CENTRAL TERMOELÉCTRICA ANDINA UNIDAD Nº 1

Size: px
Start display at page:

Download "CENTRAL TERMOELÉCTRICA ANDINA UNIDAD Nº 1"

Transcription

1 PROYECTO PROJECT CENTRAL TERMOELÉCTRICA ANDINA UNIDAD Nº 1 TÍTULO TITLE Technical Data and curves of the Generator Nº DE DOCUMENTO PROYECTO PROJECT DOCUMENT Nº CTA-12-MA EHP-SK-0086_Rev00 REV 00 FECHA DATE 01/02/08 EDITADO PARA ISSUED FOR approval 00/4 01/02/2008 Kaluza For approval / customer rev 00 = Siemens rev 4 Kaluza Ebert RE V FECHA DATE PREPARADO PREPARED DESCRIPCIÓN DESCRIPTION REVISADO CHECKED APROBADO APPROVED Nº SUBCONTRATISTA SUBCONTRACTOR Nº SUBCONTRATISTA SUBCONTRACTOR EDITADO ISSUED PARA INFORMACIÓN / FOR INFORMATION... PARA APROBACIÓN / FOR APPROVAL... PARA PETICIÓN OFERTA-COMPRA / FOR ASKING QUOTATION PURCHASING.. PARA CONSTRUCCIÓN / FOR CONSTRUCTION... SEGÚN LO CONSTRUIDO / AS- BUILT... OTROS / OTHERS... ESTE DOCUMENTO CONTIENE INFORMACIÓN PROPIETARIA Y NO PUEDE SER DUPLICADO, PROCESADO O CEDIDO A TERCEROS PARA UN USO DISTINTO AL DE ESTE PROYECTO Y EL OBJETO PARA EL QUE HA SIDO PREVISTO SIN LA AUTORIZACIÓN ESCRITA DE COBRA. THIS DOCUMENT CONTAINS PROPIETARY INFORMATION AND CAN NOT BE DUPLICATED, PROCESSED OR DISCLOSED TO THIRD PARTIES FOR ANY USE OTHER THAN THIS PROJECT AND THE PURPOSE FOR WHICH IT IS INTENDED FOR WITHOUT THE WRITTEN CONSENT OF COBRA

2 S for Steam- and Gas-Turbines from Erfurt Plant TECHNICAL DATA FOR GENERATOR OFFER Type: SGen5-100A-2P FOR THE PROJECT S N = 206,30 MVA PF = 0,80 U N = 15,75 kv f N = 50 Hz Design corresponds to: I N = 7,56 ka n N = 3000 rpm IEC 34 CONTENT OF THIS FILE Datasheet: Electrical Data, Losses and Efficiencies 0 Reactive Capability Curve 1 No Load Saturation and Short-Circuit Characteristic 2 V-Curves at Rated Voltage 3 Unbalanced Load-Time-Curve 4 Mechanical Data Sheet 5 Efficiency vs. Power and Power Factor 7 Losses vs. Power and Power Factor 8 Armature Current and Field Voltage vs. Time 10 Limitation of Earth Fault Current vs. Time 11 Short Time Voltage/Frequency Capability 12 Mechanical Air Gap Moment in Case of 2 Poles Short Circuit 13 Short Circuit Currents and Time Constants 14 Short Circuit Decrement Curve - 3 poles Short Circuit 15 Short Circuit Decrement Curve - 2 poles Short Circuit 16 Short Circuit Decrement Curve - 1 pole Short Circuit to Earth 17 Vibration Limits 19 CTA-12-MA-EHP-SK-0086_00 The given data are calculated values (if not indicated differently) Die angegebene Werte sind Rechenwerte (wenn nicht anders bezeichnet) SIEMENS Kaluza Rev. 004 Power Generation (PG) - Erfurt Plant Revision P251 G

3 Electrical Data, Losses and Efficiencies Generator Type: SGen5-100A-2P Load Point N A Standard IEC 34 IEC 34 Thermal Classification: Design / Using F / B F / B Apparent Power MVA 206,3 194,1 Active Power MW 165,0 165,0 Cold Air Temperature C 43,0 43,0 Voltage kv 15,75 15,75 Voltage Deviation + - % 5,0 5,0 5,0 5,0 Armature Current ka 7,562 7,115 Frequency Speed Hz rpm Power Factor - 0,80 0,85 Excitation No load I f0 U f0 A V Requirements 4/4-load I fn U fn A V /4-load I f5/4 U f5/4 A V Cooling Air Losses kw Air flow Temp. rise m 3 /s K 50,0 41,1 50,0 39,0 Sudden-SCC I S : 3-phase (peak) ka at No-Load and I K3 : 3-ph. (sustained at I fn ) ka 10,9 10,1 Nominal Voltage I K2 : 2-ph. (sustained at I fn ) ka 17,5 16,2 Short Circuit Ratio - 0,47 0,50 Reactances x" d unsat. sat. % % 19,1 14,3 17,9 13,5 x' d unsat. sat. % % 25,8 23,2 24,3 21,8 calculated values, x d unsat. sat. % % tolerance +/-15% x'' q unsat. sat. % % 21,0 15,7 19,7 14,8 acc. IEC x' q unsat. sat. % % 50,1 45,3 46,0 41,6 x q unsat. sat. % % x 2 unsat. sat. % % 20,0 15,0 18,8 14,1 x 0 unsat. % 10,1 9,5 x leak unsat. % 14,9 14,0 Time constants T'' d s 0,030 0,030 at 75 C T' d s 1,342 1,342 winding T' d0 s 13,680 13,680 temperature T'' d0 s 0,044 0,044 T a s 0,490 0,490 Resistance Stator winding / phase mω 0,96 0,96 at 20 C Rotor winding mω 195,51 195,51 Voltage PF = rated P.F. % 37,4 35,4 regulation PF = 1,00 % 30,9 29,6 Max. unbalanced Continuous % load Short time i 2 2 * t s Power at Underexcited Mvar 81,6 81,6 PF = 0 Overexcited Mvar 167,0 150,3 Winding temp. rise Stator (RTD) K C Winding temp. Rotor (average) K C Losses Bearing losses kw Windage losses kw Core losses kw Short circuit losses kw Rotor I 2 R losses kw Total losses kw Efficiencies with tolerance 4/4-load % 98,69 98,76 at static excitation 3/4-load % 98,55 98,60 and rated P.F. 2/4-load % 98,15 98,18 (incl. bearing losses) 1/4-load % 96,74 96,76

4 Reactive Capability Curve Load Point Rated A S N 206,30 MVA 194,10 MVA U N 15,75 kv 15,75 kv I N 7,562 ka 7,115 ka f N 50 Hz 50 Hz PF 0,80 0,85 T Cold 43,0 C 43,0 C Q/S 1,0 N 0,00 0,20 0,40 0,60 0,70 0,9 0,8 0,80 0,7 0,85 0,6 0,5 0,90 0,4 0,95 0,3 Underexcited Overexcited 0,2 0,1 0,0-0,1-0,2-0,3 0,0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 0,975 1,00 0,975 0,95-0,4-0,5 0,00 0,20 0,40 0,60 0,70 0,80 0,85 0,90 P/S N

5 No Load Saturation and Short-Circuit Characteristic Generator - Typ: SGen5-100A-2P S N = 206,30 MVA PF = 0,80 S(1,0) = 15,6 % U N = 15,75 kv SCR = 0,47 S(1,2) = 56,7 % I N = 7,562 ka I f0 = 363 A f N = 50 Hz I fn = 1112 A 2 U / U N I / I N 1,4 1,8 1,2 1,6 1,4 1 1,2 0,8 1 0,6 0,8 0,6 0,4 0,4 0,2 0, ,2 0,4 0,6 0,8 1 1,2 air-gap line no load saturation short circuit characteristic I F [ka]

6 V-Curves at Rated Voltage Generator - Typ: SGen5-100A-2P S N = 206,30 MVA PF = 0,80 I f0 = 363 A U N = 15,75 kv f N = 50 Hz I fn = 1112 A I N = 7,562 ka T Cold Air = 43,0 C practical stability limit (rotor angle safety margin at 82 degrees) rated rated ,10 1,00 0,90 0,80 0, ,60 0,50 heating limit of stator and rotor winding 4/4 3/4 2/4 1/4 0,00 0,10 0,20 0,30 0,40 0,50 0,60 0,70 0,80 0,90 1,00 1,10 I F / I FN 0,40 0,30 0,20 0,10 0,00 I / I N V-Curves Refer to Apparent Power

7 Unbalanced Load-Time-Curve Generator - Typ: SGen5-100A-2P U N = 15,75 kv f N = 50 Hz i2² * t = 10 sec. 0,10 * i2 continuous time t [s] negative sequence current i 2 [p.u.]

8 Mechanical Data Sheet U N = 15,75 kv f N = 50 Hz T Warm Air = 84,1 C P V, Cooler = 2148 kw Dimensions [mm]: L1 = 9900 H1 = 1700 Overall weight: kg L2 = 7750 H2 = 3900 Stator weight: kg L3 = 7300 H3 1) = Rotor weight: kg W1 = 4000 W2 = 1600 Rotor moment of inertia: 6900 kgm² L4 = H4 = 8100 Oil flow for both bearings: 280 l/min for rotor withdrawal crane hook height breakaway torque w. jacking oil: 273 Nm Preliminary values. breakaway torque w/o jacking oil: Nm Exact values are part of detail engineering. Thermal time constants [min]: Stator Winding: Rotor Winding: 19,9 min 7,7 min Estimation for required cooling water 2) flow (for TEWAC - cooling): T A(cooling air) - T W(cooling water) Standard water temperature rise Required cooling water flow 15 K 10 K 203 m³/hour 10 K 7 K 264 m³/hour 5 K 3,5 K 528 m³/hour 1) For cooler in top position. 2) Data are generated independent of cooling method; for DAC- or CACA-applications these data are not applicable.

9 Efficiency vs. Apparent Power and Power Factor U N = 15,75 kv f N = 50 Hz Efficiency acc. to: IEC 34 Apparent Power Output MVA 51,6 103,2 154,7 206,3 p.u. 0,25 0,50 0,75 1,00 Efficiency at P.F. = 1,00 % 97,42 98,56 98,89 99,00 Efficiency at nominal P.F. = 0,80 % 96,74 98,15 98,55 98,69 99,5 99,0 Generator Efficiency [%] 98,5 98,0 97,5 97,0 Power Factor = 1,0 Nominal Power Factor 96,5 0,25 0,50 0,75 1,00 Apparent Power Output / Rated Apparent Power Output [p.u.]

10 Total Losses vs. Apparent Power and Power Factor U N = 15,75 kv f N = 50 Hz Apparent Power Output MVA 51,6 103,2 154,7 206,3 p.u. 0,25 0,50 0,75 1,00 Losses at P.F. = 1,00 kw Losses at nominal P.F. = 0,80 kw Generator Losses [kw] Power Factor = 1,0 Nominal Power Factor 0 0,25 0,50 0,75 1,00 Apparent Power Output / Rated Apparent Power Output [p.u.]

11 Stator Current and Field Voltage versus Time U N = 15,75 kv f N = 50 Hz I fn = 1112 A Time [s] Stator Current I/I N [%] Field Voltage U f /U fn [%] Fullfills IEC and ANSI requirements Stator Current Field Voltage Stator Current [%] Field Voltage [%] Time [s] 100 The generator is capable of operating at 130 percent of rated stator current for 1 min. The generator field winding is capable of operating at 125 percent of rated load field voltage for 1 min. Both requirements are fullfilled starting from stabilized temperatures at rated conditions. It is recognized that winding temperatures under these conditiones will exceed rated-load values. Number of such operations should be limited to two times a year (corresponds to ANSI and IEC).

12 Limitation of Earth Fault Current versus Time U N = 15,75 kv f N = 50 Hz A for 30s 10 Time [s] 1 0,1 0, I 0 [A] I 0 [A] Time [s] Ground fault current over neutral point to earth Limitation time for I 0 to prevent damage from stator iron core Diagram basis is I² * t = const.; 10 A for 30 s is Siemens standard for dimensioning earthing. When exceeding limitation curve, stator iron is endangered melting in the fault region. Worst case is earth fault on phase side (opposite to neutral point side) of winding. In that case the potential of neutral point changes from zero to phase-to-phase-voltage /. 3 Fault current and recommended trip time depend on earthing resistance.

13 Short Time Voltage/Frequency Capability U N = 15,75 kv f N = 50 Hz Continuous operation limits (S1) Voltage max.: +5,0 % 1) Frequency max.: +2,0 % Voltage min.: -5,0 % Frequency min.: -2,0 % 1) 1) In case of overvoltage and underfrequency at the same time the sum of both deviations for continuous operation is limited to: 5,0 % Minimum requirements IEC 34-3 Item 5 Voltage: +/- 5 % Frequency: +/- 2 % Permissible Duration Time [s] ,0 1,1 1,2 1,3 1,4 1,5 Volts per Hertz [p.u]

14 Mechanical Air Gap Moment in Case of 2 poles Short Circuit U N = 15,75 kv f N = 50 Hz Equation for the moment at 2-pole short circuit: M = M 1 *e -t/t1 sin ωt - M 2 *e -t/t2 sin 2ωt + M 3 *e -t/t3 M 1 = 4488 knm T 1 = 0,196 s M peak = 6528 knm M 2 = 2244 knm T 2 = 0,163 s M Nom. = 657 knm M 3 = 930 knm T 3 = 0,241 s Short Circuit Moment [knm] , ,1 0,2 0,3 0,4 0, Time [s] Values based on no load and nominal voltage

15 Short Circuit Currents and Time Constants U N = 15,75 kv f N = 50 Hz > Values based on 100% load and terminal voltage = 1,05 p.u. < Three Phase Short Circuit Asymmetrical Current (Peak) 1) I p = 153,7 ka Asymmetrical Current (RMS) I a = 104,6 ka Symmetrical Current (RMS) 2) I'' i = 60,4 ka DC Current I dc = 85,4 ka Sustained SC Current I s = 10,9 ka Armature Time Constant T a = 0,490 sec Transient Time Constant T' d = 1,492 sec Subtransient Time Constant T'' d = 0,027 sec Line To Line Asymmetrical Current (Peak) 1) I pl = 129,9 ka Asymmetrical Current (RMS) I al = 88,4 ka Symmetrical Current (RMS) 2) I'' il = 51,0 ka DC Current I dcl = 72,2 ka Sustained SC Current I sl = 17,6 ka Armature Time Constant T a = 0,490 sec Transient Time Constant T' dl = 2,295 sec Subtransient Time Constant T'' dl = 0,034 sec Line To Neutral Asymmetrical Current (Peak) 1) I pn = 171,8 ka Asymmetrical Current (RMS) I an = 116,9 ka Symmetrical Current (RMS) 2) I'' in = 67,5 ka DC Current I dcn = 95,5 ka Sustained SC Current I sn = 29,4 ka Armature Time Constant T an = 0,425 sec Transient Time Constant T' dn = 2,730 sec Subtransient Time Constant T'' dn = 0,036 sec 1) = 1,8*sqrt(2)*I k " 2) initial AC short circuit current (Anfangs-Kurzschlusswechselstrom I k ")

16 Calculated Three Phase Short Circuit Decrement Curves U N = 15,75 kv f N = 50 Hz RMS ASYMMETRICAL CURRENT RMS SYMMETRICAL CURRENT DC COMPONENT Current [ka] SUSTAINED SC CURRENT 0 0,0 0,5 1,0 1,5 2,0 Time [s] > Values based on 100% load and terminal voltage = 1,05 p.u. <

17 Calculated Line-to-Line Short Circuit Decrement Curves U N = 15,75 kv f N = 50 Hz RMS ASYMMETRICAL CURRENT RMS SYMMETRICAL CURRENT DC COMPONENT Current [ka] SUSTAINED SC CURRENT ,0 0,5 1,0 1,5 2,0 Time [s] > Values based on 100% load and terminal voltage = 1,05 p.u. <

18 Calculated Line-to-Neutral Short Circuit Decrement Curves U N = 15,75 kv f N = 50 Hz RMS ASYMMETRICAL CURRENT RMS SYMMETRICAL CURRENT DC COMPONENT Current [ka] SUSTAINED SC CURRENT ,0 0,5 1,0 1,5 2,0 Time [s] > Values based on 100% load and terminal voltage = 1,05 p.u. <

19 S for Steam- and Gas-Turbines Information from Erfurt Manufacturing Plant Vibration Limits The vibration limits are kept to zone A of the ISO 7919 and ISO at generator construction and shaft alignment according to manual. For test field conditiones with temporary foundation Zone B can be used. When other (lower) limits specified - e.g. API - project-specific calculations are required. Shaft Vibration Limits - ISO Peak-to-Peak-Values in µm Zone Speed Steam-Turbine Industrial Gas-Turbine Generator Application Generator rpm ISO ISO ISO A B Alarm C Trip Bearing Housing Vibration Limits - ISO v eff in mm/s Zone Speed Steam-Turbine Industrial Gas-Turbine Generator Application Generator rpm ISO ISO ISO A ,8 3,5 4, ,8 3,5 4, ,8 3,5 3, ,8 3,5 3,5 B ,5 11,8 7,1 11 9,3 14,7 Alarm ,5 11,8 7,1 11 9,3 14,7 C ,3 8,5 7,1 11 7,1 11 Trip ,3 8,5 7,1 11 7,1 11 SIEMENS CTA-12-MA-EHP-SK-0086_00 Kaluza Rev. 004 Power Generation (PG) - Erfurt Plant P251 G

Technical Data Sheet for AvK-Alternators

Technical Data Sheet for AvK-Alternators Technical Data Sheet for AvK-Alternators FM 7.3-5 Date: 3/1/13 Customer: GENERIC DATASHEET only Project No.: AvK Reference: dig12i_4_6_416 Object data: Site: Prime Mover: Application: Stationary Power

More information

Technical Data Sheet for AvK-Alternators

Technical Data Sheet for AvK-Alternators Technical Data Sheet for AvK-Alternators FM 7.3-5 Date: 2/1/14 Customer: GENERIC DATASHEET only Project No.: AvK Reference: dsg74l1_6_6_69_a48m965 Object data: Site: Prime Mover: Application: Stationary

More information

Synchronous Machines

Synchronous Machines Synchronous Machines Synchronous generators or alternators are used to convert mechanical power derived from steam, gas, or hydraulic-turbine to ac electric power Synchronous generators are the primary

More information

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015 ECE 325 Electric Energy System Components 7- Synchronous Machines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapters 16-17) Synchronous Generators Synchronous Motors 2 Synchronous Generators

More information

Generators. What its all about

Generators. What its all about Generators What its all about How do we make a generator? Synchronous Operation Rotor Magnetic Field Stator Magnetic Field Forces and Magnetic Fields Force Between Fields Motoring Generators & motors are

More information

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1 ower ystems ower ystem tability QUETION BANK. A cylindrical rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load

More information

The Operation of a Generator on Infinite Busbars

The Operation of a Generator on Infinite Busbars The Operation of a Generator on Infinite Busbars In order to simplify the ideas as much as possible the resistance of the generator will be neglected; in practice this assumption is usually reasonable.

More information

MKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits

MKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits MKV AC Capacitors B 25 835 High dielectric strength High peak-current capability Especially suitable for snubber circuits Construction Self-healing Plastic dielectric Oil-impregnated tubular windings (no

More information

Dynamics of the synchronous machine

Dynamics of the synchronous machine ELEC0047 - Power system dynamics, control and stability Dynamics of the synchronous machine Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 38 Time constants and

More information

Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines)

Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines) Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines) d axis: L fd L F - M R fd F L 1d L D - M R 1d D R fd R F e fd e F R 1d R D Subscript Notations: ( ) fd ~ field winding quantities

More information

Dynamic simulation of a five-bus system

Dynamic simulation of a five-bus system ELEC0047 - Power system dynamics, control and stability Dynamic simulation of a five-bus system Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 16 System modelling

More information

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL 1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems:

More information

CHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS

CHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS 47 CHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS 5.1 INTRODUCTION This chapter describes the simulation model and experimental set up used for the fault analysis. For the simulation set up, the

More information

3 d Calculate the product of the motor constant and the pole flux KΦ in this operating point. 2 e Calculate the torque.

3 d Calculate the product of the motor constant and the pole flux KΦ in this operating point. 2 e Calculate the torque. Exam Electrical Machines and Drives (ET4117) 11 November 011 from 14.00 to 17.00. This exam consists of 5 problems on 4 pages. Page 5 can be used to answer problem 4 question b. The number before a question

More information

ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models

ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas A&M University, overbye@tamu.edu 1 Announcements Read Chapter

More information

Chapter 6: Efficiency and Heating. 9/18/2003 Electromechanical Dynamics 1

Chapter 6: Efficiency and Heating. 9/18/2003 Electromechanical Dynamics 1 Chapter 6: Efficiency and Heating 9/18/2003 Electromechanical Dynamics 1 Losses As a machine transforms energy from one form to another there is always a certain power loss the loss is expressed as heat,

More information

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A 1. What are the advantages of an inter connected system? The advantages of an inter-connected system are

More information

A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications. Chapter 8 2 Generator Protection 2

A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications. Chapter 8 2 Generator Protection 2 DRAFT and INCOMPLETE Table of Contents from A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications Chapter 8 Generator Protection 8. Introduction 8. Generator Protection

More information

From now, we ignore the superbar - with variables in per unit. ψ ψ. l ad ad ad ψ. ψ ψ ψ

From now, we ignore the superbar - with variables in per unit. ψ ψ. l ad ad ad ψ. ψ ψ ψ From now, we ignore the superbar - with variables in per unit. ψ 0 L0 i0 ψ L + L L L i d l ad ad ad d ψ F Lad LF MR if = ψ D Lad MR LD id ψ q Ll + Laq L aq i q ψ Q Laq LQ iq 41 Equivalent Circuits for

More information

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.685 Electric Machines Problem Set 10 Issued November 11, 2013 Due November 20, 2013 Problem 1: Permanent

More information

UNIT I INTRODUCTION Part A- Two marks questions

UNIT I INTRODUCTION Part A- Two marks questions ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR-621220 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING DESIGN OF ELECTRICAL MACHINES UNIT I INTRODUCTION 1. Define specific magnetic

More information

POWER SYSTEM STABILITY AND CONTROL

POWER SYSTEM STABILITY AND CONTROL POWER SYSTEM STABILITY AND CONTROL P. KUNDUR Vice-President, Power Engineering Powertech Labs Inc., Surrey, British Columbia Formerly Manager Analytical Methods and Specialized Studies Department Power

More information

You know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1).

You know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1). Stability 1 1. Introduction We now begin Chapter 14.1 in your text. Our previous work in this course has focused on analysis of currents during faulted conditions in order to design protective systems

More information

University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department

University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department EE471: Electrical Machines-II Tutorial # 2: 3-ph Induction Motor/Generator Question #1 A 100 hp, 60-Hz, three-phase

More information

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES ET 332b Ac Motors, Generators and Power Systems LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES 1 LEARNING OBJECTIVES After this presentation you will be able to: Interpret alternator phasor diagrams

More information

Module 3 : Sequence Components and Fault Analysis

Module 3 : Sequence Components and Fault Analysis Module 3 : Sequence Components and Fault Analysis Lecture 12 : Sequence Modeling of Power Apparatus Objectives In this lecture we will discuss Per unit calculation and its advantages. Modeling aspects

More information

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10

More information

Loss analysis of a 1 MW class HTS synchronous motor

Loss analysis of a 1 MW class HTS synchronous motor Journal of Physics: Conference Series Loss analysis of a 1 MW class HTS synchronous motor To cite this article: S K Baik et al 2009 J. Phys.: Conf. Ser. 153 012003 View the article online for updates and

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation

More information

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER 1 RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER Dr. Swarn S. Kalsi, David Madura, and Michael Ross American Superconductor Corporation (USA) Abstract: A high-temperature

More information

Introduction to Synchronous. Machines. Kevin Gaughan

Introduction to Synchronous. Machines. Kevin Gaughan Introduction to Synchronous Machines Kevin Gaughan The Synchronous Machine An AC machine (generator or motor) with a stator winding (usually 3 phase) generating a rotating magnetic field and a rotor carrying

More information

CHAPTER 3 ANALYSIS OF THREE PHASE AND SINGLE PHASE SELF-EXCITED INDUCTION GENERATORS

CHAPTER 3 ANALYSIS OF THREE PHASE AND SINGLE PHASE SELF-EXCITED INDUCTION GENERATORS 26 CHAPTER 3 ANALYSIS OF THREE PHASE AND SINGLE PHASE SELF-EXCITED INDUCTION GENERATORS 3.1. INTRODUCTION Recently increase in energy demand and limited energy sources in the world caused the researchers

More information

T20WN. Data Sheet. Torque transducers. Special features. Installation example with bellows couplings. B en

T20WN. Data Sheet. Torque transducers. Special features. Installation example with bellows couplings. B en T20WN Torque transducers Data Sheet Special features - Nominal (rated) torques 0.1 N m, 0.2 N m, 0. N m, 1 N m, 2 N m, N m, 10 N m, 20 N m, 0 N m, 100 N m, 200 N m - Accuracy class: 0.2 - Contactless transmission

More information

7. Transient stability

7. Transient stability 1 7. Transient stability In AC power system, each generator is to keep phase relationship according to the relevant power flow, i.e. for a certain reactance X, the both terminal voltages V1and V2, and

More information

GENERATOR INTERCONNECTION APPLICATION

GENERATOR INTERCONNECTION APPLICATION GENERATOR INTERCONNECTION APPLICATION FOR BUY-ALL/SELL-ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 1 MW Electric Utility Contact Information Great Lakes Energy

More information

ECE 421/521 Electric Energy Systems Power Systems Analysis I 3 Generators, Transformers and the Per-Unit System. Instructor: Kai Sun Fall 2013

ECE 421/521 Electric Energy Systems Power Systems Analysis I 3 Generators, Transformers and the Per-Unit System. Instructor: Kai Sun Fall 2013 ECE 41/51 Electric Energy Systems Power Systems Analysis I 3 Generators, Transformers and the Per-Unit System Instructor: Kai Sun Fall 013 1 Outline Synchronous Generators Power Transformers The Per-Unit

More information

Tutorial 1 (EMD) Rotary field winding

Tutorial 1 (EMD) Rotary field winding Tutorial 1 (EMD) Rotary field winding The unchorded two-layer three-phase winding of a small synchronous fan drive for a computer has the following parameters: number of slots per pole and phase q = 1,

More information

An Introduction to Electrical Machines. P. Di Barba, University of Pavia, Italy

An Introduction to Electrical Machines. P. Di Barba, University of Pavia, Italy An Introduction to Electrical Machines P. Di Barba, University of Pavia, Italy Academic year 0-0 Contents Transformer. An overview of the device. Principle of operation of a single-phase transformer 3.

More information

KINGS COLLEGE OF ENGINEERING Punalkulam

KINGS COLLEGE OF ENGINEERING Punalkulam KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK

More information

POWER SYSTEM STABILITY

POWER SYSTEM STABILITY LESSON SUMMARY-1:- POWER SYSTEM STABILITY 1. Introduction 2. Classification of Power System Stability 3. Dynamic Equation of Synchronous Machine Power system stability involves the study of the dynamics

More information

DC motors. 1. Parallel (shunt) excited DC motor

DC motors. 1. Parallel (shunt) excited DC motor DC motors 1. Parallel (shunt) excited DC motor A shunt excited DC motor s terminal voltage is 500 V. The armature resistance is 0,5 Ω, field resistance is 250 Ω. On a certain load it takes 20 A current

More information

POWER QUALITY MEASUREMENT PROCEDURE. Version 4 October Power-Quality-Oct-2009-Version-4.doc Page 1 / 12

POWER QUALITY MEASUREMENT PROCEDURE. Version 4 October Power-Quality-Oct-2009-Version-4.doc Page 1 / 12 POWER QUALITY MEASUREMENT PROCEDURE Version 4 October 2009 Power-Quality-Oct-2009-Version-4.doc Page 1 / 12 MEASNET 2009 Copyright all rights reserved This publication may not be reproduced or utilized

More information

Energy Converters. CAD and System Dynamics

Energy Converters. CAD and System Dynamics Institut für Elektrische Energiewandlung Energy Converters CAD and System Dynamics - Tutorials - Issue 2017/2018 M.Sc. Sascha Neusüs / M.Sc. Marcel Lehr Professor Dr.-Ing. habil. Dr. h.c. Andreas Binder

More information

5SJ4...-.HG Circuit Breakers to IEC and UL 489

5SJ4...-.HG Circuit Breakers to IEC and UL 489 Siemens AG 009 5SJ...-.HG Circuit Breakers to IEC and UL 89 BETA Low-Voltage Circuit Protection Compliance with industry standards is a must in today's manufacturing environment. Worldwide acceptance is

More information

Prince Sattam bin Abdulaziz University College of Engineering. Electrical Engineering Department EE 3360 Electrical Machines (II)

Prince Sattam bin Abdulaziz University College of Engineering. Electrical Engineering Department EE 3360 Electrical Machines (II) Chapter # 4 Three-Phase Induction Machines 1- Introduction (General Principles) Generally, conversion of electrical power into mechanical power takes place in the rotating part of an electric motor. In

More information

Synchronous Machines

Synchronous Machines Synchronous machine 1. Construction Generator Exciter View of a twopole round rotor generator and exciter. A Stator with laminated iron core C Slots with phase winding B A B Rotor with dc winding B N S

More information

Chapter 4. Synchronous Generators. Basic Topology

Chapter 4. Synchronous Generators. Basic Topology Basic Topology Chapter 4 ynchronous Generators In stator, a three-phase winding similar to the one described in chapter 4. ince the main voltage is induced in this winding, it is also called armature winding.

More information

Investigation of fan vibration

Investigation of fan vibration Investigation of fan vibration Jacques Muiyser 1, Frank Weissbuch 2, Trung Luu 3, Pascal Malpoix 3 and Hanno Reuter 1,3 1 Department of Mechanical and Mechatronic Engineering, Stellenbosch University 2

More information

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION PART: A 1. Define per unit value of an electrical quantity. Write equation for base impedance with respect to 3-phase system. 2. What is bus admittance

More information

Lesson 17: Synchronous Machines

Lesson 17: Synchronous Machines Lesson 17: Synchronous Machines ET 332b Ac Motors, Generators and Power Systems Lesson 17_et332b.pptx 1 Learning Objectives After this presentation you will be able to: Explain how synchronous machines

More information

Synchronous Machines

Synchronous Machines Synchronous Machines Synchronous Machines n 1 Φ f n 1 Φ f I f I f I f damper (run-up) winding Stator: similar to induction (asynchronous) machine ( 3 phase windings that forms a rotational circular magnetic

More information

Fault Calculation Methods

Fault Calculation Methods ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the

More information

The synchronous machine (detailed model)

The synchronous machine (detailed model) ELEC0029 - Electric Power System Analysis The synchronous machine (detailed model) Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct February 2018 1 / 6 Objectives The synchronous

More information

Doubly salient reluctance machine or, as it is also called, switched reluctance machine. [Pyrhönen et al 2008]

Doubly salient reluctance machine or, as it is also called, switched reluctance machine. [Pyrhönen et al 2008] Doubly salient reluctance machine or, as it is also called, switched reluctance machine [Pyrhönen et al 2008] Pros and contras of a switched reluctance machine Advantages Simple robust rotor with a small

More information

TLF80511TF. Data Sheet. Automotive Power. Low Dropout Linear Fixed Voltage Regulator TLF80511TFV50 TLF80511TFV33. Rev. 1.

TLF80511TF. Data Sheet. Automotive Power. Low Dropout Linear Fixed Voltage Regulator TLF80511TFV50 TLF80511TFV33. Rev. 1. Low Dropout Linear Fixed Voltage Regulator V50 V33 Data Sheet Rev. 1.0, 2014-01-28 Automotive Power Table of Contents 1 Overview....................................................................... 3

More information

1 Unified Power Flow Controller (UPFC)

1 Unified Power Flow Controller (UPFC) Power flow control with UPFC Rusejla Sadikovic Internal report 1 Unified Power Flow Controller (UPFC) The UPFC can provide simultaneous control of all basic power system parameters ( transmission voltage,

More information

Low Drop Voltage Regulator TLE

Low Drop Voltage Regulator TLE Low Drop Voltage Regulator TLE 4296-2 Features Two versions: 3.3 V, 5.0 V Output voltage tolerance ±4% Very low drop voltage Output current: 30 ma Inhibit input Low quiescent current consumption Wide operation

More information

Abstract The capability (P-Q) curve of generator can be determined only on the base of examinations in the power plant, i.e. on the base of: the no-lo

Abstract The capability (P-Q) curve of generator can be determined only on the base of examinations in the power plant, i.e. on the base of: the no-lo CONSTRUCTION OF GENERATOR CAPABILITY CURVES USING THE NEW METHOD FOR DETERMINATION OF POTIER REACTANCE M.M. Kostić*, M. Ivanović*, B. Kostić*, S. Ilić** and D. Ćirić** Electrical Engineering Institute

More information

ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I

ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR-621220 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I Unit I Introduction 1. What are the three basic types

More information

Electromagnetic Energy Conversion Exam 98-Elec-A6 Spring 2002

Electromagnetic Energy Conversion Exam 98-Elec-A6 Spring 2002 Front Page Electromagnetic Energy Conversion Exam 98-Elec-A6 Spring 2002 Notes: Attempt question 1 and FOUR (4) other questions (FVE (5) questions in all). Unless you indicate otherwise, the first five

More information

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department Philadelphia University Faculty of Engineering Student Name Student No: Serial No Final Exam, Second Semester: 2015/2016 Electrical Engineering Department Course Title: Power II Date: 21 st June 2016 Course

More information

EDSA IEC 909 SHORT CIRCUIT ANALYSIS

EDSA IEC 909 SHORT CIRCUIT ANALYSIS 1.0 Tutorial Exercise This tutorial exercise will serve as a validation and verification test for the EDSA IEC 909 short circuit program. The tutorial will be based on two examples documented in the IEC

More information

Characteristics Climatic Category 40/85/56 (IEC 61071) Operating Temperature. 700 ~ 2000 VDC Capacitance Range 0,2 ~ 7,5 µf Capacitance Tolerance

Characteristics Climatic Category 40/85/56 (IEC 61071) Operating Temperature. 700 ~ 2000 VDC Capacitance Range 0,2 ~ 7,5 µf Capacitance Tolerance Polypropylene Film Capacitors for Snubber Applications Features - Very low dissipation factor - Highest peak pulse capability - Double-sided metallized electrodes - Internal series connection - Metal sprayed

More information

Characteristics Climatic Category 40/105/56 (IEC 61071) Operating Temperature. 850 ~ 1200 VDC Capacitance Range 0,33 ~ 3,0 µf Capacitance Tolerance

Characteristics Climatic Category 40/105/56 (IEC 61071) Operating Temperature. 850 ~ 1200 VDC Capacitance Range 0,33 ~ 3,0 µf Capacitance Tolerance Polypropylene Film Capacitors for Snubber Applications Features - 105 C - Very low dissipation factor - High peak pulse capability - Metal sprayed contacts for low ESL - Plates for direct IGBT connection

More information

Data Sheet, Rev. 1.1, February 2008 TLE4294GV50. Low Drop Out Voltage Regulator. Automotive Power

Data Sheet, Rev. 1.1, February 2008 TLE4294GV50. Low Drop Out Voltage Regulator. Automotive Power Data Sheet, Rev. 1.1, February 2008 TLE4294GV50 Low Drop Out Voltage Regulator Automotive Power Low Drop Out Voltage Regulator TLE4294GV50 1 Overview Features Output voltage tolerance ±4% Very low drop

More information

PRODUCT SPECIFICATIONS

PRODUCT SPECIFICATIONS FEATURES AND BENEFITS* Up to 14 year DC life 56V DC working voltage Resistive cell balancing Overvoltage outputs High power density 4U, half-rack package UL registered TYPICAL APPLICATIONS UPS systems

More information

Single Phase Motors Technical Datasheets

Single Phase Motors Technical Datasheets Single Phase Motors Technical Datasheets EN A dynamic, strong and ambitious Group: Orange1 Holding is an international renown Group, one of the most important European manufacturers of single-phase and

More information

Low Drop Voltage Regulator TLE 4295

Low Drop Voltage Regulator TLE 4295 Low Drop Voltage Regulator TLE 4295 Features Four versions: 2.6 V, 3.0 V, 3.3 V, 5.0 V tolerance ±4% Very low drop voltage Output current: 30 ma Power fail output Low quiescent current consumption Wide

More information

EE 451 Power System Stability

EE 451 Power System Stability EE 451 Power System Stability Power system operates in synchronous mode Power system is subjected to a wide range of disturbances (small and large) - Loads and generation changes - Network changes - Faults

More information

Recommended Land Pattern: [mm]

Recommended Land Pattern: [mm] Dimensions: [mm] Recommended Land Pattern: [mm] Electrical Properties: Properties Test conditions Value Unit Tol. Capacitance 1 V/ 1 khz ± 0.2 khz C 150 nf ±10% Rated Voltage U R 310 V (AC) max. Rated

More information

Generators for wind power conversion

Generators for wind power conversion Generators for wind power conversion B. G. Fernandes Department of Electrical Engineering Indian Institute of Technology, Bombay Email : bgf@ee.iitb.ac.in Outline of The Talk Introduction Constant speed

More information

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session Name: Student ID: Signature: THE UNIVERSITY OF NEW SOUTH WALES School of Electrical Engineering & Telecommunications FINALEXAMINATION Session 00 ELEC46 Power System Analysis TIME ALLOWED: 3 hours TOTAL

More information

A Comparative Analysis of Three Phase Induction Motor Performance Evaluation

A Comparative Analysis of Three Phase Induction Motor Performance Evaluation RESEARCH ARTICLE International Journal of Engineering and Techniques - Volume 2 Issue 3, May June 216 OPEN ACCESS A Comparative Analysis of Three Phase Induction Motor Performance Evaluation 1 France O.

More information

6 Chapter 6 Testing and Evaluation

6 Chapter 6 Testing and Evaluation 6 Chapter 6 Testing and Evaluation n this chapter the results obtained during the testing of the LS PMSM prototype are provided. The test results are compared with Weg s LS PMSM machine, WQuattro. The

More information

S P E C I F I C A T I O N S

S P E C I F I C A T I O N S TO : 2009-09-14 S P E C I F I C A T I O N S PRODUCT : CERAMIC CAPACITOR MODEL : DA (X1,Y1) SERIES Manufacturer Customer WRITTEN CHECKED APPROVED WRITTEN CHECKED APPROVED 9/14 9/14 9/14 / / / DONG IL ELECTRONICS

More information

Control of Wind Turbine Generators. James Cale Guest Lecturer EE 566, Fall Semester 2014 Colorado State University

Control of Wind Turbine Generators. James Cale Guest Lecturer EE 566, Fall Semester 2014 Colorado State University Control of Wind Turbine Generators James Cale Guest Lecturer EE 566, Fall Semester 2014 Colorado State University Review from Day 1 Review Last time, we started with basic concepts from physics such as

More information

Chapter 9: Transient Stability

Chapter 9: Transient Stability Chapter 9: Transient Stability 9.1 Introduction The first electric power system was a dc system built by Edison in 1882. The subsequent power systems that were constructed in the late 19 th century were

More information

Preliminary Sizing Design of a 1 MW Low Duty Cycle Switched Reluctance Generator for Aerospace Applications

Preliminary Sizing Design of a 1 MW Low Duty Cycle Switched Reluctance Generator for Aerospace Applications Preliminary Sizing Design of a 1 MW Low Duty Cycle Switched Reluctance Generator for Aerospace Applications Jin-Woo Jung, Ph. D. Student Advisors: Prof. Ali Keyhani Adjunct Prof. Tomy Sebastian Oct. 25,

More information

LO 1: Three Phase Circuits

LO 1: Three Phase Circuits Course: EEL 2043 Principles of Electric Machines Class Instructor: Dr. Haris M. Khalid Email: hkhalid@hct.ac.ae Webpage: www.harismkhalid.com LO 1: Three Phase Circuits Three Phase AC System Three phase

More information

MODULE TITLE : ELECTRICAL SUPPLY AND DISTRIBUTION SYSTEMS

MODULE TITLE : ELECTRICAL SUPPLY AND DISTRIBUTION SYSTEMS MODULE TITLE : ELECTRICAL SUPPLY AND DISTRIBUTION SYSTEMS TOPIC TITLE : THE OPERATION OF THREE-PHASE TRANSFORMERS IN PARALLEL AND GENERATORS ON INFINITE BUSBARS LESSON 2 : OPERATING CHARACTERISTICS OF

More information

Understanding the Inductances

Understanding the Inductances Understanding the Inductances We have identified six different inductances (or reactances) for characterizing machine dynamics. These are: d, q (synchronous), ' d, ' q (transient), '' d,'' q (subtransient)

More information

< HIGH VOLTAGE DIODE MODULES > RM400DG-90F. APPLICATION Traction drives, High Reliability Converters / Inverters, DC choppers

< HIGH VOLTAGE DIODE MODULES > RM400DG-90F. APPLICATION Traction drives, High Reliability Converters / Inverters, DC choppers I F 4A V RRM 45V 2-element in a Pack High insulated Type Soft Recovery Diode AlSiC Baseplate APPLICATION Traction drives, High Reliability Converters / Inverters, DC choppers OUTLINE DRAWING & CIRCUIT

More information

Three Phase Circuits

Three Phase Circuits Amin Electronics and Electrical Communications Engineering Department (EECE) Cairo University elc.n102.eng@gmail.com http://scholar.cu.edu.eg/refky/ OUTLINE Previously on ELCN102 Three Phase Circuits Balanced

More information

CHAPTER 3 INFLUENCE OF STATOR SLOT-SHAPE ON THE ENERGY CONSERVATION ASSOCIATED WITH THE SUBMERSIBLE INDUCTION MOTORS

CHAPTER 3 INFLUENCE OF STATOR SLOT-SHAPE ON THE ENERGY CONSERVATION ASSOCIATED WITH THE SUBMERSIBLE INDUCTION MOTORS 38 CHAPTER 3 INFLUENCE OF STATOR SLOT-SHAPE ON THE ENERGY CONSERVATION ASSOCIATED WITH THE SUBMERSIBLE INDUCTION MOTORS 3.1 INTRODUCTION The electric submersible-pump unit consists of a pump, powered by

More information

TLF80511EJ. Data Sheet. Automotive Power. Low Dropout Linear Fixed Voltage Regulator TLF80511EJV50 TLF80511EJV33. Rev. 1.

TLF80511EJ. Data Sheet. Automotive Power. Low Dropout Linear Fixed Voltage Regulator TLF80511EJV50 TLF80511EJV33. Rev. 1. Low Dropout Linear Fixed Voltage Regulator TLF80511EJV50 TLF80511EJV33 Data Sheet Rev. 1.0, 2014-11-17 Automotive Power Table of Contents 1 Overview.......................................................................

More information

THREE PHASE CAPACITOR For WIND TURBINES

THREE PHASE CAPACITOR For WIND TURBINES RS/Cond 28.04.2003 Pg: 1 / 3 THREE PHASE CAPACITOR For WIND TURBINES Applications: Three-phase capacitor for Wind Turbine has been designed for power factor correction in high harmonic current content.

More information

Characteristics Climatic Category 40/105/56 (IEC 61071)

Characteristics Climatic Category 40/105/56 (IEC 61071) Polypropylene Film Capacitors for Snubber Applications Features - Very low dissipation factor - High peak pulse capability - Plates for direct IGBT connection - Self-healing - 105 C CBB 165 IS Series Applications

More information

DC/DC regulator Input V Output up to 16 A

DC/DC regulator Input V Output up to 16 A PMC 4000 series Contents Product Program...................... 2 Mechanical Data...................... 3 Connections......................... 3 Absolute Maximum Ratings............. 4 Input...............................

More information

Reference Only Spec. No. JEFL243B 0003F-01 P 1/ 6

Reference Only Spec. No. JEFL243B 0003F-01 P 1/ 6 Spec. No. JEFL243B 0003F-01 P 1/ 6 DC Common Mode Choke Coil PLT09HN2003R0P1B Reference Specification 1. Scope This reference specification applies to DC Common Mode Choke Coil (PLT09H Series). 2. Part

More information

Transformer. Transformer comprises two or more windings coupled by a common magnetic circuit (M.C.).

Transformer. Transformer comprises two or more windings coupled by a common magnetic circuit (M.C.). . Transformers Transformer Transformer comprises two or more windings coupled by a common magnetic circuit (M.C.). f the primary side is connected to an AC voltage source v (t), an AC flux (t) will be

More information

TLE42344G. Data Sheet. Automotive Power. Low Dropout Linear Voltage Regulator. Rev. 1.0,

TLE42344G. Data Sheet. Automotive Power. Low Dropout Linear Voltage Regulator. Rev. 1.0, Low Dropout Linear Voltage Regulator Data Sheet Rev. 1., 21-2-8 Automotive Power Low Dropout Linear Voltage Regulator 1 Overview Features Output voltage tolerance ±2% Low dropout voltage Output current

More information

Recommended Hole Pattern: [mm]

Recommended Hole Pattern: [mm] Dimensions: [mm] Recommended Hole Pattern: [mm] Electrical Properties: Properties Test conditions Value Unit Tol. Capacitance 1 V/ 1 khz ± 0.2 khz C 680 nf ±10% Rated Voltage U R 400 V (DC) Insulation

More information

PRODUCT SPECIFICATIONS

PRODUCT SPECIFICATIONS FEATURES AND BENEFITS* Up to 1,000,000 duty cycles or 10 year DC life 48V DC working voltage Active cell balancing Temperature output Overvoltage outputs available High power density TYPICAL APPLICATIONS

More information

Power System Stability GENERATOR CONTROL AND PROTECTION

Power System Stability GENERATOR CONTROL AND PROTECTION Power System Stability Outline Basis for Steady-State Stability Transient Stability Effect of Excitation System on Stability Small Signal Stability Power System Stabilizers Speed Based Integral of Accelerating

More information

WCAP-FTXX Film Capacitors

WCAP-FTXX Film Capacitors A Dimensions: [mm] B Recommended hole pattern: [mm] D1 Electrical Properties: Properties Test conditions Value Unit Tol. Capacitance 1 V/ 1 khz ± 0.2 khz C 0.1000 µf ± 10% Rated voltage U R 310 V (AC)

More information

TLE Data Sheet. Automotive Power. Low Dropout Fixed Voltage Regulator TLE42644G. Rev. 1.1,

TLE Data Sheet. Automotive Power. Low Dropout Fixed Voltage Regulator TLE42644G. Rev. 1.1, Low Dropout Fixed Voltage Regulator TLE42644G Data Sheet Rev. 1.1, 214-7-3 Automotive Power Low Dropout Fixed Voltage Regulator TLE42644G 1 Overview Features Output Voltage 5 V ± 2 % up to Output Currents

More information

Low Drop Voltage Regulator TLE 4296

Low Drop Voltage Regulator TLE 4296 Low Drop Voltage Regulator TLE 4296 Features Three versions: 3.0 V, 3.3 V, 5.0 V Output voltage tolerance ±4% Very low drop voltage Output current: 30 ma Inhibit input Low quiescent current consumption

More information

Mitigation of Diesel Generator Vibrations in Nuclear Applications Antti Kangasperko. FSD3020xxx-x_01-00

Mitigation of Diesel Generator Vibrations in Nuclear Applications Antti Kangasperko. FSD3020xxx-x_01-00 Mitigation of Diesel Generator Vibrations in Nuclear Applications Antti Kangasperko FSD3020xxx-x_01-00 1 Content Introduction Vibration problems in EDGs Sources of excitation 2 Introduction Goal of this

More information

Characteristics Climatic Category 40/105/56 (IEC 61071)

Characteristics Climatic Category 40/105/56 (IEC 61071) Polypropylene Film Capacitors for Snubber Applications Features - 105 C - Very low dissipation factor - Highest peak pulse capability - Double-sided metallized electrodes - Internal series connection -

More information

ECE 585 Power System Stability

ECE 585 Power System Stability Homework 1, Due on January 29 ECE 585 Power System Stability Consider the power system below. The network frequency is 60 Hz. At the pre-fault steady state (a) the power generated by the machine is 400

More information