CONSTRUCTION OF GENERATOR CAPABILITY CURVES USING THE NEW METHOD FOR DETERMINATION OF POTIER REACTANCE

Size: px
Start display at page:

Download "CONSTRUCTION OF GENERATOR CAPABILITY CURVES USING THE NEW METHOD FOR DETERMINATION OF POTIER REACTANCE"

Transcription

1 CONSTRUCTION OF GENERATOR CAPABILITY CURVES USING THE NEW METHOD FOR DETERMINATION OF POTIER REACTANCE M.M. Kostić *, M. Ivanović *, B. Kostić *, S. Ilić** and D. Ćirić** Electrical Engineering Institute Nikola Tesla, Belgrade, SERBIA* TPPs-OCMs "Kostolac", Kostolac, SERBIA ** Abstract: The most important objective of this paper is the fact that it enables the capability curve (P-Q curve) of generator to be determined only on the base of the results of the no-load and reactive load examinations held in the power plant. First, the values (dependences) of the Potier reactance (X P ) in the area of the relevant values of reactive loads are determined, and then according to those results the capability curve (P G -Q G curve) of the generator is being constructed. This method is verified for experimental modes of active and reactive power around the nominal values, on the example of turbogenerator 348 MW in power plant "Kostolac B". It is important that the significant discrepancies in relation to the P-Q curve of the drive manufacturer's documentation generator were established, and thereby the recommendations for defining (or testing) the P-Q curve in the period of times, every 5-6 years or after major repairs. Similar discrepancies were obtained during the extensive testing and research for newer generators in U.S. Key words: capability curve of generator, Potier reactance, inductive load test (at zero power factor), no-load test, short circuit test. 1. INTRODUCTION Capability curvess, P G -Q G curve, Figure 1, are necessary to the operating stuff for the proper selection of the generator's load. These curves define the limits of reactive power modes Q G Q G,N (Mvar) during operation of generators with a nominal or reduced the active power P G P G,N (MW), while at the same temperature and excitation currents do not exceed allowable limits. Thus, the elevated reactive power for 1% brings to the rotor winding overheating by 2% when it comes to new generators with saturated magnetic circuit. Therefore, it is important to dispose of as accurate P G -Q G curves, both for operation and planning. The most important part of the curve is the part with coordinates (Q G Q G,N, P G P G,N ), because it defines the modes when the generator is running with increased reactive power.

2 It is not unknown that, with certainty, the drive charts (P G -Q G curves), which are found in the manufacturer, can not be accepted. An additional difficulty is that, during the years of work, it comes inevitably to minor or major changes in the parameters of generators that are relevant for the definition of P-Q curves. Therefore, it is common in the period of exploitation to define or test P-Q curves periodically, every 6-7 years or after major repairs. Significant discrepancies of capability curves, compared to those given by manufacturers, were obtained during the extensive testing and research for newer generators in U.S., [1, 2], Figure 1. Figure 1: Comparison chart of actual capability curves (P-Q curves) with the manufacturer's generator capability curves 2. BASIC PRINCIPLES FOR THE DESIGN OF CAPABILITY CURVE 2.1. Capability curve of generator with unsaturated magnetic circuit The basis for designing the capability curve (P-Q curve) is a vector diagram of generator electromotive forces, Figure 2. When constructing a vector diagram, Figure 2, resistance of the generator inductor winding is ignored and the saturation of magnetic circuits is being neglected as well. For the unsaturated machine, vector diagram of generator electromotive forces represents also (with corresponding scaling ratio) the vector diagram of generator excitation currents. When the generator is connected to a strong network (unlimited power), the voltage on the generator connections remains constant (u = u n = 1 = Const.). It is further assumed that the generator is loaded with a nominal current (i = i n = 1 = Const.) while the current phase position (φ) changes

3 and thus change the corresponding values of active (p) and reactive (q) power, in relative units of apparent power (s n = u n, i = 1 ). Figure 2: Vector diagram of generator electromotive forces (and the excitation currents) Generator is sized in a way to reach the nominal temperature at the rated values of active (p n ) and reactive (q n ) powers, the point R on Figure 2. Although the stator winding retains the nominal value of temperature for all induct currents, i a = i an = 1 = Const., the generator will not be able to work with rated induct current when the current phase increases (φ > φ n ) so that the active power decreases and reactive power increases. Namely, the excitation current then begins to exceed the nominal excitation current, i.e. i a = Const. curve is above the curve i f = Const., Figure 2. As the value of excitation current in the nominal mode, as a rule, is also the maximal allowed value of the current (i fmax = i fn = Const.), allowable values of reactive power increase more slowly than in the case when there are no limitations on excitation current. Curve i f = Const., from the point (R), defines the limits of reactive power modes, q q R (), in work of the generator with a nominal or reduced active power p p R (), while not allowing to current (and temperature) of excitation winding to exceed the allowable value. The neglect of saturation of magnetic circuit enters an error, which is even greater when the mentioned generator is more saturated. When it comes to modern large power generators ( MW), its magnetic circuit is so saturated that the construction of more accurate vector diagrams, such as one on Figure 2, and the corresponding chart drive requires extensive testing with measurements and (or) complicated calculations of electric forces, Figure Capability curve of generator with saturated magnetic circuit When it comes to vector diagrams of excitation currents of generator with saturated magnetic circuit, it is necessary:

4 - to use the curve of saturated machine, which is derived from no-load test, but also - to include additional magnetic circuit saturation on the part of the rotor of loaded machine. It is particularly difficult to quantify the second impact. Some authors do this by using data on values of longitudinal synchronous reactance in saturated mode (x d,sat < x d ), while others introduce Potier reactance (x P > x l ) instead of the stator leakage reactance (x l ). By Potier method, reffered influence of additional saturation of the rotor magnetic circuit is counted by an increase of stator leakage reactance (x l ), so as x P > x l and the corresponding electromotive force behind Potier reactance e P = u+x P i>u+x l i = e l, i.e. it is greater than electromotive force behind the leakage reactance, Figure 3. Figure 3: Magnetization curves, in no-load mode i f0 (e) = i f0 (e P ) and at loaded machine i fl (e l ); vector diagrams of electromotive forces behind Potier reactance (e P ) and behind the leakage reactance (e l ); vector diagrams of excitation currents: i fp i fl, i fa,n = x d - x P and i fr = i fp + i fa,n ; saturation components Δi f (e P ) = Δi fu + Δi fs + Δi fr Qualitative view of the impact (increase) component of saturation current Δi f (e P ) = Δi fu + Δi fs + Δi fr (Figure 3) is presented on Figure 4. Component of saturation excitation current is counted in a way that starting point of a vector diagram moves down the value of Δi f (e P ). Since the length of the excitation current vector is constant (i fi = Const.), and the mentioned starting point is changed (points C R, C 1, C 2 and C M ), the corresponding arches i fi = Const. are moved down as well. Thus, for purely reactive load (p = 0), instead of point q' M, point q M with less reactive power q M < q' M is obtained (q' M - corresponding reactive for power generator with saturated magnetic circuit).

5 Figure 4: Diagrams of electromotive forces and excitation currents for generator with saturated magnetic circuit 3. DETERMINATION OF POTIER REACTANCE FOR TURBOGENERATORS The results of numerous investigations [5-10] confirm the fact that Potier reactance, considered as a constant parameter values, is not suitable for calculations and analysis of synchronous machines in a wider range of generator voltage, and even in the range of real change of generator electromotive forces (E p or E l ). This means that for accurate calculations and capability curve construction, values of Potier reactance (x P ) for examined regimes should be obtained (or defined). This means that it is necessary to determine the dependence of this reactance for the required regimes, for example x P (u,q) Determination of Potier reactance for turbogenerators in relevant regimes At equal values of reactive power (Q G ) in any operating mode and inductive load mode of generator (Q G = Q Gi,cosφ = 0 ), the corresponding values of generator voltage are also practically equal U Gi = U G,cosφ=0. On this basis, as has been shown [12, 13], the conclusion about approximate equality of the appropriate values of Potier reactances (x p,i = x p,cosφ=0 ): x p,i = x p,cosφ=0, for Q Gi = Q G,cosφ=0

6 Hereby, for a particular generator and the corresponding regime of generator voltage U Gi = f u (Q G ), dependence of Potier reactance x p = f(q G,U G ) is reduced to uniform dependence x p = f(q G ), for the (approximately) constant voltage at the point of connection to the electric power system. U EES = Const. It provides that, instead of family P-Q curves, the appropriate (unambiguous) P/Q dependence, for the voltage at the point of connection to the electric power system, should be used. By this way defined value of Potier reactance for nominal mode, is approximately equal to x P90, fot the reactive load mode with current i = i an sinφ n (u = u n, i = i an sinφ n and φ = 90 0 ), i.e.: x P,n x P90, for i 90 = i an sinφ n (1) This means that the obtained values (dependences) of Potier reactance from the inductive load tests could be used to design the appropriate capability chart for the very same generator [13, 14]. The specified rule was tested on the example of mentioned generator GTHW 360 (360 MW) in the nominal regime, i.e. by comparison of [13]: - measured values for the generator excitation current regimes around the nominal (P G P Gn, and Q G Q Gn ), and - calculated values based on the same value of Potier reactances (x P ), defined for Q G Q Gn. Calculated values of excitation current (I F ) differ by about 0.4% which is within the limits of accuracy of the measured values of excitation current (I F ). It is expected that the accuracy is higher in the area of higher values of reactive power, as appropriate (allowed) active power is less, so those regimes are less different from referent regimes for reactive loads for which the valuse of Potier reactances are determined. Based on this and equality (1), it comes to the more general equality [13]: x P x P90, for i 90 = i a sinφ n (2) 3.2. Determination of values (dependences) of Potier reactance from the induction load tests Values (dependances) of Potier reactance are determined from the induction load test for relevant values of the load. The entire process is automated and conducted on the computer (the "Excel"), by a new method for determining the value of Potier reactance [11]. Sometimes manufacturer's parameters of the machine are not reliable data. In order to verify this, no-load and short circuit tests were carried out. From no-load test the corresponding dependence i 0 (e 0 ) was obtained, and it was found that the values of excitation current in no-load regime (I f0 ) and excitation in air-gap (I fg ), are somewhat different from those obtained from the manufacture. Thus: - measured values are I f0 =807 A and I fg = 677 A, while - values from manufacturer's data are I f0 =818 A and I fg = 703 A. In the short circuit test the value of direct-axis synchronous reactance was determined, x d,mer = 2.535, which significantly differs from the value provided by manufacturer, x d,manuf =

7 The functin of Potier reactance x p = f(q G, U G ), for tested generator GTHW 360, 348 MW [14], is given in the Table 1 for wider range of reactive powers. Besides the relative values of reactive powers (Q G /Q G,N ) i voltages (U G /U G,N ), there are presented their absolute values as well (Q G, U G ). Namely, the calculation of specific valuse of Potier reactance (x p ), for this generator, the absolute values of reactive power (Q G ) and voltage (U G ) are competent, i.e. the corresponding pair of values Q Gi, U Gi. The aforementioned calculations were conducted for the nominal apparent power generator S G,N = 410 MVA and cosφ GN = 0.85, and for the most active power P G,N = MW and the corresponding reactive power Q G,N = 216 Mvar. Table 1: Values of Potier reactance x p, i.e. x p,i (Q G ) = x p,cosφ=0 (Q G ), for given values Q G [Mvar], U G [kv] and S G,N = 410 MVA QG QG U G U G Q G x p QG, N SG, N U G, N kv Mvar In Figure 5 is given a graphical representation of dependence of Potier reactance, x p,i (Q G ). The Potier reactance values (x p ), for generator GTH-360 are changing in the wider limits when reactive power changes. These values decrease with increase in load, but Potier reactance value can not become equal to the leakage reactance (x l = 0.188) as it is stated in the literature - it is rather x p,min x l , Figure 5.

8 x [r.j.] x P x l Q G /Q G,N [r.j.] Figure 5: Dependance of Potier reactance for generator GTH-360 from reactive power, x p,i (Q G ), and comparative illustration with leakage reactance values (x l = 0.188) 4. CONSTRUCTION OF GENERATOR CAPABILITY CURVE If one has the exact Potier reactance values for all investigated regimes, it would be possible to construct more accurate vector diagram and the corresponding capability curve, Figure 4. The point is to calculate, for given characteristics of the regime and the corresponding value of Potier reactance, the value of excitation current, i.e. to calculate, for given (nominal) value of excitation current (i fn ) and given value of active power (p i ), the appropriate value of allowable reactive power (q i ). Corresponding values of actve power (P Gi ) are determined by calculations, whereby the independent ariable takes the value of reactive load Q Gi Q Gi,cosφ 0. The calculations are carried out for the relevant (and changing) value of Potier reactance for the corresponding (given) value of generator reactive load (Q Gi ) Determination of P-Q curve by a new mathod The values of excitation current, for previously determined values of Potier reactance (x p ), Table 1, ' can be calculated using the following expression which is derived from a right triangle OF R F R (Figure 3): i fr i ( x x )(s / u )(sin cos cos sin ) 2 ( x x ) (cos cos sin sin ) 2 fp d P (3) d P

9 Values cosδ, sinδ and i fp are calculated for the parameters in given regimes s = S/S n = 1, p = P n /S n = cosφ, q = Q/S n = sinφ and u = U/U n = 1. Values i fl (e p ) are determined by the observed dependence i f0 (e), for e = e p. The stated dependence i f0 (e) is given in analytical form, so the complete procedure for calculating the value of i f (or i f,n ) is automated and operated by PC. Table 2 gives a tabulation of the proceedings and results of calculations according to P-Q curve of the generator GTH-360, TE "Kostolac B" (Block B1), for currently defined maximal allowed value of excitation current I f,max = 2550 A. The calculation is carried out for given values x p = f(q G ), Table 1. The calculation procedure performed in the following way: - the values of reactive loads Q Gi Q Gi,cosφ 0 were taken as independent variables, and - the corresponding values of active power (P Gi ) were determined by calculation (3). This way, as the active power changes for given reactive power (Q G ), values cosδ and sinδ (3) are also changed (and automatically calculated). The target value of maximum active power P Gi,max = P Gi is the one for which the value of excitation current is I f,max = 2550 A. The stated equation (3) is solved numerically by PC: more precisely, the increase (or variation of assumed) values of active power (P Gi ) causes the change of the excitation current value (I f ), so the calculatin can be considered to be finished in iteration in which it becomes I f I f,max. It is obvious that this is a new procedure for determining the capability diagram (P-Q dependence). The above calculations of P-Q curve are carried out for generator nominal apparent power S G,N = 410 MVA and cosφ GN = 0.85, as for the most active power P G,N = MW and the corresponding value of reactive power Q G,N = 216 Mvar, for which the value of excitation current I fn 2550 A is determined by measurements. Afterwards, values of reactive power were increased, in steps of ΔQ G = 0.05Q G,N, i.e. a range of values of generator reactive power was formed: Q G,i = 1.00Q G,N ; 1.05Q G,N ; 1.10Q G,N ; 1.15Q G,N ; 1.20Q G,N ; 1.25Q G,N ; 1.30Q G,N ; 1.35Q G,N. The corresponding (reduced) values of the active power were established by calculations, for a given value of excitation current I f1,max = 2550A. The series of corresponding values of reactive and active power were obtained, in absolute values, and they were given in Table 2. With further increase of reactive power, for example to the value Q G,i = 1.40Q G,N, the value of excitation current would be I f1,max > 2550 A also for P G,i = 0, so the (computational) test was conducted for a small increase in reactive power, the last three rows in Table 2. Table 2: Tabulation of the proceedings and results of calculations P-Q dependence for the generator GTH- 360, for the values of excitation current I f1,max = 2550 A. x p U kv u=j δo j o P MW Q Mvar S MVA p q s i f,calc I f,calc A

10 Capability curve (P-Q curve) of the generator The above dependence in Table 2 is presented in a format that is used as an capability diagram of the generator, in the form of tabular P-Q dependences. Thus, based on data obtained from Table 2 the corresponding P-Q dependence is obtained, Table 3. Table 3: Capability diagram generator for GTH - 360, P-Q spreadsheet dependency, for i f1,max = 2550 A Q G,i /Q G,N () Q G,i (Mvar) P G,i (MW) It has been established that manufacturer's P-Q curve for generator GTH 360, for a reduced active power: 250 MW (or P G = 0.71P G,N ), 200 MW (P G = 0.581P G,N ) and 50 MW (or P G 0.20P G,N ), gives, respectively, overestimated the value of reactive power by 2%, 4% and 6%. Therefore, it is usual in the period of exploitation, every 6-7 years or after major repairs, to test (or check) the generator P-Q curves. Similar discrepancies were obtained during the extensive testing and research for newer generators in the U.S. [3, 4]. On Figure 6, in addition to the capability diagram of the manufacturer's documentation (-), the capability diagram for generator GTHW-360 is drawn, based on data obtained from the results of the corresponding calculations (- - -). Figure 6: Capability diagrams for generator GTHW-360: curve from manufacturer's documentation ( ) significantly deviates from the curve obtained during tests (- - -)

11 5. CONCLUSION The most important conclusion in this paper is that it allows to determine the P-Q curve generator according to a new method - more precisely on the basis of test results at no load and reactive load tests carried out in the plant. First, the values (dependences) of Potier reactance within the limits of the relevant values of reactive loads are determined, and then on the base of those, the P-Q curve of the generator can be constructed. This method is verified experimentally, on the example of turbogenerator with nominal power of 348 MW, in the power plant "Kostolac B" [14], for the two modes with the active and reactive power around nominal values. It is significant that noticeable deviations were established, comparing the P-Q curves from manufacturer's documentation and those which are obtained during experiments. This confirms the justification for the recommendation to experimentally test (or check) the generator P-Q curves from time to time, every 5-6 years or after major repairs. Similar discrepancies were obtained during the extensive testing and research for newer generators in the U.S. [1, 2]. 6. LITERATURE [1] N. E. Nilsson, J. Mersurio, "Synchronous Generator Capability Curve Testing and Evolution", IEEE Tran. Power Deliv. and Systems, V. No. 2 January 1994, pp [2] M.M.Adibi, D.P.Milanovic, "Reactive Capability Limitation of Synchronous Machines", IEEE Tran. Power Delivery and Systems, Vol. 9, No. 1 January 1994, pp [3] Standard IEC 34-4/1985, "ROTATION ELECTRICAL MACHINES", Part 4: Methods for determining synchronous machine quantities from tests". [4] Al, "Transmission and distribution "- Manual, Chapter "Characteristics of Machine" pp , Translation, Građevinska knjiga Beograd, [5] M. P. Kostenko, L. M. Piotrobskij,, "Električeskie mašini", str. 648, "Energija", Leningrad 1973 (in Russian). [6] A. M. El-Serafi, J.Wu, "A New Method For Determining The Armature Leakage Reactance of Synchronous Machines", IEEE Transc. on Energy Conversion,Vol. 6, No. 1, March 1991, pp [7] Ion Boldea, "Synchronous Generators - The Electric Generator Handbook", pp. 512, 2006 by Taylor &Francis Group, Boca Raton London New York, [8] A.E. Fitzgerald, Charles Kingsley, "Electrical machines", Naučna knjiga Beograd, god, page 560. (Serbian translation). [9] A. Ivanov-Smolensky, "Electrical Machines, Vol. 2", pp. 464, 1988, Publishers Moscow. [10] S. H. Minnich, SM; R. P. Schulz, SM; D. H. Baker, SM; "Saturation Functions for Synchronous Generators From Finite Elements", IEEE Transc. on Energy Conversion, Vol. EC-2, No. 4, December 1987, pp [11] M.M.Kostić, "A new method for determining the Potier reactance of synchronous turbogenerator", "Elektroprivreda", No 4, 2009, pp (in Serbian) [12] M.M.Kostić, "A new rule for determining the Potier reactance for synchronous turbogenerators relevant loads", "Elektroprivreda", No 3, 2010, (in Serbian) [13] M.M.Kostic, "Proposal for addition of IEC 34-4 Standard in part for determination of Potier reactance", "Power Plant 2010", Proceeding [14] The study "Determination of regulation, power losses and the actual diagram of active and reactive power (PQ curve generator) of blocks B1 and B2 in the power plant Kostolac B", Electrical Engineering Institute Nikola Tesla, Belgrade 2008, page 58, in Serbian

12 [15] The parameters and results of the generator Block 1 in the power plant "Kostolac B" KONSTRUISANJE POGONSKIH DIJAGRAMA GENERATORA POMOĆU NOVE METODE ZA ODREĐIVANJE POTJEOVE REAKTANSE M.M. Kostić *, M. Ivanović *, B. Kostić *, S. Ilić** i D. Ćirić** Elektrotehnički institut Nikola Tesla, Beograd, Srbija* PD Termoelektrane i kopovi Kostolac, Kostolac, Srbija ** Kratak sadržaj: Najvažniji rezultat rada je u tome da omogućava da se pogonski dijagram (P-Q kriva) generatora odredi samo na osnovu rezultata ispitivanja u praznom hodu i ogleda reaktivnog opterećenja koji se sprovode u elektrani. Prvo se utvrde vrednosti (zavisnosti) Potjeove reaktanse (x P ) u području relevantnih vrednosti reaktivnih opterećenja, pa se na osnovu istih konstruiše pogonski dijagram (P G -Q G kriva) generatora. Taj metod je, na primeru turbogeneratora snage 348 MW u Termoelektrani "Kostolac B", proveren eksperimentalnim putem za režime rada sa aktivnim i reaktivnim snagama oko nominalnih vrednosti. Značajno je da su utvrđena i značajnija odstupanja, u odnosu na P-Q krivu iz pogonske dokumentacuje proizvođača generatora, pa je time potvrđena opravdanost preporuke da se u periodu eksploatacije povremeno, na svakih 5-6 godina ili posle većih remonata, ispitivanjima određuju (ili proveravaju) P-Q krive generatora. Slična odstupanja su dobijena i tokom opsežnih ispitivanja i istraživanja za novije generatore u SAD. Ključne reči: pogonski dijagram generatora, Potjeova reaktansa, ogled reaktivnog opterećenja, ogled praznog hoda, ogled kratkog spoja.

Abstract The capability (P-Q) curve of generator can be determined only on the base of examinations in the power plant, i.e. on the base of: the no-lo

Abstract The capability (P-Q) curve of generator can be determined only on the base of examinations in the power plant, i.e. on the base of: the no-lo CONSTRUCTION OF GENERATOR CAPABILITY CURVES USING THE NEW METHOD FOR DETERMINATION OF POTIER REACTANCE M.M. Kostić*, M. Ivanović*, B. Kostić*, S. Ilić** and D. Ćirić** Electrical Engineering Institute

More information

PROPOSAL FOR ADDITION OF IEC 34-4 STANDARD IN PART FOR DETERMINATION OF POTIER REACTANCE

PROPOSAL FOR ADDITION OF IEC 34-4 STANDARD IN PART FOR DETERMINATION OF POTIER REACTANCE PROPOSAL FOR ADDITION OF IEC 34-4 STANDARD IN PART FOR DETERMINATION OF POTIER REACTANCE M. M. Kostic * Electrical Engeneering Institute Nikola Tesla, Belgrade, SERBIA* Abstract: On the base of ones investigations

More information

Determining the Generator Potier Reactance for Relevant (Reactive) Loads

Determining the Generator Potier Reactance for Relevant (Reactive) Loads ELEKTROTEHNIŠKI VESTNIK 81(3): 131-136, 2014 ORIGINAL SCIENTIFIC AER Determining the Generator otier Reactance for Relevant (Reactive) Loads Miloje Kostić Electrical Engeneering Institute Nikola Tesla,

More information

Synchronous Machines

Synchronous Machines Synchronous Machines Synchronous Machines n 1 Φ f n 1 Φ f I f I f I f damper (run-up) winding Stator: similar to induction (asynchronous) machine ( 3 phase windings that forms a rotational circular magnetic

More information

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015 ECE 325 Electric Energy System Components 7- Synchronous Machines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapters 16-17) Synchronous Generators Synchronous Motors 2 Synchronous Generators

More information

Use of the finite element method for parameter estimation of the circuit model of a high power synchronous generator

Use of the finite element method for parameter estimation of the circuit model of a high power synchronous generator BULLETIN OF THE POLISH ACADEMY OF SCIENCES TECHNICAL SCIENCES, Vol. 63, No. 3, 2015 DOI: 10.1515/bpasts-2015-0067 Use of the finite element method for parameter estimation of the circuit model of a high

More information

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz EE 742 Chapter 3: Power System in the Steady State Y. Baghzouz Transmission Line Model Distributed Parameter Model: Terminal Voltage/Current Relations: Characteristic impedance: Propagation constant: π

More information

Introduction to Synchronous. Machines. Kevin Gaughan

Introduction to Synchronous. Machines. Kevin Gaughan Introduction to Synchronous Machines Kevin Gaughan The Synchronous Machine An AC machine (generator or motor) with a stator winding (usually 3 phase) generating a rotating magnetic field and a rotor carrying

More information

Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines)

Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines) Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines) d axis: L fd L F - M R fd F L 1d L D - M R 1d D R fd R F e fd e F R 1d R D Subscript Notations: ( ) fd ~ field winding quantities

More information

Synchronous Machines

Synchronous Machines Synchronous Machines Synchronous generators or alternators are used to convert mechanical power derived from steam, gas, or hydraulic-turbine to ac electric power Synchronous generators are the primary

More information

1 Unified Power Flow Controller (UPFC)

1 Unified Power Flow Controller (UPFC) Power flow control with UPFC Rusejla Sadikovic Internal report 1 Unified Power Flow Controller (UPFC) The UPFC can provide simultaneous control of all basic power system parameters ( transmission voltage,

More information

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study.

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study. Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study. Marcelo Rodrigo García Saquicela, Ernesto Ruppert Filho, José Luis Azcue

More information

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10

More information

Lesson 17: Synchronous Machines

Lesson 17: Synchronous Machines Lesson 17: Synchronous Machines ET 332b Ac Motors, Generators and Power Systems Lesson 17_et332b.pptx 1 Learning Objectives After this presentation you will be able to: Explain how synchronous machines

More information

The synchronous machine (SM) in the power system (2) (Where does the electricity come from)?

The synchronous machine (SM) in the power system (2) (Where does the electricity come from)? 1 The synchronous machine (SM) in the power system (2) (Where does the electricity come from)? 2 Lecture overview Synchronous machines with more than 2 magnetic poles The relation between the number of

More information

Analytical and Numerical Calculations of Synchronous Motors for Industrial Drives

Analytical and Numerical Calculations of Synchronous Motors for Industrial Drives 014 UKSim-AMSS 8th European Modelling Symposium Analytical and Numerical Calculations of Synchronous Motors for Industrial Drives Iossif Grinbaum ABB Switzerland Ltd., Segelhofstrasse 9P 5405 Baden-Dättwil,

More information

Dynamics of the synchronous machine

Dynamics of the synchronous machine ELEC0047 - Power system dynamics, control and stability Dynamics of the synchronous machine Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 38 Time constants and

More information

ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models

ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas A&M University, overbye@tamu.edu 1 Announcements Read Chapter

More information

ECE 585 Power System Stability

ECE 585 Power System Stability Homework 1, Due on January 29 ECE 585 Power System Stability Consider the power system below. The network frequency is 60 Hz. At the pre-fault steady state (a) the power generated by the machine is 400

More information

An Introduction to Electrical Machines. P. Di Barba, University of Pavia, Italy

An Introduction to Electrical Machines. P. Di Barba, University of Pavia, Italy An Introduction to Electrical Machines P. Di Barba, University of Pavia, Italy Academic year 0-0 Contents Transformer. An overview of the device. Principle of operation of a single-phase transformer 3.

More information

The Operation of a Generator on Infinite Busbars

The Operation of a Generator on Infinite Busbars The Operation of a Generator on Infinite Busbars In order to simplify the ideas as much as possible the resistance of the generator will be neglected; in practice this assumption is usually reasonable.

More information

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.685 Electric Machines Problem Set 10 Issued November 11, 2013 Due November 20, 2013 Problem 1: Permanent

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation

More information

Synergetic Control for Electromechanical Systems

Synergetic Control for Electromechanical Systems Synergetic Control for Electromechanical Systems Anatoly A. Kolesnikov, Roger Dougal, Guennady E. Veselov, Andrey N. Popov, Alexander A. Kolesnikov Taganrog State University of Radio-Engineering Automatic

More information

Analytical Model for Sizing the Magnets of Permanent Magnet Synchronous Machines

Analytical Model for Sizing the Magnets of Permanent Magnet Synchronous Machines Journal of Electrical Engineering 3 (2015) 134-141 doi: 10.17265/2328-2223/2015.03.004 D DAVID PUBLISHING Analytical Model for Sizing Magnets of Permanent Magnet Synchronous Machines George Todorov and

More information

Generators. What its all about

Generators. What its all about Generators What its all about How do we make a generator? Synchronous Operation Rotor Magnetic Field Stator Magnetic Field Forces and Magnetic Fields Force Between Fields Motoring Generators & motors are

More information

A Simple Nonlinear Model of the Switched Reluctance Motor

A Simple Nonlinear Model of the Switched Reluctance Motor IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL 15, NO 4, DECEMBER 2000 395 A Simple Nonlinear Model of the Switched Reluctance Motor Vladan Vujičić and Slobodan N Vukosavić Abstract The paper presents a simple

More information

AN EFFICIENT APPROACH FOR ANALYSIS OF ISOLATED SELF EXCITED INDUCTION GENERATOR

AN EFFICIENT APPROACH FOR ANALYSIS OF ISOLATED SELF EXCITED INDUCTION GENERATOR AN EFFICIENT APPROACH FOR ANALYSIS OF ISOLATED SELF EXCITED INDUCTION GENERATOR Deepika 1, Pankaj Mehara Assistant Professor, Dept. of EE, DCRUST, Murthal, India 1 PG Student, Dept. of EE, DCRUST, Murthal,

More information

Nonlinear Electrical FEA Simulation of 1MW High Power. Synchronous Generator System

Nonlinear Electrical FEA Simulation of 1MW High Power. Synchronous Generator System Nonlinear Electrical FEA Simulation of 1MW High Power Synchronous Generator System Jie Chen Jay G Vaidya Electrodynamics Associates, Inc. 409 Eastbridge Drive, Oviedo, FL 32765 Shaohua Lin Thomas Wu ABSTRACT

More information

EE 451 Power System Stability

EE 451 Power System Stability EE 451 Power System Stability Power system operates in synchronous mode Power system is subjected to a wide range of disturbances (small and large) - Loads and generation changes - Network changes - Faults

More information

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A 1. What are the advantages of an inter connected system? The advantages of an inter-connected system are

More information

An Efficient Decoupled Power Flow Control Method by use of Phase Shifting Transformers

An Efficient Decoupled Power Flow Control Method by use of Phase Shifting Transformers FACTA UNIVERSITATIS (NIŠ) SER.: ELEC. ENERG. vol. 17, April 2004, 111-119 An Efficient Decoupled Power Flow Control Method by use of Phase Shifting Transformers Dragan P. Popović Abstract: This paper presents

More information

Brief Steady of Power Factor Improvement

Brief Steady of Power Factor Improvement International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 5 (2013), pp. 531-539 International Research PublicationHouse http://www.irphouse.com Brief Steady of Power Factor Improvement

More information

Synchronous Machines

Synchronous Machines Synchronous machine 1. Construction Generator Exciter View of a twopole round rotor generator and exciter. A Stator with laminated iron core C Slots with phase winding B A B Rotor with dc winding B N S

More information

Module 3 : Sequence Components and Fault Analysis

Module 3 : Sequence Components and Fault Analysis Module 3 : Sequence Components and Fault Analysis Lecture 12 : Sequence Modeling of Power Apparatus Objectives In this lecture we will discuss Per unit calculation and its advantages. Modeling aspects

More information

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session Name: Student ID: Signature: THE UNIVERSITY OF NEW SOUTH WALES School of Electrical Engineering & Telecommunications FINALEXAMINATION Session 00 ELEC46 Power System Analysis TIME ALLOWED: 3 hours TOTAL

More information

Analyzing the Effect of Ambient Temperature and Loads Power Factor on Electric Generator Power Rating

Analyzing the Effect of Ambient Temperature and Loads Power Factor on Electric Generator Power Rating Analyzing the Effect of Ambient Temperature and Loads Power Factor on Electric Generator Power Rating Ahmed Elsebaay, Maged A. Abu Adma, Mahmoud Ramadan Abstract This study presents a technique clarifying

More information

ECE 421/521 Electric Energy Systems Power Systems Analysis I 3 Generators, Transformers and the Per-Unit System. Instructor: Kai Sun Fall 2013

ECE 421/521 Electric Energy Systems Power Systems Analysis I 3 Generators, Transformers and the Per-Unit System. Instructor: Kai Sun Fall 2013 ECE 41/51 Electric Energy Systems Power Systems Analysis I 3 Generators, Transformers and the Per-Unit System Instructor: Kai Sun Fall 013 1 Outline Synchronous Generators Power Transformers The Per-Unit

More information

3 d Calculate the product of the motor constant and the pole flux KΦ in this operating point. 2 e Calculate the torque.

3 d Calculate the product of the motor constant and the pole flux KΦ in this operating point. 2 e Calculate the torque. Exam Electrical Machines and Drives (ET4117) 11 November 011 from 14.00 to 17.00. This exam consists of 5 problems on 4 pages. Page 5 can be used to answer problem 4 question b. The number before a question

More information

From now, we ignore the superbar - with variables in per unit. ψ ψ. l ad ad ad ψ. ψ ψ ψ

From now, we ignore the superbar - with variables in per unit. ψ ψ. l ad ad ad ψ. ψ ψ ψ From now, we ignore the superbar - with variables in per unit. ψ 0 L0 i0 ψ L + L L L i d l ad ad ad d ψ F Lad LF MR if = ψ D Lad MR LD id ψ q Ll + Laq L aq i q ψ Q Laq LQ iq 41 Equivalent Circuits for

More information

Modeling of Power System Components During Electromagnetic Transients

Modeling of Power System Components During Electromagnetic Transients Modeling of Power System Components During Electromagnetic Transients 1 Paweł Sowa, 2 Rafał Kumala and 3 Katarzyna Łuszcz 1, 2,3 Faculty of Electrical Engineering, Silesian University of Technology/ Institute

More information

Steady State Modeling of Doubly Fed Induction Generator

Steady State Modeling of Doubly Fed Induction Generator Steady State Modeling of Douly Fed Induction Generator Bhola Jha 1, Dr. K. R. M Rao 2 1 Dept. of Electrical Engg., G. B. Pant Engg. College, Pauri-Garhwal, India 2 Dept. of Electrical Engg., M. J. College

More information

Chapter 6. Induction Motors. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.

Chapter 6. Induction Motors. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Chapter 6 Induction Motors 1 The Development of Induced Torque in an Induction Motor Figure 6-6 The development of induced torque in an induction motor. (a) The rotating stator field B S induces a voltage

More information

7. Transient stability

7. Transient stability 1 7. Transient stability In AC power system, each generator is to keep phase relationship according to the relevant power flow, i.e. for a certain reactance X, the both terminal voltages V1and V2, and

More information

Electrical Machines and Energy Systems: Operating Principles (Part 2) SYED A Rizvi

Electrical Machines and Energy Systems: Operating Principles (Part 2) SYED A Rizvi Electrical Machines and Energy Systems: Operating Principles (Part 2) SYED A Rizvi AC Machines Operating Principles: Synchronous Motor In synchronous motors, the stator of the motor has a rotating magnetic

More information

TRANSIENT ANALYSIS OF SELF-EXCITED INDUCTION GENERATOR UNDER BALANCED AND UNBALANCED OPERATING CONDITIONS

TRANSIENT ANALYSIS OF SELF-EXCITED INDUCTION GENERATOR UNDER BALANCED AND UNBALANCED OPERATING CONDITIONS TRANSIENT ANALYSIS OF SELF-EXCITED INDUCTION GENERATOR UNDER BALANCED AND UNBALANCED OPERATING CONDITIONS G. HARI BABU Assistant Professor Department of EEE Gitam(Deemed to be University), Visakhapatnam

More information

SYNCHRONOUS GENERATOR s ROTOR INVESTIGATION OF A HYBRID POWER SYSTEM INCLUDING A.G.

SYNCHRONOUS GENERATOR s ROTOR INVESTIGATION OF A HYBRID POWER SYSTEM INCLUDING A.G. Proc. of the 5th WSEAS/IASME Int. Conf. on Electric Power Systems, High Voltages, Electric Machines, Tenerife, Spain, December 16-18, 25 (pp59-514) SYNCHRONOUS GENERATOR s ROTOR INVESTIGATION OF A HYBRID

More information

Exercise 2: Power Factor

Exercise 2: Power Factor Power in AC Circuits AC 2 Fundamentals Exercise 2: Power Factor EXERCISE OBJECTIVE When you have completed this exercise, you will be able to determine the power factor of ac circuits by using standard

More information

Fault Analysis Power System Representation

Fault Analysis Power System Representation .1. Power System Representation Single Line Diagram: Almost all modern power systems are three phase systems with the phases of equal magnitude and equal phase difference (i.e., 10 o ). These three phase

More information

TURBO-GENERATOR MODEL WITH MAGNETIC SATURATION

TURBO-GENERATOR MODEL WITH MAGNETIC SATURATION TURBO-GENERATOR MODEL WITH MAGNETIC SATURATION R. HADIK Department for Electrotechnics, Technical University, H-1521 Budapest Received May 8, 1984 Presented by Prof. Or. I. Nagy Summary In this paper a

More information

Synchronous Generator Model Identification and Parameter Estimation From Operating Data

Synchronous Generator Model Identification and Parameter Estimation From Operating Data IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 18, NO. 1, MARCH 2003 121 Synchronous Generator Model Identification and Parameter Estimation From Operating Data H. Bora Karayaka, Ali Keyhani, Fellow, IEEE,

More information

CHAPTER 2 CAPACITANCE REQUIREMENTS OF SIX-PHASE SELF-EXCITED INDUCTION GENERATORS

CHAPTER 2 CAPACITANCE REQUIREMENTS OF SIX-PHASE SELF-EXCITED INDUCTION GENERATORS 9 CHAPTER 2 CAPACITANCE REQUIREMENTS OF SIX-PHASE SELF-EXCITED INDUCTION GENERATORS 2.. INTRODUCTION Rapidly depleting rate of conventional energy sources, has led the scientists to explore the possibility

More information

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION PART: A 1. Define per unit value of an electrical quantity. Write equation for base impedance with respect to 3-phase system. 2. What is bus admittance

More information

Energy saving in electromechanical equipment with power coefficient correction. Dimitris Al. Katsaprakakis Aeolian Land S.A.

Energy saving in electromechanical equipment with power coefficient correction. Dimitris Al. Katsaprakakis Aeolian Land S.A. Energy saving in electromechanical equipment with power coefficient correction Dimitris Al. Katsaprakakis Aeolian Land S.A. www.aiolikigi.gr Introduction Electricity production companies (utilities) provide

More information

Design and Characteristic Analysis of LSM for High Speed Train System using Magnetic Equivalent Circuit

Design and Characteristic Analysis of LSM for High Speed Train System using Magnetic Equivalent Circuit IJR International Journal of Railway Vol. 3, No. 1 / March 2010, pp. 14-18 The Korean Society for Railway Design and Characteristic Analysis of LSM for High Speed Train System using Magnetic Equivalent

More information

ECE 325 Electric Energy System Components 5 Transmission Lines. Instructor: Kai Sun Fall 2015

ECE 325 Electric Energy System Components 5 Transmission Lines. Instructor: Kai Sun Fall 2015 ECE 325 Electric Energy System Components 5 Transmission Lines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapter 25) Overview of power lines Equivalent circuit of a line Voltage regulation

More information

ELG4125: Power Transmission Lines Steady State Operation

ELG4125: Power Transmission Lines Steady State Operation ELG4125: Power Transmission Lines Steady State Operation Two-Port Networks and ABCD Models A transmission line can be represented by a two-port network, that is a network that can be isolated from the

More information

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation James Ranjith Kumar. R, Member, IEEE, Amit Jain, Member, IEEE, Power Systems Division,

More information

KINGS COLLEGE OF ENGINEERING Punalkulam

KINGS COLLEGE OF ENGINEERING Punalkulam KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK

More information

Chapter 4. Synchronous Generators. Basic Topology

Chapter 4. Synchronous Generators. Basic Topology Basic Topology Chapter 4 ynchronous Generators In stator, a three-phase winding similar to the one described in chapter 4. ince the main voltage is induced in this winding, it is also called armature winding.

More information

Regulating Transformers in Sequence Domain

Regulating Transformers in Sequence Domain ECE523: Lecture 25; Page 1/8 pu 1 Regulating Transformers in Sequence Domain A three-phase voltage regulating transformer has a per unit leakage reactance of.1, and steps the voltage from 69 kv to 35 kv.

More information

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER 1 RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER Dr. Swarn S. Kalsi, David Madura, and Michael Ross American Superconductor Corporation (USA) Abstract: A high-temperature

More information

PHASOR DIAGRAM OF TRANSFORMER. Prepared By ELECTRICALBABA.COM

PHASOR DIAGRAM OF TRANSFORMER. Prepared By ELECTRICALBABA.COM PHASOR DIAGRAM OF TRANSFORMER Prepared By ELECTRICALBABA.COM IMPORTANT POINTS FOR PHASOR OF TRANSFORMER Transformer when excited at no load, only takes excitation current which leads the working Flux by

More information

Design, analysis and fabrication of linear permanent magnet synchronous machine

Design, analysis and fabrication of linear permanent magnet synchronous machine Design, analysis and fabrication of linear permanent magnet synchronous machine Monojit Seal Dept. of Electrical Engineering, IIEST, Shibpur, Howrah - 711103 W.B., India. email: seal.monojit@gmail.com

More information

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION EE 6501 POWER SYSTEMS UNIT I INTRODUCTION PART A (2 MARKS) 1. What is single line diagram? A Single line diagram is diagrammatic representation of power system in which the components are represented by

More information

Unified Torque Expressions of AC Machines. Qian Wu

Unified Torque Expressions of AC Machines. Qian Wu Unified Torque Expressions of AC Machines Qian Wu Outline 1. Review of torque calculation methods. 2. Interaction between two magnetic fields. 3. Unified torque expression for AC machines. Permanent Magnet

More information

Parameter Estimation of Three Phase Squirrel Cage Induction Motor

Parameter Estimation of Three Phase Squirrel Cage Induction Motor International Conference On Emerging Trends in Mechanical and Electrical Engineering RESEARCH ARTICLE OPEN ACCESS Parameter Estimation of Three Phase Squirrel Cage Induction Motor Sonakshi Gupta Department

More information

ON THE PARAMETERS COMPUTATION OF A SINGLE SIDED TRANSVERSE FLUX MOTOR

ON THE PARAMETERS COMPUTATION OF A SINGLE SIDED TRANSVERSE FLUX MOTOR ON THE PARAMETERS COMPUTATION OF A SINGLE SIDED TRANSVERSE FLUX MOTOR Henneberger, G. 1 Viorel, I. A. Blissenbach, R. 1 Popan, A.D. 1 Department of Electrical Machines, RWTH Aachen, Schinkelstrasse 4,

More information

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department Philadelphia University Faculty of Engineering Student Name Student No: Serial No Final Exam, Second Semester: 2015/2016 Electrical Engineering Department Course Title: Power II Date: 21 st June 2016 Course

More information

Determination of a Synchronous Generator Characteristics via Finite Element Analysis

Determination of a Synchronous Generator Characteristics via Finite Element Analysis SERBIAN JOURNAL OF ELECTRICAL ENGINEERING Vol. 2, No. 2, November 25, 157-162 Determination of a Synchronous Generator Characteristics via Finite Element Analysis Zlatko Kolondzovski 1, Lidija Petkovska

More information

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name : Computer Methods in Power Systems Course Code : A60222

More information

A STUDY OF THE EIGENVALUE ANALYSIS CAPABILITIES OF POWER SYSTEM DYNAMICS SIMULATION SOFTWARE

A STUDY OF THE EIGENVALUE ANALYSIS CAPABILITIES OF POWER SYSTEM DYNAMICS SIMULATION SOFTWARE A STUDY OF THE EIGENVALUE ANALYSIS CAPABILITIES OF POWER SYSTEM DYNAMICS SIMULATION SOFTWARE J.G. Slootweg 1, J. Persson 2, A.M. van Voorden 1, G.C. Paap 1, W.L. Kling 1 1 Electrical Power Systems Laboratory,

More information

Towards an Improved Energy Efficiency of the Interior Permanent Magnet Synchronous Motor Drives

Towards an Improved Energy Efficiency of the Interior Permanent Magnet Synchronous Motor Drives SERBIAN JOURNAL OF ELECTRICAL ENGINEERING Vol. 11, No., June 014, 57-68 UDC: 61.311-5:61.313.33]:60.9 DOI: 10.98/SJEE131701G Towards an Improved Energy Efficiency of the Interior Permanent Magnet Synchronous

More information

Single-phase Transistor Lab Report. Module: EEE 108

Single-phase Transistor Lab Report. Module: EEE 108 Single-phase Transistor Lab Report Author: 1302509 Zhao Ruimin Module: EEE 108 Lecturer: Date: Dr.Gray May/27/2015 Abstract This lab intended to train the experimental skills of the experimenters and help

More information

Doubly salient reluctance machine or, as it is also called, switched reluctance machine. [Pyrhönen et al 2008]

Doubly salient reluctance machine or, as it is also called, switched reluctance machine. [Pyrhönen et al 2008] Doubly salient reluctance machine or, as it is also called, switched reluctance machine [Pyrhönen et al 2008] Pros and contras of a switched reluctance machine Advantages Simple robust rotor with a small

More information

Prince Sattam bin Abdulaziz University College of Engineering. Electrical Engineering Department EE 3360 Electrical Machines (II)

Prince Sattam bin Abdulaziz University College of Engineering. Electrical Engineering Department EE 3360 Electrical Machines (II) Chapter # 4 Three-Phase Induction Machines 1- Introduction (General Principles) Generally, conversion of electrical power into mechanical power takes place in the rotating part of an electric motor. In

More information

Estimation of the Armature Leakage Reactance using the Constant Excitation Test

Estimation of the Armature Leakage Reactance using the Constant Excitation Test Estimation of the Armature Leakage Reactance using the Constant Excitation Test B.T. Araujo, M.S. Han, B. Kawkabani, and E.C. Bortoni Φ Abstract -- The adoption of the best available estimate for the stator

More information

Modeling Free Acceleration of a Salient Synchronous Machine Using Two-Axis Theory

Modeling Free Acceleration of a Salient Synchronous Machine Using Two-Axis Theory 1 Modeling ree Acceleration of a Salient Synchronous Machine Using Two-Axis Theory Abdullah H. Akca and Lingling an, Senior Member, IEEE Abstract This paper investigates a nonlinear simulation model of

More information

EFFECTS OF LOAD AND SPEED VARIATIONS IN A MODIFIED CLOSED LOOP V/F INDUCTION MOTOR DRIVE

EFFECTS OF LOAD AND SPEED VARIATIONS IN A MODIFIED CLOSED LOOP V/F INDUCTION MOTOR DRIVE Nigerian Journal of Technology (NIJOTECH) Vol. 31, No. 3, November, 2012, pp. 365 369. Copyright 2012 Faculty of Engineering, University of Nigeria. ISSN 1115-8443 EFFECTS OF LOAD AND SPEED VARIATIONS

More information

DESIGN AND ANALYSIS OF AXIAL-FLUX CORELESS PERMANENT MAGNET DISK GENERATOR

DESIGN AND ANALYSIS OF AXIAL-FLUX CORELESS PERMANENT MAGNET DISK GENERATOR DESIGN AND ANALYSIS OF AXIAL-FLUX CORELESS PERMANENT MAGNET DISK GENERATOR Łukasz DR ZIKOWSKI Włodzimierz KOCZARA Institute of Control and Industrial Electronics Warsaw University of Technology, Warsaw,

More information

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 9 Transmission Line Steady State Operation Welcome to lesson 9, in Power

More information

3- BASICS. YTransformation. for balanced load. \V ab 120 = \V bc. \V ab 240 = \V ca \I a 120 = \I b \I a 240 = \I c V ab I a

3- BASICS. YTransformation. for balanced load. \V ab 120 = \V bc. \V ab 240 = \V ca \I a 120 = \I b \I a 240 = \I c V ab I a 3- BASICS YTransformation for balanced load Z =3Z Y Balanced 3- Systems \V ab 10 = \V bc \V ab 40 = \V ca \I a 10 = \I b \I a 40 = \I c V ab I a = p 3 V an = p 3 I ab \V ab 30 = \V an \I ab 30 = \I a S

More information

Tutorial Sheet Fig. Q1

Tutorial Sheet Fig. Q1 Tutorial Sheet - 04 1. The magnetic circuit shown in Fig. Q1 has dimensions A c = A g = 9 cm 2, g = 0.050 cm, l c = 30 cm, and N = 500 turns. Assume the value of the relative permeability,µ r = 70,000

More information

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis Srividya colllege of Engg & Tech,Virudhunagar Sri Vidya College of Engineering And Technology Virudhunagar 626 005 Department of Electrical and Electronics Engineering QUESTION BANK SHORT QUESTIONS AND

More information

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL 1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems:

More information

EN Power Electronics and Machines

EN Power Electronics and Machines 1/19 - Power Electronics and Machines Transformers Suryanarayana Doolla Department of Energy Science and Engineering Indian Institute of Technology, Bombay suryad@iitb.ac.in Lecture Organization - Modules

More information

EE Branch GATE Paper 2010

EE Branch GATE Paper 2010 Q.1 Q.25 carry one mark each 1. The value of the quantity P, where, is equal to 0 1 e 1/e 2. Divergence of the three-dimensional radial vector field is 3 1/r 3. The period of the signal x(t) = 8 is 0.4

More information

CPPM Mahine: A Synchronous Permanent Magnet Machine with Field Weakening

CPPM Mahine: A Synchronous Permanent Magnet Machine with Field Weakening CPPM Mahine: A Synchronous Permanent Magnet Machine with Field Weakening Juan A. Tapia, Thomas A. Lipo, Fellow, IEEE Dept. of Electrical and Computer Engineering University of Wisconsin-Madison 45 Engineering

More information

Concept Design and Performance Analysis of HTS Synchronous Motor for Ship Propulsion. Jin Zou, Di Hu, Mark Ainslie

Concept Design and Performance Analysis of HTS Synchronous Motor for Ship Propulsion. Jin Zou, Di Hu, Mark Ainslie Concept Design and Performance Analysis of HTS Synchronous Motor for Ship Propulsion Jin Zou, Di Hu, Mark Ainslie Bulk Superconductivity Group, Engineering Department, University of Cambridge, CB2 1PZ,

More information

ELECTRIC MACHINE TORQUE PRODUCTION 101

ELECTRIC MACHINE TORQUE PRODUCTION 101 ELECTRIC MACHINE TORQUE PRODUCTION 101 Best Electric Machine, 014 INTRODUCTION: The following discussion will show that the symmetrical (or true dual-ported) transformer electric machine as only provided

More information

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2)

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2) Journal of Mechanics Engineering and Automation 5 (2015) 401-406 doi: 10.17265/2159-5275/2015.07.003 D DAVID PUBLISHING Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration

More information

Harmonic Modeling of Networks

Harmonic Modeling of Networks Harmonic Modeling of Networks Thomas H. Ortmeyer ECE Dept. Clarkson University Potsdam, NY 13699-5720 M. Fayyaz Akram Dept. of Elec. Eng. Univ. of Engineering and Technology Lahore, Pakistan Takashi Hiyama

More information

Finite Element Modeling and Performance Analysis of a Permanent Magnet Synchronous Machine

Finite Element Modeling and Performance Analysis of a Permanent Magnet Synchronous Machine Finite Element Modeling and Performance Analysis of a Permanent Magnet Synchronous Machine Saadoun 1,. Guersi,A. Ouari 3 1- Université Badji Mohtar,, Faculté des Sciences de l Ingénieur, saadoun_a@yahoo.fr

More information

Micro-grid to System Synchronization Based on Pre-Insertion Impedance Method (Version 1.0) By Peter Zhou University of Alberta Jan 30 th, 2015

Micro-grid to System Synchronization Based on Pre-Insertion Impedance Method (Version 1.0) By Peter Zhou University of Alberta Jan 30 th, 2015 Micro-grid to System Synchronization Based on Pre-Insertion Impedance Method (Version 1.0) By Peter Zhou University of Alberta Jan 30 th, 2015 Outline 1. What is Synchronization? 2. Synchronization Concerns?

More information

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India Power System Stability and Control Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India Contents Chapter 1 Introduction to Power System Stability

More information

Model of Induction Machine to Transient Stability Programs

Model of Induction Machine to Transient Stability Programs Model of Induction Machine to Transient Stability Programs Pascal Garcia Esteves Instituto Superior Técnico Lisbon, Portugal Abstract- this paper reports the work performed on the MSc dissertation Model

More information

Review of Basic Electrical and Magnetic Circuit Concepts EE

Review of Basic Electrical and Magnetic Circuit Concepts EE Review of Basic Electrical and Magnetic Circuit Concepts EE 442-642 Sinusoidal Linear Circuits: Instantaneous voltage, current and power, rms values Average (real) power, reactive power, apparent power,

More information

You know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1).

You know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1). Stability 1 1. Introduction We now begin Chapter 14.1 in your text. Our previous work in this course has focused on analysis of currents during faulted conditions in order to design protective systems

More information

Dynamic simulation of a five-bus system

Dynamic simulation of a five-bus system ELEC0047 - Power system dynamics, control and stability Dynamic simulation of a five-bus system Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 16 System modelling

More information

Finite Element Method based investigation of IPMSM losses

Finite Element Method based investigation of IPMSM losses Finite Element Method based investigation of IPMSM losses Martin Schmidtner 1, Prof. Dr. -Ing. Carsten Markgraf 1, Prof. Dr. -Ing. Alexander Frey 1 1. Augsburg University of Applied Sciences, Augsburg,

More information