Compression Effects on Pressure Loss in Flexible HVAC Ducts

Size: px
Start display at page:

Download "Compression Effects on Pressure Loss in Flexible HVAC Ducts"

Transcription

1 LBNL Compression Effects on Pressure Loss in Flexible HVAC Ducts B. Abushakra, I.S. Walker and M.H. Sherman Environmental Energy Technologies Division July 2004 This work was supported by the Assistant Secretary for Energy Efficiency and Renewable Energy, Building Technologies Program, of the U.S. Department of Energy under contract No. DE-AC03-76SF

2 Disclaimer This document was prepared as an account of work sponsored by the United States Government. While this document is believed to contain correct information, neither the United States Government nor any agency thereof, nor The Regents of the University of California, nor any of their employees, makes any warranty, express or implied, or assumes any legal responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by its trade name, trademark, manufacturer, or otherwise, does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States Government or any agency thereof, or The Regents of the University of California. The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States Government or any agency thereof, or The Regents of the University of California. Ernest Orlando Lawrence Berkeley National Laboratory is an equal opportunity employer. 2

3 Compression Effects on Pressure Loss in Flexible HVAC Ducts Published in ASHRAE HVAC&R Research Journal, Vol. 10, No. 3, July 2004 Bass Abushakra, Ph.D. Iain S. Walker, Ph.D. Max H. Sherman, Ph.D. Member ASHRAE Member ASHRAE Fellow ASHRAE ABSTRACT A study was conducted to evaluate the effect of compression on pressure drop in flexible, spiral wire helix core ducts used in residential and light commercial applications. Ducts of 6, 8 and 10 (150, 200 and 250 mm) nominal diameters were tested under different compression configurations following ASHRAE Standard Methods of Testing to Determine Flow Resistance of HVAC Air Ducts and Fittings. The results showed that the available published references tend to underestimate the effects of compression. The study demonstrated that moderate compression in flexible ducts, typical of that often seen in field installations, could increase the pressure drop by a factor of four, while further compression could increase the pressure drop by factors close to ten. The results proved that the pressure drop correction factor for compressed ducts cannot be independent of the duct size, as suggested by ASHRAE Fundamentals, and therefore a new relationship was developed for better quantification of the pressure drop in flexible ducts. This study also suggests potential improvements to ASHRAE Standard and provides new data for duct design. INTRODUCTION In field studies, observed pressure drops in flexible duct systems are often higher than expected based on design calculations. This is because the flexible ducts are not installed in a fully stretched condition; they are often found to be compressed to varying degrees. This common problem leads to excessive pressure drop in many systems with associated increases in fan power, flow reduction, and noise. For design purposes and for diagnostics of duct systems, friction charts and friction loss equations and coefficients from various references are used. For fully stretched flexible duct, in particular, ASHRAE Fundamentals (ASHRAE 2001a) and ACCA Manual D (ACCA 1995) provide pressure drop calculations using such charts, equations and coefficients. The 2001 ASHRAE Fundamentals (ASHRAE 2001a), Chapter 34, Duct Design, suggests the use of the Darcy friction loss equation (Equation 1) with the Altshul-Tsal equation of friction factor (Equation 2) (Altshul and Kiselev 1975, and Tsal 1989), rather than providing a friction chart, for the calculation of pressure drop in flexible ducts: fl V fl V Pf = ρ (SI: Pf = ρ ) (1) D 1097 D 2 f = 12ε D 68 Re 0.25 (SI: f = ε D 68 Re 0.25 ) (2) 3

4 If f : f = f If f < : f = 0.85 f The problem with using the above equations is in estimating the correct value of the absolute roughness, ε, because roughness data for flexible ducts are generally not available. ASHRAE Fundamentals categorizes the roughness in five categories (smooth, medium smooth, average, medium average, and rough) and provides a general absolute roughness value for each category. It also provides a range for the roughness of each type of duct in each category. Flexible duct, all types of fabric and wire, are classified as rough, with the absolute roughness range as ft ( mm) when fully extended. As values within this wide range vary by a factor of four, the calculated friction factor (Equation 2) and the resulting pressure drop (Equation 1) could vary by 30%. On the other hand, ACCA Manual D (ACCA 1995) provides a friction chart for flexible, spiral wire helix core ducts. There are conditions for using the chart, such as maximum air velocity and temperature and positive and negative pressure, but there is no indication of whether the chart was established for fully extended ducts. However, when it comes to the compression effects on flexible ducts, the available literature does not provide enough resources for an adequate estimate of pressure drop in a duct system. ASHRAE Fundamentals provides a graph, Figure 1, showing how compressing a fully stretched flexible duct increases the pressure drop; a single graph is used for all sizes of flexible ducts. To calculate the pressure drop in a compressed flexible duct, the graph provides a correction factor as a function of the duct length, that can be multiplied by the pressure drop that would occur in a fully stretched duct case. Figure 1 ASHRAE Fundamentals (2001a) (Figure 8, p.34.8) correction factor for unextended flexible duct. Copyright 2001, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc Tullie Circle, NE, Atlanta, GA 30329, , Reprinted by permission from 2001 ASHRAE Handbook Fundamentals. When the flexible duct is compressed, the core gets crumpled and the effective surface roughness increases by orders of magnitude above the range provided in ASHRAE Fundamentals. Equation 2 is not applicable to the high roughness region (on a Moody chart) where the friction factor becomes independent of the Reynolds Number (i.e., with typical Re ranges encountered in an HVAC ducting system; 2x10 4 <Re<5x10 4 ). In this case, another model for fully-rough flow regime in pipes (ducts) found in ASHRAE Fundamentals Chapter 2 (Fluid Flow) (ASHRAE 2001a) would be more appropriate: 1 D 1 D = log (SI: = log ) (3) f 12ε f ε 4

5 The problem remains that, for a designer, even using an appropriate model for the friction factor and surface roughness, such as in Equation 3, would be problematic, since having the appropriate value of the roughness for the specific compression case of the flexible duct is not available in the literature. An experimental study on flexible spiral wire helix core ducts (of sizes commonly used in residential and light commercial buildings) was conducted at the Energy Performance of Building group (EPB) duct research facilities at Lawrence Berkeley National Laboratory (LBNL) in order to address and quantify the compression effects on the pressure drop, and to compare results with existing body of work when possible. To that end, the results were compared with pressure drop calculations in ASHRAE Fundamentals (2001a) and ACCA Manual D (ACCA 1995). The tests were conducted according to the test methods in the ASHRAE Standard Methods of Testing to Determine Flow Resistance of HVAC Air Ducts and Fittings (ASHRAE 2001b), and included experiments on duct specimens that were less than fully stretched, in an attempt to mimic the real configurations found in a typical house or a light commercial building. METHODOLOGY This study on the compression effect of flexible ducts is part of larger study conducted at LBNL (Abushakra et al. 2002) to evaluate whether component test data can be reliably used in an entire system analysis. Among tests on different components of residential air distribution systems, individual experiments were conducted on flexible duct of different diameters and under different compression ratios. The flexible duct study focused on the nominal 6, 8, and 10 (150, 200 and 250 mm) diameters only, since in a typical house these three sizes constitute the majority of ducting, and thus have a major effect on the total pressure drop in the system. Figure 2 shows the test apparatus used in all the flexible duct tests. Nozzle Flowmeter Entry sheet metal duct Upstream Piezometer Flexible duct specimen Downstream Piezometer Exit sheet metal duct Air Flow Flow Straightener 10D 25D 4D Overlap of flexible/sheet metal duct 1.5 ± 0.5 D Damper Open Cl ose Fan Figure 2 Schematic of the tests apparatus. The tests apparatus included an upstream nozzle flowmeter, an entry and an exit straight sheet metal duct pieces holding the upstream and downstream piezometers, and a flexible connection to the draw-through fan. A flow straightener was added at the entry of the highly accurate nozzle flowmeter (±0.5% accuracy). Each piezometer had four equidistant pressure taps manifolded together for a single reading; the four pressure taps provided individual readings within 1% difference with the average. The fan was equipped with a damper to modulate the flow. The flexible duct was taped to the laboratory floor to ensure a straight layout. This is of particular concern when the duct is restricted at both ends and compressed, because it tends to bulge in the middle. The tests for each duct size and compression configuration were conducted by recording the values of the volumetric flow rate and static pressure drop in the test specimen. A data acquisition system sampled five-secondaverage readings of the flow and static pressure drop measurements. Every data point (volumetric flow rate and 5

6 static pressure drop) used in the analysis was an average of 60 five-second readings. The 60 values for each data point used in the analysis were always taken after reaching a steady state flow condition. The static pressure drop in the flexible duct specimen was obtained by subtracting the static pressure drop in the straight sheet metal duct section holding the piezometers upstream and downstream (the overlap sections), from the total value of the static pressure drop between the upstream and downstream piezometers. For improved accuracy, we performed separate tests to measure the pressure drop for the sheet metal duct sections. We found that the sheet metal duct results were within 3% of those published by ASHRAE (ASHRAE 2001a). Abushakra et al. (2002) show the detailed calculation for the sheet metal ducts. The volumetric flow rate values were corrected to account for the following: (1) changing air temperatures throughout the test (corrected to start-of-test temperature), (2) calibration temperature of the flowmeter, and (3) air density changes with elevations above sea-level. Fully Stretched Flexible Duct The fully stretched duct has the inner core pulled tight resulting in a relatively smooth inner duct surface. This is rarely found in houses, because it results in ducts which are hard to keep attached to the fittings due to the longitudinal force required to stretch the duct. Fully stretched flexible ducts were tested first in order to establish a baseline for comparison to compressed cases. The fully-stretched specimens were at least 35 diameters long, satisfying the minimum 25-diameter-length suggested by Standard for fully developed flow. A 35- diameter-length specimen can be compressed by as much as 30% and still satisfies the 25-diameter overall length constraint. Nevertheless, even with a 25-diameter-length specimen, part of the duct will experience a developing flow; for instance, at the attachments to the sheet metal duct carrying the piezometers upstream and downstream of the flexible duct specimen. Allowing the flow exponent of the power-law model (pressure drop vs. volumetric flow rate) to vary in the analysis can account for effects of these developing flow regions on pressure drop. It is important to note that the term fully stretched means that the inner liner of the duct is fully stretched. The flexible duct consists of three layers: (1) outer plastic layer, (2) R-4.2 (RSI-0.74) fiberglass insulation, and (3) inner liner which is a thin plastic layer with embedded spiral wire, called core. For testing purposes, it is possible to observe what appears to be a fully stretched duct from the exterior, hiding less than fully stretched inner liner. Therefore, we ensured that the inner liner of the specimen was stretched to its full extent before every fully stretched test. Clamping the test specimen Since we followed ASHRAE Standard for conducting our tests, we applied its Annex E - Flexible Duct Setup Guide stating that Two wraps of duct tape and a clamp shall be used to secure the test duct connections and make an airtight connection. When a specimen is cut to length, the outer layer and the insulation lengths do not correspond, necessarily, to a fully stretched inner liner. Thus clamping the whole flexible duct (its three layers), as required by Standard , on the inlet and outlet straight sections of rigid duct (where the piezometers are placed) could cause a situation where the outer layers are fully stretched, and the inner liner is not. For example, in one 8 (200 mm) diameter duct sample that we tested, we experienced such a situation in which the exterior appeared to be fully stretched while the core was found to be 4% compressed. The standard test procedure should be revised to require a tight connection of the inner liner only of the test specimen with enough duct tape to the rigid duct, without clamping the outer layers (insulation and outer plastic sheet). Figure 3 shows the exterior of the test specimens of the fully stretched and the compressed 10 (250 mm) duct. Lateral constraints were used in all tests to prevent movement during the test. 6

7 Figure 3 The exterior of the fully stretched, and the compressed (29.50%) 10 (250 mm) flexible duct test specimens. Compressed Flexible Duct The compression ratios are calculated relative to the fully stretched case. The compression ratio is the change in length divided by the fully stretched length. A maximum compression ratio of 30% was achieved for the three duct sizes. Above this compression ratio, it was not possible to keep the compressed specimen straight, because it would bulge somewhere between the upstream and downstream piezometers. This bulging is caused by restrictions due to the outer liner and the insulation of the flexible duct. In our tests, a compression of around 15% was used as a moderate compression case typically found in field installation and represents a Normal Stretch flexible duct scenario; a compression of around 30% would be an extreme compression case and represents a Compressed flexible duct scenario. RESULTS In all the tests, the volumetric flow rate ranges were chosen to represent ranges that are encountered in residential and light commerical buildings. Table 1 summarizes the flow conditions ranges achieved in the tests together with the actual and target compression ratios. TABLE 1 Flow Condition Ranges in the Flexible Duct Study. Nominal Diameter in (mm) 6 (150) 8 (200) Compression Scenario Target Compression Ratio Actual Compression Ratio r c Corrected Volumetric Flow Rate cfm (L/s) Fully Stretched (41 202) Normal Stretch (38 189) Compressed (41 182) Fully Stretched (50 225) Static Pressure Drop in water/100ft (Pa/m) ( ) ( ) ( ) ( ) Bulk Velocity fpm (m/s) ( ) ( ) ( ) ( ) Reynolds Number (250) Normal Stretch (48 221) Compressed (54 220) Fully Stretched (73 211) Normal Stretch (63 213) Compressed (62 217) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( )

8 The first step in the analysis was to develop the static pressure drop model as a function of the volumetric flow rate (both variables being measured quantities). A power-law model (Equation 4) was used that allows for variations (for instance, due to boundary layer development or Reynolds Number effects) from the standard assumption of volumetric flow rate being proportional to the square root of the static pressure drop: n P = CQ (4) The static pressure drop, in this study, is calculated per unit length. ASHRAE Standard expresses the static pressure drop per unit length as a function of the calculated bulk velocity, rather than the volumetric flow rate, with a power-law model similar to Equation 4. The test on the 10 (250 mm) duct was repeated three times with two different sizes of nozzle flowmeter and three different lengths of specimens to examine repeatability effects. The coefficient of variation (RMS error divided by the mean) among repeated tests in the power-law model for the fully stretched 10 duct case was 5%. The tests on the 8 (200 mm) duct were repeated twice because the 8 (200 mm) specimen in the first fully stretched case gave doubtful results and was eventually found to be in fact compressed by 4%. The results of the experimental study are shown in Table 2. For each duct size tested, and for each compression scenario, the table reports the pressure drop coefficient and the flow exponent along with their upper and lower confidence limits, in addition to comparison from available references. The normal stretch and compressed scenarios corresponded to a compressed specimen length of around 25 and 30 diameters. The pressure drop coefficient, C, is expressed in in water/100ft.cfm n (Pa.s n /m.l n ), because pressure drop per 100ft is a standard unit used in existing design calculation procedures. The flow exponent, n, of fully developed turbulent flow has a theoretical upper limiting value of 2. The results showed that, in all the cases studied, the flow exponent was found to be slightly lower than 2. This indicates that any developing turbulent flow in the test specimens had a very small contribution. However, taking into consideration the confidence interval of all the calculated flow exponent values, in six out of nine cases (8 and 10 (200 and 250 mm) ducts), the upper limit of the confidence interval would slightly exceed the 2 value. The confidence intervals could have been reduced by sampling more data pairs in the test ( i.e., more volumetric-flowrate/static pressure-drop stations). In our tests, we took 16 data pairs in the 6 (150 mm) duct tests, then we reduced the tests to only four data points for the 8 and 10 (200 and 250 mm) ducts (only three data points are necessary to develop a power-law model), resulting in larger confidence intervals for the 8 and 10 tests. The experimental results were compared to data in ACCA Manual D (ACCA 1995) (widely used for residential duct sizing). The ACCA manual provides a look-up friction chart for flexible, spiral wire helix core ducts. We assumed that the ACCA chart applies to a fully stretched configuration (there is no explicit definition of the compression configuration in the chart s footnote, nor in the text). Thus, to compare our results with the available references, we multiplied the values provided in ACCA by the correction factors provided in ASHRAE (2001a). The ACCA chart overpredicted the pressure drop for the fully stretched duct of all sizes tested by an average of 21%. For less than fully stretched specimens, ACCA, corrected with ASHRAE pressure drop correction factors, underpredicted the pressure drop by an average of 17% for the normal stretch cases (around 15% compression), and by 24% for the compressed cases (around 30% compression). For all tests with different compression ratios, the average underprediction is 21%. Without the correction with the ASHRAE factors, ACCA underpredicted all the compression cases by an average of 73%. This indicates that ACCA Manual D data are probably obtained from fully stretched to slightly compressed flexible duct. We contacted ACCA, and they were not able to provide us with specifics on the compression ratios used to produce the chart, since the work was contracted a few years earlier, and the compression ratios were not documented. The results of compressed ducts also showed that when a flexible duct is compressed, it can have a greater static pressure drop per unit length than a fully stretched duct of a smaller diameter. This is important to be aware of when designing and installing flexible duct systems, as available friction charts (eg. ACCA Manual D) do not show this effect. 8

9 TABLE 2 Power-Law Coefficients of Three Sizes of Flexible Ducts and Comparison with Resulting Static Pressure Drop from Available References. Nominal Diameter in (mm) Compression Ratio r c C in water/ 100 ft. cfm n (Pa.s n /m.l n ) Lower 95% CL of C in water/ 100ft. cfm n (Pa.s n /m.l n ) Upper 95% CL of C in water/ 100ft. cfm n (Pa.s n /m.l n ) n Lower 95% CL of n Upper 95% CL of n ACCA- ASHRAE Static Pressure Drop* Average Over/Underprediction E E E % (150) (2.08 E-04) (1.86 E-04) (2.33 E-04) E-05 (1.05 E-03) 5.27 E-05 (9.12 E-04) 6.94 E-05 (1.20 E-03) % E E E % (2.70 E-03) (2.29 E-03) (3.18 E-03) E E E % (200) (5.76 E-05) (1.62 E-05) (2.06 E-04) E-06 (1.41 E-04) 5.69 E-06 (9.85 E-05) 1.16 E-05 (2.01 E-04) % E E E % (2.96 E-04) (1.53 E-04) (5.73 E-04) E E E % (250) (1.27 E-05) (4.55 E-06) (3.52 E-05) E-06 (4.76 E-05) 1.97 E-06 (3.41 E-05) 3.84 E-06 (6.65 E-05) % E-06 (7.84 E-05) 2.92 E-06 (5.06 E-05) 7.00 E-06 (1.21 E-04) % * ACCA-ASHRAE values are average values of pressure drop corresponding to the flow rates used in each test, and calculated by multiplying the look-up values in ACCA Manual D Chart 7, page A2-10 (ACCA 1995) by the correction factor in ASHRAE Fundamentals (ASHRAE 2001a), Figure 8, p For the fully stretched case (0% compression) the correction factor is 1. DISCUSSION Developing power-law models to quantify the pressure drop in flexible duct under different compression scenarios in this study facilitated establishing appropriate pressure drop correction factors for compressed flexible duct. The pressure drop correction factor, PDCF, is a multiplier that can be used to estimate the static pressure drop in a flexible duct when less than fully stretched, based on its static pressure drop when fully stretched: P PDCF = (5) P FS where P is the static pressure drop at a particular level of compression, and P FS is that corresponding to a fully stretched configuration. Figure 4 shows the measured PDCF (Equation 5) for all the measured data. 9

10 Measured PDCF (pressure drop ratio ( P/ PFS)) Volumetric Flow Rate (L/s) " (13.8%) 6" (28.6%) 8" (14.6%) 8" (23.8%) " (14.8%) 10" (29.5%) Volumetric Flow Rate (cfm) Figure 4 The measured pressure drop correction factor of normal stretch and compressed 6, 8, and 10 (150, 200, and 250 mm) flexible duct as a function of the volumetric flow rate. Figure 4 llustrates that the PDCF is relatively constant with the flow rate, but varies with the duct diameter and the compression ratio. The figure basically shows the greater effect of compression on the pressure drop for smaller duct sizes. Our analysis of the measured data has shown that the pressure drop correction factor, PDCF, is approximated well by a linear function of the compression ratio, r c : L rc = 1 (6) LFS PDCF = 1 + a (7) r c where PDCF would be equal to 1 (no correction) for a zero compression. The empirical coefficient, a, can be obtained from experimental data for each duct size using: k Pi m i= 1 PFS i 1 j= 1 k j a = (8) m r c j j= 1 where, k = number of volumetric-flow-rate/static pressure-drop stations in a test, m = number of compression cases (tests), including the fully stretched case. 10

11 The compression ratio, r c, is calculated using Equation 6 together with the measured length of the test specimen, fully stretched (L FS ) and under compression (L). Table 3 includes the values of r c and the calculated coefficient a obtained from the measured data. TABLE 3 Compression Ratios and Calculated Coefficients in the PDCF of three Flexible Duct Sizes Nominal Diameter in (mm) 6 (150) 8 (200) 10 (250) Compression Ratio r c Pressure Drop Correction Factor Coefficient a Table 4 shows the PDCF models developed, using Equation 7, for the 6, 8, and the 10 (150, 200, and 250 mm) ducts tested. A reference model, ASHRAE-all sizes, is also listed for comparison. This reference model was obtained with a best-fit first-order polynomial (PDCF = r c ), developed with look-up values from ASHRAE (2001a) (Figure 1). The model based on ASHRAE data is independent of duct size and underestimates the pressure drop by an average of 35% (with the flow conditon ranges and the duct sizes used in this study). Figure 5 shows the corresponding PDCF graphs obtained using Equation 7 and the values of the coefficient a in Table 3. The figure also shows the measured PDCF values (Equation 5) for the three duct sizes tested, and the graph of the reference ASHRAE model. Each measured PDCF value shown in the figure is an average value for all volumetric-flowrate/static pressure-drop stations in a given case. TABLE 4 Pressure Drop Correction Factor of Three Sizes of Flexible Duct Diameter Pressure Drop Correction Factor in PDCF (mm) r c (150) r c (200) r c (250) ASHRAE-all sizes r c 11

12 Pressure Drop Correction Factor, PDCF 9 Modeled 6" 8 Modeled 8" Modeled 10" 7 Measured 6" 6 Measured 8" Measured 10" 5 ASHRAE-all sizes Compression Ratio, r c Figure 5 Comparison of the measured PDCF s and the linear models including the model of currently available ASHRAE data. Effect of Compressibility on Pitch-to-Diameter Ratio The physical basis of the empirical relationship for the PDCF (Equation 7) can be explained in terms of change in the friction factor and the geometry of the flexible duct when compressed. Figure 6 shows a schematic of a flexible duct inner liner in fully stretched and in compressed conditions. Fully stretched Less then fully stretched D FS D λ (1 - r c )λ Figure 6 Schematic of the inner liner of a flexible duct. Compressing the flexible duct results in a crumpled inner liner which reduces the effective interior crosssectional area and increases its absolute surface roughness. The pitch, λ, is the longitudinal distance between two consecutive spirals of the flexible duct. The degree of area reduction and roughness increase depends on the pitchto-diameter ratio (larger pitch leads to higher cross-sectional area changes and greater roughness). Rather than having multiple equations for calculating PDCF, we examined the possibility of collapsing the results into a single relationship using the duct geometry factors described above. Dividing our measured values of a by the corresponding pitch-to-diameter ratio of the fully stretched duct, λ FS /D FS, generated values that are approximately equal, with an average value of 106. It is possible that this relationship could be used for ducts of other diameters and pitches, but tests on other ducts need to be carried out in order to confirm this possibility. The pitch-todiameter-normalized PDCF values use the following expression: 12

13 PDCF Norm λ = D FS FS r c (9) The use of this single value had differences of less than 5% compared to all the measured points. Figure 7 shows a comparison between the raw PDCF models using Equation 7 (shown in Figure 5) and the nomalized models, PDCF Norm (using Equation 9). The PDCF Norm compared with PDCF overpredicts by an average of 4.4% for the 6 (150 mm), underpredicts by an average of 2.0% for the 8 (200 mm), and underpredicts by an average of 1.7% for the 10 (250 mm) duct. These over-and-underprediction results were within the experimental uncertainties in the power-law model calculations of the pressure drop in the compressed ducts, as can be seen in Table 5. Pressure Drop Correction Factor, PDCF " Individual Model 8" Individual Model 10" Individual Model 6" Normalized Model 8" Normalized Model 10" Normalized Model Compression Ratio, r c Figure 7 Comparison between the individually calculated PDCF models (Equation 7) for each duct size and those derived from the normalized model (Equation 9). TABLE 5 Experimental Uncertainties in the Fitted Pressure Drop Power-Law Models 1 of the Compressed Flexible Ducts Nominal Diameter Upper 95% Confidence Limit Lower 95% Confidence Limit Compression Ratio r in c (mm) (% above the fitted value) (% below the fitted value) (150) (200) (250) The power -law models coefficients with their corresponding confidence limits are shown in Table 2. 13

14 Thus, by comparing its predictions with individual PDCF models for each duct size (Equation 7), a single PDCF Norm model (Equation 9) for different duct sizes was found to be convenient for use with acceptable accuracy. Figure 8 illustrates the static pressure drop in the compressed 10 (250 mm) duct as measured, power-law-fitted, and predicted with two different PDCF models. The compression ratio was 29.5%, and the measured data consisted of five volumetric-flow-rate/static pressure-drop stations, from which a power-law model of the pressure drop was developed. The predicted pressure drop models used the power-law model developed for the fully stretched case multiplied by the pressure drop correction factor. Considering the power-law-fitted results with their 95% confidence limits (CLs) as the basis for comparison, the model using PDCF (Equation 7) overpredicted the pressure drop, corresponding to the measured volumetric-flow-rate, by an average of 3%, while the model using the PDCF Norm (Equation 9) overpredicted the pressure drop by an average of 0.7% (results within the experimental uncertainties) Volumetric Flow Rate (L/s) Pressure Drop (in water/100ft) Fitted 29.5% Compression Predicted w ith Individual PDCF Predicted w ith Normalized PDCF Measured 29.5% Compression Upper CL of the fitted 29.5% Compression Low er CL of the fitted 29.5% Compression Pressure Drop (Pa/m) Volumetric Flow Rate (cfm) 0.0 CONCLUSIONS Figure 8 Comparison between measured, power-law-fitted, and predicted static pressure drop with PDCF models in a compressed 10 (250 mm) flexible duct. Our experiments determined pressure drops for fully stretched and compressed flexible ducts. The pressure drop for fully stretched ducts was used as a baseline in developing simple pressure drop correction factors (PDCF). The PDCF can be applied to the pressure drop for fully stretched duct to estimate the pressure drop in compressed ducts. The new relationship for the PDCF is a function of the compression ratio and both the pitch and the nominal diameter of the duct. The PDCF and the pressure drop power-law models developed in this study provide new data for duct design, and could be used by ASHRAE and ACCA to update their handbooks/manuals. The study showed that the pressure drop (flow resistance) for flexible ducts increases significantly (by factors close to 10) when the ducts are not fully stretched. Therefore it is crucial for the designer and installer to be aware of these compressibility effects and the elevated pressure drop that would affect the HVAC fan sizing. The contractor should install flexible ducts so as to reduce the compression effects. A flexible duct connecting two fittings should always be cut to an appropriate length. An excessive length would increase the pressure drop, but on the other hand, a fully-stretched duct would result in its disconnection from the fittings. The results also showed that: A change to the standard test procedure of flexible ducts, as an improvement to ASHRAE Standard , is required such that only the inner liner of the test specimen is tightly connected to the rigid duct (where the peizometers measuring the pressure drop are placed) without clamping the outer layers. This 14

15 modification would ensure a correct measurement of the fully stretched flexible duct pressure drop, and would facilitate the derivation of accurate pressure drop correction factors for any percentage of compression. The pressure drop correction factor, independent of duct size, provided by ASHRAE (ASHRAE 2001a) underestimates the pressure drop in all of the duct sizes tested, on average, by 35%. The friction chart provided in ACCA Manual D (ACCA 1995) overpredicts the pressure drop for fully stretched duct by an average of 21%. For less than fully stretched duct, ACCA values corrected with correction factors from ASHRAE Fundamentals, showed around 21% underprediction in the pressure drop (73% underprediction without the ASHRAE correction). When a flexible duct is compressed, it can have a greater static pressure drop per unit length than a fully stretched duct of a smaller diameter. In future work, more duct sizes should be tested in order to complete the range of duct sizes used in houses and light commercial buildings (up to 16 (410 mm) diameters). Further investigations should be conducted in order to quantify the absolute surface roughness of flexible duct, and to find out whether a more accurate model that relates it to the friction drop factor, f, can be developed. Such a study would lead to establishing a PDCF model in which the physical basis for the empirical number, 106, obtained in Equation 9, can be determined. ACKNOWLEDGEMENTS This work at the Lawrence Berkeley National Laboratory was funded by Pacific Gas and Electric Company under Contract S9902A, to support PG&E's energy efficiency programs in new and existing residential buildings via the California Institute for Energy Efficiency under Contract No. S9902A. Publication of research results does not imply CIEE endorsement of or agreement with these findings, nor that of any CIEE sponsor. This work was also supported by the Assistant Secretary for Energy Efficiency and Renewable Energy, Office of Building Technology, State and Community Programs, Office of Building Research and Standards, of the U.S. Department of Energy under Contract No. DE-AC03-76SF The authors like to express a word of thanks to Darryl Dickerhoff for his contribution in designing, setting up and building the test apparatus required for the experiments, and also for his invaluable input whenever needed. NOMENCLATURE a = slope of the linear equation of the pressure drop correction factor C, C = pressure drop coefficient (in water/100ft.cfm n ), (Pa.s n /m.l n ) D = flexible duct diameter (in), (mm) D = flexible duct modified diameter after compression (in), (mm) ε = absolute surface roughness of the duct (ft), (mm) f, f = friction factor L = duct length (ft), (m) n, n = volumetric flow rate exponent PDCF = pressure drop correction factor Q = volumetric flow rate (cfm), (L/s) r c = compression ratio (dimensionless) Re = Reynolds Number (dimensionless) V = air velocity (fpm), (m/s) Greek Symbols P = static pressure drop per unit length (in water/100 ft), (Pa/m) P f = static pressure drop (in water), (Pa) λ = pitch of the flexible duct (longitudinal distance between two consecutive wire spirals) (in), (mm) ρ = air density (lb/ft 3 ), (kg/m 3 ) Subscripts FS Norm = fully stretched = normalized 15

16 REFERENCES Abushakra, B., Walker, I.S., and M.H. Sherman A Study of Pressure Losses in Residential Air Distribution Systems. Proceeding of the 2002 ACEEE Summer Study on Energy Efficiency in Buildings. American Council for an Energy Efficient Economy, Washington, D.C. Also, Lawrence Berkeley National Laboratory Technical Report, LBNL ACCA Residential Duct Systems. Manual D. Air Conditioning Contractors of America. Washington, DC. Altshul, A.D. and P.G. Kiselev Hydraulics and Aerodynamics. Stroisdat Publishing House, Moscow, USSR. ASHRAE. 2001a. ASHRAE Handbook of Fundamentals. American Society of Heating Refrigerating and Airconditioning Engineers, Atlanta, Georgia. ASHRAE. 2001b. ASHRAE Standard , Methods of Testing to Determine Flow Resistance of HVAC Air Ducts and Fittings. American Society of Heating Refrigerating and Air-conditioning Engineers, Atlanta, Georgia. Tsal, R.J Altshul-Tsal friction factor equation. Heating, Piping and Air Conditioning (August). 16

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title Compression effects on pressure loss in flexible HVAC ducts Permalink https://escholarship.org/uc/item/0d7400v Authors

More information

Start-up Noise in 3-D Self-AmpMed

Start-up Noise in 3-D Self-AmpMed LBNL-388 13 UC-414 ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY CONI=- 7 6 0 8 133--5r Start-up Noise in 3-D Self-AmpMed Spontaneous Emission IC-J. Kim Accelerator and Fusion Research Division

More information

DE '! N0V ?

DE '! N0V ? "7 CONF-851174 24 DE86 004682 '! N0V26 1985? PREDICTION OF FLOW RATES THROUGH AN ORIFICE AT PRESSURES CORRESPONDING TO THE TRANSITION BETWEEN MOLECULAR AND ISENTROPIC FLOW S. F. DeMuth Fuel Recycle Division

More information

GA A22677 THERMAL ANALYSIS AND TESTING FOR DIII D OHMIC HEATING COIL

GA A22677 THERMAL ANALYSIS AND TESTING FOR DIII D OHMIC HEATING COIL GA A677 THERMAL ANALYSIS AND TESTING FOR DIII D OHMIC HEATING COIL by C.B. BAXI, P.M. ANDERSON, and A.M. GOOTGELD NOVEMBER 1997 DISCLAIMER This report was prepared as an account of work sponsored by an

More information

4kU. Measurement of Storage Ring Motion at the Advanced Light Source. QSTt ERNESTORLANDO LAWRENCE BERKELEYNATIONAL LABORATORY

4kU. Measurement of Storage Ring Motion at the Advanced Light Source. QSTt ERNESTORLANDO LAWRENCE BERKELEYNATIONAL LABORATORY LBNL-39812 UC-410 ERNESTORLANDO LAWRENCE BERKELEYNATIONAL LABORATORY Measurement of Storage Ring Motion at the Advanced Light Source Gary F. Krebs Accelerator and Fusion Research Division JUN 2 3 W QSTt

More information

Plasma Response Control Using Advanced Feedback Techniques

Plasma Response Control Using Advanced Feedback Techniques Plasma Response Control Using Advanced Feedback Techniques by M. Clement 1 with J. M. Hanson 1, J. Bialek 1 and G. A. Navratil 1 1 Columbia University Presented at 59 th Annual APS Meeting Division of

More information

Survey, Alignment and Beam Stability at the Advanced Light Source

Survey, Alignment and Beam Stability at the Advanced Light Source LBNL-4997 UC-41 ERNEST AND13 LAWRENCE BERKELEY ATI NAL LAB RATCJ RY Survey, Alignment and Beam Stability at the Advanced Light Source Gary F. Krebs Accelerator and Fusion Research Division October 1997

More information

OF A HELIUM-COOLED MODULE

OF A HELIUM-COOLED MODULE GA-A21783 DESIGN, FABRICATION, AND TESTING OF A HELIUM-COOLED MODULE FOR THE ITER DIVERTOR RECEIVED by C.B. BAXI, J.P. SMITH, and D. YOUCHISON ' MAR 2 9 1996 0 s-q-i AUGUST 1994 GENEHL ATOMfCS DISCLAIMER

More information

UPGRADED CALIBRATIONS OF THE THOMSON SYSTEM AT DIII D

UPGRADED CALIBRATIONS OF THE THOMSON SYSTEM AT DIII D GA A23440 UPGRADED CALIBRATIONS OF THE THOMSON SYSTEM AT DIII D by B. BRAY, C. HSIEH, T.N. CARLSTROM, and C.C. MAKARIOU AUGUST 2000 DISCLAIMER This report was prepared as an account of work sponsored by

More information

Undulator Interruption in

Undulator Interruption in LBNL-40689 UC-414 ERNEST DRLANDCI LAWRENCE BERKELEYNATIONAL LABORATORY Undulator Interruption in HighmGain Free Electron Lasers Kwang-JeKim Accelerator and Fusion Research Division October 1997 Presented

More information

Bandgap Photons to GaInP2

Bandgap Photons to GaInP2 LBNL- 3 9427 UC-404 Upconversion of Near GaAs Bandgap Photons to GaInP2 Emission at the GaAs/(ordered) GaJiiP 2 Heterojunction K.L. Teo,Z.P.Su,P.Y.Yu,and K. Uchida Materials Sciences Division September

More information

Plutonium 239 Equivalency Calculations

Plutonium 239 Equivalency Calculations LLNL-TR-490356 Plutonium 239 Equivalency Calculations J. Wen July 7, 2011 Disclaimer This document was prepared as an account of work sponsored by an agency of the United States government. Neither the

More information

PROJECT PROGRESS REPORT (03/lfi?lfibr-~/15/1998):

PROJECT PROGRESS REPORT (03/lfi?lfibr-~/15/1998): F?ECEVVEI) N% 05 w PROJECT PROGRESS REPORT (03/lfi?lfibr-~/15/1998): A COMPREHENSIVE STUDY OF FRACTURE PATTERNS AND DENSITIES IN THE GEYSERS GEOTHERMAL RESERVOIR USING MICROEARTHQUAKE SHEAR-WAVE SPLITTING

More information

To be published in the Proceedings of ICEC-22, Seoul Korea, July 2008 MICE Note 232 1

To be published in the Proceedings of ICEC-22, Seoul Korea, July 2008 MICE Note 232 1 To be published in the Proceedings of ICEC-22, Seoul Korea, 21-25 July 2008 MICE Note 232 1 AC Loss Analysis on the Superconducting Coupling in MICE H. Wu, L. Wang, M. A. Green*, L. K. Li, F. Y. Xu, X.

More information

The Radiological Hazard of Plutonium Isotopes and Specific Plutonium Mixtures

The Radiological Hazard of Plutonium Isotopes and Specific Plutonium Mixtures LA-13011 The Radiological Hazard of Plutonium Isotopes and Specific Plutonium Mixtures Los Alamos NATIONAL LABORATORY Los Alamos National Laboratory is operated by the University of California for the

More information

STP-TS THERMOPHYSICAL PROPERTIES OF WORKING GASES USED IN WORKING GAS TURBINE APPLICATIONS

STP-TS THERMOPHYSICAL PROPERTIES OF WORKING GASES USED IN WORKING GAS TURBINE APPLICATIONS THERMOPHYSICAL PROPERTIES OF WORKING GASES USED IN WORKING GAS TURBINE APPLICATIONS THERMOPHYSICAL PROPERTIES OF WORKING GASES USED IN GAS TURBINE APPLICATIONS Prepared by: ASME Standards Technology, LLC

More information

Lesson 37 Transmission Of Air In Air Conditioning Ducts

Lesson 37 Transmission Of Air In Air Conditioning Ducts Lesson 37 Transmission Of Air In Air Conditioning Ducts Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Describe an Air Handling Unit (AHU) and its functions (Section 37.1).

More information

Determine the Inside Wall Temperature of DSTs using an Infrared Temperature Sensor

Determine the Inside Wall Temperature of DSTs using an Infrared Temperature Sensor SUMMARY DOCUMENT Determine the Inside Wall Temperature of DSTs using an Infrared Temperature Sensor Date submitted: July 29, 2016 Prepared by: Aparna Aravelli, Ph.D. Florida International University Collaborators:

More information

Addendum to ARI Standard , Air Terminals September 2002

Addendum to ARI Standard , Air Terminals September 2002 Addendum to ARI Standard 880-98, Air Terminals September 2002 The September 2002 Addendum to ARI Standard 880-98, Air Terminals, is comprised of only the shaded portions shown, which has been incorporated

More information

Determine the Inside Wall Temperature of DSTs using an Infrared Temperature Sensor

Determine the Inside Wall Temperature of DSTs using an Infrared Temperature Sensor SUMMARY DOCUMENT Determine the Inside Wall Temperature of DSTs using an Infrared Temperature Sensor Date submitted: April 14, 2017 Prepared by: Aparna Aravelli, Ph.D. Florida International University Collaborators:

More information

Bulk Modulus Capacitor Load Cells

Bulk Modulus Capacitor Load Cells '.\ '._,. SSCL-274. Superconducting Super Collider Labora Bulk Modulus Capacitor Load Cells C. E. Dickey April 1990 SSCL-274 BULK MODULUS CAPACITOR LOAD CELLS" C. E. Dickey Superconducting Super Cullider

More information

AN INVESTIGATION OF ALTERNATIVE METHODS FOR MEASURING STATIC PRESSURE OF UNITARY AIR CONDITIONERS AND HEAT PUMPS

AN INVESTIGATION OF ALTERNATIVE METHODS FOR MEASURING STATIC PRESSURE OF UNITARY AIR CONDITIONERS AND HEAT PUMPS AN INVESTIGATION OF ALTERNATIVE METHODS FOR MEASURING STATIC PRESSURE OF UNITARY AIR CONDITIONERS AND HEAT PUMPS A Thesis by GRANT BENSON WHEELER Submitted to the Office of Graduate Studies of Texas A&M

More information

HVAC Clinic. Duct Design

HVAC Clinic. Duct Design HVAC Clinic Duct Design Table Of Contents Introduction... 3 Fundamentals Of Duct Design... 3 Pressure Changes In A System... 8 Example 1... 13 Duct Design Methods... 15 Example 2... 15 Introduction The

More information

LABORATORY MEASUREMENT OF PERMEABILITY UPSCALING:- R FOR THE TOPOPAH SPRING MEMBER OF THE PAINTBRUSH TUFF

LABORATORY MEASUREMENT OF PERMEABILITY UPSCALING:- R FOR THE TOPOPAH SPRING MEMBER OF THE PAINTBRUSH TUFF c J LABORATORY MEASUREMENT OF PERMEABILITY UPSCALING:- R FOR THE TOPOPAH SPRING MEMBER OF THE PAINTBRUSH TUFF Vincent C. Tidwell Sandia National Laboratories Geohydrology Department, MS 1324 Albuquerque,

More information

Data Comparisons Y-12 West Tower Data

Data Comparisons Y-12 West Tower Data Data Comparisons Y-12 West Tower Data Used hourly data from 2007 2010. To fully compare this data to the data from ASOS sites where wind sensor starting thresholds, rounding, and administrative limits

More information

Analysis of Shane Telescope Aberration and After Collimation

Analysis of Shane Telescope Aberration and After Collimation UCRL-ID- 133548 Analysis of Shane Telescope Aberration and After Collimation Before Don Gavel January 26,1999 This is an informal report intended primarily for internal or limited external distribution.

More information

C o f l F - 9m307-- SPREADSHEET APPLICATION TO CLASSIFY RADIOACTIVE MATERIAL FOR SHIPMENTa. A. N. Brown

C o f l F - 9m307-- SPREADSHEET APPLICATION TO CLASSIFY RADIOACTIVE MATERIAL FOR SHIPMENTa. A. N. Brown 1figlL/@N-9f-&3/.3 C o f l F - 9m307-- SPREADSHEET APPLICATION TO CLASSIFY RADIOACTIVE MATERIAL FOR SHIPMENTa A. N. Brown Idaho National Engineering and Environmental Laboratory Lockheed Martin Idaho Technologies

More information

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title ECLOUD in PS, PS+, SPS+: AN UPDATE Permalink https://escholarship.org/uc/item/7rf0rz Author Furman, M.A. Publication Date

More information

N. Tsoupas, E. Rodger, J. Claus, H.W. Foelsche, and P. Wanderer Brookhaven National Laboratory Associated Universities, Inc. Upton, New York 11973

N. Tsoupas, E. Rodger, J. Claus, H.W. Foelsche, and P. Wanderer Brookhaven National Laboratory Associated Universities, Inc. Upton, New York 11973 ,+ v Submitted t o : " 1995 Particle Accelerator Conference & International Conference on High-Energy Accelerators (May 1-5, 1995), Dallas, TX BNL-61195 DESIGN AND B-FIELD MEASUREMENTS OF A LAMBERTSON

More information

EFFECTS OF AXIAL HEAT CONDUCTION AND MATERIAL PROPERTIES ON THE PERFORMANCE CHARACTERISTICS OF A THERMAL TRANSIENT ANEMOMETER PROBE

EFFECTS OF AXIAL HEAT CONDUCTION AND MATERIAL PROPERTIES ON THE PERFORMANCE CHARACTERISTICS OF A THERMAL TRANSIENT ANEMOMETER PROBE The submitted manuscript has been authored by a contractor of the WS Government under contract No W-31-104ENG-38 Accordingly, the U S Government retains a nonexclusive, royalty-free license to publish

More information

GA A26057 DEMONSTRATION OF ITER OPERATIONAL SCENARIOS ON DIII-D

GA A26057 DEMONSTRATION OF ITER OPERATIONAL SCENARIOS ON DIII-D GA A26057 DEMONSTRATION OF ITER OPERATIONAL SCENARIOS ON DIII-D by E.J. DOYLE, J.C. DeBOO, T.A. CASPER, J.R. FERRON, R.J. GROEBNER, C.T. HOLCOMB, A.W. HYATT, G.L. JACKSON, R.J. LA HAYE, T.C. LUCE, G.R.

More information

August 3,1999. Stiffness and Strength Properties for Basic Sandwich Material Core Types UCRL-JC B. Kim, R.M. Christensen.

August 3,1999. Stiffness and Strength Properties for Basic Sandwich Material Core Types UCRL-JC B. Kim, R.M. Christensen. Preprint UCRL-JC-135347 Stiffness and Strength Properties for Basic Sandwich Material Core Types B. Kim, R.M. Christensen This article was submitted to ASME IMECE 99, Nashville, TN, November 14-19, 1999

More information

Tell uric prof i 1 es across the Darrough Known Geothermal Resource Area, Nevada. Harold Kaufniann. Open-file Report No.

Tell uric prof i 1 es across the Darrough Known Geothermal Resource Area, Nevada. Harold Kaufniann. Open-file Report No. Tell uric prof i 1 es across the Darrough Known Geothermal Resource Area, Nevada c i 4 L BY D Harold Kaufniann U.S. Geological Survey. r,. Open-file Report No. 76-286 1976 \, *\. i \ -- i 1'.- - L -.,,-.,

More information

UNDERSTANDING TRANSPORT THROUGH DIMENSIONLESS PARAMETER SCALING EXPERIMENTS

UNDERSTANDING TRANSPORT THROUGH DIMENSIONLESS PARAMETER SCALING EXPERIMENTS UNDERSTANDING TRANSPORT THROUGH DIMENSIONLESS PARAMETER SCALING EXPERIMENTS by C.C. PETTY and T.C. LUCE JULY 1997 CENERaL ATOMRCS This report was prepared as an account of work sponsored by an agency of

More information

Partial Discharge Characterization of High-Voltage Cables and Components

Partial Discharge Characterization of High-Voltage Cables and Components UCRL-JC-123503 PREPRINT Partial Discharge Characterization of High-Voltage Cables and Components R L Druce, and R S Lee Lawrence Livermore National Laboratory This paper was prepared for submission to

More information

GA A22722 CENTRAL THOMSON SCATTERING UPGRADE ON DIII D

GA A22722 CENTRAL THOMSON SCATTERING UPGRADE ON DIII D GA A22722 CENTRAL THOMSON SCATTERING UPGRADE ON DIII D by D.G. NILSON, T.N. CARLSTROM, C.L. HSIEH, B.W. STALLARD, and R.E. STOCKDALE NOVEMBER 1997 DISCLAIMER This report was prepared as an account of work

More information

ION EXCHANGE SEPARATION OF PLUTONIUM AND GALLIUM (1) Resource and Inventory Requirements, (2) Waste, Emissions, and Effluent, and (3) Facility Size

ION EXCHANGE SEPARATION OF PLUTONIUM AND GALLIUM (1) Resource and Inventory Requirements, (2) Waste, Emissions, and Effluent, and (3) Facility Size LA-UR-97-3902 -f$t I Revision 1 Los Alarnos National Laboratory is operated by the University of California for the United States Department of Energy under contract W-7405-ENG-36. TITLE: AUMOR(S): SUBMlrrED

More information

DML and Foil Measurements of ETA Beam Radius

DML and Foil Measurements of ETA Beam Radius UCRL-TR-213325 DML and Foil Measurements of ETA Beam Radius W.E. Nexsen, John Weir June 29, 25 Disclaimer This document was prepared as an account of work sponsored by an agency of the United States Government.

More information

Peak Reliability Delivering near real-time phase angle deltas using Inter-Control Center Communication Protocol (ICCP)

Peak Reliability Delivering near real-time phase angle deltas using Inter-Control Center Communication Protocol (ICCP) Peak Reliability Delivering near real-time phase angle deltas using Inter-Control Center Communication Protocol (ICCP) NASPI meeting March 23, 2015 Dan Brancaccio 1 Peak Reliability Synchrophasor Program

More information

Clifford K. Ho and Michael L. Wilson Sandia National Laboratories. P.O. Box Albuquerque, NM

Clifford K. Ho and Michael L. Wilson Sandia National Laboratories. P.O. Box Albuquerque, NM 1 L Calculation of Discrete Fracture Flow Paths in Dual-Continuum Models W + 0 Clifford K. Ho and Michael L. Wilson Sandia National Laboratories P.O. Box 5800 Albuquerque, NM 87 185-1324 ckho@sandia.gov,

More information

Colliding Crystalline Beams

Colliding Crystalline Beams BNL-65137 Colliding Crystalline Beams J. Wei BNL A.M. Sessler LBNL June 1998 RHIC Project Brookhaven National Laboratory Operated by Brookhaven Science Associates Upton NY 11973 Under Contract with the

More information

Inside Wall Temperature Measurements of DSTs Using an Infrared Temperature Sensor

Inside Wall Temperature Measurements of DSTs Using an Infrared Temperature Sensor TEST PLAN Inside Wall Temperature Measurements of DSTs Using an Infrared Temperature Sensor Date submitted: December 18, 2015 Prepared by: Aparna Aravelli, Ph.D. Florida International University Collaborators:

More information

Design of Current Leads for the MICE Coupling Magnet

Design of Current Leads for the MICE Coupling Magnet MCE Note 219 Design of Current Leads for the MCE Coupling Magnet Wang L.*, Li L. K.*, Wu H.*, Pan H.*, Xu F.Y.*, Liu X.K.*, Jia L. X.*, and Green M. A.** * nstitute of Cryogenics and Superconductivity

More information

GA A23736 EFFECTS OF CROSS-SECTION SHAPE ON L MODE AND H MODE ENERGY TRANSPORT

GA A23736 EFFECTS OF CROSS-SECTION SHAPE ON L MODE AND H MODE ENERGY TRANSPORT GA A3736 EFFECTS OF CROSS-SECTION SHAPE ON L MODE AND H MODE ENERGY TRANSPORT by T.C. LUCE, C.C. PETTY, and J.E. KINSEY AUGUST DISCLAIMER This report was prepared as an account of work sponsored by an

More information

Cdesign must consider (1) space availability, (2) space air

Cdesign must consider (1) space availability, (2) space air ASHRAE Fundimental CHAPChTER 32 DUCT DESIGN Bernoulli Equation.... 32.1 Head and Pressure.... 32.2 SYSTEM ANALYSIS.... 32.2 Pressure Changes in System.... 32.6 FLUID RESISTANCE.... 32.7 Friction Losses....

More information

Magnetic Measurements of the Elliptical Multipole Wiggler Prototype

Magnetic Measurements of the Elliptical Multipole Wiggler Prototype ANL/APS/TB-22 Magnetic Measurements of the Elliptical Multipole Wiggler Prototype by D. Frachon, I. Vasserman, P. M. Ivanov, E. A. Medvedko, E. Gluskin, and N. A. Vinokurov March 1995 Advanced Photon Source

More information

Cable Tracking System Proposal. Nick Friedman Experimenta1 Facilities Division. June 25,1993. Advanced Photon Source Argonne National Laboratory

Cable Tracking System Proposal. Nick Friedman Experimenta1 Facilities Division. June 25,1993. Advanced Photon Source Argonne National Laboratory LS224 by i contractor of the U.S Government under contract No. W31104ENG38. Accordingly, the U. S Government retains a nonexclusive, royaltyfree license to publish or reproduce the published form d this

More information

The Gas Flow from the Gas Attenuator to the Beam Line

The Gas Flow from the Gas Attenuator to the Beam Line The Gas Flow from the Gas Attenuator to the Beam Line D.D. Ryutov Lawrence Livermore National Laboratory, Livermore, CA 94551 UCRL-TR-64 LCLS-TN-06-10 July 1, 006 Abstract The gas leak from the gas attenuator

More information

RECXWH2 W/o s3-1

RECXWH2 W/o s3-1 .,, Nuclear Energy Research Initiative (NERI) DE-FG03-99SF21922 Program Tasks 1 & 3 Quarterly Technical Progress Report July 1- September 30, 2000 An Innovative Reactor Analysis Methodology Based on a

More information

Laminar and turbulent flows

Laminar and turbulent flows Ventilation 0 Duct Design Vladimír Zmrhal (room no. 84) http://users.fs.cvut.cz/~zmrhavla/index.htm Dpt. Of Environmental Engineering Laminar and turbulent flos Reynolds number d Re = ν laminar flo Re

More information

Contractor Name and Address: Oxy USA, Inc. (Oxy), Midland, Texas OBJECTIVES

Contractor Name and Address: Oxy USA, Inc. (Oxy), Midland, Texas OBJECTIVES 1 F TITLE: APPLICATION OF RESERVOIR CHARACTERIZATION AND ADVANCED TECHNOLOGY TO IMPROVE RECOVERY AND ECONOMICS IN A LOWER QUALITY SHALLOW SHELF CARBONATE RESERVOIR Cooperative Agreement No.: DE - FC22-948C14990

More information

Chapter 8: Flow in Pipes

Chapter 8: Flow in Pipes Objectives 1. Have a deeper understanding of laminar and turbulent flow in pipes and the analysis of fully developed flow 2. Calculate the major and minor losses associated with pipe flow in piping networks

More information

Status and Progress of a Fault Current Limiting HTS Cable To Be Installed In The Consolidated Edison Grid

Status and Progress of a Fault Current Limiting HTS Cable To Be Installed In The Consolidated Edison Grid Status and Progress of a Fault Current Limiting HTS Cable To Be Installed In The Consolidated Edison Grid J. Yuan, J. Maguire, D. Folts, N. Henderson, American Superconductor D. Knoll, Southwire M. Gouge,

More information

Study of a Non-Intrusrve blectron

Study of a Non-Intrusrve blectron Study of a Non-Intrusrve blectron b n i F -910s Diagnosti &m~i Radius LA-OP--77-3/37 Thomas J. T. Kwan, Barbara G. DeVolder, John C. Goldstein, and Charles M. Snell Los Alamos National Laboratory, Los

More information

ASTER. Dose Rate Visualization of Radioisotope Thermoelectric. Generators. RECElVED BEC OF THIS DOCUMEMT IS UNLlMIi L, Hanford Company

ASTER. Dose Rate Visualization of Radioisotope Thermoelectric. Generators. RECElVED BEC OF THIS DOCUMEMT IS UNLlMIi L, Hanford Company Dose Rate Visualization of Radioisotope Thermoelectric RECElVED Generators BEC 0 5 1995 Prepared for t h e US. De.partment of Energy Assistant Secretary for Environmental Management Westinghouse Hanford

More information

GA A22689 SLOW LINER FUSION

GA A22689 SLOW LINER FUSION GA A22689 SLOW LINER FUSION by AUGUST 1997 DISCLAIMER This report was prepared as an account of work sponsored by an agency of the United States Government. Neither the United States Government nor any

More information

ABSTRACT I. INTRODUCTION

ABSTRACT I. INTRODUCTION 2016 IJSRSET Volume 2 Issue 4 Print ISSN : 2395-1990 Online ISSN : 2394-4099 Themed Section: Engineering and Technology Analysis of Compressible Effect in the Flow Metering By Orifice Plate Using Prasanna

More information

(4) How do you develop an optimal signal detection technique from the knowledge of

(4) How do you develop an optimal signal detection technique from the knowledge of Signal and Noise in Global Warming Detection Final Report Gerald R. North, Principal Investigator Climate System Research Program, Texas A&M University, Texas 1. Program Objectives The specific objectives

More information

FLOW MEASUREMENT IN PIPES EXPERIMENT

FLOW MEASUREMENT IN PIPES EXPERIMENT University of Leicester Engineering Department FLOW MEASUREMENT IN PIPES EXPERIMENT Page 1 FORMAL LABORATORY REPORT Name of the experiment: FLOW MEASUREMENT IN PIPES Author: Apollin nana chaazou Partner

More information

Lawrence Berkeley Laboratory UNIVERSITY OF CALIFORNIA

Lawrence Berkeley Laboratory UNIVERSITY OF CALIFORNIA e LBL-3732 UC-414 Lawrence Berkeley Laboratory UNIVERSITY OF CALIFORNIA Accelerator & Fusion Research Division Presented at the InternationalMagnet Technology Conference 14 Tampere, Finland, June 11-16,

More information

STUDY OF CYCLOTRON RESONANCE AND MAGNETO-PHOTOLUMINESCENCE OF N-TYPE MODULATION DOPED InGaAs QUANTUM WELL LAYERS AND THEIR CHARACTERIZATIONS

STUDY OF CYCLOTRON RESONANCE AND MAGNETO-PHOTOLUMINESCENCE OF N-TYPE MODULATION DOPED InGaAs QUANTUM WELL LAYERS AND THEIR CHARACTERIZATIONS b.. '.. STUDY OF CYCLOTRON RESONANCE AND MAGNETO-PHOTOLUMINESCENCE OF N-TYPE MODULATION DOPED InGaAs QUANTUM WELL LAYERS AND THEIR CHARACTERIZATIONS N. KOTERA Kyushu Institute of Technology, Iizuka, Fukuoka

More information

BWXT Y-12 Y-12. A BWXT/Bechtel Enterprise SMALL, PORTABLE, LIGHTWEIGHT DT NEUTRON GENERATOR FOR USE WITH NMIS

BWXT Y-12 Y-12. A BWXT/Bechtel Enterprise SMALL, PORTABLE, LIGHTWEIGHT DT NEUTRON GENERATOR FOR USE WITH NMIS BWXT Y-12 A BWXT/Bechtel Enterprise Report No.: Y/LB-16,078 (Paper) SMALL, PORTABLE, LIGHTWEIGHT DT NEUTRON GENERATOR FOR USE WITH NMIS J. Reichardt J. T. Mihalczo R. B. Oberer L. G. Chiang J. K. Mattingly

More information

Measurement of fluid flow in closed conduits

Measurement of fluid flow in closed conduits BRITISH STANDARD BS 1042-2.2: 1983 ISO 7145:1982 Measurement of fluid flow in closed conduits Part 2: Velocity area methods Section 2.2 Method of measurement of velocity at one point of a conduit of circular

More information

Multicusp Sources for Ion Beam Lithography Applications

Multicusp Sources for Ion Beam Lithography Applications LBL-3 6645 UC-406 Multicusp Sources for Ion Beam Lithography Applications K.N. Leung, P. H e n, W.B. Kunkel, Y. Lee, L. Perkins, D. Pickard, M. Sarstedt, M. Weber, and M.D. Williams Accelerator and Fusion

More information

INDUSTRIAL INSULATION for Systems Operating Above Ambient Temperature

INDUSTRIAL INSULATION for Systems Operating Above Ambient Temperature INDUSTRIAL INSULATION for Systems Operating Above Ambient Temperature U.S. Department of Energy Energy Efficiency and Renewable Energy Office of Industrial Technologies Washington, D.C. 20585 From September,

More information

F L U I D S Y S T E M D Y N A M I C S

F L U I D S Y S T E M D Y N A M I C S F L U I D S Y S T E M D Y N A M I C S T he proper design, construction, operation, and maintenance of fluid systems requires understanding of the principles which govern them. These principles include

More information

Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid

Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid J. McCall, J. Yuan, D. Folts, N. Henderson, American Superconductor D. Knoll, Southwire M. Gouge, R. Duckworth, J.

More information

Controlling Backstreaming Ions from X-ray Converter Targets with Time Varying Final Focusing Solenoidal Lens and Beam Energy Variation

Controlling Backstreaming Ions from X-ray Converter Targets with Time Varying Final Focusing Solenoidal Lens and Beam Energy Variation UCRL-JC- 13059 1 PREPRINT Controlling Backstreaming Ions from X-ray Converter Targets with Time Varying Final Focusing Solenoidal Lens and Beam Energy Variation Y-J. Chen G. J. Caporaso A. C. Paul This

More information

Canal Velocity Indexing at Colorado River Indian Tribes (CRIT) Irrigation Project in Parker, Arizona using the SonTek Argonaut SL

Canal Velocity Indexing at Colorado River Indian Tribes (CRIT) Irrigation Project in Parker, Arizona using the SonTek Argonaut SL Canal Velocity Indexing at Colorado River Indian Tribes (CRIT) Irrigation Project in Parker, Arizona using the SonTek Argonaut SL Authors: Dr. Stuart Styles P.E., Mark Niblack, Beau Freeman Abstract An

More information

Walter P. Lysenko John D. Gilpatrick Martin E. Schulze LINAC '98 XIX INTERNATIONAL CONFERENCE CHICAGO, IL AUGUST 23-28,1998

Walter P. Lysenko John D. Gilpatrick Martin E. Schulze LINAC '98 XIX INTERNATIONAL CONFERENCE CHICAGO, IL AUGUST 23-28,1998 HGH ENERGY BEAM TRANSPORT BEAMLNE FOR LEDA A U THOR(S): SUBMTTED TO: Walter P. Lysenko John D. Gilpatrick Martin E. Schulze LANSCE-1 LANSCE-1 GENERAL ATOMCS LNAC '98 XX NTERNATONAL CONFERENCE CHCAGO, L

More information

OAK RIDGE NATIONAL LABORATORY

OAK RIDGE NATIONAL LABORATORY ORNL/TM-13339 OAK RDGE NATONAL LABORATORY 7+ A SMPLE ROTATONAL PENDULUM METHOD TO MEASURE THE RAD OF GYRATON OR MASS MOMENTS OF NERTA OF A ROTOR AND OTHER ASSEMBLES LOCKHEED M A R T N John B. Andriulli

More information

ACCOUNTING FOR FRICTION IN THE BERNOULLI EQUATION FOR FLOW THROUGH PIPES

ACCOUNTING FOR FRICTION IN THE BERNOULLI EQUATION FOR FLOW THROUGH PIPES ACCOUNTING FOR FRICTION IN THE BERNOULLI EQUATION FOR FLOW THROUGH PIPES Some background information first: We have seen that a major limitation of the Bernoulli equation is that it does not account for

More information

RECEIVED SEQ

RECEIVED SEQ SHOCK HUGONOT AND RELEASE STATES N CONCRETE MXTURES WTH DFFERENT AGGREGATE SZES FROM Y 3 TO 23 GPA C. A. Hall, L. C. Chhabildas, and W. D. Reinhart Sandia National Laboratories, Albuquerque, NM 87185-1

More information

FLOW FRICTION CHARACTERISTICS OF CONCRETE PRESSURE PIPE

FLOW FRICTION CHARACTERISTICS OF CONCRETE PRESSURE PIPE 11 ACPPA TECHNICAL SERIES FLOW FRICTION CHARACTERISTICS OF CONCRETE PRESSURE PIPE This paper presents formulas to assist in hydraulic design of concrete pressure pipe. There are many formulas to calculate

More information

Applications of Pulse Shape Analysis to HPGe Gamma-Ray Detectors

Applications of Pulse Shape Analysis to HPGe Gamma-Ray Detectors UCRL-JC- 134555 PREPRINT Applications of Pulse Shape Analysis to HPGe Gamma-Ray Detectors GJ. Schmid D.A. Beckedahl JJ. Blair J.E. Kammeraad This paper was prepared for submittal to the American Nuclear

More information

GA A27806 TURBULENCE BEHAVIOR AND TRANSPORT RESPONSE APPROACHING BURNING PLASMA RELEVANT PARAMETERS

GA A27806 TURBULENCE BEHAVIOR AND TRANSPORT RESPONSE APPROACHING BURNING PLASMA RELEVANT PARAMETERS GA A27806 TURBULENCE BEHAVIOR AND TRANSPORT RESPONSE APPROACHING by G.R. McKEE, C. HOLLAND, Z. YAN, E.J. DOYLE, T.C. LUCE, A. MARINONI, C.C. PETTY, T.L. RHODES, L. SCHMITZ, W.M. SOLOMON, B.J. TOBIAS, G.

More information

Shock compression of precompressed deuterium

Shock compression of precompressed deuterium LLNL-PROC-491811 Shock compression of precompressed deuterium M. R. Armstrong, J. C. Crowhurst, J. M. Zaug, S. Bastea, A. F. Goncharov, B. Militzer August 3, 2011 Shock compression of precompressed deuterium

More information

Development of a High Intensity EBIT for Basic and Applied Science

Development of a High Intensity EBIT for Basic and Applied Science UCRL-ID- 129832 Development of a High Intensity EBIT for Basic and Applied Science R.E. Marrs D. Schneider February 5,1998 This is an informal report intended primarily for internal or limited external

More information

Experiences in an Undergraduate Laboratory Using Uncertainty Analysis to Validate Engineering Models with Experimental Data

Experiences in an Undergraduate Laboratory Using Uncertainty Analysis to Validate Engineering Models with Experimental Data Experiences in an Undergraduate Laboratory Using Analysis to Validate Engineering Models with Experimental Data W. G. Steele 1 and J. A. Schneider Abstract Traditionally, the goals of engineering laboratory

More information

How Small Can a Launch Vehicle Be?

How Small Can a Launch Vehicle Be? UCRL-CONF-213232 LAWRENCE LIVERMORE NATIONAL LABORATORY How Small Can a Launch Vehicle Be? John C. Whitehead July 10, 2005 41 st AIAA/ASME/SAE/ASEE Joint Propulsion Conference and Exhibit Tucson, AZ Paper

More information

GA A THERMAL ION ORBIT LOSS AND RADIAL ELECTRIC FIELD IN DIII-D by J.S. degrassie, J.A. BOEDO, B.A. GRIERSON, and R.J.

GA A THERMAL ION ORBIT LOSS AND RADIAL ELECTRIC FIELD IN DIII-D by J.S. degrassie, J.A. BOEDO, B.A. GRIERSON, and R.J. GA A27822 THERMAL ION ORBIT LOSS AND RADIAL ELECTRIC FIELD IN DIII-D by J.S. degrassie, J.A. BOEDO, B.A. GRIERSON, and R.J. GROEBNER JUNE 2014 DISCLAIMER This report was prepared as an account of work

More information

RESEARCH OPPORTUNITIES AT THE CNS (Y-12 AND PANTEX) NUCLEAR DETECTION AND SENSOR TESTING CENTERS (NDSTC)

RESEARCH OPPORTUNITIES AT THE CNS (Y-12 AND PANTEX) NUCLEAR DETECTION AND SENSOR TESTING CENTERS (NDSTC) Y / DW-2319 RESEARCH OPPORTUNITIES AT THE CNS (Y-12 AND PANTEX) NUCLEAR DETECTION AND SENSOR TESTING CENTERS (NDSTC) Carter Hull 1 Carter.Hull@cns.doe.gov Jim Tallent 4, Dennis Tollefson 2, Martin Williamson

More information

Ray M. Stringfield Robert J. Kares J. R. Thomas, Jr.

Ray M. Stringfield Robert J. Kares J. R. Thomas, Jr. U4JR-96-1107 * v TITLE: AU THOR(S): SUBMITTED TO: TEMPERATURE DISTRIBUTION IN A FLOWING FLUID HEATED IN A MICROWAVE RESONANT CAVI'W Eric M. Nelson Ray M. Stringfield Robert J. Kares J. R. Thomas, Jr. AOT-9

More information

Quarterly Report April 1 - June 30, By: Shirley P. Dutton. Work Performed Under Contract No.: DE-FC22-95BC14936

Quarterly Report April 1 - June 30, By: Shirley P. Dutton. Work Performed Under Contract No.: DE-FC22-95BC14936 DE-FC22-95BC14936--18 Application of Advanced Reservoir Characterization, Simulation, and Production Optimization Strategies to Maximize Recovery in Slope, and Basin Clastic Reservoirs, West Texas (Delaware

More information

405 Compact Orifice Series and 1595 Conditioning Orifice Plate Flow Test Data Book and Flow Handbook

405 Compact Orifice Series and 1595 Conditioning Orifice Plate Flow Test Data Book and Flow Handbook 405 Compact Orifice Series and 1595 Conditioning Orifice Plate Flow Test Book and Flow Handbook www.rosemount.com 405 Compact Orifice Series and 1595 Conditioning Orifice Plate Flow Test Book NOTICE Read

More information

Multi-Scale Chemical Process Modeling with Bayesian Nonparametric Regression

Multi-Scale Chemical Process Modeling with Bayesian Nonparametric Regression Multi-Scale Chemical Process Modeling with Bayesian Nonparametric Regression Evan Ford, 1 Fernando V. Lima 2 and David S. Mebane 1 1 Mechanical and Aerospace Engineering 2 Chemical Engineering West Virginia

More information

sample-specific X-ray speckle contrast variation at absorption edges $ & ~ 0

sample-specific X-ray speckle contrast variation at absorption edges $ & ~ 0 . 1. Introduction X-ray speckle contrast variation at absorption edges sample-specific Cornelia C. Retsch, Yuxin Wang, Sean P. Frigo, G. Brian Stephenson, Ian McNdty Argonne National Laboratory 9700 South

More information

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title Electron-Cloud Build-up in the FNAL Main Injector Permalink https://escholarship.org/uc/item/4v35z0wd Author Furman, M.A.

More information

GA A27235 EULERIAN SIMULATIONS OF NEOCLASSICAL FLOWS AND TRANSPORT IN THE TOKAMAK PLASMA EDGE AND OUTER CORE

GA A27235 EULERIAN SIMULATIONS OF NEOCLASSICAL FLOWS AND TRANSPORT IN THE TOKAMAK PLASMA EDGE AND OUTER CORE GA A27235 EULERIAN SIMULATIONS OF NEOCLASSICAL FLOWS AND TRANSPORT IN THE TOKAMAK PLASMA EDGE AND OUTER CORE by E.A. BELLI, J.A. BOEDO, J. CANDY, R.H. COHEN, P. COLELLA, M.A. DORF, M.R. DORR, J.A. HITTINGER,

More information

A Numerical Estimate of Flexible Short-Tube Flow and Deformation with R-134a and R-410a

A Numerical Estimate of Flexible Short-Tube Flow and Deformation with R-134a and R-410a For personal use only. Additional reproduction, distribution, or transmission SL-08-043 A Numerical Estimate of Flexible Short-Tube Flow and Deformation with R-134a and R-410a Ramadan Bassiouny, PhD Dennis

More information

Bernoulli and Pipe Flow

Bernoulli and Pipe Flow Civil Engineering Hydraulics Mechanics of Fluids Head Loss Calculations Bernoulli and The Bernoulli equation that we worked with was a bit simplistic in the way it looked at a fluid system All real systems

More information

12/16/95-3/15/96 PERIOD MULTI-PARAMETER ON-LINE COAL BULK ANALYSIS. 2, 1. Thermal Neutron Flux in Coal: New Coal Container Geometry

12/16/95-3/15/96 PERIOD MULTI-PARAMETER ON-LINE COAL BULK ANALYSIS. 2, 1. Thermal Neutron Flux in Coal: New Coal Container Geometry DDG/Pc/q+wl TECHNCAL PROGRESS REPORT 2/6/95-3/5/96 PEROD GRANT DE-FG22-93PC932 MULT-PARAMETER ON-LNE COAL BULK ANALYSS Scientific work VD 0 % s g; e 0% 2% -2- G? 2,. Thermal Neutron Flux in Coal: New Coal

More information

FUSION WITH Z-PINCHES. Don Cook. Sandia National Laboratories Albuquerque, New Mexico 87185

FUSION WITH Z-PINCHES. Don Cook. Sandia National Laboratories Albuquerque, New Mexico 87185 FUSION WITH Z-PINCHES Don Cook Sandia National Laboratories Albuquerque, New Mexico 87185 RECEIVED JUN 1 5 1998 Sandia is a multiprogmm laboratory operated by Sandia C o r p w I t 1oli, h Lockheed Martin

More information

ME 305 Fluid Mechanics I. Part 8 Viscous Flow in Pipes and Ducts. Flow in Pipes and Ducts. Flow in Pipes and Ducts (cont d)

ME 305 Fluid Mechanics I. Part 8 Viscous Flow in Pipes and Ducts. Flow in Pipes and Ducts. Flow in Pipes and Ducts (cont d) ME 305 Fluid Mechanics I Flow in Pipes and Ducts Flow in closed conduits (circular pipes and non-circular ducts) are very common. Part 8 Viscous Flow in Pipes and Ducts These presentations are prepared

More information

RESONANCE INTERFERENCE AND ABSOLUTE CROSS SECTIONS IN NEAR-THRESHOLD ELECTRON-IMPACT EXCITATION OF MULTICHARGED IONS

RESONANCE INTERFERENCE AND ABSOLUTE CROSS SECTIONS IN NEAR-THRESHOLD ELECTRON-IMPACT EXCITATION OF MULTICHARGED IONS RESONANCE INTERFERENCE AND ABSOLUTE CROSS SECTIONS IN NEAR-THRESHOLD ELECTRON-IMPACT EXCITATION OF MULTICHARGED IONS M. E. BANNISTER Physics Division, Oak Ridge National Labomtory, Oak Ridge, TN 37831-6372,USA

More information

BASAL CAMBRIAN BASELINE GEOLOGICAL CHARACTERIZATION COMPLETED

BASAL CAMBRIAN BASELINE GEOLOGICAL CHARACTERIZATION COMPLETED BASAL CAMBRIAN BASELINE GEOLOGICAL CHARACTERIZATION COMPLETED Plains CO 2 Reduction (PCOR) Partnership Phase III Task 16 Milestone M33 Prepared for: Andrea T. McNemar National Energy Technology Laboratory

More information

A Distributed Radiator, Heavy Ion Driven Inertial Confinement Fusion Target with Realistic, Multibeam Illumination Geometry

A Distributed Radiator, Heavy Ion Driven Inertial Confinement Fusion Target with Realistic, Multibeam Illumination Geometry UCRL-JC-131974 PREPRINT A Distributed Radiator, Heavy Ion Driven Inertial Confinement Fusion Target with Realistic, Multibeam Illumination Geometry D. A. Callahan-Miller M. Tabak This paper was prepared

More information

Modified Kriging: Evaluation, Modification, Recommendations

Modified Kriging: Evaluation, Modification, Recommendations UCRL-ID- 12873 1 Modified Kriging: Evaluation, Modification, Recommendations and C.A. Schultz S.C. Myers September 1997 This is an informal report intended primarily forinternal or limited external distribution.

More information

SPHERICAL COMPRESSION OF A MAGNETIC FIELD. C. M. Fowler DISCLAIMER

SPHERICAL COMPRESSION OF A MAGNETIC FIELD. C. M. Fowler DISCLAIMER 1. LA-UR- @olvf-y6og/da --a saa Title: SPHERICAL COMPRESSION OF A MAGNETIC FIELD C. M. Fowler DISCLAIMER This report was prepared as an account of work sponsored by an agency of the United States Government.

More information

Chapter 8: Flow in Pipes

Chapter 8: Flow in Pipes 8-1 Introduction 8-2 Laminar and Turbulent Flows 8-3 The Entrance Region 8-4 Laminar Flow in Pipes 8-5 Turbulent Flow in Pipes 8-6 Fully Developed Pipe Flow 8-7 Minor Losses 8-8 Piping Networks and Pump

More information