1 Mitglied der Short-Circuit-Testing Liaison (STL) Test Report Report-No.: 9725Fr Copy-No.: 00 Contents: 16Sheets Equipment under Test: Manufacturer: Client: Metal-enclosed, single-pole metal-clad and SF 6 -insulated medium voltage switchgear 8DA10 (36kV; 2500A; 40kA/3s), circuit-breaker panel with circuit-breaker 3AH Siemens AG, EV MS Siemens AG, EV MS1 G Testing Station: PEHLA Prüffeld Frankfurt / M. Date of Test: Applied Test Specifications: IEC 298, , clause 6 IEC 694, , clause 6 VDE 0670 Teil 6, , Abschnitt 6 VDE 0670 Teil 1000, , Abschnitt 6 (Entwurf) Tests performed: 1. Temperature-rise test of the circuit-breaker panel with the rated normal current of 2500A. 2. Measurement of the resistance of the main circuits. Test Results: The above mentioned equipment under test has passed the temperature-rise test with the rated normal current of 2500A corresponding to the applied test specifications. GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN Technical Committee Mannheim, The test results relate only to the items tested. Without a written permission of PEHLA it is not allowed to make reproduction in extracts of this document. Copying the cover sheet accompanied by sheet 2 and the sheets mentioned here is an exception. DAT-P-013/92-51e
2 Report-No.: 9725Fr Sheet: 2 Accreditation The PEHLA-Testing station Frankfurt/Main has been approved by the DATech (German accreditation body for technology) according to DIN EN for tests in the field of high-voltage switchgear and controlgear (Registration-No. DAT-P-013/92-51e). Under reference to DIN EN PEHLA states the following: - The accreditation of the PEHLA-Testing station or any of its test reports by themselves in no way constitute or imply product approval by DATech or any other body. - If someone refers to a test in an accredited PEHLA-Testing station this reference shall include the accreditation body, i.e. DATech, the relevant scope of the accreditation and the appropriate registration number. PEHLA-Documents A Test Certificate is issued for type tests which have successfully been carried out in full compliance with the relevant specifications or standards and STL Guides valid at the time of the test. For these tests the equipment under test must be clearly identified by technical description, drawings and additional specifications. A Test Document is issued for parts of type tests which have successfully been carried out in full compliance with the relevant specifications or standards and STL Guides valid at the time of test. For these tests the equipment under test must be clearly identified by technical description, drawings and additional specifications. A Test Report is issued for all other tests which have been carried out according to specifications, standards or "PEHLA- Richtlinien" (PEHLA Guides) and/or clients instructions. Similarly, this test report contains all test results, details of the conditions under which the tests were carried out, also details relating to the behaviour of the equipment during test, and its condition after the tests. Addresses: Office: Testing Station: Manufacturer: Client: PEHLA-Geschäftsstelle Hallenweg 40 D Mannheim PEHLA-Prüffeld Frankfurt/M. Karl - Benz - Str. 22 Siemens AG Power Transmission and Distribution, Medium-Voltage Switchgear and -systems (EV MS) Karl - Benz - Str. 22 D Frankfurt/M. D Frankfurt/M. Siemens AG Power Transmission and Distribution, Medium-Voltage Switchgear and -systems (EV MS) EV MS1 G Karl - Benz - Str. 22 D Frankfurt/M.
3 Report-No.: 9725Fr Sheet: 3 Table of Contents FRONT SHEET 1 ACCREDITATION 2 TABLE OF CONTENTS 3 PARTICIPANTS OF THE TEST 4 TECHNICAL DATA OF THE EQUIPMENT UNDER TEST 5 TECHNICAL DATA OF THE EQUIPMENT UNDER TEST 6 DRAWING OF THE EQUIPMENT UNDER TEST 7 DRAWING OF THE EQUIPMENT UNDER TEST 8 DRAWING-NO. 9 TEST ARRANGEMENT AND POSITION OF THE MEASURING POINTS 10 MEASUREMENT OF THE RESISTANCE OF THE MAIN CIRCUITS 11 TEMPERATURE-RISE TEST, MEASURANDS 12 TEMPERATURE-RISE TEST, MEASURANDS 13 TEMPERATURE-RISE TEST, DIAGRAM 14 PHOTOS 15 PHOTOS 16
4 Report-No.: 9725Fr Sheet: 4 Participants of the Test Representatives of Test Committee: Mr. Schuck Mr. Weinel PEHLA-Prüffeld Frankfurt/M. PEHLA-Prüffeld Mannheim-Rheinau Test Engineer: Mr. Mayer PEHLA-Prüffeld Frankfurt/M. (guidance and performance of the test) Client: Mr. R. Müller Siemens AG, EV MS1 G PG1 Other Participants: Mr. Wolff Mr. Bär Siemens AG, EV MS1 G PG1 Siemens AG, EV MS TVF
5 Report-No.: 9725Fr Sheet: 5 Technical Data of the Equipment under Test Switchgear Instructions of the manufacturer Equipment under Test: Metal-enclosed, single-pole metal-clad and SF 6 -insulated medium-voltage switchgear Type: 8DA10 Manufacturer: Siemens AG, EV MS Serial-No.: Year of manufacture: 1997 Drawing-No.: , Änd.-Z. 00, Bl. 1- of and , Änd.-Z. 05, Bl. 1+ of The drawings and parts list used for the identification of the equipment under test were stamped and signed by the representatives of the PEHLA-Technical Committee. They are kept to the test documents in the test laboratory. The manufacturer has confirmed with his signature that the equipment under test corresponds to the applied drawings and parts list. (continued on sheet No. 9) Rated voltage Rated lightning impulse withstand voltage Rated switching impulse withstand voltage Rated power frequency withstand voltage Rated frequency Rated normal current Rated peak withstand current Rated short-time withstand current Rated duration of short circuit 36 kv 170 kv - kv 70 kv 50/60 Hz 2500 A 100 ka 40 ka 3 s Insulating agent SF 6 Rated filling gauge pressure (20 C) of the circuit-breaker compartment 0,10 MPa Minimum functional gauge pressure (20 C) of the circuit-breaker compartment 0,08 MPa Rated filling gauge pressure (20 C) of the busbar compartment 0,05 MPa Minimum functional gauge pressure (20 C) of the busbar compartment 0,03 MPa Permitted values under internal arc conditions Peak current Short-circuit alternating current Duration of short circuit - ka - ka - s Essential characteristics and installed devices: (continued on sheet No. 6)
6 Report-No.: 9725Fr Sheet: 6 Technical Data of the Equipment under Test Switchgear Instructions of the manufacturer Essential characteristics and installed devices: (continued from sheet No. 5) 1. Test arrangement (see photo No. 1 and No. 2) Panel-No. Panel type 7 Circuit breaker panel (36kV;1250A; 40kA/3s) 10 Circuit breaker panel (36kV; 1250A; 40kA/3s) 11 Circuit breaker panel (36kV; 2500A; 40kA/3s) 2. Circuit-breaker: Type 3AH / Year of manufacture 1997 Panel-No. Serial-No. of the Type of the Serial-No. of the vacuum tube circuit-breaker module vacuum tube L1 L2 L3 7 S VS / D S VS / D S VS / D Current transformers Panel-No. Type of the Transformation Serial-No. of the current transformers current transformers ratio L1 L2 L3 7 4MC4543 XD 2500A / 5A 97/ / / A / 5A 10 4MC4542 XD 2500A / 5A 97/ / / MC4543 XD 2500A / 5A 3000A / 5A 97/ / / With the transformation ratio 2500A / 5A the current transformers of the panel No. 11 were used for verification of the test current in panel No. 11 (2500A). 4. The temperature-rise test was performed at the minimum functional gauge pressure of the switchgear (0,08MPa at 20 C in the circuit-breaker compartment and 0,03MPa at 20 C in the busbar compartment). 5. Varnished were the aluminium chambers of the panel No. 11 (see photo No. 1 and No. 2). 6. Black varnished were the following parts or zones of the current path in panel No. 11: - the cooling sheet at the upper connection of the vacuum tube - the cooling sheets in the intermediate chamber and - the outer surfaces of the external copper bars in the intermediate chamber. Date of receipt of the equipment under test :
7 Report-No.: 9725Fr Sheet: 7 Drawing of the Equipment under Test
8 Report-No.: 9725Fr Sheet: 8 Drawing of the Equipment under Test
9 Report-No.: 9725Fr Sheet: 9 Drawing-No. Position-No. Number of drawing or part list Quantity Description / Gehäuse L= / Ring / Ring Querkupplung / Deckel / Tragblech / Gießharzstützer / Deckel / Schiene, Cu 80mm x 10mm / Schiene, Cu 80mm x 10mm / Schiene komplett, Cu 80mm x 10mm / Kühlblech, Cu / Kühlblech, Cu / Kühlblech, Cu / SS-Gehäuse L= / Durchführung / Deckel / Erdungsbrücke / Lasche, Cu 80mm x 10mm / Lasche, Cu 80mm x 10mm / Schiene, Cu 80mm x 10mm / Lasche, Cu 80mm x 10mm / Lasche, Cu 80mm x 10mm / Schienenträger / Gegenkontakt / Anschlußbolzen / Anschluß / Schiene, Cu 80mm x 10mm / Schiene, Cu 80mm x 10mm / Schiene, Cu 80mm x 10mm 1) 2) 1) 3) 3) 3) 1) 2) 3) silver-coated and black varnished silver-coated black varnished
10 Report-No.: 9725Fr Sheet: 10 Test Arrangement and Position of the Measuring Points Panel- No. 1250A 1250A 2500A Test current, three-phase 2 x size 1/phase 2 x size 1/phase 3 x size 1/phase Plug-in connectors from Pfisterer Terminal Cu cables, 2x(3x95mm 2 )/phase Cu cables, 2x(3x95mm 2 )/phase Cu bars, 3x60mmx10mm/phase - - Cu bars, 2x80mmx10mm Cross section (see photo of terminals no. 3) Short circuiting link (see photo no. 4)
11 Report-No.: 9725Fr Sheet: 11 Measurement of the Resistance of the Main Circuits 1. Before the temperature-rise test Measuring section between the measuring points Resistance of the main circuits µω (see sheet 10) L1 L2 L , , , , , , , , , , , ,90 9,30 11, ,60-2. After the temperature-rise test Measuring section between the measuring points Resistance of the main circuits µω (see sheet 10) L1 L2 L , , , , , , , , , , , ,90 9,80 11, ,50 - Remarks: Resistance measurement at a direct current of: 100 A
12 Report-No.: 9725Fr Sheet: 12 Temperature-rise Test, Measurands Date of test: Duration of test: 18,5 h Ambient air temperature: 24,5 C Test current: 2500 A Test frequency: 50 Hz Measuring point (see sheet 10) Description of the measuring point Nature of the measuring point Connection, Final temperature C Final temperature rise K Permissible temperature rise K 1 L2 Main busbar bolted or equivalent, 73,0 48,5 75,0 Main busbar Cu silver-coated in SF 6 Metal part in contact 2 L2 at cast resin with insulation 74,0 49,5 65,0 bushing Busbar at material class A Metal part in contact 3 L2 cast resin post with insulation 78,0 53,5 65,0 insulator material class A 4 L2 Fixed contact of Contact, 80,5 56,0 65,0 the isolator Cu silver-coated in SF 6 Fixed contact of Contact, 5 L2 the isolator at cast Cu silver-coated in SF 6 86,5 62,0 65,0 resin bushing Copper bar at Metal part in contact 6 L2 cast resin with insulation 84,0 59,5 65,0 bushing Copper bar at material class A Metal part in contact 7 L2 cast resin post with insulation 86,0 61,5 65,0 insulator Bolted joint between material class A Connection, 8 L2 copper bar and bolted or equivalent, 90,0 65,5 75,0 flexible connector Cu silver-coated in SF 6 Bolted joint between Connection, 9 L2 flexible connector and bolted or equivalent, 97,5 73,0 75,0 vacuum tube Cu silver-coated in SF 6 Lower bolted joint Connection, 10 L2 at the bolted or equivalent, 98,5 74,0 75,0 vacuum tube Cu silver-coated in SF 6 Remarks: The permissible temperature rises are valid for an ambient air temperature of 40 C. The stagnation was reached after 9,0 hours.
13 Report-No.: 9725Fr Sheet: 13 Temperature-rise Test, Measurands Date of test: Duration of test: 18,5 h Ambient air temperature: 24,5 C Test current: 2500 A Test frequency: 50 Hz Measuring point (see sheet 10) Description of the measuring point Nature of the measuring point Connection, Final temperature C Final temperature rise K Permissible temperature rise K 11 L2 Connector bolted or equivalent, 97,0 72,5 75,0 Threaded bush in Cu silver-coated in SF 6 Metal part in contact 12 L2 the cast resin with insulation 80,5 56,0 65,0 support ring material class A L1 Copper bar Terminal, bolted, 63,5 39,0 13 L2 at terminal Cu silver-coated in air 64,0 39,5 65,0 L3 63,5 39,0 L1 Copper bar, 58,5 34,0 14 L2 1m distance to - 61,0 36,5 - L3 measuring point 13 58,5 34,0 Remarks: The permissible temperature rises are valid for an ambient air temperature of 40 C. The stagnation was reached after 9,0 hours.
14 Report-No.: 9725Fr Sheet: 14 Temperature-rise Test, Diagram
15 Report-No.: 9725Fr Sheet: 15 Photos
16 Report-No.: 9725Fr Sheet: 16 Photos
Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION. on the given range of performed tests
Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION on the given range of performed tests 3M Laboratories Europe Zweigniederlassung der 3M Deutschland GmbH Carl-Schurz-Str.
More informationSWITCHGEAR: design concepts, testing, standards and safety of persons and installations
MEDIUM AND LOW VOLTAGE Part 1 SWITCHGEAR: design concepts, testing, standards and safety of persons and installations Presented by: Sergio Feitoza Costa COGNITOR Consultancy, R&D & training Ltd www.cognitor.com.br
More informationIndependent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION. on the given range of performed tests
Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION on the given range of performed tests 3M Laboratories Europe Zweigniederlassung der 3M Deutschland GmbH Carl-Schurz-Str.
More informationThermal-Magnetic Circuit Breaker 2210-S2..
Thermal-Magnetic Circuit Breaker -S.. Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed for
More informationThermal-Magnetic Circuit Breaker 2210-S2..
Thermal-Magnetic Circuit Breaker -S.. Description One, two and three pole thermal-magnetic circuit breakers with trip-free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed for
More informationThermal-Magnetic Circuit Breaker 2210-S2..
Thermal-Magnetic Circuit Breaker -S.. Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 6094/IEC 94). Designed for
More informationThermal-Magnetic Circuit Breaker 2210-S2...
Thermal-Magnetic Circuit Breaker 0-S... Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed
More informationThermal-Magnetic Circuit Breaker 2210-S2...
Description One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 6094/IEC 94). Designed for panel or plug-in mounting. Available
More informationDATA RACK BUSBAR. Data Rack Busbar Systems A.
Data Rack Busbar Systems 250...1000 A www.eae.com.tr Overview Overview To power the mission critical IT infrastructures on the Data Rack Cabinets, EAE offers a highly flexible and reliable Busbar System
More informationThermal-Magnetic Circuit Breaker 2210-T2...
Thermal-Magnetic Circuit Breaker 0-T... Description One, two and three pole thermal-magnetic circuit breakers with trip-free mechanism and toggle actuation (S-type TM CBE to EN 6094/IEC 94). Featuring
More informationSPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM
INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION January 2017 SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM I. SCOPE This
More informationTHE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE
July 04 THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE In this third part. we want to speak about how important is the correct sizing of the
More informationVX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity
VX Enclosure System Technical documentation PE conductor connection, current carrying capacity Enclosure system VX Contents Contents. General remarks. Introduction. Notes on the design of the earthing
More informationTEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD.
Page 2 of 29 TEST CERTIFICATES OR REPORTS ISSUED BY LTD. Type Test Certificate of Complete Type Test This certificate provides the verification of all the rated characteristics of the equipment as assigned
More informationVEIKI-VNL ELECTRIC LARGE LABORATORIES Ltd. TYPE TEST REPORT
Page 1 of 13 TYPE TEST REPORT Test object: Designation: All Aluminium Alloy Conductor (AAAC) 50 mm 2 All Aluminium Alloy Conductor (Code: 49-AL3) Manufacturer: BMET Energy Telecom Industry and Trade LLC.
More information5SJ4...-.HG Circuit Breakers to IEC and UL 489
Siemens AG 009 5SJ...-.HG Circuit Breakers to IEC and UL 89 BETA Low-Voltage Circuit Protection Compliance with industry standards is a must in today's manufacturing environment. Worldwide acceptance is
More informationVarius SUMMARY OF MODELS OF HRC FUSE-LINKS
SUMMARY OF MODELS OF HRC FUSE-LINKS Type PNA000 PHNA000 PNA00 PHNA00 Rated current I n up to A up to 0 A up to A up to 0 A Rated voltage U n AC 00 V, 00 V 90 V 00 V 90 V DC 0 V 0 V 0 V 0 V Fuse-link size
More informationF F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions
FAULT CURRENT F F13-13 FAULT CURRENT - Contents 1. Introduction 2. Types of fault conditions 3 fault current must be determined 3.1 Purposes for which of prospective fault current magnitudes are used 3.2
More informationMagnetic and Hydraulic-Magnetic Circuit Breaker 8340-T...
Magnetic and Hydraulic-Magnetic Circuit Breaker 830-T... Description ngle, two and three pole magnetic and hydraulic-magnetic circuit breakers with trip-free mechanism and toggle actuation. A choice of
More informationMCB NB1-63H Miniature Circuit Breaker
NB-H Miniature Circuit Breaker. General. Function protection of circuits against short-circuit currents, protection of circuits against overload currents, switch, isolation, NB-H circuit-breakers are used
More informationMKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits
MKV AC Capacitors B 25 835 High dielectric strength High peak-current capability Especially suitable for snubber circuits Construction Self-healing Plastic dielectric Oil-impregnated tubular windings (no
More informationInternal Components Forms of Separation
IEC 60439-1 One or more of the following conditions can be attained by dividing ASSEMBLIES by means of partitions or barriers (metallic or non-metallic) into separate compartments or enclosed protected
More informationELINEMK Technical Characteristics Rated Current Busbar Code Standards Rated Isolation Voltage Max. Rated Operational Voltage Rated Frequency Pollution Degree Protection Degree External Mechanical Impacts
More informationBETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008
LV HRC fuse links Overview LV HRC fuses are used for installation systems in non-residential, commercial and industrial buildings as well as in switchboards of power supply companies. They therefore protect
More informationIssued August DATA SHEET. 3VT3 MCCB up to 630 A
ssued August 9 DATA SHEET VT MCCB up to 6 A Based on Siemens Catalog V 6 8 Circuit breakers Switch disconnectors Technical specifications Specifications Type VT 76-AA6/6/56-AA, VT 76-AA6/6/56-AA Circuit
More informationA Novel Optimized Design for Busbar Structures using Finite Element Methods
A Novel Optimized Design for Busbar Structures using Finite Element Methods Xiaojuan Sun 1, Shuhong Wang, Ruilei Gong,3 1 School of Electronic Information Engeering,Xi an Technological University Xi an,71001,china
More information5SP and 5SY Supplementary Protection UL 1077
Product Guide 5SP and 5SY Supplementary Protection UL 077 for North merican and International applications usa.siemens.com/5sy Table of contents Certifications, standards, features and description Characteristic
More informationFAZ tripping characteristics at 30 C: B, C, D to IEC/EN FAZ tripping characteristics at 30 C: R to IEC/EN
FAZ, AZ High-Capacity Tripping Characteristics Moeller HPL011-001/00 1/07 FAZ tripping characteristics at 0 C: B, C, D to IEC/EN 0 9 FAZ tripping characteristics at 0 C: R to IEC/EN 0 97 t [s] 700 00 100
More information3VT4 Molded Case Circuit Breakers up to 1000 A
VT4 Molded Case Circuit Breakers up to 00 A Catalog Technical nformation VT4 Molded Case Circuit Breakers up to 00 A General data / - Overview Circuit breakers Switch disconnectors / - Selection and ordering
More informationSIRCOVER Manual transfer switches from 125 to 3200 A
Manual transfer switches svr_149_a 3200 A Function are manual multipolar transfer switches with positive break indication. The family includes two ranges: AC for dead time switching (I-0-II), for overlapping
More informationMR medium rating busbar
technical information General features MR is fully compliant with S EN 0-, specifically, the rated current of the Zucchini busbar trunking systems is always rated at the average ambient temperature of
More informationIssued August DATA SHEET. 3VT5 MCCB up to 1600 A
ssued August 9 DATA SHEET VT5 MCCB up to 0 A Based on Siemens Catalog V 8 Standard circuit breakers Releases Technical specifications Specifications VT5 circuit breakers Switch disconnectors Type Standards
More informationAmphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH
Amphenol C 091 A/B/D Circular Connectors Amphenol-Tuchel Electronics GmbH General information These connectors are designed and produced in conformity with the low-voltage directive (/3/EWG) respectively
More informationEA Guidelines on the Calibration of Temperature Indicators and Simulators by Electrical Simulation and Measurement
Publication Reference EA-10/11 EA Guidelines on the Calibration of Temperature Indicators and Simulators by Electrical PURPOSE This document has been produced by EA as a means of giving advice for calibrating
More informationPage 2 of 14 Report Ref. No
age 2 of 14 Summary of testing: Tests performed (name of test and test clause): Clause 6.1, Initial measurements: - MST 01: Visual inspection - 10.2: Maximum power determination - MST 16: Dielectric withstand
More informationNYY-J/-o 34 NYCWY 36 NYCY 37 NAYY 38
NYY-J/-o 34 NYCWY 36 NYCY 37 NAYY 38 NYY-J/-O Energy and control cable acc. to DIN VDE 0276 and HD 603 Application Indoor and outdoor installation, laying in ducts and underground, for power stations,
More informationPressure transmitters for industrial applications MBS 32 and MBS 33
Data sheet Pressure transmitters for industrial applications MBS 32 and MBS 33 The standard pressure transmitters MBS 32 and MBS 33 are designed for use in almost all industrial applications, and offer
More informationWIESON TECHNOLOGIES CO., LTD.
TABLE OF CONTENT 1. Scope.... 2 2. Reference Documents. 2 3. Material and Components.... 2 4. Design and Construction.... 2 5. Rating.. 2 6. Performance and Test Descriptions. 2 7. Test Requirements and
More informationSiemens AG Miniature Circuit Breakers. Totally Integrated Power SENTRON. Configuration. Edition 10/2014. Manual. siemens.
Siemens AG 05 Totally Integrated Power SENTRON Configuration Manual Edition 0/0 siemens.com/lowvoltage Siemens AG 05 Siemens AG 05 Introduction 5SL miniature circuit breakers 5SY and 5SP miniature circuit
More informationINSULATORS INSULATORS
INSULATORS INSULATORS INSULATORS CONTENTS > INDOOR INSULATORS 0 /02 Post Insulators 03 /04/0 Capacitive Divider Insulators 0 Wall Bushings /07 08 Bolt Bushings /0 GENERAL INFORMATION ON INSULATORS Rated
More informationSealing possibility Electrical endurance (ops) Mechanical endurance (ops) Overvoltage category Standards
Miniature circuit breaker ETIMAT 7,7 0.5 Rated voltage Rated current Rated frequency Rated short-circuit capacity Energy limiting class characteristic Build-in width Mounting on the rail 0/00 V AC, max.
More informationThree Core XLPE/LSF/SWA/LSF Power Cable
1 Three Core XLPE/LSF/SWA/LSF Power Cable./ kv Application LSF armoured power cable for use in fixed installations. Especially for use in areas where fire would create dense smoke and toxic fumes causing
More informationTeSys circuit-breakers
Presentation Thermal-magnetic motor circuit-breakers types GV2, GV and GV7 GV2-ME, GV2-P, GV-ME and GV7-R motor circuit-breakers are -pole thermal-magnetic circuit-breakers specifically designed for the
More informationAmphenol. Amphenol-Tuchel Electronics GmbH. Circular Connectors C 091 A/B/D Series
Amphenol Amphenol-Tuchel Electronics GmbH Circular Connectors C 09 A/B/D Series The Company Amphenol-Tuchel Electronics GmbH is a member of the USA based Amphenol Corporation. With our own global presence
More informationImformation of C091D series
Imformation of C09D series The QTY of contacts is -pin to -pin, the connection method for the thread type, pinhole connections for welding type, press-fit and PCB type. This series of connectors to prevent
More informationO Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A
TYPE TEST REPORT O Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A 02 1 Abstract 02 2 Certification 03 3 Introduction 03 3.1 Description and ratings 03 3.2 Overview of tests 03 3.3 Applicable standards
More informationAn Optimised High Current Impulse Source
An Optimised High Current Impulse Source S. Kempen, D. Peier Institute of High Voltage Engineering, University of Dortmund, Germany Abstract Starting from a predefined 8/0 µs impulse current, the design
More informationElectrical safety testing Checklist
ety al Check testing Check - Checklist EN) ctrical Electrical safety testing Checklist SOP - Electrical Check Copyright 2013 Eppendorf AG. All rights reserved, including graphics and images. No part of
More informationAn Innovative Simple Test Circuit for Single-Phase Short Circuit Making Test of High-Voltage Switching Devices
An Innovative Simple Test Circuit for Single-Phase Short Circuit Making Test of High-Voltage Switching Devices Downloaded from jiaeee.com at 2:32 +33 on Sunday November 4th 28 Abstract: N. Nikpour K. Niayesh
More informationEXEMPLAR NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 ( ) (X-Paper) 09:00 12:00
NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 2008 (12041002) (X-Paper) 09:00 12:00 EXEMPLAR This question paper consists of 7 pages. EXEMPLAR -2- NC(V) TIME: 3 HOURS
More information90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION
MCB - MTC - MT - MTHP Technical data TYPE MTC MT MTC45 MTC60 MTC100 MT 45 MT 60 Rated current (In) (A) 2-32 6-32 6-32 6-40 1-63 Utilization category A A A A A Rated operational voltage (Ue) (V) 230/400-240/415
More informationINFORMATION TECHNOLOGY SYSTEMS SPDs FOR 19 TECHNOLOGY. NET Protector Surge Arrester. Protects switches, HUBs and telecommunication
Surge Arrester Protects switches, HUBs and telecommunication systems Class D according to EN 0 possible (Gigabit Ethernet) Variably equippable patch panels Units available with plug-in inputs and outputs
More informationC120N circuit-breakers B, C and D curves EN 60898/EN 61009: IEC : 10 ka
C0N circuit-breakers B, C and D curves EN 09/EN 009: 0000 - IEC 097-: 0 ka function # protection of cables against overloads and short-circuits in final distribution # manual control and isolation # earth
More information90 MCB range Modular circuit breakers for circuit protection
MCB - MTC - MT - MTHP Technical data TYPE MTC MT MTC45 MTC60 MTC100 MT 45 MT 60 Rated current (In) (A) 2-32 6-32 6-32 6-40 1-63 Utilization category A A A A A Rated operational voltage (Ue) (V) 230 / 400
More informationATyS Automatic and remotely operated transfer switches from 125 to 3200 A
atys-p_001_b atys_d_001_a_1_cat ATyS p I-0-II 4P ATyS d I-0-II 4P Function The ATyS are three-phase motorised transfer switches with positive break indication. They enable the on load transfer of two three-phase
More informationTable of Contents Pin-Configuration Selection Guide for HDE, HDS, & EFP
Table of Contents -Configuration Selection Guide for HDE, HDS, & EFP Service Voltage Rating... Electrical Service Ratings... Ampacity Ratings by Contact... Electrical Service Ratings Explained... Operating
More information8 Installation Equipment
8 Installation Equipment Plugs and Sockets CES System Series 8, 88, 8, 881 Te plugs and sockets in te CES system comply wit CEE publication 1 and European standards EN 0 01. Te small 1 A socket as switcing
More information40 CD RANGE FLUSH-MOUNTING DISTRIBUTION BOARDS AND ENCLOSURES
DISTRIBUTION BOARDS FLUSH-MOUNTING DISTRIBUTION BOARDS GWTEST SOFTWARE (see page 322) Complementary system items Ordinary installation - protected flush mounting DISTRIBUTION / JUNCTION Protection devices...
More informationSingle Phase Motors Technical Datasheets
Single Phase Motors Technical Datasheets EN A dynamic, strong and ambitious Group: Orange1 Holding is an international renown Group, one of the most important European manufacturers of single-phase and
More informationTEST REPORT ENVIRONMENTAL EN 60529:1991+A1:2000
Page 1 of 11 Report Reference No... : TEST REPORT ENVIRONMENTAL EN 60529:1991+A1:2000 93702-1TRFENV Tested by... : Cristian Simone.. Verified by... : Daniele Claudio Mapelli. Date of issue... : 2007-09-28
More informationDr. Michael Müller. Thermal Management for LED applications
Thermal Management for LED applications Content Thermal Design Basics thermal management Internal thermal management External thermal management 2 1967 founded with the production of insulation parts for
More informationProduct Series Specification Document
Product Series 3.96mm pitch board-to-board connectors - Socket SCOPE This document covers 3.96mm socket connectors. The connector will perform to the specifications outlined. All tests have been performed
More informationO Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents
Type test report O Plus Dry Bushing 69 kv system, 0 kv BIL, 000 A Table of contents Abstract... 2 2 Certification... 2 Introduction.... Description and ratings....2 Overview of tests.... Applicable standards....4
More information16 Appendix 16 Electrical Research Association Report
Guide to the Wiring Regulations 16 Appendix 16 Electrical Research Association Report (ERA) report on armoured cables with external CPCs The attached report was commissioned by the ECA and is copyright
More informationAnalysis of Very Fast Transients in EHV Gas Insulated Substations
Analysis of Very Fast Transients in EHV Gas Insulated Substations A.Raghu Ram, k. Santhosh Kumar raghuram_a@yahoo.com,ksanthosheee@gmail.com Abstract: Gas insulated switchgear (GIS) has been in operation
More informationElectric Filed Simulation and Structure Optimization for 40.5kV GIS Based on Finite Element Method
3rd International Conference on Mechanical Engineering and Intelligent Systems (ICMEIS 2015) Electric Filed Simulation and Structure Optimization for 40.5kV GIS Based on Finite Element Method Xian CHENG
More informationC60N circuit breakers0 B, C and D curves IEC 60898: 6000 A, IEC : 10 ka
C0N circuit breakers0 B, C and s IEC 0898: 000 A, IEC 097-: 0 ka Function b The circuit-breakers combine the following functions: v protection of circuits against short-circuit currents v protection of
More informationAmphenol. Amphenol-Tuchel Electronics GmbH. Series C 146 Heavy Duty Connectors Core Programme
Amphenol Amphenol-Tuchel Electronics GmbH Series C 146 Heavy Duty Connectors Core Programme The Company General information These connectors are designed and produced in conformity with the voltage directive
More informationMasterpact. Installation recommendations
90 Installation recommendations Presentation Functions and characteristics 9 Dimensions and connection 5 Electrical diagrams 8 Operating conditions 92 Installation in switchboard 9 Door interlock catch
More informationLD-LP-LL-LC Rope Safety Switches with reset for emergency stop
TECHNICA DATASHEET D-P--C Rope Safety Switches with reset for emergency stop Metal or polymer housing, from one or three conduit entries Protection degree IP6 In conformity with EN ISO 13850 contact blocks
More informationNon-Contact Safety Systems CMS
Selection table for non-contact safety system // Evaluation units Connection Desi Read head contact assembly Assured switch-on distance S ao [mm] Assured switch-on distance S ar [mm] Number of outputs
More informationVK2 volume flow controller Overview
New option with sound attenuator Maintenance-free VK2 volume flow controller that operates without an auxiliary power supply, for ventilation and air conditioning systems. Adjustable on site. Outstanding
More informationFilm Capacitors. EMI suppression capacitors. Date: June 2018
Film Capacitors EMI suppression capacitors Date: June 2018 EPCOS AG 2018. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein without
More informationFault Calculation Methods
ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the
More informationCDS. high density spring connection
CDS high density spring connection DENSTY STANDARD 1A CDS DENSTY A A spring connection CDS Series The originality of multipole connectors represents one of the core values of LE, a leading company in this
More informationUL 1077 DIN Rail Supplementary Protectors
UL 0 DIN Rail Supplementary Protectors Product Overview UL 0 DIN Rail Supplementary Protectors PRODUCT OVERVIEW Product Overview Standard Features WMZS breaker terminals provide finger and back-of-hand
More informationEA-10/14. EA Guidelines on the Calibration of Static Torque Measuring Devices. Publication Reference PURPOSE
Publication Reference EA-10/14 EA Guidelines on the Calibration of Static Torque Measuring Devices PURPOSE This document has been produced by EA to improve harmonisation in determining the calibration
More informationInstruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution
Instruction 0001-22-2--00 Vacuum Circuit Breaker Operator Module Type 3AH 4.16kV to 38kV Power Transmission & Distribution Hazardous voltages and high-speed moving parts. Will cause death, serious injury
More informationBETA Protecting Miniature Circuit Breakers
Siemens AG 00 / Product overview / High-capacity range 000 A 0000 A 0000 A, high current 0000 A, universal current 000 A ka /0 Comfort range with plug-in terminal / Compact range +N in MW / Additional
More informationSION Lateral 3AE6 Vacuum Circuit Breaker with Lateral Operating Mechanism
Catalog HG.07 Edition 03/ 07 SION Lateral 3AE Vacuum Circuit Breaker with Lateral Operating Mechanism Medium-Voltage Equipment siemens.com/sion R-HG-3.psd Catalog HG.07 03 / 07 SION 3AE Vacuum Circuit
More informationv = m / s Thermal Flow Sensors TA with thin-film sensor element Probes Probe Guides Measuring Tubes
Thermal Flow Sensors TA with thin-film sensor element Probes Probe Guides Measuring Tubes Examples of Application Flow measurements also in hazardous locations X zone 0 or zone 1 in clean rooms in air
More informationSUPPLY, ERECTION & COMMISSIONING OF 2 X 3.15 MVA 33/11KV SUB-STATION at Khuntlipalli,Bargarh ( PACKAGE - B )
SUPPLY, ERECTION & COMMISSIONING OF 2 X 3.15 MVA 33/11KV SUB-STATION at Khuntlipalli,Bargarh ( PACKAGE - B ) Sl. 1 2 Description of Work Supply,Erection & Commissioning of 2 x 3.15 MVA, New 33/11 KV Primary
More informationIdentification File of Type ZE64G23
Identification File of Type ZE64G23 for use in oil CONTENTS Page No. 1. Category 1 2. Structure 1 3. Manufacturing process 2 4. Manufacturing control 2 5. Shop and acceptance test 3 6. Electrical characteristics
More informationHydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid
Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid J. McCall, J. Yuan, D. Folts, N. Henderson, American Superconductor D. Knoll, Southwire M. Gouge, R. Duckworth, J.
More informationModeling of Transmission Line and Substation for Insulation Coordination Studies
TRAINING DUBROVNIK, CROATIA - APRIL, 27-29 2009 SIMULATION & ANALYSIS OF POWER SYSTEM TRANSIENTS WITH EMTP-RV Modeling of Transmission Line and Substation for Insulation Coordination Studies Prof. Ivo
More informationTEST REPORT IEC :2002 Circuit-Breakers for overcorrect protection for household and similar installation
age 1 of 92 R e port ref. No.: C009-CB2012CQC-044407 Test Report issued under the responsibility of: TEST REORT IEC 60 898-1:2002 Circuit-Breakers for overcorrect protection for household and similar installation
More informationInstallation guide 862 MIT / MIR
Installation guide 862 MIT / MIR in combination with: 864 MTT or 863 MRT or (dual) spot element November 2005 Part no. 4416.232_Rev3 Enraf BV PO Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100
More informationCOPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS
European Copper Institute COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS David Chapman August 2011 ECI Available from www.leonardo-energy.org Document Issue Control Sheet Document Title: Publication
More informationDamping resistor design consideration
http : //www.cigre.org CIGRÉ B4-054 CIGRÉ Winnipeg 2017 Colloquium Study Committees A3, B4 & D1 Winnipeg, Canada September 30 October 6, 201717 Damping resistor design consideration Elassad Yann MS Resistances
More informationEasyDry transformer bushing Better performance made easy. Power and productivity for a better world TM ABB
EasyDry transformer bushing Better performance made easy Power and productivity for a better world TM ABB ABB, the world leader in high voltage bushing technology Global experience and resources The ABB
More informationEx-Floodlight PXLED. (Ex-Zone 1, 2, 21 and 22)
Ex-Floodlight PXLED (Ex-Zone 1, 2, 21 and 22) Lighting under harsh conditions The new modular LED floodlight series PXLED is suited for nearly every kind of lighting task in hazardous areas, including
More informationImpedance relay and protection assemblies
RXZK 21H, 22H, 23H 509 006-BEN Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970175) (SE970184) Features Micro-processor based impedance relay with R and X settings
More informationFeasibility of HTS DC Cables on Board a Ship
Feasibility of HTS DC Cables on Board a Ship K. Allweins, E. Marzahn Nexans Deutschland GmbH 10 th EPRI Superconductivity Conference Feasibility of HTS DC Cables on Board a Ship 1. Can superconducting
More informationReport No 247/ This Report consists of 41 pages
Test Report Report No 247/ 7340511 This Report consists of 41 pages Client Electrical Safety Council 18 Buckingham Gate London SW1E 6LB Authority & date BSI Estimate Acceptance No 0000191154 dated 12 March
More informationSuperconducting Fault Current Limiters
Superconducting Fault Current Limiters Prof. Dr.-Ing. Mathias Noe, Karlsruhe Institute of Technology Institute for Technical Physics EASITrain Summer School,, September 3rd-7th 2018, Vienna KIT-ENERGY
More informationFLT5A FLT5A. abc. abc. Thermometer User Guide. Thermometer User Guide. Internet:
abc instruments international FLT5A Thermometer Land Instruments International Dronfield, S18 1DJ England Telephone: (1246) 417691 Facsimile: (1246) 41585 Email: infrared.sales@landinst.com Internet: www.landinst.com
More informationTest Report issued under the responsibility of: Report Number...: B Date of issue...: Total number of pages...
Test Report issued under the responsibility of: TEST REORT Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) art 1: General rules
More informationBASE. Rotary limit switch. OptiOnS. FEAtuRES. CERtiFiCAtiOnS
Rotary limit switch BASE Rotary limit switch used to control and measure the movement of industrial machines. Its compact size make it suitable for use in narrow spaces. FEAtuRES It consists of a gear
More informationAM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS. October, 1999 IM No
AM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS October, 1999 IM No. 597 1112 EQUIPMENT LOST OR DAMAGED IN TRANSIT. When delivering the equipment to you, the truck driver or carrier s agent
More informationTEST REPORT IEC/EN Circuit-breakers for over current protection for household and similar installations
Test Report issued under the responsibility of: TEST REORT IEC/EN 60898-1 Circuit-breakers for over current protection for household and similar installations Report Reference No.... : 130100913SHA-004
More information