Electrical Power Cables Part 2 Cable Rating Calculations

Size: px
Start display at page:

Download "Electrical Power Cables Part 2 Cable Rating Calculations"

Transcription

1 ELEC971 High Voltage Systems Electrical Power Cables Part Cable Rating Calculations The calculation of cable ratings is a very complex determination because of the large number of interacting characteristics and parameters involved in the establishment of a heat balance (for steady state ratings) or general heat dissipation/heat generation equation (for transient ratings). The cable heat dissipation is achieved by means of thermal conduction to the cable surface (an inefficient heat transfer process compared to convection and radiation transfer). From the cable surface heat is then dissipated by a variety of means, depending on the cable installation, the ambient conditions and the general configuration. The cable thermal properties and also the thermal characteristics of the environment of the cable installation are thus very important in the rating calculations. 1. Cable installation methods Cables are installed in a very large variety of environments, including the following examples: ELEC971: Power Cables Part p. 1/3

2 Direct burial in the ground with no special backfill material Burial in a trench packed with thermally enhanced dissipation material Installation in ducts or pipes buried in the ground Installation in a duct or pipe situated in open air Installation in large diameter tunnels Installation directly in open air situations Undersea: open or buried In troughs with circulating water In addition to the usual case of internal heat generation in a single cable (self-heating), it will generally be the case that cables will be installed in closely-coupled three phase groups or even double circuit arrangements of six cables. The result of this close interaction will be that mutual heat generation between cables must also be taken into consideration when determining the heat generation level. In all of these cases the thermal properties, including the thermal resistances, of the material surrounding the cable must be known in detail so that the heat dissipation rates from the cable surface to the infinite heat sink at ambient temperature can be determined. It is also necessary to determine such details, particularly the internal thermal resistances, for the cable and its component parts and materials. ELEC971: Power Cables Part p. /3

3 In particular, the following are the important material characteristics required: thermal resistivity of insulation (g: o C/W or thermal Ω.m) specific heat of insulation and of the metal (c: J/kg/C) mass density of the insulation and the metal (δ : kg/m 3 ) The thermal resistivity (g) of the various materials is of major importance in determining the thermal resistance of various parts of the thermal circuit used for steady state rating calculations. The thermal diffusivity of the insulation, defined as: 1 α = [m /s] gc.. δ is also an important parameter for transient rating calculations of buried cables. In this case the heat storage characteristics are important. Typical values of the above quantities for some relevant materials are shown in the accompanying table. The thermal diffusivity of different soil materials does not vary very much, being generally in the range of about 1.0 ± 0.8 m /sec. An average value of about 0.6 is often used. A value of soil thermal resistivity of 1. thermal Ω.m is often used. Typically insulation materials will have thermal resistivities of about 5-6 thermal Ω.m. ELEC971: Power Cables Part p. 3/3

4 . Heat generation in cables In addition to the heat dissipation details, the heat generation characteristics of all of the relevant cable materials are required. These details have been outlined previously in these notes. Typical values of thermal properties of materials used in the design and installation of power cable systems. ELEC971: Power Cables Part p. 4/3

5 3. Cable component thermal characteristics The general thermal characteristics of the component parts of cable systems that are of importance in the rating calculation process are: (1) Main conductor Ohmic heating losses No thermal resistance () Main insulant Dielectric losses at high voltages (electrical) Calculable thermal resistance (3) Metallic sheath Eddy current losses No thermal resistance (4) Insulating sheath No losses Calculable thermal resistance (5) Bedding No losses Calculable thermal resistance (6) Armour Eddy current losses No thermal resistance (7) Serving (insulating No losses (outer sheath) Calculable thermal resistance (8) Metal pipe (duct) Eddy current losses No thermal resistance (9) Insulating duct No losses (pipe) Calculable thermal resistance ELEC971: Power Cables Part p. 5/3

6 In addition to the thermal characteristics of the cable components, the thermal characteristics of the cable installation environment are also required: these include, for example, the ground (soil) thermal resistance, the air thermal resistance and the associated heat capacities and diffusivities etc. If the cable is in open air, the radiative and convective dissipation properties are also needed. 3.1 Equivalent Steady State Thermal Circuit The general thermal equivalent circuit used for steady state rating calculation is shown below. It is an electrical-thermal analogy using the heat generation as the equivalent current sources, the thermal resistances for electrical resistances and the temperature as the voltage potential analogue. From the equivalent circuit it can be seen that it is necessary to calculate accurately the thermal resistances and the heat generation losses and to be able to specify the fixed temperatures at the conductor and at the ambient condition (the ground surface, for example). The unknown is the current level (the thermal rating) which will be determined by the heat balance at steady state operation. ELEC971: Power Cables Part p. 6/3

7 conductor insulation G i surface bedding serving dissipation sheath armour surface ambient T s G T b G s G o c T a T o T A I R W d λ 1 I R λ I R Thermal equivalent circuit for a single core cable with metal sheath and armour. T c = maximum allowable conductor temperature T A = ambient temperature T s = sheath temperature T a = armour temperature T o = cable outer surface temperature W d = main insulation dielectric heat loss per unit length I R = conductor ohmic heat generation at rated current (I is the unknown) R = AC resistance of the conductor per unit length λ 1 = (conducting) eddy current sheath loss coefficient λ = armour eddy current heat loss coefficient G i = main insulation thermal resistance G b = bedding thermal resistance ELEC971: Power Cables Part p. 7/3

8 G s = serving or insulating sheath thermal resistance G o = effective thermal resistance between the cable surface and the ambient G o will depend on the nature of the cable installation and may ultimately be the most difficult quantity to evaluate accurately, particularly when the cable surface is open to air or fluid environments. Note that the (distributed) dielectric heat generation W d is normally included at the mid-point of the insulation resistance, so that W d passes through only half of the thermal resistance. It can be shown mathematically that the temperature rise of insulation due to dielectric heating is: 1 Δ T = W G d i Thus it is necessary to place the dielectric heat input at the midpoint of G i in the equivalent circuit Specified Conductor Temperature The maximum conductor temperature to be used in the calculation will be that specified by the manufacturer as the maximum permissible steady state temperature of the insulation material that is in contact with the main insulation. Some typical upper limits of temperature are shown over. ELEC971: Power Cables Part p. 8/3

9 ELEC971: Power Cables Part p. 9/3

10 ELEC971: Power Cables Part p. 10/3

11 3.1. Ambient Temperature The ambient ground temperature (or the general main heatsink temperature in other environments) to be used for rating determinations is normally specified as a weighted average. For example, in Australia, an ambient ground temperature of 5 o C is normally used whenever rating tables such as those given in Standards are utilized. If the rated values of a Standards table of ratings are to be varied for different ambient temperatures, the following multiplying factor is used to adjust from an ambient of 5 o C to another ambient of T o C. I T A = I 5 T T T cmax A cmax 5 where T cmax = maximum allowable conductor temperature T A = the new ambient temperature applicable 3. Equivalent Thermal Circuit for Transient Effects When considering transient thermal ratings, which are perhaps a more common requirement than steady ratings, it is necessary to take thermal storage elements in the cable structure into account in the cable s equivalent circuit. In the most general case this means determining an equivalent thermal capacitance Q (i.e. ability to store the heat) for all of the cable components, as shown in the circuit ELEC971: Power Cables Part p. 11/3

12 diagram below. This will require use of the material thermal capacities and mass densities. I R W sh Q c G i dielectric pq d G b ( ) 1 pq d P T A (ambient) conductor sheath Equivalent circuit for transient heating of cable. In the particular case of the main dielectric, it is necessary to split its thermal capacitance Q d and divide it between the conductor and the sheath, as below. The sharing factor p (Van Wormer coefficient) is determined assuming a logarithmic temperature distribution in the dielectric material. The factor p can be determined from the following equation: 1 1 p = ln R R 1 r o ro R is the outer dielectric radius and r o is the inner dielectric radius. Note that p = 0.39 when R/r o =.0. ELEC971: Power Cables Part p. 1/3

13 4. Rating Calculations Steady state rating calculations for cables are performed according to the International Electrotechnical Committee Standard IEC This specifies uniform methods of calculation. The preceding details and equivalent circuits are based on this Standard. For coaxial cables, the various thermal resistances used in the equivalent circuit are determined from the general formula: G i g i d i = ln thermal ohms/metre π dc where d i is the outer diameter of the insulation layer, and d c is the inner diameter of the insulation layer. This comes from the analogy with the shunt electrical resistance of a coaxial insulation system. From the thermal equivalent circuit on the previous page, the determination of the current rating I for a maximum conductor temperature proceeds by logical steps: T = T + W + 1+ λ + λ I R G e.g. we use ( ) a o d 1 s Note that: T T = ( T T ) + ( T T ) + ( T T ) c A c s s a a A Proceeding in this manner, we find the thermal rating is given by: ELEC971: Power Cables Part p. 13/3

14 I 1 Tc TA Wd Gi + [ Gb + Gs + Go] = RGi + R( 1+ λ1) Gb + R( 1+ λ1+ λ)( Gs + Go) 1/ The thermal resistance G o, representing the heat dissipation from the cable surface to the ambient, must be determined from the installation configuration and the environment details. The various possibilities that may occur are discussed below. 4.1 Cables in air In this case thermal dissipation from the cable surface will be by a combination of convection and radiation and G o will be determined from the total heat dissipation coefficient of those two mechanisms. ht = hc + hr H = hat T = haδ T we have ( ) T A T but also GH o =Δ T [thermal Ohm s law] thus G o = 1 ha T For example, for a cylindrical cable of diameter D in open air, ELEC971: Power Cables Part p. 14/3

15 hence: and: ( π )[ ] 5/4 H = k D T T s [ ] 1/4 h = k T T G T s A o 1 1 = = ha k D T T A ( π )[ ] 1/4 T s A Thus, G o is a function of T s and this relationship must be found and used in order to get G o, unless we can specify h T exactly. [Sometimes a general value of h T 10 W/m /K is used for normal operating temperatures and ambient conditions, but more accurate estimations should be used whenever available.] A more accurate rating calculation technique is to use iteration to find the surface temperature T o. The method used is as follows: From the equivalent circuit: [ ] T T = I R G + G + G + G c A i b s o + W Gi + G + G + G + λ + + d b s o [ b s o] [ G ] 1I R G G G I R Gs o + λ + This can be rewritten as follows: ELEC971: Power Cables Part p. 15/3

16 [ ] T T = I R G + G + G c A i b s Gi + W + G + G d b s λ1i R[ Gb Gs] λi R[ Gs ] [ T T ] o A Hence: Gi ( T T ) ( T T ) W + G + G c A o A d b s ( 1 λ ) ( 1 λ λ ) = I R Gi Gb 1 Gs 1 [eq.1] But the total heat dissipation from the surface is: ( + λ + λ ) + = ( π )[ ] 5/4 I R 1 1 Wd k D To TA Thus: I R = ( π )[ ] 5/4 k D T T W o A d 1+ λ + λ 1 Substitute into eq.1 above and then solve by iterative means (e.g. method of bisection) for T o. ELEC971: Power Cables Part p. 16/3

17 4. Cables in ducts, pipes etc. In this case G o is the sum of the various thermal resistances in series: i.e. G o = G cable-duct + G duct-ground surface + etc 4.3 Direct buried cables Here, G o is the thermal resistance between the cable surface and the ground surface: the ground thermal resistance as shown below. We use the method of images, the electrical thermal analogy and the two-wire line capacitance expression to determine the thermal resistance as follows: Capacitance of a line to ground: ELEC971: Power Cables Part p. 17/3

18 C = πε ln / ( h a) Using the general equality RC insulation material, we have ( h a) ρε ln / ρ R = = ρε = ln / C πε π = ρε for an electrical ( h a) Thus, using the electrical-thermal analogy, we have, for the ground thermal resistance: G o g h = ln thermal ohms/m π a where: g = soil thermal resistivity h = depth of burial a = cable outer radius ELEC971: Power Cables Part p. 18/3

19 ELEC971: Power Cables Part p. 19/3

20 4.4 Multi-core cables For three phase cables, there will be mutual heating between the cores and the thermal resistances G i will be affected by this mutual heating. This is particularly true of belted cables. The calculation will be more complex as a result, in this case. t 1 r 0 t A 3-core belted-type cable For the case shown above, an approximate formula (Simons formula) is given by: G i where: g t t t = + + π ln t t ro t 1 = insulation belt thickness t = conductor insulation thickness r o = conductor radius The G i above are for each core s thermal resistance to the outer surface of the belt. ELEC971: Power Cables Part p. 0/3

21 G i G i G b G s G i sheath 4.5 Cables in ducts For cables in ducts, an empirical expression is used, followed by iteration to get the rating. A G = 1 + ( B + CTm) De where: values of A, B and C are given in IEC T m is the mean temperature of the duct filling material D e is the equivalent diameter of the cores. [For a single core cable: D e = OD of cable two cores cable: D e = 1.65 x OD three core cable: D e =.15 x OD ] The thermal resistance is the thermal resistance between the pipe and the cable surfaces. The calculation procedure requires an initial educated guess of T m and then iteration. Following is an example of a calculation by this method. ELEC971: Power Cables Part p. 1/3

22 Example: Determine the rating of a 500kV, 60Hz, three-phase oil pipe type cable buried in ground. The details are: Pipe loss factor = 0.8 (eddy current loss) Conductor OD = 4.14 cm Insulation thickness = 3.40 cm Pipe diameter = 30 cm Burial depth = 100 cm Soil resistivity = 0.9 o C.m/W Ambient temperature = 5 o C AC resistance = Ω/ph/km Insulation: g = 5.0 o C.m/W tanδ = 0.00 T max = 80 o C Thermal resistance from pipe to cable is obtained from: G cp A = 1 + B + CT D ( ) max where (from previous table) for an oil pressure pipe type cable: A = 0.6 ; B = 0 ; C = D e =.15 x O.D. of core =.15 x ( x 3.4) cm = 3.5 cm e ELEC971: Power Cables Part p. /3

23 We take T m as 55 o C for first guess. Then: 0.6 G cp = ( ) = 0.06 thermal Ω/m For the cable insulation: G i = ln = 0.77 thermal Ω/m π 4.14 For the ground: G o = ln = 0.37 thermal Ω/m π 15 Thus the equivalent circuit is: G i I R AC 0.77 G cp G o I R AC I R AC T A = 5 o C 80 o C ( ) I R = I = I W/m/phase 3 5 AC 5 Pipe loss ( I ) = W/m Dielectric loss: Po = ωcv tanδ ELEC971: Power Cables Part p. 3/3

24 but: πε C = = ln 4.14 hence: P o 3 pf/m/ph = 314 ( ) = W/m/core W/m T C T = 80 5 = 55 A o C Hence: ( 5 I )( ) ( 5 I )( ) 55 = ( ) I 0.37 i.e I ( ) I = A 5 = 599 then use this to check T m guess. T m 5 ( ) ( ) = = = 6 o C [c.f. 55 o C] This is too high. Thus try T m =58 o C next and repeat until agreement is reached. ELEC971: Power Cables Part p. 4/3

25 5. Transient Heating of Cables When operated under non-steady state conditions, we can define three different transient ratings for cables. Because of the high thermal capacity of power cables, particularly when buried in the ground, these transient ratings are more relevant and more often used than the steady state rating determinations because of the long time constants associated with the cables. The three transient ratings used are: (i) Short circuit rating: Determined from adiabatic heating of the cable under short circuit. (ii) Cyclic rating: Determined using specified daily load cycles (iii) Emergency Rating: Usually calculated for 1- hours of overload conditions 5.1 Short circuit rating This is calculated for a specified maximum (short circuit) temperature T sc and a specified protection operating time (t sc ) to clear the fault current. The equation previously quoted for adiabatic heating is used: ELEC971: Power Cables Part p. 5/3

26 Itsc ( T( t ) T ) ( ) δ c 1+ α sc o = ln A ρα 1 + α ( T 0 To ) where: δ = conductor mass density c = insulation specific heat ρ = conductor electrical resistivity α = temperature coefficient of resistivity for ρ I = short circuit current rating t sc = short circuit duration (protection operating time) T o = cable surface temperature T(0) = initial conductor temperature T(t sc ) = T sc = maximum permissible temperature For example, typical maximum permissible (short circuit) temperatures are: Main conductor: 10 o C Aluminium sheath: 00 o C Lead sheath: 00 o C In some cases the sheath temperature limit may be the determining factor rather than the conductor maximum temperature. The following example illustrates the case. Example: A 500 mm three-core Al conductor, screened cable with lead sheath and steel armour has a continuous rating of 480A for a ELEC971: Power Cables Part p. 6/3

27 T c of 70 o C. It is an 11 kv cable. The sheath O.D. is 6.96 cm and the sheath thickness is 0.9 cm. At rated current, T c = 70 o C, T s = 66. o C, and the ambient T A = 0 o C. Find the maximum short circuit currents for T ( max) = 10 o C and T c ( max) = 00 o C if the protection operating s time is 1 second. (a) Al conductor: I sc A δ c ( ) ( ) α 10 0 = 8 ln α 70 0 ρ α = ln 1.0 i.e. I sc ( ) = 8.9 ka (b) Lead sheath: Cross-section area Initial T s = 66. o C. Thus: = π d thickness = π = 6.1 cm 1 ELEC971: Power Cables Part p. 7/3

28 I sc A δ c ( ) ( ) α 00 0 = 8 ln α ρ α 1 i.e. I sc ( ) = ln 1.18 = 15.8 ka Thus, the lead sheath is the limiting factor. (c) Note that if an Al sheath is used instead: I sc A ( ) ( ) 8 1+ α 00 0 = ln 1 + α i.e. I sc ( ) = = 56 ka Cyclic rating of cables The main problem in determining the rating in this case is the part played by the thermal capacity of both the cable and ground materials. Thermal diffusion into the ground must be considered. Thus the soil thermal diffusivity (α D ) is important: this quantity incorporates thermal conductivity ELEC971: Power Cables Part p. 8/3

29 (resistivity), density and specific heat of the soil: α D = k ( cδ ). To do this we must use a thermal equivalent circuit which includes energy storage elements, with the thermal capacitance included as well as thermal resistance. The following diagram shows the equivalent circuit used: T c T s T A G i G o Q 1 Q Q 3 where: Q 1 is the thermal capacitance of the conductor plus a fraction (p) of the thermal capacitance of the electrical insulation. Q is the thermal capacitance of the sheath plus a fraction( 1 p) of the thermal capacitance of the electrical insulation. Q 3 is the effective thermal capacitance of the earth (this is the difficult estimate). The fraction p is calculated from: ELEC971: Power Cables Part p. 9/3

30 where: 1 1 p = ln ( R/ r) ( R/ r) 1 R = the outer radius of the electrical insulation r = the conductor radius The problem is the determination of Q 3, the ground thermal capacity. This is dependent on the soil thermal diffusivity which can vary with soil condition. The simplest way is to divide the ground around the cable into a distributed set of coaxial cylinders, as shown below: T A G 1 G G 3 G 4 Q 1 Q Q 3 Q 4 For more accurate analysis the problem is modeled using a full distributed system which then requires use of the exponential integral Ei(x), defined as: ( ) Ei x e = t x t dt This function arises when a linear heat source is considered to be a continuous distribution of point sources of heat along a line. ELEC971: Power Cables Part p. 30/3

31 Using this function and the model of the cable and its mirror image, the cable surface temperature rise as a function of time is given by the equation: gw T d h To () t = Ei + Ei 4π 16αDt αdt plus any contributions from mutual heating by other cables where: d = cable outer diameter h = burial depth W T = total losses per unit length g = soil thermal resistivity [ = 1 k] = 1 gcδ α D = soil thermal diffusivity ( ) c = soil specific heat δ = soil mass density t = time 5.3 Emergency ratings Emergency ratings are determined for 1 or hours of overload with the temperature of the insulation not to exceed the maximum limit. It is also complicated by the thermal diffusivity factor as with the cyclic rating. Emergency rating are an important consideration and are often used. The overload rating can be quite high because of ELEC971: Power Cables Part p. 31/3

32 the high thermal capacity and thermal diffusivity of the cable and surrounding ground. ELEC971: Power Cables Part p. 3/3

ELEC9712 High Voltage Systems. 1.2 Heat transfer from electrical equipment

ELEC9712 High Voltage Systems. 1.2 Heat transfer from electrical equipment ELEC9712 High Voltage Systems 1.2 Heat transfer from electrical equipment The basic equation governing heat transfer in an item of electrical equipment is the following incremental balance equation, with

More information

Three Core XLPE/LSF/SWA/LSF Power Cable

Three Core XLPE/LSF/SWA/LSF Power Cable 1 Three Core XLPE/LSF/SWA/LSF Power Cable./ kv Application LSF armoured power cable for use in fixed installations. Especially for use in areas where fire would create dense smoke and toxic fumes causing

More information

Comparison of Finite Element Analysis to IEC for Predicting Underground Cable Ampacity

Comparison of Finite Element Analysis to IEC for Predicting Underground Cable Ampacity Comparison of Finite Element Analysis to IEC-60287 for Predicting Underground Cable Ampacity Simon Dubitsky Tor Ltd, St. Petersburg, Russia simon.dubitsky@ieee.org Georgy Greshnyakov Sevkabel Research

More information

Single Core XLPE/LSF/AWA/LSF Power Cable

Single Core XLPE/LSF/AWA/LSF Power Cable Single Core XLPE/LSF/AWA/LSF Power Cable 00/00V and 100/00V Application LSF insulated, armoured and sheathed, single core power cable for use in fixed installations. Especially for use in areas where fire

More information

Politecnico di Torino THERMAL ANALYSIS OF POWER LINES: METHODOLOGIES AND APPLICATIONS

Politecnico di Torino THERMAL ANALYSIS OF POWER LINES: METHODOLOGIES AND APPLICATIONS Politecnico di Torino Dottorato in Ingegneria Elettrica Scienze elettriche THERMAL ANALYSIS OF POWER LINES: METHODOLOGIES AND APPLICATIONS Tesi di Dottorato Supervisors: Prof. Aldo CANOVA Ing. Fabio FRESCHI

More information

ELECTRICAL AND THERMAL DESIGN OF UMBILICAL CABLE

ELECTRICAL AND THERMAL DESIGN OF UMBILICAL CABLE ELECTRICAL AND THERMAL DESIGN OF UMBILICAL CABLE Derek SHACKLETON, Oceaneering Multiflex UK, (Scotland), DShackleton@oceaneering.com Luciana ABIB, Marine Production Systems do Brasil, (Brazil), LAbib@oceaneering.com

More information

Thermal and Mechanical Properties of EPR Cable Compound. Steven Boggs ICC Educational Session 7 November 2005 Phoenix, Arizona

Thermal and Mechanical Properties of EPR Cable Compound. Steven Boggs ICC Educational Session 7 November 2005 Phoenix, Arizona Thermal and Mechanical Properties of EPR Cable Compound Steven Boggs ICC Educational Session 7 November 2005 Phoenix, Arizona Source of Data All data were measured during 2005 at the Institute of Materials

More information

QUESTION ANSWER. . e. Fourier number:

QUESTION ANSWER. . e. Fourier number: QUESTION 1. (0 pts) The Lumped Capacitance Method (a) List and describe the implications of the two major assumptions of the lumped capacitance method. (6 pts) (b) Define the Biot number by equations and

More information

Fire Resistant Armoured Power Cable

Fire Resistant Armoured Power Cable Power and Wiring Cables Fire Resistant Armoured Power Cable 00/00V Application Armoured fire resistant cable for use in fixed wiring installations where it is necessary for the cable to retain circuit

More information

Time-Dependent Conduction :

Time-Dependent Conduction : Time-Dependent Conduction : The Lumped Capacitance Method Chapter Five Sections 5.1 thru 5.3 Transient Conduction A heat transfer process for which the temperature varies with time, as well as location

More information

Overhead lines. 110 kv wood tower with guy wires

Overhead lines. 110 kv wood tower with guy wires Overhead lines a) ja b) 0 kv wood poles c) free standing 0 kv metal tower with I-strings d) free standing 440 kv metal tower with V-strings e) 400 kv metal tower with guy wires 0 kv wood tower with guy

More information

Introduction to Heat and Mass Transfer. Week 7

Introduction to Heat and Mass Transfer. Week 7 Introduction to Heat and Mass Transfer Week 7 Example Solution Technique Using either finite difference method or finite volume method, we end up with a set of simultaneous algebraic equations in terms

More information

Three-Terminal Low Current Positive Voltage Regulators BL78XX

Three-Terminal Low Current Positive Voltage Regulators BL78XX FEATURES Internal Thermal Overload Protection. Internal Short Circuit Current Limiting. Output Current up to 1.5A. Satisfies IEC-65 Specification. (International Electronical Commission). MSL 3 Pb Lead-free

More information

Chapter 24 Capacitance and Dielectrics

Chapter 24 Capacitance and Dielectrics Chapter 24 Capacitance and Dielectrics 1 Capacitors and Capacitance A capacitor is a device that stores electric potential energy and electric charge. The simplest construction of a capacitor is two parallel

More information

Heat Transfer Analysis of Centric Borehole Heat Exchanger with Different Backfill Materials

Heat Transfer Analysis of Centric Borehole Heat Exchanger with Different Backfill Materials Proceedings World Geothermal Congress 2015 Melbourne, Australia, 19-25 April 2015 Heat Transfer Analysis of Centric Borehole Heat Exchanger with Different Backfill Materials Lei H.Y. and Dai C.S. Geothermal

More information

Thermal Analysis by Conduction Convection and Radiation in a Power Cable

Thermal Analysis by Conduction Convection and Radiation in a Power Cable IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 3 Ver. II (May Jun. 2014), PP 51-56 Thermal Analysis by Conduction Convection and

More information

Deliverable Report. Offshore House, Albert Street, Blyth, Northumberland, NE24 1LZ

Deliverable Report. Offshore House, Albert Street, Blyth, Northumberland, NE24 1LZ Deliverable Report Report issued to: ORE Catapult Project: ORE1601 Offshore House, Albert Street, Blyth, Northumberland, NE24 1LZ Project Engineer: Hytham Emam Deliverable Number: 1 Email: hytham.emam@ore.catapult.org.uk

More information

Chapter 24 Capacitance and Dielectrics

Chapter 24 Capacitance and Dielectrics Chapter 24 Capacitance and Dielectrics 1 Capacitors and Capacitance A capacitor is a device that stores electric potential energy and electric charge. The simplest construction of a capacitor is two parallel

More information

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager. 1 -A - Introduction - Thank for your purchasing MITSUBISHI ELECTRIC MELPRO TM D Series Digital Protection

More information

Chapter 3: Steady Heat Conduction

Chapter 3: Steady Heat Conduction 3-1 Steady Heat Conduction in Plane Walls 3-2 Thermal Resistance 3-3 Steady Heat Conduction in Cylinders 3-4 Steady Heat Conduction in Spherical Shell 3-5 Steady Heat Conduction with Energy Generation

More information

Wave Phenomena Physics 15c. Lecture 8 LC Transmission Line Wave Reflection

Wave Phenomena Physics 15c. Lecture 8 LC Transmission Line Wave Reflection Wave Phenomena Physics 15c Lecture 8 LC Transmission Line Wave Reflection Midterm Exam #1 Midterm #1 has been graded Class average = 80.4 Standard deviation = 14.6 Your exam will be returned in the section

More information

Chapter 27. Current and Resistance

Chapter 27. Current and Resistance Chapter 27 Current and Resistance Electric Current Most practical applications of electricity deal with electric currents. The electric charges move through some region of space. The resistor is a new

More information

Introduction to Heat and Mass Transfer. Week 5

Introduction to Heat and Mass Transfer. Week 5 Introduction to Heat and Mass Transfer Week 5 Critical Resistance Thermal resistances due to conduction and convection in radial systems behave differently Depending on application, we want to either maximize

More information

Lesson 3. Electric Potential. Capacitors Current Electricity

Lesson 3. Electric Potential. Capacitors Current Electricity Electric Potential Lesson 3 Potential Differences in a Uniform Electric Field Electric Potential and Potential Energy The Millikan Oil-Drop Experiment Capacitors Current Electricity Ohm s Laws Resistance

More information

Magnetic field shielding of underground power cables in urban areas: a real-life example

Magnetic field shielding of underground power cables in urban areas: a real-life example Boundary Elements XXVII 527 Magnetic field shielding of underground power cables in urban areas: a real-life example L. Battistelli, A. Geri & G. M. Veca Department of Electrical Engineering, University

More information

THERMAL ANALYSIS OF UMBILICAL CABLES

THERMAL ANALYSIS OF UMBILICAL CABLES Proceedings of COBEM 2007 Copyright 2007 by ABCM 19th International Congress of Mechanical Engineering November 5-9, 2007, Brasília, DF THERMAL ANALYSIS OF UMBILICAL CABLES Rosianita Balena, rbalena@oceaneering.com

More information

ELECO'2001. Paper Submission Form

ELECO'2001. Paper Submission Form ELECO'2001 Paper Submission Form Name of Presenting Author... Cuneyt OYSU Address... Kocaeli Üniversitesi Mekatronik Mühendisliği Bölümü Veziroğlu Kampüsü 41040 İzmit/Kocaeli Phone (262) 5282467 (532)

More information

Today in Physics 122: resistance

Today in Physics 122: resistance Today in Physics 122: resistance Ohm s Law Resistivity and the physics behind resistance Resistors of different shapes and sizes, and how to calculate their resistance from their resistivity Resistor networks

More information

Calculations of Capacitance for Transposed Bundled Conductor Transmission Lines

Calculations of Capacitance for Transposed Bundled Conductor Transmission Lines Calculations of Capacitance for Transposed Bundled Conductor Transmission Lines Multi-conductor Lines. An example with a conductor bundle r: conductor radius, d: distance between conductors of the same

More information

AN78xx/AN78xxF Series

AN78xx/AN78xxF Series 3-pin positive output voltage regulator ( type) Overview The N7xx series and the N7xxF series are 3- pin, fixed positive output type monolithic voltage regulators. Stabilized fixed output voltage is obtained

More information

Physics (

Physics ( Question 2.12: A charge of 8 mc is located at the origin. Calculate the work done in taking a small charge of 2 10 9 C from a point P (0, 0, 3 cm) to a point Q (0, 4 cm, 0), via a point R (0, 6 cm, 9 cm).

More information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME: EE 2303 - TRANSMISSION & DISTRIBUTION YEAR / SEM: III/V UNIT-I TRANSMISSION SYSTEM INTRODUCTION PART-A 1. What is

More information

Introduction to AC Circuits (Capacitors and Inductors)

Introduction to AC Circuits (Capacitors and Inductors) Introduction to AC Circuits (Capacitors and Inductors) Amin Electronics and Electrical Communications Engineering Department (EECE) Cairo University elc.n102.eng@gmail.com http://scholar.cu.edu.eg/refky/

More information

The Steady Magnetic Field

The Steady Magnetic Field The Steady Magnetic Field Prepared By Dr. Eng. Sherif Hekal Assistant Professor Electronics and Communications Engineering 1/13/016 1 Agenda Intended Learning Outcomes Why Study Magnetic Field Biot-Savart

More information

Collation Studies of Sequence Impedances for Underground Cables with Different Layouts

Collation Studies of Sequence Impedances for Underground Cables with Different Layouts Collation Studies of Sequence Impedances for Underground Cables with Different Layouts M.Ramya 1, G.Radhika 2, Poonam Upadhyay 3 1 Department of EEE, VNRVJIET, Hyderabad, India 2 Department of EEE, Sr.Assistant

More information

The Steady Magnetic Fields

The Steady Magnetic Fields The Steady Magnetic Fields Prepared By Dr. Eng. Sherif Hekal Assistant Professor Electronics and Communications Engineering 1/8/017 1 Agenda Intended Learning Outcomes Why Study Magnetic Field Biot-Savart

More information

AC vs. DC Circuits. Constant voltage circuits. The voltage from an outlet is alternating voltage

AC vs. DC Circuits. Constant voltage circuits. The voltage from an outlet is alternating voltage Circuits AC vs. DC Circuits Constant voltage circuits Typically referred to as direct current or DC Computers, logic circuits, and battery operated devices are examples of DC circuits The voltage from

More information

Principles of Food and Bioprocess Engineering (FS 231) Problems on Heat Transfer

Principles of Food and Bioprocess Engineering (FS 231) Problems on Heat Transfer Principles of Food and Bioprocess Engineering (FS 1) Problems on Heat Transfer 1. What is the thermal conductivity of a material 8 cm thick if the temperature at one end of the product is 0 C and the temperature

More information

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT B.Tech. [SEM V (ME-51, 52, 53, 54)] QUIZ TEST-1 (Session: )

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT B.Tech. [SEM V (ME-51, 52, 53, 54)] QUIZ TEST-1 (Session: ) QUIZ TEST-1 Time: 1 Hour HEAT AND MASS TRANSFER Note: All questions are compulsory. Q1) The inside temperature of a furnace wall ( k=1.35w/m.k), 200mm thick, is 1400 0 C. The heat transfer coefficient

More information

PH213 Chapter 24 Solutions

PH213 Chapter 24 Solutions PH213 Chapter 24 Solutions 24.12. IDENTIFY and S ET UP: Use the expression for derived in Example 24.4. Then use Eq. (24.1) to calculate Q. E XECUTE: (a) From Example 24.4, The conductor at higher potential

More information

Ampacity simulation of a high voltage cable to connecting off shore wind farms

Ampacity simulation of a high voltage cable to connecting off shore wind farms Ampacity simulation of a high voltage cable to connecting off shore wind farms Pelster 1, Wenger 1 1 Wenger Engineering GmbH, Einsteinstr. 55, 89077 Ulm, mail@wenger-engineering.com Abstract: The ampacity

More information

1. Nusselt number and Biot number are computed in a similar manner (=hd/k). What are the differences between them? When and why are each of them used?

1. Nusselt number and Biot number are computed in a similar manner (=hd/k). What are the differences between them? When and why are each of them used? 1. Nusselt number and Biot number are computed in a similar manner (=hd/k). What are the differences between them? When and why are each of them used?. During unsteady state heat transfer, can the temperature

More information

Thermal Systems. What and How? Physical Mechanisms and Rate Equations Conservation of Energy Requirement Control Volume Surface Energy Balance

Thermal Systems. What and How? Physical Mechanisms and Rate Equations Conservation of Energy Requirement Control Volume Surface Energy Balance Introduction to Heat Transfer What and How? Physical Mechanisms and Rate Equations Conservation of Energy Requirement Control Volume Surface Energy Balance Thermal Resistance Thermal Capacitance Thermal

More information

Do not fill out the information below until instructed to do so! Name: Signature: Section Number:

Do not fill out the information below until instructed to do so! Name: Signature:   Section Number: Do not fill out the information below until instructed to do so! Name: Signature: E-mail: Section Number: No calculators are allowed in the test. Be sure to put a box around your final answers and clearly

More information

Capacitance and Dielectrics. Chapter 26 HW: P: 10,18,21,29,33,48, 51,53,54,68

Capacitance and Dielectrics. Chapter 26 HW: P: 10,18,21,29,33,48, 51,53,54,68 Capacitance and Dielectrics Chapter 26 HW: P: 10,18,21,29,33,48, 51,53,54,68 Capacitors Capacitors are devices that store electric charge and energy Examples of where capacitors are used include: radio

More information

1. Introduction. 2. Use of COMSOL Multiphysics

1. Introduction. 2. Use of COMSOL Multiphysics Excerpt from the Proceedings of the COMSOL Conference 2009 Milan Failure Modes of Underground MV Cables: Electrical and Thermal Modelling. Peter A Wallace *, Mohamed Alsharif, Donald M Hepburn and Chengke

More information

Equivalent circuit for the thermal analysis of cables in non-vented vertical risers

Equivalent circuit for the thermal analysis of cables in non-vented vertical risers IET Science, Measurement & Technology Research Article Equivalent circuit for the thermal analysis of cables in non-vented vertical risers ISSN 1751-8822 Received on 30th April 2014 Accepted on 7th November

More information

Chapter 3: Steady Heat Conduction. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

Chapter 3: Steady Heat Conduction. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University Chapter 3: Steady Heat Conduction Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University Objectives When you finish studying this chapter, you should be able to: Understand the concept

More information

Transient analysis of the behaviour of grounding systems consisted by driven rods

Transient analysis of the behaviour of grounding systems consisted by driven rods Transient analysis of the behaviour of grounding systems consisted by driven rods I.F. GONOS M.K. ANTONIOU I.A. STATHOPULOS F.V. TOPALIS Department of Electrical and Computer Engineering, High Voltage

More information

Chapter 10: Steady Heat Conduction

Chapter 10: Steady Heat Conduction Chapter 0: Steady Heat Conduction In thermodynamics, we considered the amount of heat transfer as a system undergoes a process from one equilibrium state to another hermodynamics gives no indication of

More information

CHAPTER 7 ELECTRODYNAMICS

CHAPTER 7 ELECTRODYNAMICS CHAPTER 7 ELECTRODYNAMICS Outlines 1. Electromotive Force 2. Electromagnetic Induction 3. Maxwell s Equations Michael Faraday James C. Maxwell 2 Summary of Electrostatics and Magnetostatics ρ/ε This semester,

More information

Preliminary Sizing Design of a 1 MW Low Duty Cycle Switched Reluctance Generator for Aerospace Applications

Preliminary Sizing Design of a 1 MW Low Duty Cycle Switched Reluctance Generator for Aerospace Applications Preliminary Sizing Design of a 1 MW Low Duty Cycle Switched Reluctance Generator for Aerospace Applications Jin-Woo Jung, Ph. D. Student Advisors: Prof. Ali Keyhani Adjunct Prof. Tomy Sebastian Oct. 25,

More information

Chapter 28 Solutions

Chapter 28 Solutions Chapter 8 Solutions 8.1 (a) P ( V) R becomes 0.0 W (11.6 V) R so R 6.73 Ω (b) V IR so 11.6 V I (6.73 Ω) and I 1.7 A ε IR + Ir so 15.0 V 11.6 V + (1.7 A)r r 1.97 Ω Figure for Goal Solution Goal Solution

More information

Experimental Study on the Cyclic Ampacity and Its Factor of 10 kv XLPE Cable

Experimental Study on the Cyclic Ampacity and Its Factor of 10 kv XLPE Cable Energy and Power Engineering, 203, 5, 22-225 doi:0.4236/epe.203.54b23 Published Online July 203 (http://www.scirp.org/journal/epe) Experimental Study on the Cyclic Ampacity and Its Factor of 0 kv XLPE

More information

COVENANT UNIVERSITY NIGERIA TUTORIAL KIT OMEGA SEMESTER PROGRAMME: MECHANICAL ENGINEERING

COVENANT UNIVERSITY NIGERIA TUTORIAL KIT OMEGA SEMESTER PROGRAMME: MECHANICAL ENGINEERING COVENANT UNIVERSITY NIGERIA TUTORIAL KIT OMEGA SEMESTER PROGRAMME: MECHANICAL ENGINEERING COURSE: MCE 524 DISCLAIMER The contents of this document are intended for practice and leaning purposes at the

More information

The development of a Roebel cable based 1 MVA HTS transformer

The development of a Roebel cable based 1 MVA HTS transformer The development of a Roebel cable based 1 MVA HTS transformer Neil Glasson 11 October 2011 Mike Staines 1, Mohinder Pannu 2, N. J. Long 1, Rod Badcock 1, Nathan Allpress 1, Logan Ward 1 1 Industrial Research

More information

A capacitor is a device that stores electric charge (memory devices). A capacitor is a device that stores energy E = Q2 2C = CV 2

A capacitor is a device that stores electric charge (memory devices). A capacitor is a device that stores energy E = Q2 2C = CV 2 Capacitance: Lecture 2: Resistors and Capacitors Capacitance (C) is defined as the ratio of charge (Q) to voltage (V) on an object: C = Q/V = Coulombs/Volt = Farad Capacitance of an object depends on geometry

More information

Interconnection Relationships. Derive Input/Output Models. School of Mechanical Engineering Purdue University

Interconnection Relationships. Derive Input/Output Models. School of Mechanical Engineering Purdue University hermal Systems Basic Modeling Elements esistance esistance Conduction Convection adiation Capacitance Interconnection elationships Energy Balance - st Law of hermodynamics Derive Input/Output Models ME375

More information

Transient Heat Transfer Experiment. ME 331 Introduction to Heat Transfer. June 1 st, 2017

Transient Heat Transfer Experiment. ME 331 Introduction to Heat Transfer. June 1 st, 2017 Transient Heat Transfer Experiment ME 331 Introduction to Heat Transfer June 1 st, 2017 Abstract The lumped capacitance assumption for transient conduction was tested for three heated spheres; a gold plated

More information

4.1 Derivation and Boundary Conditions for Non-Nipped Interfaces

4.1 Derivation and Boundary Conditions for Non-Nipped Interfaces Chapter 4 Roller-Web Interface Finite Difference Model The end goal of this project is to allow the correct specification of a roller-heater system given a general set of customer requirements. Often the

More information

Physics 122, Fall October 2012

Physics 122, Fall October 2012 Today in Physics 122: resistance Ohm s Law esistivity and the physics behind resistance esistors of different shapes and sizes, and how to calculate their resistance from their resistivity esistor networks

More information

ELECTRO MAGNETIC FIELDS

ELECTRO MAGNETIC FIELDS SET - 1 1. a) State and explain Gauss law in differential form and also list the limitations of Guess law. b) A square sheet defined by -2 x 2m, -2 y 2m lies in the = -2m plane. The charge density on the

More information

CHAPTER 4 THERMAL CONDUCTIVITY AND VISCOSITY MEASUREMENTS

CHAPTER 4 THERMAL CONDUCTIVITY AND VISCOSITY MEASUREMENTS 50 CHAPTER 4 THERMAL CONDUCTIVITY AND VISCOSITY MEASUREMENTS 4.1 INTRODUCTION In the development of any energy-efficient heat transfer fluids for enhanced heat transfer performance, in practical applications,

More information

Can current flow in electric shock?

Can current flow in electric shock? Can current flow in electric shock? Yes. Transient current can flow in insulating medium in the form of time varying displacement current. This was an important discovery made by Maxwell who could predict

More information

HEAT AND MASS TRANSFER IN A HIGH-POROUS LOW- TEMPERATURE THERMAL INSULATION IN REAL OPERATING CONDITIONS

HEAT AND MASS TRANSFER IN A HIGH-POROUS LOW- TEMPERATURE THERMAL INSULATION IN REAL OPERATING CONDITIONS MATEC Web of Conferences 3, 0033 ( 05) DOI: 0.05/ matecconf/ 0530033 C Owned by the authors, published by EDP Sciences, 05 HEAT AND MASS TRANSFER IN A HIGH-POROUS LOW- TEMPERATURE THERMAL INSULATION IN

More information

Thermal Systems. Basic Modeling Elements. Interconnection Relationships. Derive Input/Output Models. Resistance. Capacitance

Thermal Systems. Basic Modeling Elements. Interconnection Relationships. Derive Input/Output Models. Resistance. Capacitance hermal Systems Basic Modeling Elements Resistance Conduction Convection Radiation Capacitance Interconnection Relationships Energy Balance - 1st Law of hermodynamics Derive Input/Output Models ME375 hermal

More information

ASSUMPTIONS: (1) One-dimensional, radial conduction, (2) Constant properties.

ASSUMPTIONS: (1) One-dimensional, radial conduction, (2) Constant properties. PROBLEM 5.5 KNOWN: Diameter and radial temperature of AISI 00 carbon steel shaft. Convection coefficient and temperature of furnace gases. FIND: me required for shaft centerline to reach a prescribed temperature.

More information

University of TN Chattanooga Physics 1040L 8/18/2012 PHYSICS 1040L LAB LAB 4: R.C. TIME CONSTANT LAB

University of TN Chattanooga Physics 1040L 8/18/2012 PHYSICS 1040L LAB LAB 4: R.C. TIME CONSTANT LAB PHYSICS 1040L LAB LAB 4: R.C. TIME CONSTANT LAB OBJECT: To study the discharging of a capacitor and determine the time constant for a simple circuit. APPARATUS: Capacitor (about 24 μf), two resistors (about

More information

Modeling of Transmission Line and Substation for Insulation Coordination Studies

Modeling of Transmission Line and Substation for Insulation Coordination Studies TRAINING DUBROVNIK, CROATIA - APRIL, 27-29 2009 SIMULATION & ANALYSIS OF POWER SYSTEM TRANSIENTS WITH EMTP-RV Modeling of Transmission Line and Substation for Insulation Coordination Studies Prof. Ivo

More information

University of Rome Tor Vergata

University of Rome Tor Vergata University of Rome Tor Vergata Faculty of Engineering Department of Industrial Engineering THERMODYNAMIC AND HEAT TRANSFER HEAT TRANSFER dr. G. Bovesecchi gianluigi.bovesecchi@gmail.com 06-7259-727 (7249)

More information

MKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits

MKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits MKV AC Capacitors B 25 835 High dielectric strength High peak-current capability Especially suitable for snubber circuits Construction Self-healing Plastic dielectric Oil-impregnated tubular windings (no

More information

Fault Calculation Methods

Fault Calculation Methods ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the

More information

16 Appendix 16 Electrical Research Association Report

16 Appendix 16 Electrical Research Association Report Guide to the Wiring Regulations 16 Appendix 16 Electrical Research Association Report (ERA) report on armoured cables with external CPCs The attached report was commissioned by the ECA and is copyright

More information

Keywords: HVDC cable, Analytical calculation, PMLTCT, PMITD.

Keywords: HVDC cable, Analytical calculation, PMLTCT, PMITD. 017 nd International Conference on Applied Mathematics, Simulation and Modelling (AMSM 017) ISBN: 978-1-60595-480-6 Analytical Calculation Method for Steady-state Current Capacity of HVDC Cables Chun-sheng

More information

convection coefficient, h c = 18.1 W m K and the surrounding temperature to be 20 C.) (20 marks) Question 3 [35 marks]

convection coefficient, h c = 18.1 W m K and the surrounding temperature to be 20 C.) (20 marks) Question 3 [35 marks] COP 311 June Examination 18 June 005 Duration: 3 hours Starting time: 08:30 Internal examiners: Prof. T. Majozi Mnr. D.J. de Kock Mnr. A.T. Tolmay External examiner: Mnr. B. du Plessis Metallurgists: Questions

More information

Thermal model of oil power transformers with a tap changer

Thermal model of oil power transformers with a tap changer Turkish Journal of Electrical Engineering & Computer Sciences http:// journals. tubitak. gov. tr/ elektrik/ Research Article Turk J Elec Eng & Comp Sci (2016) 24: 3293 3308 c TÜBİTAK doi:10.3906/elk-1408-208

More information

Chapter 27. Current and Resistance

Chapter 27. Current and Resistance Chapter 27 Current and Resistance Electric Current Most practical applications of electricity deal with electric currents. The electric charges move through some region of space. The resistor is a new

More information

Physics 212 Spring 2009 Exam 2 Version C (832725)

Physics 212 Spring 2009 Exam 2 Version C (832725) Physics 212 Spring 2009 Exam 2 Version C (832725) Question 1 2 3 4 5 6 7 8 9 10 Instructions Be sure to answer every question. Follow the rules shown on the first page for filling in the Scantron form.

More information

Chapter 27. Current And Resistance

Chapter 27. Current And Resistance Chapter 27 Current And Resistance Electric Current Electric current is the rate of flow of charge through some region of space The SI unit of current is the ampere (A) 1 A = 1 C / s The symbol for electric

More information

15 Inductance solenoid, shorted coax

15 Inductance solenoid, shorted coax z 15 nductance solenoid, shorted coax 3 Given a current conducting path C, themagneticfluxψ linking C can be expressed as a function of current circulating around C. 2 1 Ψ f the function is linear, i.e.,

More information

Extensions to the Finite Element Technique for the Magneto-Thermal Analysis of Aged Oil Cooled-Insulated Power Transformers

Extensions to the Finite Element Technique for the Magneto-Thermal Analysis of Aged Oil Cooled-Insulated Power Transformers Journal of Electromagnetic Analysis and Applications, 2012, 4, 167-176 http://dx.doi.org/10.4236/jemaa.2012.44022 Published Online April 2012 (http://www.scirp.org/journal/jemaa) 167 Extensions to the

More information

H07RN-F. Flexible Cables and Cords 60 C 450/750 V. Application. Specifications

H07RN-F. Flexible Cables and Cords 60 C 450/750 V. Application. Specifications H0RN-F 0 C 0/0 V Application For mains supply or extension leads for portable or fixed equipment operating indoors or outdoors (domestic or industrial) under conditions of frequent handling trailing or

More information

Chapter 10: Air Breakdown

Chapter 10: Air Breakdown ELECTOMAGNETIC COMPATIBILITY HANDBOOK 1 Chapter 10: Air Breakdown 10.1 How is a silicon controlled rectifier (SC) similar to the breakdown of a gas? 10.S By comparing to an actual Paschen curve for air

More information

Code No: RR Set No. 1

Code No: RR Set No. 1 Code No: RR410209 Set No. 1 1. What are the gases mainly used in insulating medium at high pressures? Which is more suitable? Why? What about its dielectric strength? Explain. [16] 2. (a) Define time lags

More information

On Designing of a High Voltage Standard Capacitor Using a Semi-Analytical Field Computation Method

On Designing of a High Voltage Standard Capacitor Using a Semi-Analytical Field Computation Method Proc. 2016 Electrostatics Joint Conference 1 On Designing of a High Voltage Standard Capacitor Using a Semi-Analytical Field Computation Method N. K. Kishore Professor, Dept. of Electrical Engineering

More information

The Proposed Electric Circuit Diagram Of The Buried Bare Pipe Segment- Soil - Earth System With And Without Applying Cathodic Protection System

The Proposed Electric Circuit Diagram Of The Buried Bare Pipe Segment- Soil - Earth System With And Without Applying Cathodic Protection System The Proposed Electric Circuit Diagram Of The Buried Bare Pipe Segment- Soil - Earth System With And Without Applying Cathodic Protection System Dr. Ashraf Abdel Raouf Mohamed Fouad Ahmed Canadian International

More information

High Frequency Dielectric Strength Tests

High Frequency Dielectric Strength Tests High Frequency Dielectric Strength Tests Insulation tests at high frequency (HF) need to be done with great care. The mechanism of breakdown is different to normal mains frequency dielectric strength tests

More information

which checks. capacitance is determined entirely by the dimensions of the cylinders.

which checks. capacitance is determined entirely by the dimensions of the cylinders. 4.3. IDENTIFY and SET UP: It is a parallel-plate air capacitor, so we can apply the equations of Section 4.. EXEUTE: (a) (b) = ε 0 A d (c) V ab so Q V = so 0 ab V ab 6 Q 0. 48 0 = = = 604 V. 45 0 F 3 d

More information

Metallized polyester film capacitors MKT 470

Metallized polyester film capacitors MKT 470 MKT RADIAL POTTED TYPE PITCH 5 mm CBA141 Fig.1 Simplified outlines. FEATURES Low-inductive wound cell of metallized (PETP) film Potted with epoxy resin in a flame-retardant case Radial leads of solder-coated

More information

Thermal Management for LED Applications

Thermal Management for LED Applications Thermal Management for LED Applications What is the role of the PCB? http://saturnelectronics.com/thermal_pcb_design_led_signup.htm Presented by Clemens Lasance Clemens is a former Principal Scientist

More information

Thermal Resistance, Power Dissipation and Current Rating for Ceramic and Porcelain Multilayer Capacitors

Thermal Resistance, Power Dissipation and Current Rating for Ceramic and Porcelain Multilayer Capacitors Thermal Resistance, Power Dissipation and Current Rating for Ceramic and Porcelain Multilayer Capacitors by F. M. Schaubauer and R. Blumkin American Technical Ceramics Reprinted from RF Design Magazine,

More information

Lecture 18 Capacitance and Conductance

Lecture 18 Capacitance and Conductance Lecture 18 Capacitance and Conductance Sections: 6.3, 6.4, 6.5 Homework: See homework file Definition of Capacitance capacitance is a measure of the ability of the physical structure to accumulate electrical

More information

Thermal and Mechanical Properties of EPR and XLPE Cable Compounds

Thermal and Mechanical Properties of EPR and XLPE Cable Compounds F E A T U R E A R T I C L E Thermal and Mechanical Properties of EPR and XLPE Cable Compounds Key Words: EPR, TRXLPE, thermal conductivity/resistivity, thermal diffusivity, heat capacity, thermal expansion,

More information

Review. Spring Semester /21/14. Physics for Scientists & Engineers 2 1

Review. Spring Semester /21/14. Physics for Scientists & Engineers 2 1 Review Spring Semester 2014 Physics for Scientists & Engineers 2 1 Notes! Homework set 13 extended to Tuesday, 4/22! Remember to fill out SIRS form: https://sirsonline.msu.edu Physics for Scientists &

More information

Chapter 6: Efficiency and Heating. 9/18/2003 Electromechanical Dynamics 1

Chapter 6: Efficiency and Heating. 9/18/2003 Electromechanical Dynamics 1 Chapter 6: Efficiency and Heating 9/18/2003 Electromechanical Dynamics 1 Losses As a machine transforms energy from one form to another there is always a certain power loss the loss is expressed as heat,

More information

FIND: (a) Sketch temperature distribution, T(x,t), (b) Sketch the heat flux at the outer surface, q L,t as a function of time.

FIND: (a) Sketch temperature distribution, T(x,t), (b) Sketch the heat flux at the outer surface, q L,t as a function of time. PROBLEM 5.1 NOWN: Electrical heater attached to backside of plate while front surface is exposed to convection process (T,h); initially plate is at a uniform temperature of the ambient air and suddenly

More information

Trade of Electrician. Resistance Network Measurement

Trade of Electrician. Resistance Network Measurement Trade of Electrician Standards Based Apprenticeship Resistance Network Measurement Phase 2 Module No. 2.1 Unit No. 2.1.5 COURSE NOTES Created by Gerry Ryan - Galway TC Revision 1. April 2000 by Gerry Ryan

More information

Consider a point P on the line joining the two charges, as shown in the given figure.

Consider a point P on the line joining the two charges, as shown in the given figure. Question 2.1: Two charges 5 10 8 C and 3 10 8 C are located 16 cm apart. At what point(s) on the line joining the two charges is the electric potential zero? Take the potential at infinity to be zero.

More information

THERMAL BEHAVIOR OF DISTRIBUTION TRANSFORMERS IN SUMMERTIME AND SEVERE LOADING CONDITIONS

THERMAL BEHAVIOR OF DISTRIBUTION TRANSFORMERS IN SUMMERTIME AND SEVERE LOADING CONDITIONS THERMAL BEHAVIOR OF DISTRIBUTION TRANSFORMERS IN SUMMERTIME AND SEVERE LDING CONDITIONS Cesare RAVETTA Massimo SAMANNA Angelo STUCCHI Antonio BOSSI Aem Elettricità Italy Aem Elettricità Italy Aem Calore

More information

Capacitance and Dielectrics

Capacitance and Dielectrics Slide 1 / 39 Capacitance and Dielectrics 2011 by Bryan Pflueger Capacitors Slide 2 / 39 A capacitor is any two conductors seperated by an insulator, such as air or another material. Each conductor has

More information