (FH) Eva Müller Telephone +49(89)85602 3206 Eva.Mueller@mbbm.com
More informationFabric STREAMER pro. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M111250/04
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.de M.Eng. Philipp Meistring Telephone +49(89)85602 228 Philipp.Meistring@mbbm.com
More informationRoller blind fabric PRIMACOUSTIC R
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.de Dipl.-Ing. (FH) Dominik Reif Telephone +49(89)85602 3566 Dominik.Reif@mbbm.com
More informationFabric VELOS STRATO. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/10
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.com Dipl.-Ing. (FH) Eva Müller Telephone +49(89)85602 3206 Eva.Mueller@mbbm.com
More informationReport. Laboratory for Acoustics
3 Report Member NLingenieurs ISO 9001 certified Laboratory for Acoustics Determination of the sound absorption (reverberation room method) of ceiling panels type Lithos, manufacturer Rockfon, Rockwool
More informationPRODUCT DATA. Sound Intensity Calibrator Type 3541-A. Uses and Features
PRODUCT DATA Sound Intensity Calibrator Type 3541-A Type 3541-A enables calibration of sound intensity measuring instruments by using a coupler designed especially for sound intensity calibrations. Intensity-probe
More informationFabric XPRESS + PU-foam Manufacturer Gabriel A/S
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.com Dipl.-Ing. (FH) Dominik Reif Telephone +49(89)85602 3566 Dominik.Reif@mbbm.com
More informationFabric Zetacoustic. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/07
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.de Dipl.-Ing. (FH) Eva Müller Telephone +49(89)85602 3206 Eva.Mueller@mbbm.com
More informationLaboratory for Acoustics. Determination of the sound insulation of sliding door constructions, manufactured by Metaflex
Laboratory for Acoustics Determination of the sound insulation of sliding door constructions, manufactured by Metaflex Report number A 2641-1E-RA-002 d.d. January 26, 2015 Laboratory for Acoustics Determination
More informationREPORT. Client. Test object. Date of testt. Results. Rönnåsgatan 5B Ulricehamn. (7 appendices) content of the
Riss sued by an Accreditedd Testing Laboratory Contact person Malin Lindgren Sustainable Builtt Environment +46 10 516 50 722 malin.lindgren@ @sp.se 2016-01-11 5P08641-A/Engg 1 (8)) Stellan Bygård Rönnåsgatan
More informationLaboratory for Acoustics
Laboratory for Acoustics Determination of the sound absorption (reverberation room method) of a wooden linear ceiling/wall system, manufacturer Derako International Report number AB 1079-1E-RA d.d. November
More informationFabric UDINE. Measurement of sound absorption according to EN ISO 354. Test Report No. M102794/32
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.de Dipl.-Ing. (FH) Dominik Reif Telephone +49(89)85602 3566 Dominik.Reif@mbbm.com
More informationFabric TWIST MELANGE Manufacturer Gabriel A/S
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.com Dipl.-Ing. (FH) Dominik Reif Telephone +49(89)85602 3566 Dominik.Reif@mbbm.com
More informationISO INTERNATIONAL STANDARD
INTERNATIONAL STANDARD ISO 140-6 Second edition 1998-08-15 Acoustics Measurement of sound insulation in buildings and of building elements Part 6: Laboratory measurements of impact sound insulation of
More informationFabric Medley Manufacturer Gabriel A/S
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.com Dipl.-Ing. (FH) Dominik Reif Telephone +49(89)85602 3566 Dominik.Reif@mbbm.com
More informationFabric Umbria III R. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/13
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.com Dipl.-Ing. (FH) Eva Müller Telephone +49(89)85602 3206 Eva.Mueller@mbbm.com
More informationEvaluation of standards for transmission loss tests
Evaluation of standards for transmission loss tests M. Cassidy, R. K Cooper, R. Gault and J. Wang Queen s University Belfast, School of Mechanical and Aerospace Engineering, Ashby Building, Stranmillis
More informationReport. P.O. Box 70 NL 5700 AB Deurne The Netherlands Report number: A E-RA Date: 12 februari 2014 TS/TS/JW/A E-RA
Report Member NLingenieurs ISO 9001 certified Laboratory for Acoustics Determination of the sound absorption (reverberation room method) of curtains type Athens and Chicago, manufacturer Vescom Reportnumber
More informationPaseo Recoletos, nº Madrid TEST REPORT
LGAI LGAI Technological Center, S.A. Campus de la UAB Apartado de Correos 18 E - 08193 BELLATERRA (Barcelona) T +34 93 567 20 00 F +34 93 567 20 01 www.applus.com 9/LE766 Bellaterra: June 5 th, 2012 File
More informationAn examination of some aspects of the use of ISO 140 Part 4 and 7 in field measurements.
Edinburgh, Scotland EURONOISE 00 October - An examination of some aspects of the use of ISO 0 Part and in field measurements. Philip R Dunbavin a Philip Dunbavin Acoustics Ltd (ANC) Keepers House, Deans
More informationR & D AKUSTIKA * SIA. Test Report of laboratory Sound Insulation measurements Nr. 569 / 2011 AL 8.4. CUSTOMER: AEROC AS (Estonia)
SIA * R & D AKUSTIKA * ============================================================================================= LATVIJAS REPUBLIKA, LV - 1067, R GA, KURZEMES PROSPEKTS 3, Re istr. Nr. : LV 010310045
More informationstylegreen Iceland Moss / Reindeer Moss of the company FlowerArt
Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.com Dipl.-Phys. Elmar Schröder Telephone +49(89)85602 145 Elmar.Schroeder@mbbm.com
More informationProduct Data. Brüel & Kjær B. Sound Intensity Calibrator Type 3541
Product Data Sound Intensity Calibrator Type 3541 USES: Sound intensity and particle velocity calibrations Sound pressure calibration Measurement of pressure-residual intensity index FEATURES: Intensity
More informationMAC Aura XB Acoustic Test Report
MAC Aura XB Acoustic Test Report 2017. Information subject to change without notice. HARMAN Professional and all affiliated companies disclaim liability for any injury, damage, direct or indirect loss,
More informationEUROVENT 8/12 SOUND TEST METHOD FOR DUCTED FAN COIL UNITS. FCP 2008 testing procedures FCP acoustical test method pag. 1
EUROVENT 8/12 SOUND TEST METHOD FOR DUCTED FAN COIL UNITS FCP 2008 testing procedures FCP acoustical test method pag. 1 CONTENTS 1 - PURPOSE... 3 2 - NORMATIVE REFERENCES... 3 3 - DEFINITIONS... 3 3.1
More informationThe information included in the following report presents the results of sound pressure and sound power testing.
ISO 7779:2010 Acoustics -- Measurement of airborne noise emitted by information technology and telecommunications equipment 1 of 14 DEVICES - solid panel case - window panel case Report Date: 06/25/2015
More informationAir distribution systems. Linear whirl outlet WL...
Air distribution systems Linear whirl outlet WL... DS 0 E 1.013 Preliminary remarks Mode of operation The linear whirl outlet generates turbulent mixing ventilation. It can be installed on or in a wall
More informationinter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE
Copyright SFA - InterNoise 2000 1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 1.1 DESIGN OF TERMINATING
More informationLaser scanning vibrometry measurements on a light weight building element
Laser scanning vibrometry measurements on a light weight building element N.B. Roozen, M. Rychtáriková, Katholieke Universiteit Leuven, Laboratory for Acoustics and Thermal Physics (ATF), Department of
More informationInvestigations on real-scale experiments for the measurement of the ISO scattering coefficient in the reverberation room
Investigations on real-scale experiments for the measurement of the scattering coefficient in the reverberation room 43.55.BR Lieven De Geetere, Gerrit Vermeir K.U.Leuven, Laboratory for Building Physics
More informationReport. Laboratory for Acoustics Determination of the sound absorption (reverberation room method) of different wired mats, manufacturer Rockwool
Report Member ONRI ISO-9001: 2000 certified Laboratory for Acoustics Determination of the sound absorption (reverberation room method) of different wired mats, manufacturer Rockwool Reportnumber A 1978-1E-RA
More information1. Introduction. 2. ISO 3745 and ISO standard comparison
Acoustic performance analysis of anechoic chambers based on ISO 3745 and ISO 26101: standards comparison and performance analysis of the anechoic chamber at the University of Split Mladen Russo Luka Kraljević
More informationSound power level measurement in diffuse field for not movable sources or emitting prominent discrete tones
CFA 2018 - Le Havre Sound power level measurement in diffuse field for not movable sources or emitting prominent discrete tones F. Bessaca et P. Cellardb a CETIAT, Domaine Scientifique de la Doua, 25,
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 128 133 6th International Building Physics Conference, IBPC 2015 Sound insulation of building elements at low frequency:
More informationSIMPLE APPLICATION OF STI-METHOD IN PREDICTING SPEECH TRANSMISSION IN CLASSROOMS. Jukka Keränen, Petra Larm, Valtteri Hongisto
SIMPLE APPLICATION OF STI-METHOD IN PREDICTING SPEECH TRANSMISSION IN CLASSROOMS Jukka Keränen, Petra Larm, Valtteri Hongisto Finnish Institute of Occupational Health Laboratory of Ventilation and Acoustics
More informationCERTIFICATE OF CALIBRATION
Page 1 of 10 CALIBRATION OF Sound Level Meter: Brüel & Kjær Type 3050-A-040 No: 3050-100751 Id: - Microphone: Brüel & Kjær Type 4189 No: 2621142 Preamplifier: Brüel & Kjær Type 2669 No: 2679073 Supplied
More informationSome issues in measurement of the random-incidence scattering coefficients in a reverberation room
Proceedings of ACOUSTICS 6 20-22 November 6, Christchurch, New Zealand Some issues in measurement of the random-incidence scattering coefficients in a reverberation room Young-Ji Choi, Dae-Up Jeong and
More informationThe diagram below. to the by the. outlet into. calculation. Since TRANSMISSION VIA STRUCTURE. Vibration Via Supports Duct Breakout
NOISE CONTROL IN VENTILATING SYSTEMS INTRODUCTION The diagram below shows the various noise sources and transmission paths of plant rooms and ventilation systems. For the ventilation system this can be
More informationHELLA. Linear slot diffuser. Ordering codes. HELLA - Linear diffuser. Linear Diffusers 1 / 18. Example of the ordering code HELLA B-0-0-AN
Linear Diffusers / 8 HELLA Linear slot diffuser Ordering codes HELLA - Linear diffuser HELLA - Number of slots... Diffuser length L (mm) ) Increment mm... Deflector colour Damper Diffuser construction
More informationYalıtım Kontrol Koruma. Insulation Control Protection
Yalıtım Kontrol Koruma Insulation Control Protection Tunex 17/8 ISO 10140-3 Darbe Sesi İndirgeme (Impact Sound Insulation) Test Raporu page 1 of 15 Customer : DKM INSAAT TAAHHUT VE DANISMANLIK PAZARLAMA
More informationACOUSTICS 1.01 Pantone 144 U & Pantone 5405 U
ACOUSTICS 1.01 CONTENT 1. INTRODUCTION 3 2. WHAT IS SOUND? 4 2.1 Sound 4 2.2 Sound Pressure 5 2.3 The Decibel Scale 5 2.4 Sound Pressure Increase For Muliple Sound Sources 6 2.5 Frequency 7 2.6 Wavelength
More informationseries KAT Acoustic air transfer units
series Acoustic air transfer units www.koolair.com 1 Acoustic Air Transfer Unit CONTENTS Acoustic Air Transfer Unit 2 Dimensions 3 Technical Data 5 Product Codes 7 2 Acoustic Air Transfer Unit - Description
More informationEngineering Noise Control
Engineering Noise Control Theory and practice Second edition David A. Bies and Colin H. Hansen Department of Mechanical Engineering University of Adelaide South Australia E & FN SPON An Imprint of Chapman
More informationCERTIFICATE OF CALIBRATION
Page 1 of 10 CALIBRATION OF Sound Level Meter: Brüel & Kjær Type 3050-A-040 No: 3050-100751 Id: - Microphone: Brüel & Kjær Type 4189 No: 2621142 Preamplifier: Brüel & Kjær Type 2669 No: 2803547 Supplied
More informationPostprint.
http://www.diva-portal.org Postprint This is the accepted version of a paper presented at WCTE, World Conference on timber Engineering, August 22-25, 2016, Vienna, Austria. Citation for the original published
More informationAcoustic test report AU01+N01
Customer Industriezeile 35 4021 inz Tel.: +43 732 7664-3105 Fax: +43 732 7664-113 Acoustic test report 110379-AU01+N01 Favorit 5000 IM 04 Select The test result refer exclusively to the model tested. This
More informationByggakustik Mätning av ljudabsorption i efterklangsrum (ISO 354:2003)
SVENSK STANDARD SS-EN ISO 354 Fastställd 2003-06-18 Utgåva 1 Byggakustik Mätning av ljudabsorption i efterklangsrum (ISO 354:2003) Acoustics Measurement of sound absorption in a reverberation room (ISO
More informationThe practical application of G and C 50 in classrooms
The practical application of G and C 50 in classrooms Jack Harvie-Clark 1, Nicholas Dobinson 2 1 Apex Acoustics Ltd 2 Apex Acoustics Ltd ABSTRACT Reverberation time remains the primary indicator of room
More information1 BAKER HOUSE DINING: LIGHTING DIAGNOSTIC
Shauna Jin + Caitlin Mueller 4.401: Lighting and Acoustics Analyses 27 April 2006 1 BAKER HOUSE DINING: LIGHTING DIAGNOSTIC 1.1 Sunlight Penetration The Baker House Dining room is exposed mostly to southern
More informationUncertainties associated with the use of a sound level meter
NPL REPORT DQL-AC 002 Uncertainties associated with the use of a sound level meter Richard Payne April 2004 April 2004 ABSTRACT Uncertainties associated with the use of a sound level meter Richard Payne
More informationPart 2: Methods for special reverberation test rooms
Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 3743-2 Second edition 2018-02 Acoustics Determination of sound power levels of noise sources using sound pressure Engineering methods for small,
More informationCIRCO. Sound-attenuating transfer unit QUICK FACTS
Sound-attenuating transfer unit QUICK FACTS Supplied in pairs For the transfer of air through a wall Fits in a circular cut opening Simple to install Mounting frame integrated into the transfer diffuser
More informationStudy of Wenger Audience Seating Chair Absorption. Ron Freiheit
Study of Wenger Audience Seating Chair Absorption Ron Freiheit January 22, 2002 Study of Wenger Audience Seating Chair Absorption Purpose The purpose of this project was to evaluate the acoustical performance
More information