Two-Way Flat Plate Concrete Floor System Analysis and Design

Size: px
Start display at page:

Download "Two-Way Flat Plate Concrete Floor System Analysis and Design"

Transcription

1 Two-Way Flat Plate Concrete Floor System Analysis and Design Version: Aug

2 Two-Way Flat Plate Concrete Floor System Analysis and Design The concrete floor slab system shown below is for an intermediate floor to be designed considering partition weight = 0 psf, and unfactored live load = 40 psf. Flat plate concrete floor system does not use beams between columns or drop panels and it is usually suited for lightly loaded floors with short spans typically for residential and hotel buildings. The lateral loads are independently resisted by shear walls. The two design procedures shown in ACI : Direct Design Method (DDM) and the Equivalent Frame Method (EFM) are illustrated in detail in this example. The hand solution from EFM is also used for a detailed comparison with the analysis and design results of the engineering software program spslab. Figure 1 - Two-Way Flat Concrete Floor System Version: Aug

3 Contents 1. Preliminary Member Sizing Two-Way Slab Analysis and Design Direct Design Method (DDM) Direct design method limitations Design moments Flexural reinforcement requirements Factored moments in columns Equivalent Frame Method (EFM) Equivalent frame method limitations Frame members of equivalent frame Equivalent frame analysis Design moments Distribution of design moments Flexural reinforcement requirements Column design moments Design of Interior, Edge, and Corner Columns Determination of factored loads Column Capacity Diagram (Axial-Moment Interaction Diagram) Two-Way Slab Shear Strength One-Way (Beam action) Shear Strength Two-Way (Punching) Shear Strength Two-Way Slab Deflection Control (Serviceability Requirements) Immediate (Instantaneous) Deflections Time-Dependent (Long-Term) Deflections (Δ lt) Computer Program Solution Summary and Comparison of Two-Way Slab Design Results Comparison of Two-Way Slab Analysis and Design Methods Version: Aug

4 Code Building Code Requirements for Structural Concrete (ACI ) and Commentary (ACI 318R-14) Minimum Design Loads for Buildings and Other Structures (ASCE/SEI 7-10) International Code Council, 01 International Building Code, Washington, D.C., 01 Reference Notes on ACI Building Code Requirements for Structural Concrete, Twelfth Edition, 013 Portland Cement Association, Example 0.1 Concrete Floor Systems (Guide to Estimating and Economizing), Second Edition, 00 David A. Fanella Simplified Design of Reinforced Concrete Buildings, Fourth Edition, 011 Mahmoud E. Kamara and Lawrence C. Novak Design Data Floor-to-Floor Height = 9 ft (provided by architectural drawings) Superimposed Dead Load, SDL =0 psf for framed partitions, wood studs plaster sides ASCE/SEI 7-10 (Table C3-1) Live Load, LL = 40 psf for Residential floors ASCE/SEI 7-10 (Table 4-1) f c = 4000 psi (for slabs) f c = 6000 psi (for columns) f y = 60,000 psi Required fire resistance rating = hours Solution 1. Preliminary Member Sizing a. Slab minimum thickness - Deflection ACI ( ) In this example deflection will be calculated and checked to satisfy project deflection limits. Minimum member thickness and depths from ACI will be used for preliminary sizing. Using ACI minimum slab thickness for two-way construction without interior beams in Table l n 00 Exterior Panels: h ACI (Table ) But not less than 5 ACI ( (a)) l n 00 Interior Panels: h ACI (Table ) But not less than 5 ACI ( (a)) 1

5 Where l n = length of clear span in the long direction = = 00 Try 7 slab for all panels (self-weight = 87.5 psf) b. Slab shear strength one way shear Evaluate the average effective depth (Figure ): db 0.5 dl tslab cclear db db 0.5 dt tslab cclear d d l t d 5.75 avg Where: c clear = 3/4 for # 4 steel bar ACI (Table ) d b = 0.5 for # 4 steel bar Figure - Two-Way Flat Concrete Floor System Factored dead load, qdu 1. (87.5 0) 19 psf Factored live load, qlu psf ACI (5.3.1) Total factored load qu 193 psf Check the adequacy of slab thickness for beam action (one-way shear) ACI (.5) at an interior column: Consider a 1- wide strip. The critical section for one-way shear is located at a distance d, from the face of support (see Figure 3) Tributary area for one-way shear is A [( ) ( ) ( )] ( ) ft Tributary V u qu A kips Tributary Vc fc ' bwd ACI (Eq ) where 1for normal weight concrete

6 5.75 V c kips 1000 Slab thickness of 7 is adequate for one-way shear. c. Slab shear strength two-way shear V u Check the adequacy of slab thickness for punching shear (two-way shear) at an interior column (Figure 4): Tributary area for two-way shear is A (18 14) ( ) 48.7 ft Tributary 1 V u qu A kips Tributary Vc 4 fc ' bo d (For square interior column) ACI (Table.6.5.(a)) 5.75 V c (41.75) 16.6 kips 1000 V kips V c Slab thickness of 7 is adequate for two-way shear. u Figure 3 Critical Section for One-Way Figure 4 Critical Section for Two-Way d. Column dimensions - axial load Check the adequacy of column dimensions for axial load: Tributary area for interior column is ATributary P u qu ATributary kips (18 14) 5 ft P 0.80P 0.80 (0.85 f '( A A ) f A ) (For square interior column) ACI (.4.) n o c g st y st P 0.80 (0.85(6000)( ) 0) 1,044,480 lb 1,044 kips n P , kips P 48.6 kips n u Column dimensions of 16 x 16 are adequate for axial load.. Two-Way Slab Analysis and Design ACI 318 states that a slab system shall be designed by any procedure satisfying equilibrium and geometric compatibility, provided that strength and serviceability criteria are satisfied. Distinction of two-systems from one-way systems is given by ACI (R & R8.3.1.). 3

7 ACI 318 permits the use of Direct Design Method (DDM) and Equivalent Frame Method (EFM) for the gravity load analysis of orthogonal frames and is applicable to flat plates, flat slabs, and slabs with beams. The following sections outline the solution per DDM, EFM, and spslab software respectively..1. Direct Design Method (DDM) Two-way slabs satisfying the limits in ACI (8.10.) are permitted to be designed in accordance with the DDM Direct design method limitations There is a minimum of three continuous spans in each direction ACI ( ) Successive span lengths are equal ACI (8.10..) Long-to-short span ratio is 1.9 < ACI ( ) Columns are not offset ACI ( ) Loads are uniformly distributed over the entire panel ACI ( ) Service live-to-dead load ratio of 0.37 <.0 ACI ( ) Slab system is without beams and this requirement is not applicable ACI ( ) Since all the criteria are met, Direct Design Method can be utilized..1.. Design moments a. Calculate the total factored static moment: M o qu n ft-kips ACI ( ) 8 8 b. Distribute the total factored moment, M o, in an interior and end span: ACI (8.10.4) Exterior Span Table 1 - Distribution of Mo along the span Location Total Design Strip Moment, MDS (ft-kips) Exterior Negative 0.6 x M o = 4.3 Positive 0.5 x M o = 48.7 Interior Negative 0.70 x M o = 65.5 Interior Span Positive 0.35 x M o = 3.8 c. Calculate the column strip moments. ACI (8.10.5) That portion of negative and positive total design strip moments not resisted by column strips shall be proportionally assigned to corresponding two half-middle strips. ACI ( ) 4

8 Table - Lateral Distribution of the Total Design Strip Moment, MDS Location Total Design Strip Moment, MDS (ft-kips) Column Strip Moment, (ft-kips) Moment in Two Half Middle Strips, (ft-kips) Exterior Negative * x M DS = x M DS = 0.0 Exterior Span Positive x M DS = x M DS = 19.5 Interior Negative * x M DS = x M DS = 16.4 Interior Span Positive x M DS = x M DS = 13.1 * All negative moments are at face of support Flexural reinforcement requirements a. Determine flexural reinforcement required for column and middle strips at all critical sections The following calculation is for the exterior span exterior negative location of the column strip. M 4.3 u ft-kips Use average d avg = 5.75 To determine the area of steel, assumptions have to be made whether the section is tension or compression controlled, and regarding the distance between the resultant compression and tension forces along the slab section (jd). In this example, tension-controlled section will be assumed so the reduction factor is equal to 0.9, and jd will be taken equal to 0.95d. The assumptions will be verified once the area of steel in finalized. Assume jd 0.95 d 5.46 Column strip width, b 14 1 / 84 Middle strip width, b A M u s f jd 0.99 in y Recalculate a for the actual A s = 0.99 : Af s y a 0.08 in 0.85 f ' b c a 0.08 c 0.44 in t ( ) dt ( ) c

9 Therefore, the assumption that section is tension-controlled is valid. A M u s f 0.96 ( d a in y / ) ( / ) Min As in 0.96 in ACI (4.4.3.) Maximum spacing smax h 7 14 in 18 in ACI (8.7..) Provide 6 - #4 bars with A 1.0 s in and s 84 / 6 14 in s max Based on the procedure outlined above, values for all span locations are given in Table 3. Column Strip Middle Strip Column Strip Middle Strip Span Location Table 3 - Required Slab Reinforcement for Flexure (DDM) Mu (ft-kips) b () d () End Span As Req d for flexure (in ) Min As (in ) Reinforcement Provided As Prov. for flexure (in ) Exterior Negative #4 1. Positive #4 1. Interior Negative #4 Exterior Negative #4 1. Positive #4 1. Interior Negative #4 1. Interior Span Positive #4 1. Positive #4 1. b. Calculate additional slab reinforcement at columns for moment transfer between slab and column The factored slab moment resisted by the column ( f Mu ) shall be assumed to be transferred by flexure. Concentration of reinforcement over the column by closer spacing or additional reinforcement shall be used to resist this moment. The fraction of slab moment not calculated to be resisted by flexure shall be assumed to be resisted by eccentricity of shear. ACI (8.4..3) Portion of the unbalanced moment transferred by flexure is f Mu ACI ( ) Where 1 f ACI ( ) 1 ( / 3) b / b 1 b1 Dimension of the critical section determined in ACI 318, Chapter 8 (see Figure 5). b o measured in the direction of the span for which moments are 6

10 b Dimension of the critical section bo measured in the direction perpendicular to b1 in ACI 318, Chapter 8 (see Figure 5). b b = Effective slab width = c 3h ACI ( ) Figure 5 Critical Shear Perimeters for Columns Column Strip Table 4 - Additional Slab Reinforcement required for moment transfer between slab and column (DDM) Span Location M u * (ft-kips) γ f γ f M u (ft-kips) End Span Effective slab width, b b () d () A s req d within b b (in ) A s prov. For flexure within b b (in ) Exterior Negative #4 Interior Negative *M u is taken at the centerline of the support in Equivalent Frame Method solution. Add l Reinf Factored moments in columns a. Interior columns: M 0.07 [( q 0.5 q ) ' ' ' ] Du Lu n q n ACI ( ) u Du M u 0.07 ( ) ft-kips 1 1 7

11 With the same column size and length above and below the slab, M 8.87 ft-kips column b. Exterior Columns: Total exterior negative moment from slab must be transferred directly to the column: ftkips. With the same column size and length above and below the slab, M 4.3 u 4.3 M column 1.15 ft-kips The moments determined above are combined with the factored axial loads (for each story) for design of column sections as shown later in this example... Equivalent Frame Method (EFM) EFM is the most comprehensive and detailed procedure provided by the ACI 318 for the analysis and design of two-way slab systems where the structure is modeled by a series of equivalent frames (interior and exterior) on column lines taken longitudinally and transversely through the building. The equivalent frame consists of three parts: 1) Horizontal slab-beam strip, including any beams spanning in the direction of the frame. Different values of moment of inertia along the axis of slab-beams should be taken into account where the gross moment of inertia at any cross section outside of joints or column capitals shall be taken, and the moment of inertia of the slab-beam at the face of the column, bracket or capital divide by the quantity (1-c /l ) shall be assumed for the calculation of the moment of inertia of slab-beams from the center of the column to the face of the column, bracket or capital. ACI (8.11.3) ) Columns or other vertical supporting members, extending above and below the slab. Different values of moment of inertia along the axis of columns should be taken into account where the moment of inertia of columns from top and bottom of the slab-beam at a joint shall be assumed to be infinite, and the gross cross section of the concrete is permitted to be used to determine the moment of inertia of columns at any cross section outside of joints or column capitals. ACI (8.11.4) 3) Elements of the structure (Torsional members) that provide moment transfer between the horizontal and vertical members. These elements shall be assumed to have a constant cross section throughout their length consisting of the greatest of the following: (1) portion of slab having a width equal to that of the column, bracket, or capital in the direction of the span for which moments are being determined, () portion of slab specified in (1) plus that part of the transverse beam above and below the slab for monolithic or fully composite construction, (3) the transverse beam includes that portion of slab on each side of the beam extending a distance equal to the projection of the beam above or below the slab, whichever is greater, but not greater than four times the slab thickness. ACI (8.11.5) 8

12 ..1. Equivalent frame method limitations In EFM, live load shall be arranged in accordance with which requires slab systems to be analyzed and designed for the most demanding set of forces established by investigating the effects of live load placed in various critical patterns. ACI ( & 6.4.3) Complete analysis must include representative interior and exterior equivalent frames in both the longitudinal and transverse directions of the floor ACI ( ) Panels shall be rectangular, with a ratio of longer to shorter panel dimensions, measured center-to-center of supports, not to exceed. ACI ( )... Frame members of equivalent frame Determine moment distribution factors and fixed-end moments for the equivalent frame members. The moment distribution procedure will be used to analyze the equivalent frame. Stiffness factors k, carry over factors COF, and fixed-end moment factors FEM for the slab-beams and column members are determined using the design aids tables at Appendix 0A of PCA Notes on ACI These calculations are shown below. a. Flexural stiffness of slab-beams at both ends, K sb. c N (18 1) 1, c N (14 1) For cf1 cf, stiffness factors, knf kfn 4.13 PCA Notes on ACI (Table A1) E I E I Thus, K k cs s 4.13 cs s NF PCA Notes on ACI (Table A1) sb K lb sb 16 where, (7) 3 s h I s 480 in E w f cs c c psi ACI ( a) Carry-over factor COF PCA Notes on ACI (Table A1) Fixed-end moment FEM w u PCA Notes on ACI (Table A1) 1 b. Flexural stiffness of column members at both ends, K c. Referring to Table A7, Appendix 0A, ta 3.5, tb 3.5, ta H H 9 ft 108, Hc 101, 1, 1.07 tb Hc 9

13 Thus, k k 4.74 by interpolation. AB BA 4.74E cc I K c PCA Notes on ACI (Table A7) c c K c -lb 108 Where 4 4 c (16) Ic E w f cc c c psi ACI ( a) c 9 ft 108 c. Torsional stiffness of torsional members, K t. K t 9EcsC c 3 [ (1 ) ] ACI (R ) K t -lb 168(0.905) 3 Where 3 x x y C ( )( ) ACI (Eq b) y C ( )(7 ) 135 in c 16, and 14 ft 168 d. Equivalent column stiffness Kc K K t ec Kc Kt K ec. K ( 115.5)( 367) 10 6 ec [(115.5) (367)] Figure 6 - Torsional Member 10

14 K ec -lb Where K t column, and is for two torsional members one on each side of the K c is for the upper and lower columns at the slabbeam joint of an intermediate floor. e. Slab-beam joint distribution factors, DF. At exterior joint, 35 DF ( ) Figure 7 Column and Edge of Slab At interior joint, 35 DF 0.80 ( ) COF for slab-beam Equivalent frame analysis Determine negative and positive moments for the slab-beams using the moment distribution method. Since the unfactored live load does not exceed three-quarters of the unfactored dead load, design moments are assumed to occur at all critical sections with full factored live on all spans. ACI (6.4.3.) L D (87.5 0) 4 a. Factored load and Fixed-End Moments (FEM s). Factored dead load qdu 1.(87.5 0) 19 psf Factored live load qlu 1.6(40) 64 psf Factored load q q q 193 psf u Du Lu Figure 8 Slab and Column Stiffness FEM s for slab-beams m q PCA Notes on ACI (Table A1) NF u ( ) ft-kips 11

15 b. Moment distribution. Computations are shown in Table 5. Counterclockwise rotational moments acting on the member ends are taken as positive. Positive span moments are determined from the following equation: ( MuL MuR ) (midspan) M o M u Where M o is the moment at the midspan for a simple beam. When the end moments are not equal, the maximum moment in the span does not occur at the midspan, but its value is close to that midspan for this example. Positive moment in span 1-: 18 ( ) M u ( ) 44.1 ft-kips 8 Positive moment span -3: 18 ( ) M u ( ) 33. ft-kips 8 Table 5 Moment Distribution for Equivalent Frame Joint Member DF COF FEM Dist CO Dist CO Dist CO Dist CO Dist Neg. M M at midspan Design moments Positive and negative factored moments for the slab system in the direction of analysis are plotted in Figure 9. The negative moments used for design are taken at the faces of supports (rectangle section or equivalent rectangle for circular or polygon sections) but not at distances greater than from the centers of supports. ACI ( ) ft ft (use face of support location) 1 1

16 Figure 9 - Positive and Negative Design Moments for Slab-Beam (All Spans Loaded with Full Factored Live Load)..5. Distribution of design moments a. Check whether the moments calculated above can take advantage of the reduction permitted by ACI ( ): If the slab system analyzed using EFM within the limitations of ACI (8.10.), it is permitted by the ACI code to reduce the calculated moments obtained from EFM in such proportion that the absolute sum of the positive and average negative design moments need not exceed the value obtained from the following equation: qu n (16.67) M o ft-kips ACI (Eq )

17 End spans: ( ) ft-kips Interior span: ( ) ft-kips The total design moments from the Equivalent Frame Method yield a static moment equal to that given by the Direct Design Method and no appreciable reduction can be realized. b. Distribute factored moments to column and middle strips: After the negative and positive moments have been determined for the slab-beam strip, the ACI code permits the distribution of the moments at critical sections to the column strips, beams (if any), and middle strips in accordance with the DDM. ACI ( ) Distribution of factored moments at critical sections is summarized in Table 6. End Span Interior Span Table 6 - Distribution of factored moments Slab-beam Strip Column Strip Middle Strip Moment (ft-kips) Percent Moment (ft-kips) Percent Moment (ft-kips) Exterior Negative Positive Interior Negative Negative Positive Flexural reinforcement requirements a. Determine flexural reinforcement required for strip moments The flexural reinforcement calculation for the column strip of end span exterior negative location is provided below. M u 3.3 ft-kips Use average d avg = 5.75 To determine the area of steel, assumptions have to be made whether the section is tension or compression controlled, and regarding the distance between the resultant compression and tension forces along the slab section (jd). In this example, tension-controlled section will be assumed so the reduction factor is equal to 0.9, and jd will be taken equal to 0.95d. The assumptions will be verified once the area of steel in finalized. Assume jd 0.95 d

18 Column strip width, b 14 1 / 84 Middle strip width, b Mu As 1.31 f jd y Recalculate a for the actual A s = 1.31 : Af s y a f ' b c a 0.76 c t ( ) dt ( ) c 0.35 Therefore, the assumption that section is tension-controlled is valid. Mu As 1.8 f ( d a / ) ( / ) y Min As in 1.8 ACI (4.4.3.) Maximum spacing smax h ACI (8.7..) Provide 7 - #4 bars with A s = 1.40 and s = 84/7 = 1 s max Based on the procedure outlined above, values for all span locations are given in Table 7. Column Strip Middle Strip Column Strip Middle Strip Span Location Table 7 - Required Slab Reinforcement for Flexure [Equivalent Frame Method (EFM)] Mu (ft-kips) b * () d ** () As Req d for flexure (in ) End Span Min As (in ) Reinforcement Provided As Prov. for flexure (in ) Exterior Negative #4 1.4 Positive #4 1. Interior Negative #4. Exterior Negative #4 1. Positive #4 1. Interior Negative #4 1. Interior Span Positive #4 1. Positive #4 1. b. Calculate additional slab reinforcement at columns for moment transfer between slab and column by flexure 15

19 The factored slab moment resisted by the column ( M f u ) shall be assumed to be transferred by flexure. Concentration of reinforcement over the column by closer spacing or additional reinforcement shall be used to resist this moment. The fraction of slab moment not calculated to be resisted by flexure shall be assumed to be resisted by eccentricity of shear. ACI (8.4..3) Portion of the unbalanced moment transferred by flexure is f Mu ACI ( ) Where 1 f ACI ( ) 1 ( / 3) b / b 1 b1 Dimension of the critical section determined in ACI 318, Chapter 8 (see Figure 5). b o measured in the direction of the span for which moments are b Dimension of the critical section 8 (see Figure 5). b o measured in the direction perpendicular to b 1 in ACI 318, Chapter b b = Effective slab width = c 3 h ACI ( ) Column Strip Table 8 - Additional Slab Reinforcement required for moment transfer between slab and column (EFM) Span Location M u * (ft-kips) γ f γ f M u (ft-kips) End Span Effective slab width, b b () d () A s req d within b b (in ) A s prov. For flexure within b b (in ) Exterior Negative #4 Interior Negative *M u is taken at the centerline of the support in Equivalent Frame Method solution. Add l Reinf...7. Column design moments The unbalanced moment from the slab-beams at the supports of the equivalent frame are distributed to the support columns above and below the slab-beam in proportion to the relative stiffness of the support columns. Referring to Figure 9, the unbalanced moment at joints 1 and are: Joint 1= ft-kips Joint = = -7.8 ft-kips The stiffness and carry-over factors of the actual columns and the distribution of the unbalanced slab moments (M sc) to the exterior and interior columns are shown in Figure 10a. 16

20 Figure 10a - Column Moments (Unbalanced Moments from Slab-Beam) In summary: M col,exterior=.08 ft-kips M col,interior = 3.66 ft-kips The moments determined above are combined with the factored axial loads (for each story) and factored moments in the transverse direction for design of column sections. Figure 10b shows the moment diagrams in the longitudinal and transverse direction for the interior and exterior equivalent frames. Following the previous procedure, the moment values at the face of interior, exterior, and corner columns from the unbalanced moment values can be obtained. These values are shown in the following table. 17

21 Figure 10b Moment Diagrams (kips-ft) Mu kips-ft Column number (See Figure 10b) Mux Muy Design of Interior, Edge, and Corner Columns This section includes the design of interior, edge, and corner columns using spcolumn software. The preliminary dimensions for these columns were calculated previously in section one. The reduction of live load per ASCE 7-10 will be ignored in this example. However, the detailed procedure to calculate the reduced live loads is explained in the wide-module Joist System example. 18

22 3.1. Determination of factored loads Interior Column (Column #1): Assume 4 story building Tributary area for interior column is ATributary P 4q A kips u u Tributary M u,x = 3.66 ft-kips (see the previous Table) M u,y =.3 ft-kips (see the previous Table) (18 14) 5 ft Edge (Exterior) Column (Column #): Tributary area for interior column is ATributary P 4q A kips u u Tributary M u,x =.08 ft-kips (see the previous Table) M u,y = 1.8 ft-kips (see the previous Table) (18 / 14) 16 ft Edge (Exterior) Column (Column #3): Tributary area for interior column is ATributary P 4q A kips u u Tributary M u,x =.04 ft-kips (see the previous Table) M u,y = 1.49 ft-kips (see the previous Table) (18 14 / ) 16 ft Corner Column (Column #4): Tributary area for interior column is ATributary P 4q A kips u u Tributary M u,x = 1.39 ft-kips (see the previous Table) M u,y = 6.79 ft-kips (see the previous Table) (18 / 14 / ) 63 ft The factored loads are then input into spcolumn to construct the axial load moment interaction diagram. 19

23 3.. Column Capacity Diagram (Axial-Moment Interaction Diagram) Interior Column (Column #1): 0

24 Edge Column (Column #): 1

25 Edge Column (Column #3):

26 Corner Column (Column #4): 3

27 4. Two-Way Slab Shear Strength Shear strength of the slab in the vicinity of columns/supports includes an evaluation of one-way shear (beam action) and two-way shear (punching) in accordance with ACI 318 Chapter One-Way (Beam action) Shear Strength ACI (.5) One-way shear is critical at a distance d from the face of the column as shown in Figure 3. Figure 11 shows the factored shear forces (V u) at the critical sections around each column. In members without shear reinforcement, the design shear capacity of the section equals to the design shear capacity of the concrete: Vn Vc Vs Vc, Where: ( V s 0) ACI (Eq ) V f ' c cbwd ACI (Eq ) 1for normal weight concrete 4000 V c (14 1) kips 1000 Because Vc Vu at all the critical sections, the slab has adequate one-way shear strength. Figure 11 One-way shear at critical sections (at distance d from the face of the supporting column) 4

28 4.. Two-Way (Punching) Shear Strength ACI (.6) Two-way shear is critical on a rectangular section located at d/ away from the face of the column as shown in Figure 5. a. Exterior column: The factored shear force (V u) in the critical section is computed as the reaction at the centroid of the critical section minus the self-weight and any superimposed surface dead and live load acting within the critical section (d/ away from column face) Vu kips The factored unbalanced moment used for shear transfer, M unb, is computed as the sum of the joint moments to the left and right. Moment of the vertical reaction with respect to the centroid of the critical section is also taken into account / M ( ) 37.8 kips-ft unb 1 For the exterior column in Figure 5, the location of the centroidal axis z-z is: moment of area of the sides about AB ( / ) cab 5.99 area of the sides The polar moment J c of the shear perimeter is: b d 3 db 3 J 1 1 b 1 b d 1 c b dc c 1 1 AB AB J c γ 1 γ ACI (Eq ) v f The length of the critical perimeter for the exterior column: bo ( / ) ( ) 59.5 The two-way shear stress (v u) can then be calculated as: V γ M c v u v unb u AB b d J o c ACI (R ) 5

29 ( ) 5.99 vu psi ' 4 v min 4, ', s ' c fc fc d f b c o ACI (Table.6.5.) vc min , , vc min 53, 79.5, 371 psi vc psi 53 psi Since v c v u b. Interior column: at the critical section, the slab has adequate two-way shear strength at this joint Vu kips M (0) 7.8 unb kips-ft For the interior column in Figure 5, the location of the centroidal axis z-z is: b 1.75 c 1 AB The polar moment J c of the shear perimeter is: b d 3 db 3 J 1 1 b 1 b d c b dc c AB AB J c γ 1 γ ACI (Eq ) v f The length of the critical perimeter for the interior column: bo ( ) ( ) 87 V γ M c v u v unb u AB b d J o c ACI (R ) vu 110. psi

30 ' 4 v min 4, ', s ' c fc fc d f b c o ACI (Table.6.5.) vc min , , vc min 53, 79.5, 93.7 psi vc psi 53 psi Since vc v at the critical section, the slab has adequate two-way shear strength at this joint. u c. Corner column: In this example, interior equivalent frame strip was selected where it only have exterior and interior supports (no corner supports are included in this strip). However, the two-way shear strength of corner supports usually governs. Thus, the two-way shear strength for the corner column in this example will be checked for educational purposes. Same procedure is used to find the reaction and factored unbalanced moment used for shear transfer at the centroid of the critical section for the corner support for the exterior equivalent frame strip Vu kips / M ( ) 19.3 kips-ft unb 1 For the corner column in Figure 5, the location of the centroidal axis z-z is: moment of area of the sides about AB ( / ) cab 4.7 area of the sides The polar moment J c of the shear perimeter is: b d 3 db 3 J 1 1 b 1 b d 1 c b dc c 1 1 AB AB J c γ 1 γ ACI (Eq ) v f Where: 1 f 1 ( / 3) b / 1 b ACI ( ) 7

31 f 1 ( / 3) /18.88 The length of the critical perimeter for the exterior column: b o ( / ) ( / ) The two-way shear stress (v u) can then be calculated as: V γ M c v u v unb u AB b d J o c ACI (R ) ( ) 4.7 vu psi ' 4 v min 4, ', s ' c fc fc d f b c o ACI (Table.6.5.) vc min , , vc min 53, 79.5, 319. psi = 53 psi vc psi Since vc v at the critical section, the slab has adequate two-way shear strength at this joint. u 5. Two-Way Slab Deflection Control (Serviceability Requirements) Since the slab thickness was selected based on the minimum slab thickness tables in ACI , the deflection calculations are not required. However, the calculations of immediate and time-dependent deflections are covered in this section for illustration and comparison with spslab model results Immediate (Instantaneous) Deflections The calculation of deflections for two-way slabs is challenging even if linear elastic behavior can be assumed. Elastic analysis for three service load levels (D, D + L sustained, D+L Full) is used to obtain immediate deflections of the two-way slab in this example. However, other procedures may be used if they result in predictions of deflection in reasonable agreement with the results of comprehensive tests. ACI (4..3) The effective moment of inertia (I e) is used to account for the cracking effect on the flexural stiffness of the slab. I e for uncracked section (M cr > M a) is equal to I g. When the section is cracked (M cr < M a), then the following equation should be used: 3 3 Mcr Mcr I I 1 I I Ma M a e g cr g ACI (Eq a) 8

32 Where: M a = Maximum moment in member due to service loads at stage deflection is calculated. The values of the maximum moments for the three service load levels are calculated from structural analysis as shown previously in this document. These moments are shown in Figure 1. M cr = cracking moment. Figure 1 Maximum Moments for the Three Service Load Levels M cr fi r g ft-kip y t f r = Modulus of rapture of concrete. ACI (Eq b) f r 7.5 f ' psi ACI (Eq ) c I g = Moment of inertia of the gross uncracked concrete section I g 3 lh h 7 yt 3.5 I cr = moment of inertia of the cracked section transformed to concrete. PCA Notes on ACI (9.5..) The calculations shown below are for the design strip (frame strip). The values of these parameters for column and middle strips are shown in Table 9. As calculated previously, the exterior span frame strip near the interior support is reinforced with 17 #4 bars located at 1.5 along the section from the top of the slab. Figure 13 shows all the parameters needed to calculate the moment of inertia of the cracked section transformed to concrete. 9

33 E cs = Modulus of elasticity of slab concrete. Figure 13 Cracked Transformed Section E w 33 f psi ACI ( a) cs c c Es n 7.56 PCA Notes on ACI (Table 10-) E cs b 141 B 6.54 na s 1 PCA Notes on ACI (Table 10-) db kd 1.18 PCA Notes on ACI (Table 10-) B 6.54 b( kd) I na d kd 3 3 cr s ( ) PCA Notes on ACI (Table 10-) I cr 141 (1.18) The effective moment of inertia procedure described in the Code is considered sufficiently accurate to estimate deflections. The effective moment of inertia, I e, was developed to provide a transition between the upper and lower bounds of I g and I cr as a function of the ratio M cr/m a. For conventionally reinforced (nonprestressed) members, the effective moment of inertia, Ie, shall be calculated by Eq. (4..3.5a) unless obtained by a more comprehensive analysis. Ie shall be permitted to be taken as the value obtained from Eq. (4..3.5a) at midspan for simple and continuous spans, and at the support for cantilevers. ACI (4..3.7) For continuous one-way slabs and beams. I e shall be permitted to be taken as the average of values obtained from Eq. (4..3.5a) for the critical positive and negative moment sections. ACI (4..3.6) For the exterior span (span with one end continuous) with service load level (D+LL full): 3 3 M M cr cr I I 1 I, since M cr 54.3 ft-kips < M a = ft-kips e M g M cr a a ACI (4..3.5a) - Where I e is the effective moment of inertia for the critical negative moment section (near the support). 30

34 I e I I M M e g 4 480, since cr 54.3 ft-kips > a =34.5 ft-kips Where I e + is the effective moment of inertia for the critical positive moment section (midspan). Since midspan stiffness (including the effect of cracking) has a dominant effect on deflections, midspan section is heavily represented in calculation of I e and this is considered satisfactory in approximate deflection calculations. The averaged effective moment of inertia (I e,avg) is given by: I e, avg 0.85 I 0.15 I for end span PCA Notes on ACI (9.5..4(1)) e I, e avg Where: I e I e e 4 = The effective moment of inertia for the critical negative moment section near the support. = The effective moment of inertia for the critical positive moment section (midspan). For the interior span (span with both ends continuous) with service load level (D+LL full): 3 3 M M cr cr I I 1 I, since M cr 54.3 ft-kips < M a = 58.7 ft-kips e M g M cr a a ACI (4..3.5a) I e I I M M e g 4 480, since cr 54.3 ft-kips > a = 5.34 ft-kips The averaged effective moment of inertia (I e,avg) is given by: e, avg e e, l e, r I 0.70 I 0.15 I I for interior span PCA Notes on ACI (9.5..4()) Ie, avg Where: 4 I el, = The effective moment of inertia for the critical negative moment section near the left support. I er, = The effective moment of inertia for the critical negative moment section near the right support. 31

35 Table 9 provides a summary of the required parameters and calculated values needed for deflections for exterior and interior equivalent frame. It also provides a summary of the same values for column strip and middle strip to facilitate calculation of panel deflection. Table 9 Averaged Effective Moment of Inertia Calculations Span Ext Int zone Left Ig, 4 Icr, 4 D Ma, ft-kip D + LLSus For Frame Strip D + Lfull Mcr, k-ft D Ie, 4 Ie,avg, 4 D + LLSus Right Left D + Lfull Midspan Mid Right D D + LLSus D + Lfull Deflections in two-way slab systems shall be calculated taking into account size and shape of the panel, conditions of support, and nature of restraints at the panel edges. For immediate deflections two-way slab systems the midpanel deflection is computed as the sum of deflection at midspan of the column strip or column line in one direction (Δ cx or Δ cy) and deflection at midspan of the middle strip in the orthogonal direction (Δ mx or Δ my). Figure 14 shows the deflection computation for a rectangular panel. The average Δ for panels that have different properties in the two direction is calculated as follows: ( ) ( ) cx my cy mx PCA Notes on ACI ( Eq. 8) Figure 14 Deflection Computation for a rectangular Panel 3

36 To calculate each term of the previous equation, the following procedure should be used. Figure 15 shows the procedure of calculating the term Δ cx. same procedure can be used to find the other terms. For exterior span - service dead load case: Figure 15 Δ cx calculation procedure 4 wl frame, fixed PCA Notes on ACI ( Eq. 10) 384EI Where: c frame, averaged frame, fixed = Deflection of column strip assuing fixed end condition. w ( / 1)(14) 1505 lb/ft E w 33 f psi ACI ( a) c c c I frame,averaged = The averaged effective moment of inertia (I e,avg) for the frame strip for service dead load case from Table 9 = (1505)(18) (1) frame, fixed ( )(480) I frame, averaged c, fixed LDFc frame, fixed PCA Notes on ACI ( Eq. 11) Icg, Where LDF c is the load distribution factor for the column strip. The load distribution factor for the column strip can be found from the following equation: 33

37 LDF LDF c LDF l LDF R And the load distribution factor for the middle strip can be found from the following equation: LDF m 1 LDF c For the end span, LDF for exterior negative region (LDF L ), interior negative region (LDF R ), and positive region (LDF + L ) are 1.00, 0.75, and 0.60, respectively (From Table 6 of this document). Thus, the load distribution factor for the column strip for the end span is given by: LDF c I c,g = The gross moment of inertia (I g) for the column strip for service dead load = c, fixed ( M ) net, L frame cl, PCA Notes on ACI ( Eq. 1) K Where: ec cl, = Rotation of the span left support. ( M ) 6.3 ft-kips = Net frame strip negative moment of the left support. net, L frame K ec = effective column stiffness = x lb (calculated previously) rad cl, 6 I l PCA Notes on ACI ( Eq. 14) g c, L c, L 8 I e frame Where: cl, = Midspan deflection due to rotation of left support. 34

38 I I g e frame = Gross-to-effective moment of inertia ratio for frame strip cl, ( M ) ( ) rad net, R frame cr, 6 Kec Where cr, = rotation of the span right support. ( M ) = Net frame strip negative moment of the right support. net, R frame I l g cr, cr, I e frame Where: cr, = Midspan delfection due to rotation of right support. cx fixed PCA Notes on ACI ( Eq. 9) cx, cx, R cx, L cx Following the same procedure, Δ mx can be calculated for the middle strip. This procedure is repeated for the equivalent frame in the orthogonal direction to obtain Δ cy, and Δ my for the end and middle spans for the other load levels (D+LL sus and D+LL full). Assuming square panel, Δ cx = Δ cy= and Δ mx = Δ my= The average Δ for the corner panel is calculated as follows: ( ) ( ) cx my cy mx cx my cy mx

39 Table 10 Immediate (Instantaneous) Deflections in the x-direction Column Strip Middle Strip Span LDF Δ frame-fixed, Δ c-fixed, θ c1, rad D θ c, rad Δθ c1, Δθ c, Δ cx, LDF Δ frame-fixed, Ext Int Δ m-fixed, θ m1, rad D θ m, rad Δθ m1, Δθ m, Δ mx, Span LDF Δ frame-fixed, Δ c-fixed, θ c1, rad D+LL sus θ c, rad Δθ c1, Δθ c, Δ cx, LDF Δ frame-fixed, Ext Int Δ m-fixed, θ m1, rad D+LL sus θ m, rad Δθ m1, Δθ m, Δ mx, Span LDF Δ frame-fixed, Δ c-fixed, θ c1, rad D+LL full θ c, rad Δθ c1, Δθ c, Δ cx, LDF Δ frame-fixed, Ext Int Δ m-fixed, θ m1, rad D+LL full θ m, rad Δθ m1, Δθ m, Δ mx, Span LDF LL Δ cx, Ext Int LDF LL Δ mx, 36

40 From the analysis in the transverse direction the deflection values below are obtained: For DL loading case: my cy For DL+LL sust loading case: my cy For DL+LL full loading case: my cy These values for the x-direction are shown in Table 10. Then, the total midpanel deflection is calculated by combining the contributions of the column and middle strip deflections from the X and Y directions: cx my cy mx PCA Notes on ACI ( Eq. 8) 5.. Time-Dependent (Long-Term) Deflections (Δlt) The additional time-dependent (long-term) deflection resulting from creep and shrinkage (Δ cs) may be estimated as follows: ( ) PCA Notes on ACI ( Eq. 4) cs sust Inst The total time-dependent (long-term) deflection is calculated as: ( ) ( ) (1 ) [( ) ( ) ] CSA A (N9.8..5) total lt sust Inst total Inst sust Inst Where: ( ) Immediate (instantaneous) deflection due to sustained load, sust Inst 1 50 ' ACI ( ) 37

41 ( ) Time-dependent (long-term) total delfection, total lt ( ) Total immediate (instantaneous) deflection, total Inst For the exterior span =, consider the sustained load duration to be 60 months or more. ACI (Table ) ' = 0, conservatively cs total lt Table 11 shows long-term deflections for the exterior and interior spans for the analysis in the x-direction, for column and middle strips. Table 11 - Long-Term Deflections Column Strip Span (Δ sust) Inst, in λδ Δ cs, in (Δ total) Inst, in (Δ total) lt, in Exterior Interior Middle Strip Exterior Interior Computer Program Solution spslab program utilizes the Equivalent Frame Method described and illustrated in details here for modeling, analysis and design of two-way concrete floor slab systems. spslab uses the exact geometry and boundary conditions provided as input to perform an elastic stiffness (matrix) analysis of the equivalent frame taking into account the torsional stiffness of the slabs framing into the column. It also takes into account the complications introduced by a large number of parameters such as vertical and torsional stiffness of transverse beams, the stiffening effect of drop panels, column capitals, and effective contribution of columns above and below the floor slab using the of equivalent column concept (ACI (R8.11.4)). spslab Program models the equivalent frame as a design strip. The design strip is, then, separated by spslab into column and middle strips. The program calculates the internal forces (Shear Force & Bending Moment), moment 38

42 and shear capacity vs. demand diagrams for column and middle strips, instantaneous and long-term deflection results, and required flexural reinforcement for column and middle strips. The graphical and text results are provided below for both input and output of the spslab model. 39

43 40

44 41

45 4

46 43

47 44

48 45

49 46

50 47

51 48

52 49

53 50

54 51

55 5

56 53

57 54

58 55

59 56

60 57

61 7. Summary and Comparison of Two-Way Slab Design Results Table 1 - Comparison of Moments obtained from Hand (EFM) and spslab Solution Hand (EFM) spslab Exterior Span Exterior Negative * Column Strip Positive Interior Negative * Exterior Negative * Middle Strip Positive Interior Negative * Interior Span Column Strip Interior Negative * Positive Middle Strip Interior Negative * Positive * negative moments are taken at the faces of supports Table 13 - Comparison of Reinforcement Results with Hand and spslab Solution Span Location Reinforcement Provided for Flexure Additional Reinforcement Provided for Unbalanced Moment Transfer* Total Reinforcement Provided Column Strip Middle Strip Column Strip Middle Strip Exterior Negative Hand spslab Hand spslab Hand spslab Exterior Span 7-#4 7-#4 3-#4 3-#4 10-#4 10-#4 Positive 6-#4 6-#4 n/a n/a 6-#4 6-#4 Interior Negative Exterior Negative 11-#4 11-# #4 11-#4 6-#4 6-#4 n/a n/a 6-#4 6-#4 Positive 6-#4 6-#4 n/a n/a 6-#4 6-#4 Interior Negative 6-#4 6-#4 n/a n/a 6-#4 6-#4 Interior Span Positive 6-#4 6-#4 n/a n/a 6-#4 6-#4 Positive 6-#4 6-#4 n/a n/a 6-#4 6-#4 *In the EFM, the unbalanced moment (M sc, M unb) at the support centerline is used to determine the value of the additional reinforcement as compared with DDM using the moments at the face of support. 58

62 Table 14 - Comparison of One-Way (Beam Action) Shear Check Results Using Hand and spslab Solution Span Vu, kips xu *, φvc, kips Hand spslab Hand spslab Hand spslab Exterior Interior * x u calculated from the centerline of the left column for each span Table 15 - Comparison of Two-Way (Punching) Shear Check Results Using Hand and spslab Solution b 1, b, b o, A c, V u, kips v u, psi Support Hand spslab Hand spslab Hand spslab Hand spslab Hand spslab Hand spslab Exterior Interior c AB, J c, 4 γ v M unb, kips-ft v u, psi φv c, psi Support Hand spslab Hand spslab Hand spslab Hand spslab Hand spslab Hand spslab Exterior Interior Table 16 - Comparison of Immediate Deflection Results Using Hand and spslab Solution () Column Strip Span D D+LLsus D+LLfull LL Hand spslab Hand spslab Hand spslab Hand spslab Exterior Interior Middle Strip Span D D+LLsus D+LLfull LL Hand spslab Hand spslab Hand spslab Hand spslab Exterior Interior Table 17 - Comparison of Time-Dependent Deflection Results Using Hand and spslab Solution Column Strip Span λδ Δcs, Δtotal, Hand spslab Hand spslab Hand spslab Exterior Interior Middle Strip Span λδ Δcs, Δtotal, Hand spslab Hand spslab Hand spslab Exterior Interior

Serviceability Deflection calculation

Serviceability Deflection calculation Chp-6:Lecture Goals Serviceability Deflection calculation Deflection example Structural Design Profession is concerned with: Limit States Philosophy: Strength Limit State (safety-fracture, fatigue, overturning

More information

Lecture-08 Gravity Load Analysis of RC Structures

Lecture-08 Gravity Load Analysis of RC Structures Lecture-08 Gravity Load Analysis of RC Structures By: Prof Dr. Qaisar Ali Civil Engineering Department UET Peshawar www.drqaisarali.com 1 Contents Analysis Approaches Point of Inflection Method Equivalent

More information

DEFLECTION CALCULATIONS (from Nilson and Nawy)

DEFLECTION CALCULATIONS (from Nilson and Nawy) DEFLECTION CALCULATIONS (from Nilson and Nawy) The deflection of a uniformly loaded flat plate, flat slab, or two-way slab supported by beams on column lines can be calculated by an equivalent method that

More information

Lecture 7 Two-Way Slabs

Lecture 7 Two-Way Slabs Lecture 7 Two-Way Slabs Two-way slabs have tension reinforcing spanning in BOTH directions, and may take the general form of one of the following: Types of Two-Way Slab Systems Lecture 7 Page 1 of 13 The

More information

Design of Reinforced Concrete Structures (II)

Design of Reinforced Concrete Structures (II) Design of Reinforced Concrete Structures (II) Discussion Eng. Mohammed R. Kuheil Review The thickness of one-way ribbed slabs After finding the value of total load (Dead and live loads), the elements are

More information

ε t increases from the compressioncontrolled Figure 9.15: Adjusted interaction diagram

ε t increases from the compressioncontrolled Figure 9.15: Adjusted interaction diagram CHAPTER NINE COLUMNS 4 b. The modified axial strength in compression is reduced to account for accidental eccentricity. The magnitude of axial force evaluated in step (a) is multiplied by 0.80 in case

More information

Two-Way Flat Slab (Concrete Floor with Drop Panels) System Analysis and Design

Two-Way Flat Slab (Concrete Floor with Drop Panels) System Analysis and Design Two-Way Flat Slab (Conrete Floor with Drop Panels) System Analysis and Design Two-Way Flat Slab (Conrete Floor with Drop Panels) System Analysis and Design Design the onrete floor slab system shown below

More information

Moment Redistribution

Moment Redistribution TIME SAVING DESIGN AID Page 1 of 23 A 3-span continuous beam has center-to-center span lengths of 30 ft-0 in. The beam is 20 in. by 28 in. and all columns are 20 in. by 20 in. In this example, the beam

More information

Case Study in Reinforced Concrete adapted from Simplified Design of Concrete Structures, James Ambrose, 7 th ed.

Case Study in Reinforced Concrete adapted from Simplified Design of Concrete Structures, James Ambrose, 7 th ed. ARCH 631 Note Set 11 S017abn Case Study in Reinforced Concrete adapted from Simplified Design of Concrete Structures, James Ambrose, 7 th ed. Building description The building is a three-story office building

More information

SERVICEABILITY OF BEAMS AND ONE-WAY SLABS

SERVICEABILITY OF BEAMS AND ONE-WAY SLABS CHAPTER REINFORCED CONCRETE Reinforced Concrete Design A Fundamental Approach - Fifth Edition Fifth Edition SERVICEABILITY OF BEAMS AND ONE-WAY SLABS A. J. Clark School of Engineering Department of Civil

More information

PUNCHING SHEAR CALCULATIONS 1 ACI 318; ADAPT-PT

PUNCHING SHEAR CALCULATIONS 1 ACI 318; ADAPT-PT Structural Concrete Software System TN191_PT7_punching_shear_aci_4 011505 PUNCHING SHEAR CALCULATIONS 1 ACI 318; ADAPT-PT 1. OVERVIEW Punching shear calculation applies to column-supported slabs, classified

More information

Lecture-04 Design of RC Members for Shear and Torsion

Lecture-04 Design of RC Members for Shear and Torsion Lecture-04 Design of RC Members for Shear and Torsion By: Prof. Dr. Qaisar Ali Civil Engineering Department UET Peshawar drqaisarali@uetpeshawar.edu.pk www.drqaisarali.com 1 Topics Addressed Design of

More information

Sway Column Example. PCA Notes on ACI 318

Sway Column Example. PCA Notes on ACI 318 Sway Column Example PCA Notes on ACI 318 ASDIP Concrete is available for purchase online at www.asdipsoft.com Example 11.2 Slenderness Effects for Columns in a Sway Frame Design columns C1 and C2 in the

More information

Lecture-05 Serviceability Requirements & Development of Reinforcement

Lecture-05 Serviceability Requirements & Development of Reinforcement Lecture-05 Serviceability Requirements & Development of Reinforcement By: Prof Dr. Qaisar Ali Civil Engineering Department UET Peshawar drqaisarali@uetpeshawar.edu.pk www.drqaisarali.com 1 Section 1: Deflections

More information

Dr. Hazim Dwairi. Example: Continuous beam deflection

Dr. Hazim Dwairi. Example: Continuous beam deflection Example: Continuous beam deflection Analyze the short-term and ultimate long-term deflections of end-span of multi-span beam shown below. Ignore comp steel Beam spacing = 3000 mm b eff = 9000/4 = 2250

More information

Flexure: Behavior and Nominal Strength of Beam Sections

Flexure: Behavior and Nominal Strength of Beam Sections 4 5000 4000 (increased d ) (increased f (increased A s or f y ) c or b) Flexure: Behavior and Nominal Strength of Beam Sections Moment (kip-in.) 3000 2000 1000 0 0 (basic) (A s 0.5A s ) 0.0005 0.001 0.0015

More information

3.5 Reinforced Concrete Section Properties

3.5 Reinforced Concrete Section Properties CHAPER 3: Reinforced Concrete Slabs and Beams 3.5 Reinforced Concrete Section Properties Description his application calculates gross section moment of inertia neglecting reinforcement, moment of inertia

More information

Chapter 2. Design for Shear. 2.1 Introduction. Neutral axis. Neutral axis. Fig. 4.1 Reinforced concrete beam in bending. By Richard W.

Chapter 2. Design for Shear. 2.1 Introduction. Neutral axis. Neutral axis. Fig. 4.1 Reinforced concrete beam in bending. By Richard W. Chapter 2 Design for Shear By Richard W. Furlong 2.1 Introduction Shear is the term assigned to forces that act perpendicular to the longitudinal axis of structural elements. Shear forces on beams are

More information

Design of a Multi-Storied RC Building

Design of a Multi-Storied RC Building Design of a Multi-Storied RC Building 16 14 14 3 C 1 B 1 C 2 B 2 C 3 B 3 C 4 13 B 15 (S 1 ) B 16 (S 2 ) B 17 (S 3 ) B 18 7 B 4 B 5 B 6 B 7 C 5 C 6 C 7 C 8 C 9 7 B 20 B 22 14 B 19 (S 4 ) C 10 C 11 B 23

More information

Sabah Shawkat Cabinet of Structural Engineering Walls carrying vertical loads should be designed as columns. Basically walls are designed in

Sabah Shawkat Cabinet of Structural Engineering Walls carrying vertical loads should be designed as columns. Basically walls are designed in Sabah Shawkat Cabinet of Structural Engineering 17 3.6 Shear walls Walls carrying vertical loads should be designed as columns. Basically walls are designed in the same manner as columns, but there are

More information

spslab v3.11. Licensed to: STRUCTUREPOINT, LLC. License ID: D2DE-2175C File: C:\Data\CSA A Kt Revised.slb

spslab v3.11. Licensed to: STRUCTUREPOINT, LLC. License ID: D2DE-2175C File: C:\Data\CSA A Kt Revised.slb X Z Y spslab v3.11. Licensed to: STRUCTUREPOINT, LLC. License ID: 00000-0000000-4-2D2DE-2175C File: C:\Data\CSA A23.3 - Kt Revised.slb Project: CSA A23.3 - Kt Torsional Stiffness Illustration Frame: Engineer:

More information

Slenderness Effects for Concrete Columns in Sway Frame - Moment Magnification Method (CSA A )

Slenderness Effects for Concrete Columns in Sway Frame - Moment Magnification Method (CSA A ) Slenderness Effects for Concrete Columns in Sway Frame - Moment Magnification Method (CSA A23.3-94) Slender Concrete Column Design in Sway Frame Buildings Evaluate slenderness effect for columns in a

More information

4.3 Moment Magnification

4.3 Moment Magnification CHAPTER 4: Reinforced Concrete Columns 4.3 Moment Magnification Description An ordinary or first order frame analysis does not include either the effects of the lateral sidesway deflections of the column

More information

Figure 1: Representative strip. = = 3.70 m. min. per unit length of the selected strip: Own weight of slab = = 0.

Figure 1: Representative strip. = = 3.70 m. min. per unit length of the selected strip: Own weight of slab = = 0. Example (8.1): Using the ACI Code approximate structural analysis, design for a warehouse, a continuous one-way solid slab supported on beams 4.0 m apart as shown in Figure 1. Assume that the beam webs

More information

Appendix J. Example of Proposed Changes

Appendix J. Example of Proposed Changes Appendix J Example of Proposed Changes J.1 Introduction The proposed changes are illustrated with reference to a 200-ft, single span, Washington DOT WF bridge girder with debonded strands and no skew.

More information

APPENDIX D SUMMARY OF EXISTING SIMPLIFIED METHODS

APPENDIX D SUMMARY OF EXISTING SIMPLIFIED METHODS APPENDIX D SUMMARY OF EXISTING SIMPLIFIED METHODS D-1 An extensive literature search revealed many methods for the calculation of live load distribution factors. This appendix will discuss, in detail,

More information

Two-Way Concrete Floor Slab with Beams Design and Detailing (CSA A )

Two-Way Concrete Floor Slab with Beams Design and Detailing (CSA A ) Two-Way Conrete Floor Slab with Beams Design and Detailing (CSA A.-14) Two-Way Conrete Floor Slab with Beams Design and Detailing (CSA A.-14) Design the slab system shown in Figure 1 for an intermediate

More information

This Technical Note describes how the program checks column capacity or designs reinforced concrete columns when the ACI code is selected.

This Technical Note describes how the program checks column capacity or designs reinforced concrete columns when the ACI code is selected. COMPUTERS AND STRUCTURES, INC., BERKELEY, CALIFORNIA DECEMBER 2001 CONCRETE FRAME DESIGN ACI-318-99 Technical Note This Technical Note describes how the program checks column capacity or designs reinforced

More information

Two Way Beam Supported Slab

Two Way Beam Supported Slab Two Way Beam Supported Slab Part 2 The following example was done by Mr. Naim Hassan, 3 rd Year 2 nd Semester Student of CE Dept., AUST 16 The following Example was done by Md. Mahmudun Nobe, ID -.01.03.078,

More information

SERVICEABILITY LIMIT STATE DESIGN

SERVICEABILITY LIMIT STATE DESIGN CHAPTER 11 SERVICEABILITY LIMIT STATE DESIGN Article 49. Cracking Limit State 49.1 General considerations In the case of verifications relating to Cracking Limit State, the effects of actions comprise

More information

DES140: Designing for Lateral-Torsional Stability in Wood Members

DES140: Designing for Lateral-Torsional Stability in Wood Members DES140: Designing for Lateral-Torsional Stability in Wood embers Welcome to the Lateral Torsional Stability ecourse. 1 Outline Lateral-Torsional Buckling Basic Concept Design ethod Examples In this ecourse,

More information

CHAPTER 5. T a = 0.03 (180) 0.75 = 1.47 sec 5.12 Steel moment frame. h n = = 260 ft. T a = (260) 0.80 = 2.39 sec. Question No.

CHAPTER 5. T a = 0.03 (180) 0.75 = 1.47 sec 5.12 Steel moment frame. h n = = 260 ft. T a = (260) 0.80 = 2.39 sec. Question No. CHAPTER 5 Question Brief Explanation No. 5.1 From Fig. IBC 1613.5(3) and (4) enlarged region 1 (ASCE 7 Fig. -3 and -4) S S = 1.5g, and S 1 = 0.6g. The g term is already factored in the equations, thus

More information

twenty one concrete construction: shear & deflection ARCHITECTURAL STRUCTURES: FORM, BEHAVIOR, AND DESIGN DR. ANNE NICHOLS SUMMER 2014 lecture

twenty one concrete construction: shear & deflection ARCHITECTURAL STRUCTURES: FORM, BEHAVIOR, AND DESIGN DR. ANNE NICHOLS SUMMER 2014 lecture ARCHITECTURAL STRUCTURES: FORM, BEHAVIOR, AND DESIGN DR. ANNE NICHOLS SUMMER 2014 lecture twenty one concrete construction: Copyright Kirk Martini shear & deflection Concrete Shear 1 Shear in Concrete

More information

Accordingly, the nominal section strength [resistance] for initiation of yielding is calculated by using Equation C-C3.1.

Accordingly, the nominal section strength [resistance] for initiation of yielding is calculated by using Equation C-C3.1. C3 Flexural Members C3.1 Bending The nominal flexural strength [moment resistance], Mn, shall be the smallest of the values calculated for the limit states of yielding, lateral-torsional buckling and distortional

More information

Appendix K Design Examples

Appendix K Design Examples Appendix K Design Examples Example 1 * Two-Span I-Girder Bridge Continuous for Live Loads AASHTO Type IV I girder Zero Skew (a) Bridge Deck The bridge deck reinforcement using A615 rebars is shown below.

More information

Annex - R C Design Formulae and Data

Annex - R C Design Formulae and Data The design formulae and data provided in this Annex are for education, training and assessment purposes only. They are based on the Hong Kong Code of Practice for Structural Use of Concrete 2013 (HKCP-2013).

More information

Design 1 Calculations

Design 1 Calculations Design 1 Calculations The following calculations are based on the method employed by Java Module A and are consistent with ACI318-99. The values in Fig. 1 below were taken from the Design 1 Example found

More information

Job No. Sheet No. Rev. CONSULTING Engineering Calculation Sheet. Member Design - Steel Composite Beam XX 22/09/2016

Job No. Sheet No. Rev. CONSULTING Engineering Calculation Sheet. Member Design - Steel Composite Beam XX 22/09/2016 CONSULTING Engineering Calculation Sheet jxxx 1 Member Design - Steel Composite Beam XX Introduction Chd. 1 Grade 50 more common than Grade 43 because composite beam stiffness often 3 to 4 times non composite

More information

Lecture-03 Design of Reinforced Concrete Members for Flexure and Axial Loads

Lecture-03 Design of Reinforced Concrete Members for Flexure and Axial Loads Lecture-03 Design of Reinforced Concrete Members for Flexure and Axial Loads By: Prof. Dr. Qaisar Ali Civil Engineering Department UET Peshawar drqaisarali@uetpeshawar.edu.pk www.drqaisarali.com Prof.

More information

Design of a Balanced-Cantilever Bridge

Design of a Balanced-Cantilever Bridge Design of a Balanced-Cantilever Bridge CL (Bridge is symmetric about CL) 0.8 L 0.2 L 0.6 L 0.2 L 0.8 L L = 80 ft Bridge Span = 2.6 L = 2.6 80 = 208 Bridge Width = 30 No. of girders = 6, Width of each girder

More information

Module 11 Design of Joints for Special Loading. Version 2 ME, IIT Kharagpur

Module 11 Design of Joints for Special Loading. Version 2 ME, IIT Kharagpur Module 11 Design of Joints for Special Loading Version ME, IIT Kharagpur Lesson Design of Eccentrically Loaded Welded Joints Version ME, IIT Kharagpur Instructional Objectives: At the end of this lesson,

More information

Lecture-09 Introduction to Earthquake Resistant Analysis & Design of RC Structures (Part I)

Lecture-09 Introduction to Earthquake Resistant Analysis & Design of RC Structures (Part I) Lecture-09 Introduction to Earthquake Resistant Analysis & Design of RC Structures (Part I) By: Prof Dr. Qaisar Ali Civil Engineering Department UET Peshawar www.drqaisarali.com 1 Topics Introduction Earthquake

More information

Karbala University College of Engineering Department of Civil Eng. Lecturer: Dr. Jawad T. Abodi

Karbala University College of Engineering Department of Civil Eng. Lecturer: Dr. Jawad T. Abodi Chapter 05 Structural Steel Design According to the AISC Manual 13 th Edition Analysis and Design of Beams By Dr. Jawad Talib Al-Nasrawi University of Karbala Department of Civil Engineering 71 Introduction

More information

Beam Design and Deflections

Beam Design and Deflections Beam Design and Deflections tation: a = name for width dimension A = name for area Areq d-adj = area required at allowable stress when shear is adjusted to include self weight Aweb = area of the web of

More information

Interaction Diagram Dumbbell Concrete Shear Wall Unsymmetrical Boundary Elements

Interaction Diagram Dumbbell Concrete Shear Wall Unsymmetrical Boundary Elements Interaction Diagram Dumbbell Concrete Shear Wall Unsymmetrical Boundary Elements Interaction Diagram - Dumbbell Concrete Shear Wall Unsymmetrical Boundary Elements Investigate the capacity for the irregular

More information

Chapter. Materials. 1.1 Notations Used in This Chapter

Chapter. Materials. 1.1 Notations Used in This Chapter Chapter 1 Materials 1.1 Notations Used in This Chapter A Area of concrete cross-section C s Constant depending on the type of curing C t Creep coefficient (C t = ε sp /ε i ) C u Ultimate creep coefficient

More information

PROPOSED SATSANG HALL TECHNICAL REPORT

PROPOSED SATSANG HALL TECHNICAL REPORT PROPOSED SATSANG HALL - VERTICAL STRIP V1 1 ------------------------------------------------------------------------------ ADAPT CORPORATION STRUCTURAL CONCRETE SOFTWARE SYSTEM 1733 Woodside Road, Suite

More information

Chapter 8: Bending and Shear Stresses in Beams

Chapter 8: Bending and Shear Stresses in Beams Chapter 8: Bending and Shear Stresses in Beams Introduction One of the earliest studies concerned with the strength and deflection of beams was conducted by Galileo Galilei. Galileo was the first to discuss

More information

Analytical Model for Estimating Long-Term Deflections of Two-Way Reinforced Concrete Slabs *

Analytical Model for Estimating Long-Term Deflections of Two-Way Reinforced Concrete Slabs * Analytical Model for Estimating Long-Term Deflections of Two-Way Reinforced Concrete Slabs * Dr. Bayan Salim Al-Nu'man Civil Engineering Department, College of Engineering Al-Mustansiriya University, Baghdad,

More information

Chapter (6) Geometric Design of Shallow Foundations

Chapter (6) Geometric Design of Shallow Foundations Chapter (6) Geometric Design of Shallow Foundations Introduction As we stated in Chapter 3, foundations are considered to be shallow if if [D (3 4)B]. Shallow foundations have several advantages: minimum

More information

1/29/2010 Page 2 of 65 1/29/2010 Page 3 of 65 1/29/2010 Page 4 of 65 Project Information 1/29/2010 Page 5 of 65 Muckleshoot Indian Tribe Project Number 09-118 West Detention Vault West Vault City of Auburn

More information

Beam Design - FLOOR JOIST

Beam Design - FLOOR JOIST Beam Design - FLOOR JOIST 1. Beam Data Load Type: Uniform Dist. Load Support: Simple Beam Beam Type: Sawn Lumber Species: Douglas Fir-Larch Grade: DF No.2 Size: 2 x 10 Design Span (L): 11.83 ft. Clear

More information

Design of Reinforced Concrete Beam for Shear

Design of Reinforced Concrete Beam for Shear Lecture 06 Design of Reinforced Concrete Beam for Shear By: Civil Engineering Department UET Peshawar drqaisarali@uetpeshawar.edu.pk Topics Addressed Shear Stresses in Rectangular Beams Diagonal Tension

More information

Roadway Grade = m, amsl HWM = Roadway grade dictates elevation of superstructure and not minimum free board requirement.

Roadway Grade = m, amsl HWM = Roadway grade dictates elevation of superstructure and not minimum free board requirement. Example on Design of Slab Bridge Design Data and Specifications Chapter 5 SUPERSTRUCTURES Superstructure consists of 10m slab, 36m box girder and 10m T-girder all simply supported. Only the design of Slab

More information

Chapter 7: Bending and Shear in Simple Beams

Chapter 7: Bending and Shear in Simple Beams Chapter 7: Bending and Shear in Simple Beams Introduction A beam is a long, slender structural member that resists loads that are generally applied transverse (perpendicular) to its longitudinal axis.

More information

A.2 AASHTO Type IV, LRFD Specifications

A.2 AASHTO Type IV, LRFD Specifications A.2 AASHTO Type IV, LRFD Specifications A.2.1 INTRODUCTION A.2.2 DESIGN PARAMETERS 1'-5.0" Detailed example showing sample calculations for design of typical Interior AASHTO Type IV prestressed concrete

More information

SPECIFIC VERIFICATION Chapter 5

SPECIFIC VERIFICATION Chapter 5 As = 736624/(0.5*413.69) = 3562 mm 2 (ADAPT 3569 mm 2, B29, C6) Data Block 27 - Compressive Stresses The initial compressive strength, f ci, is the strength entered in the Material/Concrete input screen.

More information

Where and are the factored end moments of the column and >.

Where and are the factored end moments of the column and >. 11 LIMITATION OF THE SLENDERNESS RATIO----( ) 1-Nonsway (braced) frames: The ACI Code, Section 6.2.5 recommends the following limitations between short and long columns in braced (nonsway) frames: 1. The

More information

Earthquake Loads According to IBC IBC Safety Concept

Earthquake Loads According to IBC IBC Safety Concept Earthquake Loads According to IBC 2003 The process of determining earthquake loads according to IBC 2003 Spectral Design Method can be broken down into the following basic steps: Determination of the maimum

More information

3.2 Reinforced Concrete Slabs Slabs are divided into suspended slabs. Suspended slabs may be divided into two groups:

3.2 Reinforced Concrete Slabs Slabs are divided into suspended slabs. Suspended slabs may be divided into two groups: Sabah Shawkat Cabinet of Structural Engineering 017 3. Reinforced Concrete Slabs Slabs are divided into suspended slabs. Suspended slabs may be divided into two groups: (1) slabs supported on edges of

More information

Part 1 is to be completed without notes, beam tables or a calculator. DO NOT turn Part 2 over until you have completed and turned in Part 1.

Part 1 is to be completed without notes, beam tables or a calculator. DO NOT turn Part 2 over until you have completed and turned in Part 1. NAME CM 3505 Fall 06 Test 2 Part 1 is to be completed without notes, beam tables or a calculator. Part 2 is to be completed after turning in Part 1. DO NOT turn Part 2 over until you have completed and

More information

Supplement: Statically Indeterminate Frames

Supplement: Statically Indeterminate Frames : Statically Indeterminate Frames Approximate Analysis - In this supplement, we consider another approximate method of solving statically indeterminate frames subjected to lateral loads known as the. Like

More information

3.4 Reinforced Concrete Beams - Size Selection

3.4 Reinforced Concrete Beams - Size Selection CHAPER 3: Reinforced Concrete Slabs and Beams 3.4 Reinforced Concrete Beams - Size Selection Description his application calculates the spacing for shear reinforcement of a concrete beam supporting a uniformly

More information

TABLE OF CONTANINET 1. Design criteria. 2. Lateral loads. 3. 3D finite element model (SAP2000, Ver.16). 4. Design of vertical elements (CSI, Ver.9).

TABLE OF CONTANINET 1. Design criteria. 2. Lateral loads. 3. 3D finite element model (SAP2000, Ver.16). 4. Design of vertical elements (CSI, Ver.9). TABLE OF CONTANINET 1. Design criteria. 2. Lateral loads. 2-1. Wind loads calculation 2-2. Seismic loads 3. 3D finite element model (SAP2000, Ver.16). 4. Design of vertical elements (CSI, Ver.9). 4-1.

More information

PEER/SSC Tall Building Design. Case study #2

PEER/SSC Tall Building Design. Case study #2 PEER/SSC Tall Building Design Case study #2 Typical Plan View at Ground Floor and Below Typical Plan View at 2 nd Floor and Above Code Design Code Design Shear Wall properties Shear wall thickness and

More information

Design of Beams (Unit - 8)

Design of Beams (Unit - 8) Design of Beams (Unit - 8) Contents Introduction Beam types Lateral stability of beams Factors affecting lateral stability Behaviour of simple and built - up beams in bending (Without vertical stiffeners)

More information

Example 1 - Single Headed Anchor in Tension Away from Edges BORRADOR. Calculations and Discussion

Example 1 - Single Headed Anchor in Tension Away from Edges BORRADOR. Calculations and Discussion Example 1 - Single Headed Anchor in Tension Away from Edges Check the capacity of a single anchor, 1 in. diameter, F1554 Grade 36 headed bolt with heavy-hex head installed in the top of a foundation without

More information

CHAPTER 4. Design of R C Beams

CHAPTER 4. Design of R C Beams CHAPTER 4 Design of R C Beams Learning Objectives Identify the data, formulae and procedures for design of R C beams Design simply-supported and continuous R C beams by integrating the following processes

More information

5. What is the moment of inertia about the x - x axis of the rectangular beam shown?

5. What is the moment of inertia about the x - x axis of the rectangular beam shown? 1 of 5 Continuing Education Course #274 What Every Engineer Should Know About Structures Part D - Bending Strength Of Materials NOTE: The following question was revised on 15 August 2018 1. The moment

More information

Seismic Pushover Analysis Using AASHTO Guide Specifications for LRFD Seismic Bridge Design

Seismic Pushover Analysis Using AASHTO Guide Specifications for LRFD Seismic Bridge Design Seismic Pushover Analysis Using AASHTO Guide Specifications for LRFD Seismic Bridge Design Elmer E. Marx, Alaska Department of Transportation and Public Facilities Michael Keever, California Department

More information

A q u a b l u e a t t h e G o l d e n M i l e

A q u a b l u e a t t h e G o l d e n M i l e A q u a b l u e a t t h e G o l d e n M i l e H a t o R e y, P u e r t o R i c o G e n e r a l B u i l d i n g I n f o r m a t i o n Building Facts: 7-story parking structure + luxury apartments 900,000

More information

Structural Calculations For:

Structural Calculations For: Structural Calculations For: Project: Address: Job No. Revision: Date: 1400 N. Vasco Rd. Livermore, CA 94551 D031014 Delta 1 - Plan Check May 8, 2015 Client: Ferreri & Blau MEMBER REPORT Roof, Typical

More information

ABS Consulting Project No

ABS Consulting Project No SUPPORTING STRUCTURE DESIGN FOR BLAST RESISTANT WINDOWS CHILD DEVELOPMENT CENTER MOODY AFB, GA ABS Consulting Project No. 898 PREPARED FOR: ATLANTIC ENGINEERING SERVICE 6 ARLINGTON EXPRESSWAY BLDG. B,

More information

9.5 Compression Members

9.5 Compression Members 9.5 Compression Members This section covers the following topics. Introduction Analysis Development of Interaction Diagram Effect of Prestressing Force 9.5.1 Introduction Prestressing is meaningful when

More information

MODULE C: COMPRESSION MEMBERS

MODULE C: COMPRESSION MEMBERS MODULE C: COMPRESSION MEMBERS This module of CIE 428 covers the following subjects Column theory Column design per AISC Effective length Torsional and flexural-torsional buckling Built-up members READING:

More information

Design of Reinforced Concrete Beam for Shear

Design of Reinforced Concrete Beam for Shear Lecture 06 Design of Reinforced Concrete Beam for Shear By: Prof Dr. Qaisar Ali Civil Engineering Department UET Peshawar drqaisarali@uetpeshawar.edu.pk 1 Topics Addressed Shear Stresses in Rectangular

More information

TORSION INCLUDING WARPING OF OPEN SECTIONS (I, C, Z, T AND L SHAPES)

TORSION INCLUDING WARPING OF OPEN SECTIONS (I, C, Z, T AND L SHAPES) Page1 TORSION INCLUDING WARPING OF OPEN SECTIONS (I, C, Z, T AND L SHAPES) Restrained warping for the torsion of thin-wall open sections is not included in most commonly used frame analysis programs. Almost

More information

SIMPLIFIED DESIGN OF REINFORCED CONCRETE SLABS AND BEAMS

SIMPLIFIED DESIGN OF REINFORCED CONCRETE SLABS AND BEAMS SIMPLIFIED DESIGN OF REINFORCED CONCRETE SLABS AND BEAMS MD. MAHMUDUN NOBE NASIMA SULTANA A.F.M. ASHIK RAHMAN DEPARTMENT OF CIVIL ENGINEERING AHSANULLAH UNIVERSITY OF SCIENCE AND TECHNLOLOGY JUNE 2016

More information

Beam Bending Stresses and Shear Stress

Beam Bending Stresses and Shear Stress Beam Bending Stresses and Shear Stress Notation: A = name or area Aweb = area o the web o a wide lange section b = width o a rectangle = total width o material at a horizontal section c = largest distance

More information

Beam Design - Awning

Beam Design - Awning Beam Design - Awning 1. Beam Data Load Type: Uniform Dist. Load Support: Simple Beam Beam Type: Sawn Lumber Species: Douglas Fir-Larch Grade: DF No.2 Size: 4 x 12 Design Span (L): 21.50 ft. Clear Span:

More information

Column Design. Columns Axial Load and Bending

Column Design. Columns Axial Load and Bending Column Design MORGAN STATE UNIVERSITY SCHOOL OF ARCHITECTURE AND PLANNING LECTURE VI Dr. Jason E. Charalambides = = Columns Axial Load and Bending We tend to have this image of columns that we envision

More information

CIVL 8/7117 Chapter 12 - Structural Dynamics 1/75. To discuss the dynamics of a single-degree-of freedom springmass

CIVL 8/7117 Chapter 12 - Structural Dynamics 1/75. To discuss the dynamics of a single-degree-of freedom springmass CIV 8/77 Chapter - /75 Introduction To discuss the dynamics of a single-degree-of freedom springmass system. To derive the finite element equations for the time-dependent stress analysis of the one-dimensional

More information

Chapter 8. Shear and Diagonal Tension

Chapter 8. Shear and Diagonal Tension Chapter 8. and Diagonal Tension 8.1. READING ASSIGNMENT Text Chapter 4; Sections 4.1-4.5 Code Chapter 11; Sections 11.1.1, 11.3, 11.5.1, 11.5.3, 11.5.4, 11.5.5.1, and 11.5.6 8.2. INTRODUCTION OF SHEAR

More information

research report Design Example for Analytical Modeling of a Curtainwall and Considering the Effects of Bridging (All-Steel Design Approach)

research report Design Example for Analytical Modeling of a Curtainwall and Considering the Effects of Bridging (All-Steel Design Approach) research report Design Example for Analytical Modeling of a Curtainwall and Considering the Effects of Bridging (All-Steel Design Approach) RESEARCH REPORT RP18- August 018 Committee on Specifications

More information

Problem 7.1 Determine the soil pressure distribution under the footing. Elevation. Plan. M 180 e 1.5 ft P 120. (a) B= L= 8 ft L e 1.5 ft 1.

Problem 7.1 Determine the soil pressure distribution under the footing. Elevation. Plan. M 180 e 1.5 ft P 120. (a) B= L= 8 ft L e 1.5 ft 1. Problem 7.1 Determine the soil pressure distribution under the footing. Elevation Plan M 180 e 1.5 ft P 10 (a) B= L= 8 ft L e 1.5 ft 1.33 ft 6 1 q q P 6 (P e) 180 6 (180) 4.9 kip/ft B L B L 8(8) 8 3 P

More information

Properties of Sections

Properties of Sections ARCH 314 Structures I Test Primer Questions Dr.-Ing. Peter von Buelow Properties of Sections 1. Select all that apply to the characteristics of the Center of Gravity: A) 1. The point about which the body

More information

CH. 5 TRUSSES BASIC PRINCIPLES TRUSS ANALYSIS. Typical depth-to-span ratios range from 1:10 to 1:20. First: determine loads in various members

CH. 5 TRUSSES BASIC PRINCIPLES TRUSS ANALYSIS. Typical depth-to-span ratios range from 1:10 to 1:20. First: determine loads in various members CH. 5 TRUSSES BASIC PRINCIPLES Typical depth-to-span ratios range from 1:10 to 1:20 - Flat trusses require less overall depth than pitched trusses Spans: 40-200 Spacing: 10 to 40 on center - Residential

More information

Design of Steel Structures Prof. Damodar Maity Department of Civil Engineering Indian Institute of Technology, Guwahati

Design of Steel Structures Prof. Damodar Maity Department of Civil Engineering Indian Institute of Technology, Guwahati Design of Steel Structures Prof. Damodar Maity Department of Civil Engineering Indian Institute of Technology, Guwahati Module 7 Gantry Girders and Plate Girders Lecture - 3 Introduction to Plate girders

More information

Chapter 6: Cross-Sectional Properties of Structural Members

Chapter 6: Cross-Sectional Properties of Structural Members Chapter 6: Cross-Sectional Properties of Structural Members Introduction Beam design requires the knowledge of the following. Material strengths (allowable stresses) Critical shear and moment values Cross

More information

CH. 4 BEAMS & COLUMNS

CH. 4 BEAMS & COLUMNS CH. 4 BEAMS & COLUMNS BEAMS Beams Basic theory of bending: internal resisting moment at any point in a beam must equal the bending moments produced by the external loads on the beam Rx = Cc + Tt - If the

More information

FIXED BEAMS IN BENDING

FIXED BEAMS IN BENDING FIXED BEAMS IN BENDING INTRODUCTION Fixed or built-in beams are commonly used in building construction because they possess high rigidity in comparison to simply supported beams. When a simply supported

More information

Beam Design - Pine Tree

Beam Design - Pine Tree - Pine Tree 1. Beam Data Load Type: Uniform Dist. Load Support: Simple Beam Beam Type: Sawn Lumber Species: Southern Pine Grade: SP DSS Size: 2 x 8 Design Span (L): 11.83 ft. Clear Span: 11.67 ft. Total

More information

Curved Steel I-girder Bridge LFD Guide Specifications (with 2003 Edition) C. C. Fu, Ph.D., P.E. The BEST Center University of Maryland October 2003

Curved Steel I-girder Bridge LFD Guide Specifications (with 2003 Edition) C. C. Fu, Ph.D., P.E. The BEST Center University of Maryland October 2003 Curved Steel I-girder Bridge LFD Guide Specifications (with 2003 Edition) C. C. Fu, Ph.D., P.E. The BEST Center University of Maryland October 2003 Guide Specifications (1993-2002) 2.3 LOADS 2.4 LOAD COMBINATIONS

More information

Beam Design - Shed Roof Back Wall Beam-S

Beam Design - Shed Roof Back Wall Beam-S Beam Design - Shed Roof Back Wall Beam-S 1. Beam Data Load Type: Uniform Dist. Load Support: Simple Beam Beam Type: Glulam Species: Western Species Grade: 24F-V4 1.8E DF/DF Size: 2.5 x 6 Design Span (L):

More information

Karbala University College of Engineering Department of Civil Eng. Lecturer: Dr. Jawad T. Abodi

Karbala University College of Engineering Department of Civil Eng. Lecturer: Dr. Jawad T. Abodi Chapter 04 Structural Steel Design According to the AISC Manual 13 th Edition Analysis and Design of Compression Members By Dr. Jawad Talib Al-Nasrawi University of Karbala Department of Civil Engineering

More information

ORIGIN 0. PTC_CE_BSD_7.2_us_mp.mcdx. Mathcad Enabled Content Copyright 2011 Knovel Corp.

ORIGIN 0. PTC_CE_BSD_7.2_us_mp.mcdx. Mathcad Enabled Content Copyright 2011 Knovel Corp. PC_CE_BSD_7._us_mp.mcdx Copyright 011 Knovel Corp. Building Structural Design homas P. Magner, P.E. 011 Parametric echnology Corp. Chapter 7: Reinforced Concrete Column and Wall Footings 7. Pile Footings

More information

RESILIENT INFRASTRUCTURE June 1 4, 2016

RESILIENT INFRASTRUCTURE June 1 4, 2016 RESILIENT INFRASTRUCTURE June 1 4, 2016 INSTANTANEOUS DEFLECTIONS OF CONCRETE SLABS COMPUTED USING DISCRETIZED ANALYSIS Caitlin Mancuso Western University, Canada F. Michael Bartlett Western University,

More information

999 TOWN & COUNTRY ROAD ORANGE, CALIFORNIA TITLE PUSHOVER ANALYSIS EXAMPLE BY R. MATTHEWS DATE 5/21/01

999 TOWN & COUNTRY ROAD ORANGE, CALIFORNIA TITLE PUSHOVER ANALYSIS EXAMPLE BY R. MATTHEWS DATE 5/21/01 DESCRIPTION Nonlinear static (pushover) analysis will be performed on a railroad bridge bent using several methods to determine its ultimate lateral deflection capability. 1. SAP2000 Nonlinear with axial-moment

More information

CHAPTER 4. ANALYSIS AND DESIGN OF COLUMNS

CHAPTER 4. ANALYSIS AND DESIGN OF COLUMNS 4.1. INTRODUCTION CHAPTER 4. ANALYSIS AND DESIGN OF COLUMNS A column is a vertical structural member transmitting axial compression loads with or without moments. The cross sectional dimensions of a column

More information

STRUCTURAL ANALYSIS CHAPTER 2. Introduction

STRUCTURAL ANALYSIS CHAPTER 2. Introduction CHAPTER 2 STRUCTURAL ANALYSIS Introduction The primary purpose of structural analysis is to establish the distribution of internal forces and moments over the whole part of a structure and to identify

More information