CHAPTER 3 TUNING METHODS OF CONTROLLER

Size: px
Start display at page:

Download "CHAPTER 3 TUNING METHODS OF CONTROLLER"

Transcription

1 57 CHAPTER 3 TUNING METHODS OF CONTROLLER 3.1 INTRODUCTION This chapter deals with a simple method of designing PI and PID controllers for first order plus time delay with integrator systems (FOPTDI). Controllers have been designed using various tuning methods like equating coefficient method (EQ), direct synthesis method (DS), model reference control (MRC) method and dual loop control (DLC) method. In order to demonstrate the effectiveness of the developed methods to tune PI and PID controller for setpoint tracking and disturbance rejection, the IMC and ZN tuning methodologies are chosen for comparison. The performance of the controller under uncertainty in model parameters has been analyzed and its robustness is verified. 3.2 EQUATING COEFFICIENT METHOD System whose dynamics are slow with large time constant can be approximated as integrating systems. Integrating processes are frequently encountered in the process industries. The process would be non-minimumphase if it contains time delays and/or right-half-plane zeros. The design of controllers for such integrating processes is challenging and an interesting problem. Conventional PI and PID methods with unity feedback control structure have been developed by several authors (Lee et al 2003) have

2 58 proposed unity feedback control structure for the control of integrating processes with time delay. In this equating coefficient method, the closed loop transfer function of the given process along with the given controller is being found for the servo problem and the coefficients of the corresponding s, s 2, s 3 in the numerator and that in the denominator are equated to find the tuning parameters. Tuning parameters can be of single or more than one. In this work, tuning of both PI and PID controllers has been done. The equations for the controller settings are simple. More the tuning parameter, the complexity of the tuning is increased. Closed loop identification method is preferred over that of the open loop method since the former is insensitive to disturbances. Transfer function models are used for designing PI/ PID controllers. The methods for designing PID controllers for unstable FOPTD systems have been developed by DePaor and O Malley (1989), Ho and Xu (1998), optimization method by Cheng and Hwang (1998), Manoj and Chidambaram (2001) and synthesis method by and Jung et al (1999). An excellent review of the work reported on the design of PID controllers is given by Astrom and Hagglund (1995). Transfer function models are used for designing PI/PID controllers. In many of these methods, one or two adjustable parameters are used to calculate the PID settings but the design procedure is complicated. In this work, a simple method proposed by Sakthe Vivek and Chidambaram (2005) to design PI and PID controllers for both stable and unstable First Order Plus Time Delay(FOPTD) system have been developed for FOPTDI systems.

3 EQ- PI Controller The Equating Coefficient (EC) method developed to design PI controllers for FOPTD system is extended for FOPTDI systems. The equating coefficient method gives simple equations for the controller settings. This method is based on matching the coefficient of corresponding powers of s in the numerator and that in the denominator of the closed loop transfer function, since the objective of the controller is to make y/y r =1. Controllers are designed using single tuning parameter, and to improve the performance of the controller under uncertainty in model parameters, concept of two tuning parameters is used. The performance of the closed loop system is evaluated for both the original and the approximated model. The controllers are also tuned using IMC and ZN, and its performance has been compared by simulation. The following sets of linear algebraic equations are obtained for PI controller for FOPTDI system, (1-a)k1+ 0.5(1 +a )k2 = 0 (3.1) 0.5(1 +a )k 1+ (1 -a= )k2 a (3.2) derived: By solving the equations (3.1) and (3.2) the following equations are k 1 =k c k p t d (3.3) k 2 = æ k1 t 1 ö ç ètd ø (3.4) q =st d (3.5)

4 60 The value of a is greater than one and this parameter is considered as tuning parameter. It has been found by simulation that a = 1.01 gives best result for Rmodel1, Rmodel2 and Rmodel3. The value of a less than 1.01 doesn t yield better Integral Square Error (ISE) and Integral Absolute Error (IAE) values. Solving the equations (3.3) to (3.5), the values of k 1 and k 2 are obtained. Using the definitions of k 1 and k 2, the PI controller settings are obtained as, kckpt = (3.6) d t t I d = (3.7) From the equations (3.6) and (3.7), the controller settings has been obtained by substituting the k p and t d of the given model. For k p =1.667, t d = and t = 0.558, the value of k c = 1.7 and t i = are obtained. By using these controller parameters, the transfer function model is simulated for both servo and regulatory responses and its performance has been compared with IMC and ZN methods EQ - PID Controller A stable FOPTD system with an Integrator is represented by -td ke s p s t s+ 1, where k is the process gain, t p d is the time delay and t is the time ( ) constant of the process. For the purpose of designing controllers, the dynamics of many processes can be described adequately by a FOPTD model. The method gives simple set of equations for the controller settings. The performance of the control system is compared with that of the IMC method

5 61 and ZN methods. The closed loop transfer function relating the output(y) to the set point (y r ) is given by, y(q) (k q + k + k q )e y (q) [q [( )q 1] (k q k k q )e ] 2 -q = 2 2 -q r t t d (3.8) where q = t s, and s - is the laplace operator. Using pade s approximation for q e - as [(1-0.5q)/ (1+0.5q)] in the denominator of the equation (3.8), the numerator and the denominator terms are expanded using the taylor series for 0.5q e and 0.5q e -. The coefficient of q in the numerator is equated to a 1 times that of the denominator of the closed loop transfer function. The coefficients of q 2 and q 3 of the numerator are equated to a 1 times that of the denominator. The following sets of linear algebraic equations are obtained for PID controller. Since the objective of the control system is to make y to follow y r, the corresponding coefficients of q, q 2 and q 3 of the numerator with that of the denominator are equated. Since the presence of integral model makes the offset zero, the constant term in the numerator and that in the denominator is the same. (1 -a )k + 0.5(1 +a )k = 0 (3.9) (1 +a )k + (1 -a )k + (1 -a=)k a (3.10) (1 -a )k (1 )k [0.5 ( )] a= t t d a 2 (3.11) By solving these linear algebraic equations 3.9, 3.10 and 3.11, PID controller settings are obtained. It has been found by simulation that a 1=1.1, a 2 =0.8 a 1 gives best result for Rmodel1, Rmodel2 and Rmodel3. The ISE

6 62 and IAE values are also obtained to evaluate the performance criteria. The performance of the EQ-PID controller is compared with the controller designed by the EQ-PI method. The Figure 3.1 and Figure 3.2 show the servo and regulatory response of EQ-PI controller respectively and it has been compared with the IMC and ZN methods of controller. The simulation shows that the IMC and ZN method produces a response having large undershoots on the other hand the EQ-PI method shows marginally quicker settling time than IMC and ZN method. EQ-PI IMC ZN Figure 3.1 Servo response of Rmodel 3

7 63 EQ-PI IMC ZN Figure 3.2 Regulatory response of Rmodel 3 The PI controller settings obtained by using the equations 3.6 and 3.7 for the FOPTDI system with k p = ,t =1.0659, t d =0.673 are k c =0.296, t i = By using these controller settings, the process has been simulated and it shows a response having large overshoot. With the same controller settings, the model3 has been simulated and response is shown in Figure 3.3 where IMC and ZN controller gives sluggish response with offset.

8 64 EQ-PID EQ-PI Figure 3.3 Regulatory response of model 3 The tuning parameters obtained using EQ-PID method are k c = , t I = and t d =0.4 for the average FOPTDI transfer function (Rmodel3) model. The same controller settings give better response for the Rmodel1 and Rmodel2 also.

9 65 EQ-PID EQ-PI Figure 3.4 Servo response under parameter uncertainty +12% in process gain k p The robustness of the EQ method is studied by using +12% perturbation in process gain k p from the nominal value is shown in Figure 3.4, whereas the controller settings are those calculated for the process with nominal parameters. The servo response of the system under +12% uncertainties in time constant t and +16% uncertainties in time delay t d are shown in Figure 3.5 and Figure 3.6 respectively. From these results, it is observed that the EQ-PI method produce an oscillatory response with overshoot and longer settling time following a setpoint.

10 66 EQ-PI EQ-PID Figure 3.5 Servo response under parameter uncertainty of +12% in time constant t EQ-PID EQ-PI Figure 3.6 Servo response under parameter uncertainty of +16% in time delay t d

11 67 Analyses of the results indicate that the tuning method IMC referring to the response curves of Figures 3.4 to 3.6 under uncertainty in process gain, time constant and time delay respectively, the EQ-PID method settles with less oscillation and offset. The ISE and IAE value comparison for EQ-PI and EQ-PID tuning method are shown in Table 3.1. Table 3.1 ISE, IAE value comparison for EQ-PI and EQ-PID controller (k c = , t I =1.0659,t d = 0.673); PI(k c =0.296, t i =0.002) Models for simulation RModel 1 RModel 2 RModel 3 Method Servo Response Regulatory Response ISE IAE ISE IAE PID PI PID PI PID PI The controller parameters obtained are k c = ,t i =0.0454, t d = 0.4 for the FOPTDI system with k p =3.1818,t =1.0659,t d = The performance evaluation criteria ISE and IAE values for EQ-PID method gives less value compare to EQ-PI controller. The performance under model parameter uncertainty is better for EQ-PID method compared to EQ-PI method. Also the Table 3.2 shows the ISE and IAE values comparison for the transfer function of the system under uncertainty in process gain k p, time constant t and time delay t d.

12 68 Table 3.2 ISE, IAE value comparison for system under parameter uncertainty (Parameters for controller design K p = , t =1.0659, t d = 0.673) S.No Method ISE values for uncertainty IAE values for uncertainty +12% in k p +12% in t +16% in t d +12% in k p +12% in t +16% in t d 1. EQ-PI EQ-PID For uncertainty in process parameters, the performance evaluation criteria such as ISE and IAE are comparatively less for EQ-PID method. 3.3 DIRECT SYNTHESIS METHOD Time delay is common in all process industries due to transportation delay, recycle loops, composition analysis loops and the like. These types of processes can be approximated as integrating processes with time delay for the purpose of designing controllers instead of controlling in the original form. Using direct synthesis method, a PID controller in series with a lead/lag compensator is designed for control of closed loop FOPTD processes with time delay. Guidelines are provided for selection of the desired closed loop tuning parameter. The method gives significant load disturbance rejection performance. With the reference to the literature studied, several PI and PID controllers design methods have been proposed by Bhattacharya et al (1993 and 1995) for control of integrating processes with time delay. However, when there is large time delay, control of integrating processes is

13 69 difficult because of the limitations imposed by the time delay on system performance and stability. The controller for the processes such as Integrating Plus Unstable First-Order Plus Time Delay (IUFOPTD), Double Integrating Plus Time Delay(DIPTD) and Double-Integrating Plus First-Order Plus Time Delay(DIFOPTD) have been addressed by Skogested (2003) and Hang et al (2003). But most of the method uses modified form of Smith Predictor whose structure is complicated. The number of tuning parameters required is also more. Practically a simple control structure with a simple controller is desirable as it is very easy for the operator to tune. In general G p is the process transfer function and G c is the controller transfer function. For designing the controller G c, the method developed by Seshagiri Rao et al (2008) has been considered. In this DS method for set point tracking, a simple controller design method with only one controller in a single feedback loop for all classes of integrating processes has been considered. The desired output behavior of the closed loop can be specified as a trajectory model based on the process to design the required form of the controller. With the conventional controllers, there may be problems like overshoot and settling time. In this work, based on the nature of the integrating process, the desired closed loop transfer function is chosen and correspondingly the controller structure is derived. In this case PID controller in series with lead / lag compensator is obtained. The controllers are also tuned using ZN method (Ziegler 1942) and Rivera et al (1986), and the performance has been compared by simulation. The direct synthesis method gives simple equations for the controller settings. The performance of the closed loop system has

14 70 been evaluated for both original and approximated model. The transfer function model is of the type, G p -qs ke = (3.12) s( t s + 1) The desired closed loop transfer function is considered as, y ( h s +h s + 1)e y ( l s + 1) r 2 -qs 2 1 (3.13) This design method is chosen here because the desired output behavior of the closed loop can be specified as a trajectory model based on the process to design the required form of the controller. The closed loop relation for setpoint changes is given by, y GG y 1 GG c p = (3.14) + r c p from equation (3.14) the controller is given by, 1 (y/y) r Gc = G p 1 - (y/y) r (3.15) According to the direct synthesis method, the closed loop trajectory model should be specified for designing the controller. The controller can be written as G c 1 (y/y) r d = G 1 -(y/y) p r d (3.16)

15 71 where (y/y r ) d is the desired closed loop trajectory for set-point changes. The PID controller is designed in series with the lead/ lag compensator. If the process is G p -qs ke =, the desired closed loop transfer function is s( t s + 1) 2 -qs æ y ( h 2s +h 1s + 1)e ö considered as, ç = 3. Using first-order pade èy r ( l s + 1) ø approximation for the time delay, after simplification the controller is obtained as, c c d i ( a s+ 1) 1 G = k (1 + +t s) ts ( b s + 1) (3.17) where k h1 = k(3l + 1.5ql qh - h ) c (3.18) t= h 1 1 h 2 t d = h ql a= 0.5, qb= t l + ql+ qh -h 2 ( ) (3.19) in which h 1 =3l+ q and h = 2 ( 0.5 q-tl ) 3 + ( 3t 2-1.5qt) l 2 + 3qtl qt 2 2 ) t(0.5 q+t) (3.20) The tuning parameter l should be selected in such a way that the resulting controller gains should be positive for positive values of k. Hence to get positive values of controller gain (k c ), the constraint to be followed is,

16 72 h < l + ql - h + qh (3.21) In addition, lshould be selected in such a way that the resulting controller gives good robust control performance. The initial value of the tuning parameter can be taken as equal to half of the time delay of the process to get good control performance. If not, then, the tuning parameter can be increased from this value till good nominal and robust control performance are achieved. For suitable value of l and b, the controller designed on DS method gives good control performances. However for high value of b, the phase lag imposed by the term (bs+1) in the controller is more, thus the designed controller with this value of b is not able to give robust control performances which results in low gain and phase margins of the open loop system than the required values (gain margin should be >1.7 and phase margin should be >35 0 for robust control of a process). Based on many simulation studies, it is observed that taking 0.1 b instead of b gives good compromise between nominal performance and robust control performance. Thus, in the present work, the value of b obtained is modified as 0.1b for simulation studies. The desired closed loop transfer function is chosen based on the nature of the integrating process and correspondingly the controller structure is derived in this method.

17 73 Rmodel1 Rmodel2 Rmodel3. Figure 3.7 Closed loop performance comparison of Rmodel 1, 2 and 3. Controller designed on Rmodel 2 In Figure 3.7, performance of the closed loop system are evaluated by giving a unit step input in the set point and a negative step input of 0.1 in the load at t= 25s. In this work, the controller is designed using DS method for Rmodel2 and simulated for other models such as Rmodel1 and Rmodel3. From the response curves, it is clearly observed that the controller gives better performance for the other models such as Rmodel1 and Rmodel2 too. Referring to Figure 3.8, the IMC method settles at a faster rate than that of DS method for model3 and the ZN gives a very sluggish response confirming that it may not be suited for process of this nature. Whereas the same IMC controller does not give good performance for model1 and model 2.

18 74 DS IMC ZN Figure 3.8 Closed loop performance comparison of model 3 Table 3.3 gives the ISE and IAE values for the closed loop response of the system. It is clearly seen that the DS method gives less ISE and IAE values comparatively Table 3.3 DS, IMC and NZ comparison of ISE and IAE values for servo problem Process Controller ISE IAE RModel 1 DS IMC ZN RModel 2 RModel 2 DS IMC ZN DS IMC ZN

19 75 For any closed loop system it is necessary to analyze the stability and robustness for uncertainties in the process. The controller parameters obtained for the FOPTDI system of Rmodel3 using the equations ( ) are K c =1.25; t i =0.125; t D = and b = with the tuning parametera = and q =0.67. Using these controller settings the closed loop performance of the system is evaluated. Figure 3.9 shows the response of the system for +34% perturbations in time delay and the DS method gives the best performance for upto ± 28 % uncertainty in K p, ± 26% uncertainty in t and ± 34% uncertainty in time delay t d whereas other two methods IMC and ZN gives unstable performance for such uncertainty values. DS IMC ZN Figure 3.9 Responses for a perturbation of +34 % in process time delay t for the Rmodel 2 Table 3.4 gives the corresponding ISE and IAE values for the closed loop response of the system under +34% uncertainty in time delay. IMC, ZN gives more higher error value.

20 76 Table 3.4 DS method comparison of ISE and IAE values for uncertainty in time delay Process Controller ISE IAE DS RModel 1 IMC Z-N DS RModel 2 IMC Z-N DS RModel 2 IMC Z-N By giving positive and negative step input at certain point of time, among the comparison of DS and EQ-PID, DS method gives faster settling time for both servo and regulatory response. Figure 3.10 and Figure 3.11 shows the closed loop response comparison for the methods DS and EQ-PID under uncertainty of +23% in process gain k p and +24% of time constantt. Whereas the controller has been designed for the nominal values. With such percentage of uncertainty the IMC method takes more settling time and gives undershoot also.

21 77 DS EQ-PID Figure 3.10 Closed loop response of RModel2 for uncertainty of 23% of process gain k p DS EQ-PID Figure 3.11 Closed loop response of RModel 2 for uncertainty of +24% times constant

22 78 Referring to the Table 3.5, the performance evaluation criteria ISE and IAE are low for DS method of controller when compared to the other method. The EQ-PID method produce large undershoot for the negative input and takes more time to settle than DS method. The response has been obtained after applying negative step input, The DS controller settles faster comparatively. PID controller tuning parameters have been obtained using different methods like EQ-PI, EQ-PID, optimization method, and direct synthesis method. In the equating coefficient method single and two tuning parameters have been used to design the controller. Table 3.5 Performance comparison of DS and EQ-PID method Models for Simulation Model 1 Method Evaluation Criteria ISE IAE DS EQ-PID DS Model 2 EQ-PID DS Model 3 EQ-PID This method gives simple equations and the performance of the system is evaluated by simulation comparing with IMC and ZN method. Among EQ-PI and EQ-PID, EQ-PID performance is better in terms of evaluation criteria like ISE and IAE. The controllers have also been tuned using and direct synthesis method. Comparing the DS with EQ-PID, DS gives less error value and overshoot.

23 MODEL REFERENCE CONTROL For controller design purposes, the dynamics of the processes are described by first order time delay model. In this model reference control Jacob and Chidambaram (1996) have designed PI controller to force the error to follow the given error dynamics for unstable first order plus time delay system. In this work, for stable first order plus time delay system with integrator, the model reference control method has been extended to design PID controller. By specifying the settling time, t s, the value of the controller gain is obtained. Thus the controller is robust. For nonlinear systems, the values of time constant and gain will be varying. Hence, the controller settings based on fixed values of time constant and gain have to be detuned. However, the controller is shown to be robust for perturbation in time constant and gain. Normally due to certain non linearity of the systems, many real systems exhibit multiple steady states. Sometimes for safety reasons, it may also be necessary to operate the system at unstable steady state. In this work PID controller for stable first order plus time delay systems has been designed. The performance of the closed loop system is evaluated for both the actual and the approximated model. The controllers are also tuned using Internal Model Control (IMC) and the performance is compared by simulation. The general transfer function of the process to be controlled is given by, k p - Ls e s( t s + 1) (3.21) where k p is the process gain,t is the time constant, and L is the process lag. The corresponding time domain description is given by,

24 80 && y = ((- y& + k u(t -L)) t (3.22) p with t=0, y& =0 Let the error can be defined as, e= yr - y (3.23) where given by, yr is the setpoint value. Hence, the double derivative of the error is && e= && y -&& y r Figure 3.12 Block diagram representation of the process with the control law equation && e = && y -[- y& + k u(t -L)] t (3.24) r p equated to To get the expression for u(t), let the right side of equation 3.24 be c I t 0 D. - k [e + (1 t ) ò edt +t e] (3.25)

25 81 Then, the control law equation u (t) is given by, t t u(t) = {y && r+ (y& t ) + k [e + (1 t c I) ò 0edt +tdedt]} t+ L (3.26) k p u(t) t = pt+ L, where t L kp p + = p + Lp& by solving the equation 3.26, the tuning parameters for PID controller are obtained as, k 25 = (3.27) z t c 2 s 1 t= 0.4t z (1 + +t s) 2 I s D tis (3.28) t D = 0.4ts (3.29) Thus specifying the settling time and damping coefficient ( z ) for the error system, controller gain and integral time can be calculated. To use the control law equation (3.26), it required the prediction of y at (t+ t d ). A simple prediction formula for y(t+ t d ) can be obtained from the truncated Taylor s series expansion of y(t+ t d ) as y(t+ t d )=y(t)+ t. ' d y(t). The block diagram representation of the feedback system of the control law is shown in Figure The closed loop system is thus stable and for a step input in y r, we get y equals y r as tà. For nonlinear systems, the value of time constant and gain will be varying. However, the present controller is shown to be robust for perturbations in the values of time constant and gain. Hence, it is expected that the present linear controller will give good performance on the nonlinear system also.

26 82 The performance of the control system is evaluated for step change in y r at the input and the load and the simulated results are shown in Figures 3.13 and 3.14 respectively. Referring to the servo response of Rmodel2 in Figure 3.13, MRC gives less overshoot and faster settling time. In the regulatory response of the same model, MRC gives less undershoot comparatively. MRC IMC Figure 3.13 Servo response of Rmodel 2 MRC IMC Figure 3.14 Regulatory response of Rmodel2

27 83 With the same controller settings, the other first order plus time delay with integrator models like Rmodel1 and Rmodel2 and the original models Model1, Model2 and Model3 are simulated for both servo and regulatory responses. The values of the error in both cases give very less value. The ISE and the IAE performance indices have been calculated and is shown in Table 3.6. The parameters of the open loop system are k p =2.1818, t = ; t d = The parameters obtained for PID controller are k c = 0.452; t I = 0.96 and t D =0.366 for MRC method and kc= 0.12;t I = and t D = for IMC method. The controller settings are obtained for the average model using MRC and IMC method. Table 3.6 Performance comparison of MRC with IMC(K c =0.452, t i 0.96 t d =0.36); IMC (K c =0.12, t i =0.012; t d =0.131) Models for simulation RModel 1 RModel 2 RModel 3 Method Servo Response Regulatory Response ISE IAE ISE IAE MRC IMC MRC IMC MRC IMC Figure 3.15 shows the step response of average original model. The IMC controller shows offset whereas the model reference controller gives faster settling time. The regulatory response of the same model is shown in Figure 3.16 demonstrate the improvement obtained with the MRC controller. The response of the MRC controller was comparatively better in terms of reducing the overshoot and settling time.

28 84 MRC IMC Figure 3.15 Servo response of model 3 MRC IMC Figure 3.16 Regulator response of model 3

29 85 The behavior of manipulated variable versus time behavior is shown in Figure The performance in terms of ISE and IAE is listed in Table 3.7. The performance of the model reference control is significantly better than that of the IMC controller. MRC IMC Figure 3.17 Manipulated variables versus time behavior Table 3.7 Performance comparison for actual model 2 Method Servo Response ISE IAE MRC IMC Regulatory Response ISE IAE MRC IMC

30 86 The simulation results demonstrate the capability of the MRC controller in accommodating uncertainty in the process model. Uncertainty of about -19% in time constantt, -29% in process lag L and -21% in process gain k p are separately introduced and the response is shown in the Figures 3.18 to 3.20 respectively. When the IMC controller almost fails to cope with the model-process mismatch, the MRC controller provides acceptable results. It can also be noticed that the response of the MRC controller settles at the desired setpoint with minimum oscillations compared to IMC controller where oscillations persist for quite long time. MRC IMC Figure 3.18 Comparison of MRC and IMC for uncertainty of -19% in time constant t for Rmodel 3

31 87 MRC IMC Figure 3.19 Comparison of MRC and IMC for uncertainty of -29% in process lag L for Rmodel 3 MRC IMC Figure 3.20 Comparison of MRC and IMC for uncertainty of -21% in process gain k p for Rmodel 3

32 88 The results of the above simulation examples indicate, in general, that the MRC controller reduced the sensitivity to modeling errors comparatively. In addition, both the overshoot and settling time have been considerably reduced. 3.5 DUAL LOOP PID CONTROL In the Dual loop control, the process to be controlled is controlled using dual loops. The general transfer function of the process to be controlled is given by equation (3.21), where k p is the process gain,t is the time constant and L is the process lag. The general block diagram of the dual loop PID is shown in the Figure Figure 3.21 Block diagram of the dual loop control PID The inner loop consists of PI controller and the outer loop consists of PID controller designed using direct synthesis method developed by Sheshagiri Roa et al (2009) for unstable system. In this work, it has been extended for stable system. The closed loop transfer function of the inner loop is given by y kke c p = y s + kke in c p -Ls -Ls The delay is approximated as resultant equation is given by, e Ls 1 0.5Ls = Ls - - and the

33 89 k ck p ( 1-0.5Ls) ( + ) + ( - ) y = y s 1 0.5Ls k k 1 0.5Ls in c p (3.30) c p( + ) ( ) -Ls y k k 1 0.5Ls e = y s 1 0.5L s k k 1 0.5L s ( + ) + ( -( ) ) in c p ( + ) -Ls y kckp 1 0.5Ls e = y 0.5Ls k k L s + k k ( ) 2 in c p c p The closed loop transfer function of the inner loop is given by, ( + ) -Ls y k ck p 1 0.5Ls e = y 0.5Ls k k L s + k k ( ) 2 in c p c p (3.31) Figure 3.22 Block diagram of the simplified dual PID Figure 3.22 shows the simple block diagram of the simplified dual PID controller. After simplification, the closed loop transfer function of the controller is obtained as, 1 ( a s + 1) Gc = k c(1 + +tds) tis ( b s + 1) (3.32)

34 90 where 3 0.5ql b= t l + ql+ h -h 2 ( ) t= i2 h1 t d2 h = h 2 1 a 0.5 =q h 1 =3l+q and (0.5 q-tl ) + (3t -1.5 qtl ) + 3qtl+ 0.5qt h 2 = t(0.5 q+t) The performance of the closed loop control system is evaluated for a step input y r. The response of the dual loop controller is compared with model reference controller. Simulation of the plant models have been conducted to study the performance of the dual loop controller comparing with MRC type controller. Referring to the figures 3.23 and 3.24, it is observed clearly that the dual loop PID controller provides improved performance and settles at a faster rate both in servo and regulatory responses whereas the MRC controller shows sluggish response.

35 91 Dual MRC Figure 3.23 Servo response of Rmodel2 Dual MRC Figure 3.24 Regulatory response of Rmodel 2

36 92 The sensitivity of the controller to model inaccuracies is also considered and is shown in the Figures 3.25 to The robustness of the controller is evaluated using ± 23% perturbations in the process gain and the controller used was the one designed for the actual value of the process parameters. Similarly robust response for perturbation in time delay and time constant is obtained. Dual IMRC Figure 3.25 The regulatory performance of controller under -23% uncertainty in process gain for Rmodel2 It is clear from the figures 3.26 and 3.27 that the MRC controller has reduced the effects of mismatch between the process and the model on the system performance and it is less sensitive to model errors. It provides stable response up to ± 20% variation in time delay and ± 26% variation in time constant.

37 93 Dual MRC Figure 3.26 Comparison of MRC and dual loop for uncertainty of -20% in time delay for Rmodel2 Dual MRC Figure 3.27 The servo performance of controller under -26% uncertainty in time constant for Rmodel 2

38 94 The simulation results demonstrate the capability of the dual loop controller in accommodating uncertainty in the process model. When the MRC controller almost fails to cope with model-process mismatch, the dual controller provides acceptable results. The response of the dual loop controller settles at the desired setpoint with minimum oscillations compared to the MRC where oscillations persist for quite long time. The ISE and the IAE performance indices have been calculated, and presented in Table 3.8. The content of the table shows the improvement in performance in terms of the ISE and IAE. Table 3.8 ISE, IAE value comparison of MRC and dual loop PID controller S.No Models Servo Response Regulator Response ISE IAE ISE IAE Model 1 MRC Dual Loop Model 2 MRC Dual Loop Model 3 MRC Dual Loop

39 95 Dual MRC Figure 3.28 The regulatory performance of controller under -34% uncertainty in time delay in the Rmodel2 Dual MRC Figure 3.29 Servo response of dual loop and MRC for RModel 2

40 96 The comparison of dual loop and MRC controller for both servo and regulatory response are shown in figures 3.28 and 3.29 respectively. Dual loop PID shows good response compared to MRC controller. Table 3.8 gives the calculated performance evaluation criteria. For all types of FOPTDI systems and the actual models like model1, model2 and model3 responses, the Dual loop PID method gives comparatively less error value. Dual MRC Figure 3.30 Servo Response of MRC, DS and Dual loop Figure 3.30 shows the overall comparison of servo response of MRC, DS and dual loop controller. The DS and Dual loop controller settles at the faster rate without any overshoot whereas the MRC controller settles with bit oscillation. Perturbation in process gain, time delay and time constant has also been simulated separately with the same controller parameters. Kharitonov s theorem has been used to determine the range at which the controller attains instability.

41 SUMMARY The transfer function model of the web guide used to control the position of the web in cold rolling mill is controlled using different tuning methods and its simulation results have been compared. The performance indices such as ISE and IAE values have been obtained and compared. The process parameters are perturbed for certain percentage of process gain, time constant and time delays separately and simulated with nominal controller parameters in order to check the range at which the controller attains instability.

Feedback Control of Linear SISO systems. Process Dynamics and Control

Feedback Control of Linear SISO systems. Process Dynamics and Control Feedback Control of Linear SISO systems Process Dynamics and Control 1 Open-Loop Process The study of dynamics was limited to open-loop systems Observe process behavior as a result of specific input signals

More information

CHBE320 LECTURE XI CONTROLLER DESIGN AND PID CONTOLLER TUNING. Professor Dae Ryook Yang

CHBE320 LECTURE XI CONTROLLER DESIGN AND PID CONTOLLER TUNING. Professor Dae Ryook Yang CHBE320 LECTURE XI CONTROLLER DESIGN AND PID CONTOLLER TUNING Professor Dae Ryook Yang Spring 2018 Dept. of Chemical and Biological Engineering 11-1 Road Map of the Lecture XI Controller Design and PID

More information

NonlinearControlofpHSystemforChangeOverTitrationCurve

NonlinearControlofpHSystemforChangeOverTitrationCurve D. SWATI et al., Nonlinear Control of ph System for Change Over Titration Curve, Chem. Biochem. Eng. Q. 19 (4) 341 349 (2005) 341 NonlinearControlofpHSystemforChangeOverTitrationCurve D. Swati, V. S. R.

More information

CHAPTER 5 ROBUSTNESS ANALYSIS OF THE CONTROLLER

CHAPTER 5 ROBUSTNESS ANALYSIS OF THE CONTROLLER 114 CHAPTER 5 ROBUSTNESS ANALYSIS OF THE CONTROLLER 5.1 INTRODUCTION Robust control is a branch of control theory that explicitly deals with uncertainty in its approach to controller design. It also refers

More information

A unified approach for proportional-integral-derivative controller design for time delay processes

A unified approach for proportional-integral-derivative controller design for time delay processes Korean J. Chem. Eng., 32(4), 583-596 (2015) DOI: 10.1007/s11814-014-0237-6 INVITED REVIEW PAPER INVITED REVIEW PAPER pissn: 0256-1115 eissn: 1975-7220 A unified approach for proportional-integral-derivative

More information

Chapter 5 The SIMC Method for Smooth PID Controller Tuning

Chapter 5 The SIMC Method for Smooth PID Controller Tuning Chapter 5 The SIMC Method for Smooth PID Controller Tuning Sigurd Skogestad and Chriss Grimholt 5.1 Introduction Although the proportional-integral-derivative (PID) controller has only three parameters,

More information

IMC based automatic tuning method for PID controllers in a Smith predictor configuration

IMC based automatic tuning method for PID controllers in a Smith predictor configuration Computers and Chemical Engineering 28 (2004) 281 290 IMC based automatic tuning method for PID controllers in a Smith predictor configuration Ibrahim Kaya Department of Electrical and Electronics Engineering,

More information

CHAPTER 6 CLOSED LOOP STUDIES

CHAPTER 6 CLOSED LOOP STUDIES 180 CHAPTER 6 CLOSED LOOP STUDIES Improvement of closed-loop performance needs proper tuning of controller parameters that requires process model structure and the estimation of respective parameters which

More information

Lecture 12. Upcoming labs: Final Exam on 12/21/2015 (Monday)10:30-12:30

Lecture 12. Upcoming labs: Final Exam on 12/21/2015 (Monday)10:30-12:30 289 Upcoming labs: Lecture 12 Lab 20: Internal model control (finish up) Lab 22: Force or Torque control experiments [Integrative] (2-3 sessions) Final Exam on 12/21/2015 (Monday)10:30-12:30 Today: Recap

More information

arxiv: v1 [cs.sy] 30 Nov 2017

arxiv: v1 [cs.sy] 30 Nov 2017 Disturbance Observer based Control of Integrating Processes with Dead-Time using PD controller Sujay D. Kadam SysIDEA Lab, IIT Gandhinagar, India. arxiv:1711.11250v1 [cs.sy] 30 Nov 2017 Abstract The work

More information

A unified double-loop multi-scale control strategy for NMP integrating-unstable systems

A unified double-loop multi-scale control strategy for NMP integrating-unstable systems Home Search Collections Journals About Contact us My IOPscience A unified double-loop multi-scale control strategy for NMP integrating-unstable systems This content has been downloaded from IOPscience.

More information

CM 3310 Process Control, Spring Lecture 21

CM 3310 Process Control, Spring Lecture 21 CM 331 Process Control, Spring 217 Instructor: Dr. om Co Lecture 21 (Back to Process Control opics ) General Control Configurations and Schemes. a) Basic Single-Input/Single-Output (SISO) Feedback Figure

More information

Research Article. World Journal of Engineering Research and Technology WJERT.

Research Article. World Journal of Engineering Research and Technology WJERT. wjert, 2015, Vol. 1, Issue 1, 27-36 Research Article ISSN 2454-695X WJERT www.wjert.org COMPENSATOR TUNING FOR DISTURBANCE REJECTION ASSOCIATED WITH DELAYED DOUBLE INTEGRATING PROCESSES, PART I: FEEDBACK

More information

Control Systems II. ETH, MAVT, IDSC, Lecture 4 17/03/2017. G. Ducard

Control Systems II. ETH, MAVT, IDSC, Lecture 4 17/03/2017. G. Ducard Control Systems II ETH, MAVT, IDSC, Lecture 4 17/03/2017 Lecture plan: Control Systems II, IDSC, 2017 SISO Control Design 24.02 Lecture 1 Recalls, Introductory case study 03.03 Lecture 2 Cascaded Control

More information

Analysis and Synthesis of Single-Input Single-Output Control Systems

Analysis and Synthesis of Single-Input Single-Output Control Systems Lino Guzzella Analysis and Synthesis of Single-Input Single-Output Control Systems l+kja» \Uja>)W2(ja»\ um Contents 1 Definitions and Problem Formulations 1 1.1 Introduction 1 1.2 Definitions 1 1.2.1 Systems

More information

Simple analytic rules for model reduction and PID controller tuning

Simple analytic rules for model reduction and PID controller tuning Journal of Process Control 3 (2003) 29 309 www.elsevier.com/locate/jprocont Simple analytic rules for model reduction and PID controller tuning Sigurd Sogestad* Department of Chemical Engineering, Norwegian

More information

Improved cascade control structure for enhanced performance

Improved cascade control structure for enhanced performance Improved cascade control structure for enhanced performance Article (Unspecified) Kaya, İbrahim, Tan, Nusret and Atherton, Derek P. (7) Improved cascade control structure for enhanced performance. Journal

More information

Additional Closed-Loop Frequency Response Material (Second edition, Chapter 14)

Additional Closed-Loop Frequency Response Material (Second edition, Chapter 14) Appendix J Additional Closed-Loop Frequency Response Material (Second edition, Chapter 4) APPENDIX CONTENTS J. Closed-Loop Behavior J.2 Bode Stability Criterion J.3 Nyquist Stability Criterion J.4 Gain

More information

A Tuning of the Nonlinear PI Controller and Its Experimental Application

A Tuning of the Nonlinear PI Controller and Its Experimental Application Korean J. Chem. Eng., 18(4), 451-455 (2001) A Tuning of the Nonlinear PI Controller and Its Experimental Application Doe Gyoon Koo*, Jietae Lee*, Dong Kwon Lee**, Chonghun Han**, Lyu Sung Gyu, Jae Hak

More information

Automatic Control 2. Loop shaping. Prof. Alberto Bemporad. University of Trento. Academic year

Automatic Control 2. Loop shaping. Prof. Alberto Bemporad. University of Trento. Academic year Automatic Control 2 Loop shaping Prof. Alberto Bemporad University of Trento Academic year 21-211 Prof. Alberto Bemporad (University of Trento) Automatic Control 2 Academic year 21-211 1 / 39 Feedback

More information

CompensatorTuning for Didturbance Rejection Associated with Delayed Double Integrating Processes, Part II: Feedback Lag-lead First-order Compensator

CompensatorTuning for Didturbance Rejection Associated with Delayed Double Integrating Processes, Part II: Feedback Lag-lead First-order Compensator CompensatorTuning for Didturbance Rejection Associated with Delayed Double Integrating Processes, Part II: Feedback Lag-lead First-order Compensator Galal Ali Hassaan Department of Mechanical Design &

More information

EE 422G - Signals and Systems Laboratory

EE 422G - Signals and Systems Laboratory EE 4G - Signals and Systems Laboratory Lab 9 PID Control Kevin D. Donohue Department of Electrical and Computer Engineering University of Kentucky Lexington, KY 40506 April, 04 Objectives: Identify the

More information

Controller Design Based on Transient Response Criteria. Chapter 12 1

Controller Design Based on Transient Response Criteria. Chapter 12 1 Controller Design Based on Transient Response Criteria Chapter 12 1 Desirable Controller Features 0. Stable 1. Quik responding 2. Adequate disturbane rejetion 3. Insensitive to model, measurement errors

More information

Model-based PID tuning for high-order processes: when to approximate

Model-based PID tuning for high-order processes: when to approximate Proceedings of the 44th IEEE Conference on Decision and Control, and the European Control Conference 25 Seville, Spain, December 2-5, 25 ThB5. Model-based PID tuning for high-order processes: when to approximate

More information

An Improved Relay Auto Tuning of PID Controllers for SOPTD Systems

An Improved Relay Auto Tuning of PID Controllers for SOPTD Systems Proceedings of the World Congress on Engineering and Computer Science 7 WCECS 7, October 4-6, 7, San Francisco, USA An Improved Relay Auto Tuning of PID Controllers for SOPTD Systems Sathe Vivek and M.

More information

Open Loop Tuning Rules

Open Loop Tuning Rules Open Loop Tuning Rules Based on approximate process models Process Reaction Curve: The process reaction curve is an approximate model of the process, assuming the process behaves as a first order plus

More information

Ian G. Horn, Jeffery R. Arulandu, Christopher J. Gombas, Jeremy G. VanAntwerp, and Richard D. Braatz*

Ian G. Horn, Jeffery R. Arulandu, Christopher J. Gombas, Jeremy G. VanAntwerp, and Richard D. Braatz* Ind. Eng. Chem. Res. 996, 35, 3437-344 3437 PROCESS DESIGN AND CONTROL Improved Filter Design in Internal Model Control Ian G. Horn, Jeffery R. Arulandu, Christopher J. Gombas, Jeremy G. VanAntwerp, and

More information

Tuning of Internal Model Control Proportional Integral Derivative Controller for Optimized Control

Tuning of Internal Model Control Proportional Integral Derivative Controller for Optimized Control Tuning of Internal Model Control Proportional Integral Derivative Controller for Optimized Control Thesis submitted in partial fulfilment of the requirement for the award of Degree of MASTER OF ENGINEERING

More information

Part II. Advanced PID Design Methods

Part II. Advanced PID Design Methods Part II Advanced PID Design Methods 54 Controller transfer function C(s) = k p (1 + 1 T i s + T d s) (71) Many extensions known to the basic design methods introduced in RT I. Four advanced approaches

More information

Improved Identification and Control of 2-by-2 MIMO System using Relay Feedback

Improved Identification and Control of 2-by-2 MIMO System using Relay Feedback CEAI, Vol.17, No.4 pp. 23-32, 2015 Printed in Romania Improved Identification and Control of 2-by-2 MIMO System using Relay Feedback D.Kalpana, T.Thyagarajan, R.Thenral Department of Instrumentation Engineering,

More information

Video 5.1 Vijay Kumar and Ani Hsieh

Video 5.1 Vijay Kumar and Ani Hsieh Video 5.1 Vijay Kumar and Ani Hsieh Robo3x-1.1 1 The Purpose of Control Input/Stimulus/ Disturbance System or Plant Output/ Response Understand the Black Box Evaluate the Performance Change the Behavior

More information

Chapter 2. Classical Control System Design. Dutch Institute of Systems and Control

Chapter 2. Classical Control System Design. Dutch Institute of Systems and Control Chapter 2 Classical Control System Design Overview Ch. 2. 2. Classical control system design Introduction Introduction Steady-state Steady-state errors errors Type Type k k systems systems Integral Integral

More information

Improved Autotuning Using the Shape Factor from Relay Feedback

Improved Autotuning Using the Shape Factor from Relay Feedback Article Subscriber access provided by NATIONAL TAIWAN UNIV Improved Autotuning Using the Shape Factor from Relay Feedback T. Thyagarajan, and Cheng-Ching Yu Ind. Eng. Chem. Res., 2003, 42 (20), 4425-4440

More information

CHAPTER 7 FRACTIONAL ORDER SYSTEMS WITH FRACTIONAL ORDER CONTROLLERS

CHAPTER 7 FRACTIONAL ORDER SYSTEMS WITH FRACTIONAL ORDER CONTROLLERS 9 CHAPTER 7 FRACTIONAL ORDER SYSTEMS WITH FRACTIONAL ORDER CONTROLLERS 7. FRACTIONAL ORDER SYSTEMS Fractional derivatives provide an excellent instrument for the description of memory and hereditary properties

More information

Index Accumulation, 53 Accuracy: numerical integration, sensor, 383, Adaptive tuning: expert system, 528 gain scheduling, 518, 529, 709,

Index Accumulation, 53 Accuracy: numerical integration, sensor, 383, Adaptive tuning: expert system, 528 gain scheduling, 518, 529, 709, Accumulation, 53 Accuracy: numerical integration, 83-84 sensor, 383, 772-773 Adaptive tuning: expert system, 528 gain scheduling, 518, 529, 709, 715 input conversion, 519 reasons for, 512-517 relay auto-tuning,

More information

ISA-PID Controller Tuning: A combined min-max / ISE approach

ISA-PID Controller Tuning: A combined min-max / ISE approach Proceedings of the 26 IEEE International Conference on Control Applications Munich, Germany, October 4-6, 26 FrB11.2 ISA-PID Controller Tuning: A combined min-max / ISE approach Ramon Vilanova, Pedro Balaguer

More information

Analysis and Design of Control Systems in the Time Domain

Analysis and Design of Control Systems in the Time Domain Chapter 6 Analysis and Design of Control Systems in the Time Domain 6. Concepts of feedback control Given a system, we can classify it as an open loop or a closed loop depends on the usage of the feedback.

More information

Process Identification for an SOPDT Model Using Rectangular Pulse Input

Process Identification for an SOPDT Model Using Rectangular Pulse Input Korean J. Chem. Eng., 18(5), 586-592 (2001) SHORT COMMUNICATION Process Identification for an SOPDT Model Using Rectangular Pulse Input Don Jang, Young Han Kim* and Kyu Suk Hwang Dept. of Chem. Eng., Pusan

More information

Enhanced Single-Loop Control Strategies (Advanced Control) Cascade Control Time-Delay Compensation Inferential Control Selective and Override Control

Enhanced Single-Loop Control Strategies (Advanced Control) Cascade Control Time-Delay Compensation Inferential Control Selective and Override Control Enhanced Single-Loop Control Strategies (Advanced Control) Cascade Control Time-Delay Compensation Inferential Control Selective and Override Control 1 Cascade Control A disadvantage of conventional feedback

More information

STABILITY OF CLOSED-LOOP CONTOL SYSTEMS

STABILITY OF CLOSED-LOOP CONTOL SYSTEMS CHBE320 LECTURE X STABILITY OF CLOSED-LOOP CONTOL SYSTEMS Professor Dae Ryook Yang Spring 2018 Dept. of Chemical and Biological Engineering 10-1 Road Map of the Lecture X Stability of closed-loop control

More information

CHAPTER 7 MODELING AND CONTROL OF SPHERICAL TANK LEVEL PROCESS 7.1 INTRODUCTION

CHAPTER 7 MODELING AND CONTROL OF SPHERICAL TANK LEVEL PROCESS 7.1 INTRODUCTION 141 CHAPTER 7 MODELING AND CONTROL OF SPHERICAL TANK LEVEL PROCESS 7.1 INTRODUCTION In most of the industrial processes like a water treatment plant, paper making industries, petrochemical industries,

More information

CHAPTER 10: STABILITY &TUNING

CHAPTER 10: STABILITY &TUNING When I complete this chapter, I want to be able to do the following. Determine the stability of a process without control Determine the stability of a closed-loop feedback control system Use these approaches

More information

Iterative Feedback Tuning

Iterative Feedback Tuning Iterative Feedback Tuning Michel Gevers CESAME - UCL Louvain-la-Neuve Belgium Collaboration : H. Hjalmarsson, S. Gunnarsson, O. Lequin, E. Bosmans, L. Triest, M. Mossberg Outline Problem formulation Iterative

More information

MULTILOOP PI CONTROLLER FOR ACHIEVING SIMULTANEOUS TIME AND FREQUENCY DOMAIN SPECIFICATIONS

MULTILOOP PI CONTROLLER FOR ACHIEVING SIMULTANEOUS TIME AND FREQUENCY DOMAIN SPECIFICATIONS Journal of Engineering Science and Technology Vol. 1, No. 8 (215) 113-1115 School of Engineering, Taylor s University MULTILOOP PI CONTROLLER FOR ACHIEVING SIMULTANEOUS TIME AND FREQUENCY DOMAIN SPECIFICATIONS

More information

Laboratory Exercise 1 DC servo

Laboratory Exercise 1 DC servo Laboratory Exercise DC servo Per-Olof Källén ø 0,8 POWER SAT. OVL.RESET POS.RESET Moment Reference ø 0,5 ø 0,5 ø 0,5 ø 0,65 ø 0,65 Int ø 0,8 ø 0,8 Σ k Js + d ø 0,8 s ø 0 8 Off Off ø 0,8 Ext. Int. + x0,

More information

Multiple Model Based Adaptive Control for Shell and Tube Heat Exchanger Process

Multiple Model Based Adaptive Control for Shell and Tube Heat Exchanger Process Multiple Model Based Adaptive Control for Shell and Tube Heat Exchanger Process R. Manikandan Assistant Professor, Department of Electronics and Instrumentation Engineering, Annamalai University, Annamalai

More information

FEEDBACK CONTROL SYSTEMS

FEEDBACK CONTROL SYSTEMS FEEDBAC CONTROL SYSTEMS. Control System Design. Open and Closed-Loop Control Systems 3. Why Closed-Loop Control? 4. Case Study --- Speed Control of a DC Motor 5. Steady-State Errors in Unity Feedback Control

More information

6.1 Sketch the z-domain root locus and find the critical gain for the following systems K., the closed-loop characteristic equation is K + z 0.

6.1 Sketch the z-domain root locus and find the critical gain for the following systems K., the closed-loop characteristic equation is K + z 0. 6. Sketch the z-domain root locus and find the critical gain for the following systems K (i) Gz () z 4. (ii) Gz K () ( z+ 9. )( z 9. ) (iii) Gz () Kz ( z. )( z ) (iv) Gz () Kz ( + 9. ) ( z. )( z 8. ) (i)

More information

Design of Decentralised PI Controller using Model Reference Adaptive Control for Quadruple Tank Process

Design of Decentralised PI Controller using Model Reference Adaptive Control for Quadruple Tank Process Design of Decentralised PI Controller using Model Reference Adaptive Control for Quadruple Tank Process D.Angeline Vijula #, Dr.N.Devarajan * # Electronics and Instrumentation Engineering Sri Ramakrishna

More information

1 An Overview and Brief History of Feedback Control 1. 2 Dynamic Models 23. Contents. Preface. xiii

1 An Overview and Brief History of Feedback Control 1. 2 Dynamic Models 23. Contents. Preface. xiii Contents 1 An Overview and Brief History of Feedback Control 1 A Perspective on Feedback Control 1 Chapter Overview 2 1.1 A Simple Feedback System 3 1.2 A First Analysis of Feedback 6 1.3 Feedback System

More information

Observer Based Friction Cancellation in Mechanical Systems

Observer Based Friction Cancellation in Mechanical Systems 2014 14th International Conference on Control, Automation and Systems (ICCAS 2014) Oct. 22 25, 2014 in KINTEX, Gyeonggi-do, Korea Observer Based Friction Cancellation in Mechanical Systems Caner Odabaş

More information

Chapter 7 - Solved Problems

Chapter 7 - Solved Problems Chapter 7 - Solved Problems Solved Problem 7.1. A continuous time system has transfer function G o (s) given by G o (s) = B o(s) A o (s) = 2 (s 1)(s + 2) = 2 s 2 + s 2 (1) Find a controller of minimal

More information

Subject: Introduction to Process Control. Week 01, Lectures 01 02, Spring Content

Subject: Introduction to Process Control. Week 01, Lectures 01 02, Spring Content v CHEG 461 : Process Dynamics and Control Subject: Introduction to Process Control Week 01, Lectures 01 02, Spring 2014 Dr. Costas Kiparissides Content 1. Introduction to Process Dynamics and Control 2.

More information

Linear State Feedback Controller Design

Linear State Feedback Controller Design Assignment For EE5101 - Linear Systems Sem I AY2010/2011 Linear State Feedback Controller Design Phang Swee King A0033585A Email: king@nus.edu.sg NGS/ECE Dept. Faculty of Engineering National University

More information

Process Control J.P. CORRIOU. Reaction and Process Engineering Laboratory University of Lorraine-CNRS, Nancy (France) Zhejiang University 2016

Process Control J.P. CORRIOU. Reaction and Process Engineering Laboratory University of Lorraine-CNRS, Nancy (France) Zhejiang University 2016 Process Control J.P. CORRIOU Reaction and Process Engineering Laboratory University of Lorraine-CNRS, Nancy (France) Zhejiang University 206 J.P. Corriou (LRGP) Process Control Zhejiang University 206

More information

Chapter 7 Control. Part Classical Control. Mobile Robotics - Prof Alonzo Kelly, CMU RI

Chapter 7 Control. Part Classical Control. Mobile Robotics - Prof Alonzo Kelly, CMU RI Chapter 7 Control 7.1 Classical Control Part 1 1 7.1 Classical Control Outline 7.1.1 Introduction 7.1.2 Virtual Spring Damper 7.1.3 Feedback Control 7.1.4 Model Referenced and Feedforward Control Summary

More information

Appendix A MoReRT Controllers Design Demo Software

Appendix A MoReRT Controllers Design Demo Software Appendix A MoReRT Controllers Design Demo Software The use of the proposed Model-Reference Robust Tuning (MoReRT) design methodology, described in Chap. 4, to tune a two-degree-of-freedom (2DoF) proportional

More information

PROPORTIONAL-Integral-Derivative (PID) controllers

PROPORTIONAL-Integral-Derivative (PID) controllers Multiple Model and Neural based Adaptive Multi-loop PID Controller for a CSTR Process R.Vinodha S. Abraham Lincoln and J. Prakash Abstract Multi-loop (De-centralized) Proportional-Integral- Derivative

More information

Should we forget the Smith Predictor?

Should we forget the Smith Predictor? FrBT3. Should we forget the Smith Predictor? Chriss Grimholt Sigurd Skogestad* Abstract: The / controller is the most used controller in industry. However, for processes with large time delays, the common

More information

CDS 101/110a: Lecture 8-1 Frequency Domain Design

CDS 101/110a: Lecture 8-1 Frequency Domain Design CDS 11/11a: Lecture 8-1 Frequency Domain Design Richard M. Murray 17 November 28 Goals: Describe canonical control design problem and standard performance measures Show how to use loop shaping to achieve

More information

1 Loop Control. 1.1 Open-loop. ISS0065 Control Instrumentation

1 Loop Control. 1.1 Open-loop. ISS0065 Control Instrumentation Lecture 4 ISS0065 Control Instrumentation 1 Loop Control System has a continuous signal (analog) basic notions: open-loop control, close-loop control. 1.1 Open-loop Open-loop / avatud süsteem / открытая

More information

Step input, ramp input, parabolic input and impulse input signals. 2. What is the initial slope of a step response of a first order system?

Step input, ramp input, parabolic input and impulse input signals. 2. What is the initial slope of a step response of a first order system? IC6501 CONTROL SYSTEM UNIT-II TIME RESPONSE PART-A 1. What are the standard test signals employed for time domain studies?(or) List the standard test signals used in analysis of control systems? (April

More information

Robust Internal Model Control for Impulse Elimination of Singular Systems

Robust Internal Model Control for Impulse Elimination of Singular Systems International Journal of Control Science and Engineering ; (): -7 DOI:.59/j.control.. Robust Internal Model Control for Impulse Elimination of Singular Systems M. M. Share Pasandand *, H. D. Taghirad Department

More information

Control Introduction. Gustaf Olsson IEA Lund University.

Control Introduction. Gustaf Olsson IEA Lund University. Control Introduction Gustaf Olsson IEA Lund University Gustaf.Olsson@iea.lth.se Lecture 3 Dec Nonlinear and linear systems Aeration, Growth rate, DO saturation Feedback control Cascade control Manipulated

More information

Design and Tuning of Fractional-order PID Controllers for Time-delayed Processes

Design and Tuning of Fractional-order PID Controllers for Time-delayed Processes Design and Tuning of Fractional-order PID Controllers for Time-delayed Processes Emmanuel Edet Technology and Innovation Centre University of Strathclyde 99 George Street Glasgow, United Kingdom emmanuel.edet@strath.ac.uk

More information

Dr Ian R. Manchester

Dr Ian R. Manchester Week Content Notes 1 Introduction 2 Frequency Domain Modelling 3 Transient Performance and the s-plane 4 Block Diagrams 5 Feedback System Characteristics Assign 1 Due 6 Root Locus 7 Root Locus 2 Assign

More information

MAE143a: Signals & Systems (& Control) Final Exam (2011) solutions

MAE143a: Signals & Systems (& Control) Final Exam (2011) solutions MAE143a: Signals & Systems (& Control) Final Exam (2011) solutions Question 1. SIGNALS: Design of a noise-cancelling headphone system. 1a. Based on the low-pass filter given, design a high-pass filter,

More information

Robust PID and Fractional PI Controllers Tuning for General Plant Model

Robust PID and Fractional PI Controllers Tuning for General Plant Model 2 مجلة البصرة للعلوم الهندسية-المجلد 5 العدد 25 Robust PID and Fractional PI Controllers Tuning for General Plant Model Dr. Basil H. Jasim. Department of electrical Engineering University of Basrah College

More information

Introduction to System Identification and Adaptive Control

Introduction to System Identification and Adaptive Control Introduction to System Identification and Adaptive Control A. Khaki Sedigh Control Systems Group Faculty of Electrical and Computer Engineering K. N. Toosi University of Technology May 2009 Introduction

More information

Index. INDEX_p /15/02 3:08 PM Page 765

Index. INDEX_p /15/02 3:08 PM Page 765 INDEX_p.765-770 11/15/02 3:08 PM Page 765 Index N A Adaptive control, 144 Adiabatic reactors, 465 Algorithm, control, 5 All-pass factorization, 257 All-pass, frequency response, 225 Amplitude, 216 Amplitude

More information

Design and Comparative Analysis of Controller for Non Linear Tank System

Design and Comparative Analysis of Controller for Non Linear Tank System Design and Comparative Analysis of for Non Linear Tank System Janaki.M 1, Soniya.V 2, Arunkumar.E 3 12 Assistant professor, Department of EIE, Karpagam College of Engineering, Coimbatore, India 3 Associate

More information

Determining Controller Constants to Satisfy Performance Specifications

Determining Controller Constants to Satisfy Performance Specifications Determining Controller Constants to Satisfy Performance This appendix presents a procedure for determining the tuning constants for feed back controllers that satisfy robust, time-domain performance specifications.

More information

An improved auto-tuning scheme for PI controllers

An improved auto-tuning scheme for PI controllers ISA Transactions 47 (2008) 45 52 www.elsevier.com/locate/isatrans An improved auto-tuning scheme for PI controllers Rajani K. Mudi a,, Chanchal Dey b, Tsu-Tian Lee c a Department of Instrumentation and

More information

DESIGN OF AN ON-LINE TITRATOR FOR NONLINEAR ph CONTROL

DESIGN OF AN ON-LINE TITRATOR FOR NONLINEAR ph CONTROL DESIGN OF AN ON-LINE TITRATOR FOR NONLINEAR CONTROL Alex D. Kalafatis Liuping Wang William R. Cluett AspenTech, Toronto, Canada School of Electrical & Computer Engineering, RMIT University, Melbourne,

More information

Control System Design

Control System Design ELEC ENG 4CL4: Control System Design Notes for Lecture #36 Dr. Ian C. Bruce Room: CRL-229 Phone ext.: 26984 Email: ibruce@mail.ece.mcmaster.ca Friday, April 4, 2003 3. Cascade Control Next we turn to an

More information

Simulation Study on Pressure Control using Nonlinear Input/Output Linearization Method and Classical PID Approach

Simulation Study on Pressure Control using Nonlinear Input/Output Linearization Method and Classical PID Approach Simulation Study on Pressure Control using Nonlinear Input/Output Linearization Method and Classical PID Approach Ufuk Bakirdogen*, Matthias Liermann** *Institute for Fluid Power Drives and Controls (IFAS),

More information

Control 2. Proportional and Integral control

Control 2. Proportional and Integral control Control 2 Proportional and Integral control 1 Disturbance rejection in Proportional Control Θ i =5 + _ Controller K P =20 Motor K=2.45 Θ o Consider first the case where the motor steadystate gain = 2.45

More information

AN INTRODUCTION TO THE CONTROL THEORY

AN INTRODUCTION TO THE CONTROL THEORY Open-Loop controller An Open-Loop (OL) controller is characterized by no direct connection between the output of the system and its input; therefore external disturbance, non-linear dynamics and parameter

More information

YTÜ Mechanical Engineering Department

YTÜ Mechanical Engineering Department YTÜ Mechanical Engineering Department Lecture of Special Laboratory of Machine Theory, System Dynamics and Control Division Coupled Tank 1 Level Control with using Feedforward PI Controller Lab Date: Lab

More information

Iterative Controller Tuning Using Bode s Integrals

Iterative Controller Tuning Using Bode s Integrals Iterative Controller Tuning Using Bode s Integrals A. Karimi, D. Garcia and R. Longchamp Laboratoire d automatique, École Polytechnique Fédérale de Lausanne (EPFL), 05 Lausanne, Switzerland. email: alireza.karimi@epfl.ch

More information

A FEEDBACK STRUCTURE WITH HIGHER ORDER DERIVATIVES IN REGULATOR. Ryszard Gessing

A FEEDBACK STRUCTURE WITH HIGHER ORDER DERIVATIVES IN REGULATOR. Ryszard Gessing A FEEDBACK STRUCTURE WITH HIGHER ORDER DERIVATIVES IN REGULATOR Ryszard Gessing Politechnika Śl aska Instytut Automatyki, ul. Akademicka 16, 44-101 Gliwice, Poland, fax: +4832 372127, email: gessing@ia.gliwice.edu.pl

More information

D(s) G(s) A control system design definition

D(s) G(s) A control system design definition R E Compensation D(s) U Plant G(s) Y Figure 7. A control system design definition x x x 2 x 2 U 2 s s 7 2 Y Figure 7.2 A block diagram representing Eq. (7.) in control form z U 2 s z Y 4 z 2 s z 2 3 Figure

More information

ISA Transactions ( ) Contents lists available at ScienceDirect. ISA Transactions. journal homepage:

ISA Transactions ( ) Contents lists available at ScienceDirect. ISA Transactions. journal homepage: ISA Transactions ( ) Contents lists available at ScienceDirect ISA Transactions journal homepage: www.elsevier.com/locate/isatrans An improved auto-tuning scheme for PID controllers Chanchal Dey a, Rajani

More information

Tuning Method of PI Controller with Desired Damping Coefficient for a First-order Lag Plus Deadtime System

Tuning Method of PI Controller with Desired Damping Coefficient for a First-order Lag Plus Deadtime System PID' Brescia (Italy), March 8-0, 0 FrA. Tuning Method of PI Controller with Desired Damping Coefficient for a First-order Lag Plus Deadtime System Yuji Yamakawa*. Yohei Okada** Takanori Yamazaki***. Shigeru

More information

Control of Electromechanical Systems

Control of Electromechanical Systems Control of Electromechanical Systems November 3, 27 Exercise Consider the feedback control scheme of the motor speed ω in Fig., where the torque actuation includes a time constant τ A =. s and a disturbance

More information

PID control of FOPDT plants with dominant dead time based on the modulus optimum criterion

PID control of FOPDT plants with dominant dead time based on the modulus optimum criterion Archives of Control Sciences Volume 6LXII, 016 No. 1, pages 5 17 PID control of FOPDT plants with dominant dead time based on the modulus optimum criterion JAN CVEJN The modulus optimum MO criterion can

More information

Learn2Control Laboratory

Learn2Control Laboratory Learn2Control Laboratory Version 3.2 Summer Term 2014 1 This Script is for use in the scope of the Process Control lab. It is in no way claimed to be in any scientific way complete or unique. Errors should

More information

Control of Manufacturing Processes

Control of Manufacturing Processes Control of Manufacturing Processes Subject 2.830 Spring 2004 Lecture #18 Basic Control Loop Analysis" April 15, 2004 Revisit Temperature Control Problem τ dy dt + y = u τ = time constant = gain y ss =

More information

Comparative study of three practical IMC algorithms with inner controller of first and second order

Comparative study of three practical IMC algorithms with inner controller of first and second order Journal of Electrical Engineering, Electronics, Control and Computer Science JEEECCS, Volume 2, Issue 4, pages 2-28, 206 Comparative study of three practical IMC algorithms with inner controller of first

More information

A New Internal Model Control Method for MIMO Over-Actuated Systems

A New Internal Model Control Method for MIMO Over-Actuated Systems Vol. 7, No., 26 A New Internal Model Control Method for MIMO Over-Actuated Systems Ahmed Dhahri University of Tuins El Manar, National Engineering School of Tunis, Laboratory of research in Automatic Control,

More information

Chapter 2 Review of Linear and Nonlinear Controller Designs

Chapter 2 Review of Linear and Nonlinear Controller Designs Chapter 2 Review of Linear and Nonlinear Controller Designs This Chapter reviews several flight controller designs for unmanned rotorcraft. 1 Flight control systems have been proposed and tested on a wide

More information

Chapter 15 - Solved Problems

Chapter 15 - Solved Problems Chapter 5 - Solved Problems Solved Problem 5.. Contributed by - Alvaro Liendo, Universidad Tecnica Federico Santa Maria, Consider a plant having a nominal model given by G o (s) = s + 2 The aim of the

More information

EE3CL4: Introduction to Linear Control Systems

EE3CL4: Introduction to Linear Control Systems 1 / 17 EE3CL4: Introduction to Linear Control Systems Section 7: McMaster University Winter 2018 2 / 17 Outline 1 4 / 17 Cascade compensation Throughout this lecture we consider the case of H(s) = 1. We

More information

Classify a transfer function to see which order or ramp it can follow and with which expected error.

Classify a transfer function to see which order or ramp it can follow and with which expected error. Dr. J. Tani, Prof. Dr. E. Frazzoli 5-059-00 Control Systems I (Autumn 208) Exercise Set 0 Topic: Specifications for Feedback Systems Discussion: 30.. 208 Learning objectives: The student can grizzi@ethz.ch,

More information

THE THEORY, DEVELOPMENT, AND IMPLEMENTATION OF PARTITIONED ERROR CONTROL. Mark Leland Rutherford. Dissertation. Submitted to the Faculty of the

THE THEORY, DEVELOPMENT, AND IMPLEMENTATION OF PARTITIONED ERROR CONTROL. Mark Leland Rutherford. Dissertation. Submitted to the Faculty of the THE THEORY, DEVELOPMENT, AND IMPLEMENTATION OF PARTITIONED ERROR CONTROL By Mark Leland Rutherford Dissertation Submitted to the Faculty of the Graduate School of Vanderbilt University in partial fulfillment

More information

A Method for PID Controller Tuning Using Nonlinear Control Techniques*

A Method for PID Controller Tuning Using Nonlinear Control Techniques* A Method for PID Controller Tuning Using Nonlinear Control Techniques* Prashant Mhaskar, Nael H. El-Farra and Panagiotis D. Christofides Department of Chemical Engineering University of California, Los

More information

Chapter 7 Interconnected Systems and Feedback: Well-Posedness, Stability, and Performance 7. Introduction Feedback control is a powerful approach to o

Chapter 7 Interconnected Systems and Feedback: Well-Posedness, Stability, and Performance 7. Introduction Feedback control is a powerful approach to o Lectures on Dynamic Systems and Control Mohammed Dahleh Munther A. Dahleh George Verghese Department of Electrical Engineering and Computer Science Massachuasetts Institute of Technology c Chapter 7 Interconnected

More information

Control of MIMO processes. 1. Introduction. Control of MIMO processes. Control of Multiple-Input, Multiple Output (MIMO) Processes

Control of MIMO processes. 1. Introduction. Control of MIMO processes. Control of Multiple-Input, Multiple Output (MIMO) Processes Control of MIMO processes Control of Multiple-Input, Multiple Output (MIMO) Processes Statistical Process Control Feedforward and ratio control Cascade control Split range and selective control Control

More information

Multi-objective LQR with Optimum Weight Selection to Design FOPID Controllers for Delayed Fractional Order Processes

Multi-objective LQR with Optimum Weight Selection to Design FOPID Controllers for Delayed Fractional Order Processes Multi-objective LQR with Optimum Weight Selection to Design FOPID Controllers for Delayed Fractional Order Processes Saptarshi Das a,b *, Indranil Pan b,c, and Shantanu Das d a) School of Electronics and

More information

Solutions for Tutorial 10 Stability Analysis

Solutions for Tutorial 10 Stability Analysis Solutions for Tutorial 1 Stability Analysis 1.1 In this question, you will analyze the series of three isothermal CSTR s show in Figure 1.1. The model for each reactor is the same at presented in Textbook

More information