Report No: NCTL NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 12/14/15

Size: px
Start display at page:

Download "Report No: NCTL NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 12/14/15"

Transcription

1 MGM INDUSTRIES, INC. Report No: NCTL NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 12/14/15 Test Specimen NFRC Code Manufacturer: MGM Industries, Inc. Series/Model: Series 4600 Window Type: Double Hung VSDH Frame Composition: Vinyl VY Sash/Vent/Panel Composition: Vinyl w/ Reinforcement-Interlock VI Thermal Break Mat'l: Not Applicable Overall Size: mm (47-1/4 ) wide by mm (59 ) high Glazing Description Overall w/low E and Argon No. of Glazing Layers (including films): 2 2 Primary Glazing: Double Glazed DG Spacer Type: Stainless Steel U-Shaped SU-D Gap Fill 1: Argon/ Air (95% Double Probe) ARG Gap Fill 2: Not Applicable Glass/Film Thicknesses (ext to int): 0.086, Air Gap 1: Air Gap 2: Not Applicable Secondary Glazing: Not Applicable Low Emissivity Coatings: Surface 2: Procedure: Standardized Thermal Transmittance (U st ) was determined using the NFRC procedure with a temperature of 69.8 ± 0.5 F on the room side of the specimen and -0.4 ± 0.5 F on the weather side of specimen. The net air leakage across the test specimen was 0.0 cfm. Test Results: Results of the test period on 12/14/11 using the Equivalent CTS Method: Thermal transmittance at test conditions (U s ): 0.34 BTU/hr/ft 2 / F Standardized thermal transmittance of test specimen (U st ): 0.32 BTU/hr/ft 2 / F Reference should be made to Thermal Performance Test Report Number NCTL for complete specimen description and test data. NATIONAL CERTIFIED TESTING LABORATORIES STEVEN H. COBLE Simulator In Responsible Charge

2 Report Number NCTL Report Date 01/06/12 Report To MGM Industries, Inc. 287 Freehill Road Hendersonville, TN Test End Date 12/14/11 Expiration Date 12/14/15 Specification NFRC Procedure for Measuring the Steady-State Thermal Transmittance of Fenestration Systems (2010 edition)". Description of Sample Tested Note: All dimensions are in the order (Width x Height x Thickness) unless otherwise noted. Model/Type: 4600 Configuration Tilt Double Hung Frame Size mm x mm (47-1/4 x 59 ) Top Sash Size mm x mm (44 x 28-1/4 ) Bottom Sash Size 1143 mm x 742 mm (45 x 29-1/4 ) Top Sash Viewing Area mm x mm (41-1/8 x 25-1/2 ) Bottom Sash Viewing Area mm x mm (41-1/4 x 25-1/2 ) Frame & Sash Type Joint Construction Glazing Components Overall Glass Thickness Coating Extruded vinyl Frame & Sash Mitered, welded 25.0 mm (0.986") nominal Two (2) panes of 2.2 mm (0.086 ) nominal A Cardinal LoE sputter-type emissivity coating (e= per client) was applied to glazing surface no. 2 Spacer Type/Size Stainless steel U-shaped (SU-D) 20.7 mm (0.814 ) Fill Argon 95% double probe per client Glazing System Exterior glazed with silicone back-bedding and snap-in rigid vinyl glazing bead

3 MGM Industries, Inc. NCTL Weatherstrip Type Size Type Size Sill Extender Type Operating Hardware Latches Type Keeper Type Balance Type Pivot Bar Type Auxiliary Type (2) Strips center fin 6.9 mm (0.270") high Stiles, top rail and exterior meeting rail (1) Strip center fin 6.9 mm (0.270 ) high Bottom rail, interior meeting rail, sill and head Foam-filled bulb-vinyl Bottom rail Cam- type sweep mm (12.25 ) from each end of the interior meeting rail Metal Exterior meeting rail at the locked position (1) Dual coil spring Interior and exterior jamb track (1) T-shaped Each end of the bottom rail and exterior meeting rail fastened with (2) screws Weatherstrip holder/ interior vertical leg Head Reinforcement Type Size Contour-shaped aluminum 2.1 mm (0.082") thick Exterior meeting rail Weep Description Size 31.8 mm x 6.4 mm (1.25 x 0.25 ) 76.2 mm (3 ) from each end of the sill face Size 9.5 mm x 3.18 mm (0.375 x ) Each end of the exterior meeting rail and bottom rail Size 12.7 mm x 4.76 mm (0.5 x ) 22.2 mm (0.874 ) from each end of the screen track Interior/ Exterior Surface Finish Sealant Insect Screen White vinyl (PVC) No apparent sealant applied No screen employed

4 MGM Industries, Inc. NCTL SPECIMEN PREPARATION PRIOR TO TEST The test specimen was pre-conditioned at ambient laboratory conditions prior to the test. The surround panel-tospecimen interfaces were sealed with a non-reflective tape. The specimen was sealed on the interior with a caulk sealant resulting in a measured net air leakage of 0.0 cfm per square foot. TEST PARAMETERS Tests to determine the Standardized Thermal Transmittance (U st ) of the specimen were performed in the guarded hot box apparatus located at the York, PA facility. The most recent calibration of the hot box apparatus was in February 16, The thermal performance evaluations were completed in accordance with the NFRC 102 procedure using a dynamic wind perpendicular to the specimen on the weather side and simulated natural convection on the room side. A zero static pressure differential (0.00" ± 0.04" H 2 O) was maintained across the specimen during the test by pressurizing the metering box on the room side. Data was collected over two successive 2 hour periods after 4 hours of steady state conditions as defined in section of the NFRC 102 procedure were achieved. The test was considered completed when the data of the successive 2 hour periods also satisfied the criteria defined in section of the NFRC 102 procedure. GLASS THICKNESS AND GLAZING DEFLECTION: Glass Thicknesses Glazing Deflection Before Test Glazing Deflection After Test Top Sash 0.086, Bottom Sash 0.086, PROJECTED FRAME DIMENSIONS OF MEMBERS: Member: Bottom Jamb Head Meeting Rail Sill Top Jamb Dimension: TEST DURATION: The test chamber environmental systems were initiated at 0857 on 12/14/11. The test conditions were considered stable for two consecutive two hour test periods from and on 12/15/11. The thermal performance test results were derived from the test period. Areas: Test Specimen Projected Area (A s ): ft² Test Specimen Interior Exposed (Wetted) Surface Area (A int ): 0 ft² Test Specimen Exterior Exposed (Wetted) Surface Area (A ext ): 0 ft² Metering Box Opening Area (A mb ): ft² Metering Box Baffle Area (A b1 ): ft² Surround Panel Interior Exposed Area (A sp ): ft² Exposed Area of Mods to Surround Panel Opening: 6.65 ft² Test Conditions: Average Room Side Air Temperature: 69.8 F Average Weather Side Air Temperature: -0.3 F Average Guard Box Air Temperature: 72.1 F Average Warm Side Surround Panel Temperature: 66.1 F Average Cold Side Surround Panel Temperature: 0.1 F Metering Box Average Relative Humidity: 12 %

5 MGM Industries, Inc. NCTL Test Conditions: (Continued) Measured Weather Side Wind Velocity: 14.3 mph Static Pressure Difference Across Specimen (assumed) : 0.0 H 2 0 Heat Flows: Heat Input Rate to Metering Box (Q total ): BTU/hr Surround Panel Heat Flow (Q sp ): 87.5 BTU/hr Surround Panel Thickness: Inches Surround Panel Conductance: BTU/hr/ft²/ F Metering Box Heat Flow (Q mb ): BTU/hr Flanking Loss Heat Flow (Q fl ): 37.7 BTU/hr Net Test Specimen Heat Flow (Qs): BTU/hr EMF vs Heat Flow Equation: y= * EMF Test Results & Calculated Test Data: Emittance of Glass (e 1 ): 0.84 Warm Side Baffle Emittance (e b1 ): 0.96 Equivalent Room Side Surface Temperature: 53.2 ºF Equivalent Weather Side Surface Temperature: 4.1 ºF Room Side Baffle Surface Temperature: 68.5 ºF Measured Room Side Surface Conductance (h h ): 1.42 BTU/hr/ft²/ F Measured Weather Side Surface Conductance (h c ): 5.29 BTU/hr/ft²/ F Test Specimen Thermal Conductance (C s ): 0.48 BTU/hr/ft²/ F Convection Coefficient (K): Radiative Test Specimen Heat Flow (Q r1 ): BTU/hr Convective Test Specimen Heat Flow (Q c1 ): BTU/hr Radiative Heat Flux of Test Specimen (q r1 ): BTU/hr/ft² Convective Heat Flux of Test Specimen (q c1 ): BTU/hr/ft² Standardized Room Side Surface Conductance (h STh ): 1.22 BTU/hr/ft²/ F Standardized Weather Side Surface Conductance (h STc ): 5.28 BTU/hr/ft²/ F Test Specimen Thermal Transmittance (U s ): 0.34 BTU/hr/ft²/ F Test Specimen Standardized Thermal Transmittance (U ST ): 0.32 BTU/hr/ft²/ F This test method does not include procedures to determine the heat flow due to either air movement through the specimen or solar radiation effects. As a consequence, the thermal transmittance results obtained do not reflect performances which may be expected from field installations due to not accounting for solar radiation, air leakage effects, and the thermal bridge effects that may occur due to the specific design and construction of the fenestration system opening. Therefore, it should be recognized that the thermal transmittance results obtained from this test method are for ideal laboratory conditions and should only be used for fenestration product comparisons and as input to thermal performance analyses which also include solar, air leakage, and thermal bridge effects. An estimate of the experimental uncertainty for these results is available upon request.

6 MGM Industries, Inc. NCTL Per the client, the test specimen described in this report was a production line unit submitted for initial certification and plant qualification and is described as tested. Detailed drawings were available for laboratory records and compared to the test specimen at the time of this report. A copy of this report along with representative sections of the test specimen will be retained by NCTL for a period of four (4) years. The results obtained apply only to the specimen tested. This report may not be reproduced, except in full, without the written approval of National Certified Testing Laboratories. NCTL is a testing lab accredited by A2LA to ISO/IEC and assumes that all information provided by the client is accurate and does not guarantee or warranty any product tested or installed. Testing described in this report was conducted in full compliance with NFRC requirements; any deviations are noted. ASTM C1363 and C1199 testing was performed with published NFRC deviations. Ratings included in this report are for submittal to an NFRC licensed IA for certification purposes and are not meant to be used for labeling purposes. Only those values identified on a valid Certification Authorization Report (CAR) are to be used for labeling purposes. National Certified Testing Laboratories STEVEN H. COBLE Simulator In Responsible Charge RAYMOND W. LAMB, P.E. Senior Project Engineer Person-in-Responsible Charge ZM/ hl

7 ATTACHMENT 1 Section 1: Component Drawings, with Applicable Part Numbers, Manufacturing and Modeling Details, were Reviewed (as submitted) for Product Verification (Reference: NCTL ) See Attached Documentation; any deviations noted. Note: The above referenced component drawings along with representative sections of the test specimen will be retained per procedure by NCTL. This testing facility assumes that all information provided by the client is accurate. Section 2: Identification Date Page & Revision Original Issue 01/06/12 Not Applicable

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

Report No: NCTL S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 07/14/15. Test Specimen

Report No: NCTL S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 07/14/15. Test Specimen MGM INDUSTRIES, INC. Report No: NCTL-110-13834-1S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 07/14/15 Test Specimen NFRC Code Manufacturer: MGM Industries, Inc. Series/Model: 8017 Window Type: Double

More information

Test Results: Results of the test period on 06/19/16 using the Equivalent CTS Method: Thermal transmittance at test conditions (U s ):

Test Results: Results of the test period on 06/19/16 using the Equivalent CTS Method: Thermal transmittance at test conditions (U s ): NORTH EAST WINDOWS USA, INC. NFRC THERMAL TEST SUMMARY REPORT Report No: NCTL-110-17842-3S Test Specimen NFRC Code Manufacturer: North East Windows USA, Inc. Series/Model: Series CW 300 Window Type: Casement-

More information

NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 03/31/06

NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 03/31/06 ALL SEASONS DOOR & WINDOW, INC. Report No: NCTL-110-8058-5S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 03/31/06 Test Specimen NFRC Code Manufacturer : All Seasons Door & Window, Inc. Series/Model

More information

NFRC THERMAL TEST SUMMARY REPORT January 27, 1999 Test Specimen

NFRC THERMAL TEST SUMMARY REPORT January 27, 1999 Test Specimen * This is not the original copy of the test report if you would like an original copy, please contact our East Brunswick office or the NCTL to request a copy. ALL SEASONS DOOR & WINDOW, INC. REPORT NO:

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NORTH EAST WINDOWS USA, INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NORTH EAST WINDOWS USA, INC. NFRC 102-2014 THERMAL PERFORMANCE TEST REPORT Rendered to: NORTH EAST WINDOWS USA, INC. SERIES/MODEL: 100 Double Hung TYPE: Vertical Slider (Double Hung) Summary of Results Standardized Thermal Transmittance

More information

AIR-INS inc. 1320, boul. Lionel-Boulet, Varennes (Quebec) J3X 1P7 Tél. : (450) Fax : (450)

AIR-INS inc. 1320, boul. Lionel-Boulet, Varennes (Quebec) J3X 1P7 Tél. : (450) Fax : (450) 1320, boul. Lionel-Boulet, Varennes (Quebec) J3X 1P7 Tél. : (450) 652-0838 Fax : (450) 652-7588 info@air-ins.com THERMAL PERFORMANCE VALIDATION TEST CONDUCTED ON YOUR 300 / 301 FIXED WINDOW IN ACCORDANCE

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. NFRC 102-2014 THERMAL PERFORMANCE TEST REPORT Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: 45X - High Performance Dual Thermally Broken Storefront TYPE: Glazed Wall Systems (Site-built) Summary of

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NU VISTA WD, INC. SERIES/MODEL: Malibu 250 T TYPE: Fixed

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NU VISTA WD, INC. SERIES/MODEL: Malibu 250 T TYPE: Fixed NFRC 102-201 THERMAL PERFORMANCE TEST REPORT Rendered to: NU VISTA WD, INC. SERIES/MODEL: Malibu 250 T TYPE: Fixed Summary of Results Standardized Thermal Transmittance (U-Factor) 0.39 Unit Size: 7" x

More information

THERMAL PERFORMANCE TEST REPORT

THERMAL PERFORMANCE TEST REPORT THERMAL PERFORMANCE TEST REPORT Manufacture: Address: Coral Architectural Products 7704B Industrial Lane Tampa, Florida 33637 Specifications: ANSI/NFRC 102-2014: Test Procedure for Measuring the Steady-State

More information

SHANGHAI MYLCH WINDOWS & DOORS THERMAL PERFORMANCE TEST REPORT

SHANGHAI MYLCH WINDOWS & DOORS THERMAL PERFORMANCE TEST REPORT SHANGHAI MYLCH WINDOWS & DOORS THERMAL PERFORMANCE TEST REPORT SCOPE OF WORK DR65 FIXED REPORT NUMBER H3108.01-301-46 R0 TEST DATE 11/09/17 ISSUE DATE 11/14/17 RECORD RETENTION END DATE 11/09/22 PAGES

More information

Simulation Report (Revised) Rendered To: Showcase Custom Vinyl Windows 1002 Olde Towne Drive Irving, TX 75061

Simulation Report (Revised) Rendered To: Showcase Custom Vinyl Windows 1002 Olde Towne Drive Irving, TX 75061 ETC Laboratories ETC Laboratories Corporate Offices / Laboratories 297 Buell Road Rochester, NY 14624 (585) 328-7668 Fax: (585) 328-7777 Simulation Report (Revised) Rendered To: Showcase Custom Vinyl Windows

More information

SIMULATION TEST REPORT NCTL E0A0

SIMULATION TEST REPORT NCTL E0A0 SIMULATION TEST REPORT NCTL-610-21539-1E0A0 REPORT TO: All Seasons Window & Door System Inc. 1340 Metropolitan Avenue Brooklyn, NY 11237 SIMULATION DATE: 11/20/18 PRODUCT: EU400 Tilt & Turn This report

More information

NFRC SOLAR HEAT GAIN COEFFICIENT TEST REPORT. Rendered to: CLEAR FOCUS IMAGING

NFRC SOLAR HEAT GAIN COEFFICIENT TEST REPORT. Rendered to: CLEAR FOCUS IMAGING NFRC 201-2004 SOLAR HEAT GAIN COEFFICIENT TEST REPORT Rendered to: CLEAR FOCUS IMAGING SERIES/MODEL: SunSecure BASE WINDOW: 3/16" Clear Single Glazed PRODUCT TYPE: Window Film on the Interior of Clear

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: INTERNATIONAL ARCHITECTURAL PRODUCTS, INC. DBA: UNITED STATES ALUMINUM

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: INTERNATIONAL ARCHITECTURAL PRODUCTS, INC. DBA: UNITED STATES ALUMINUM Architectural Testing NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: INTERNATIONAL ARCHITECTURAL PRODUCTS, INC. DBA: UNITED STATES ALUMINUM SERIES/MODEL: 7600 Projected Vent TYPE: Projecting

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: PARAMOUNT WINDOWS CORPORATION. SERIES/MODEL: 4000 TYPE: Fixed

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: PARAMOUNT WINDOWS CORPORATION. SERIES/MODEL: 4000 TYPE: Fixed Architectural Testing NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: PARAMOUNT WINDOWS CORPORATION SERIES/MODEL: 4000 TYPE: Fixed Summary of Results Standardized Thermal Transmittance (U-Factor)

More information

WINDOW SIMULATION REPORT

WINDOW SIMULATION REPORT WINDOW SIMULATION REPORT NFRC 100: Procedure for Determining Fenestration Product U-Factors NFRC 200: Solar Heat Gain Coefficient and Visible Transmittance NFRC 500: Procedure for Determining Fenestration

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 7400 TYPE: Fixed

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 7400 TYPE: Fixed NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM SERIES/MODEL: 7400 TYPE: Fixed Summary of Results Standardized Thermal Transmittance (U-Factor) 0.37 Unit Size 47-1/4''

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: 375-T - High Performance Medium Stile Thermal Door (Dual Glazed) TYPE: Swinging Door with Frame Summary

More information

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC. PRODUCT: Fiberglass Door Slab

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC. PRODUCT: Fiberglass Door Slab ASTM C 1363-11 THERMAL PERFORMANCE TEST REPORT Rendered to: UNIVERSAL PULTRUSIONS, LLC PRODUCT: Fiberglass Door Slab Summary of Results Thermal Transmittance (Btu/hr.ft².F), U-factor Overall Thermal Resistance

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC. Architectural Testing NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: T14000 Storefront (Standard) TYPE: Glazed Wall Systems (Site-built) Summary of Results Standardized

More information

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: CMI ARCHITECTURAL PRODUCTS, INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: CMI ARCHITECTURAL PRODUCTS, INC. NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: CMI ARCHITECTURAL PRODUCTS, INC. SERIES/MODEL: CTS Thermal Clip Framing System TYPE: Glazed Wall Systems (Site-built) Summary of Results Standardized

More information

Standard Test Method for Measuring the Steady-State Thermal Transmittance of Fenestration Systems Using Hot Box Methods 1

Standard Test Method for Measuring the Steady-State Thermal Transmittance of Fenestration Systems Using Hot Box Methods 1 Designation: 97 AMERICAN SOCIETY FOR TESTING AND MATERIALS 100 Barr Harbor Dr., West Conshohocken, PA 19428 Reprinted from the Annual Book of ASTM Standards. Copyright ASTM Standard Test Method for Measuring

More information

Determination of thermal transmittance of window (test title)

Determination of thermal transmittance of window (test title) INSTITUTE OF ARCHITECTURE AND CONSTRUCTION OF KAUNAS UNIVERSITY OF TECHNOLOGY SCIENCE LABORATORY OF BUILDING THERMAL PHYSICS Notified Body number: 2018 BANDYMAI ISO/IEC 17025 Nr. LA. 01.031 page (pages)

More information

Vinyl Products Pella Windows and Doors

Vinyl Products Pella Windows and Doors Vinyl Products Pella Windows and Doors 2017 PELLA PRODUCT PORTFOLIO BRAND Encompass by Pella Pella 250 Series Pella 350 Series Pella Impervia Pella 450 Series Designer Series Architect Series Contemporary

More information

Winter Night. Thermos 6mm Outdoors # #

Winter Night. Thermos 6mm Outdoors # # February 26, 2016 By Gagnon, Stephan stephan@thermosrn.ca Thermos 3mm à 6mm vs Climaguard 80/70 Make-up Name Make-up Icon Transmittance Reflectance U-Value Visible (τ v %) (τ e %) Visible ρ v % out ρ v

More information

THE EFFECTS OF CALORIMETER TILT ON THE INWARD-FLOWING FRACTION OF ABSORBED SOLAR RADIATION IN A VENETIAN BLIND

THE EFFECTS OF CALORIMETER TILT ON THE INWARD-FLOWING FRACTION OF ABSORBED SOLAR RADIATION IN A VENETIAN BLIND Collins, M.R., and Harrison, S.J., "The Effects of Calorimeter Tilt on the Inward-Flowing Fraction of Absorbed Solar Radiation in a Venetian Blind", ASHRAE Transactions, Vol. 107 (1), pp. 677-683, 2001.

More information

National Fenestration Rating Council. Incorporated. NFRC [E0A1] Procedure for Determining Fenestration Product Condensation Resistance Values

National Fenestration Rating Council. Incorporated. NFRC [E0A1] Procedure for Determining Fenestration Product Condensation Resistance Values National Fenestration Rating Council Incorporated NFRC 500-2010 [E0A1] Procedure for Determining Fenestration Product Condensation Resistance Values 2010 NATIONAL FENESTRATION RATING COUNCIL, INC. PREPARED

More information

Window air permeability measurement, watertightness and resistance to wind load (designation of the test)

Window air permeability measurement, watertightness and resistance to wind load (designation of the test) KTU INSTITUTE OF ARCHITECTURE AND CONSTRUCTION BUILDING THERMAL PHYSICS Notified Body number: 2018 BANDYMAI ISO/IEC 17025 Nr. LA. 01.031 Test performed: Product: Page (pages) 05 of August 2013 1 (8) Window

More information

REPORT NUMBER: MID-001 ORIGINAL ISSUE DATE: April 22, 2016 REVISED DATE: NA. EVALUATION CENTER Intertek 8431 Murphy Drive Middleton, WI 53562

REPORT NUMBER: MID-001 ORIGINAL ISSUE DATE: April 22, 2016 REVISED DATE: NA. EVALUATION CENTER Intertek 8431 Murphy Drive Middleton, WI 53562 REPORT NUMBER: 102550917MID-001 ORIGINAL ISSUE DATE: April 22, 2016 REVISED DATE: NA TEST REPORT EVALUATION CENTER Intertek 8431 Murphy Drive Middleton, WI 53562 RENDERED TO Cali Bamboo 6675 Mesa Ridge

More information

Customer: Ashton Industrial Sales Ltd. South Road, Harlow Essex CM20 2AR UNITED KINGDOM. Project/Customer: Profilex HM spacer

Customer: Ashton Industrial Sales Ltd. South Road, Harlow Essex CM20 2AR UNITED KINGDOM. Project/Customer: Profilex HM spacer Page 1 of 11 Customer: Ashton Industrial Sales Ltd. South Road, Harlow Essex CM20 2AR UNITED KINGDOM Project/Customer: Profilex HM spacer Content: U f simulation of profiles in accordance to EN ISO 10077-2

More information

TEST METHOD FOR THERMAL TRANSMITTANCE AND AIR INFILTRATION OF GARAGE DOORS

TEST METHOD FOR THERMAL TRANSMITTANCE AND AIR INFILTRATION OF GARAGE DOORS ANSI/DASMA 105-1992 (R2004) AMERICAN NATIONAL STANDARD TEST METHOD FOR THERMAL TRANSMITTANCE AND AIR INFILTRATION OF GARAGE DOORS Door & Access Systems Manufacturers Association, International Sponsor:

More information

Determination of installed thermal resistance into a roof of TRISO-SUPER 12 BOOST R

Determination of installed thermal resistance into a roof of TRISO-SUPER 12 BOOST R INSTITUTE OF ARCHITECTURE AND CONSTRUCTION OF KAUNAS UNIVERSITY OF TECHNOLOGY LABORATORY OF BUILDING PHYSICS Notified Body number: 2018 TEST REPORT No. 037-10/11(C) SF/15 Date: 26 of November 2015 page

More information

Solar Radiation 230 BTU s per Hr/SF. Performance Glazing Coatings, Layers & Gases

Solar Radiation 230 BTU s per Hr/SF. Performance Glazing Coatings, Layers & Gases Solar Radiation 230 BTU s per Hr/SF 89 83 82 90 Performance Glazing Coatings, Layers & Gases Learning Objectives After Viewing This Presentation You Will Understand: q The NFRC Labeling System q Light

More information

Introduction...COMB-2 Design Considerations and Examples...COMB-3

Introduction...COMB-2 Design Considerations and Examples...COMB-3 SECTION DIRECTORY General Information Introduction...COMB-2 Design Considerations and Examples...COMB-3 Combination Assembly Recommendations and Limitations Composite Configurations...COMB-4 Typical Sealant

More information

THERMAL TRANSMITTANCE OF MULTI-LAYER GLAZING WITH ULTRATHIN INTERNAL PARTITIONS. Agnieszka A. Lechowska 1, Jacek A. Schnotale 1

THERMAL TRANSMITTANCE OF MULTI-LAYER GLAZING WITH ULTRATHIN INTERNAL PARTITIONS. Agnieszka A. Lechowska 1, Jacek A. Schnotale 1 THERMAL TRANSMITTANCE OF MULTI-LAYER GLAZING WITH ULTRATHIN INTERNAL PARTITIONS Agnieszka A. Lechowska 1, Jacek A. Schnotale 1 1 Cracow University of Technology, Department of Environmental Engineering,

More information

ASTM C STEADY-STATE HEAT FLUX MEASUREMENTS AND THERMAL TRANSMISSION PROPERTIES BY MEANS OF THE HEAT FLOW METER APPARATUS

ASTM C STEADY-STATE HEAT FLUX MEASUREMENTS AND THERMAL TRANSMISSION PROPERTIES BY MEANS OF THE HEAT FLOW METER APPARATUS Page 1 of 10 ASTM C 518 04 STEADY-STATE HEAT FLUX MEASUREMENTS AND THERMAL TRANSMISSION PROPERTIES BY MEANS OF THE HEAT FLO METER APPARATUS Rockwool Premium Plus Insulation Project No. 3194876SAT-001A

More information

CRYOGENIC CONDUCTION COOLING TEST OF REMOVABLE PANEL MOCK-UP FOR ITER CRYOSTAT THERMAL SHIELD

CRYOGENIC CONDUCTION COOLING TEST OF REMOVABLE PANEL MOCK-UP FOR ITER CRYOSTAT THERMAL SHIELD CRYOGENIC CONDUCTION COOLING TEST OF REMOVABLE PANEL MOCK-UP FOR ITER CRYOSTAT THERMAL SHIELD K. Nam, a D. K. Kang, a W. Chung, a C. H. Noh, a J. Yu, b N. I. Her, b C. Hamlyn-Harris, b Y. Utin, b and K.

More information

PERFORMANCE TEST REPORT. Rendered to: WORLDWIDE DOOR COMPONENTS, INC. PRODUCTS: PVC and Composite Door Jamb Material

PERFORMANCE TEST REPORT. Rendered to: WORLDWIDE DOOR COMPONENTS, INC. PRODUCTS: PVC and Composite Door Jamb Material PERFORMANCE TEST REPORT Rendered to: WORLDWIDE DOOR COMPONENTS, INC. PRODUCTS: PVC and Composite Door Jamb Material Report No: Report Date: 10/24/11 Expiration Date: 09/27/15 130 Derry Court York, PA 17406-8405

More information

Assessing The Thermal Performance of Building Enclosure Materials Using A Medium-Size Hot Box Chamber Summer Meeting Torkan Fazli

Assessing The Thermal Performance of Building Enclosure Materials Using A Medium-Size Hot Box Chamber Summer Meeting Torkan Fazli Assessing The Thermal Performance of Building Enclosure Materials Using A Medium-Size Hot Box Chamber 2014 Summer Meeting Torkan Fazli Introduction The building construction industry consumes significant

More information

TEST OF MEASURED SOLAR HEAT GAIN VARIATION WITH RESPECT TO TEST SPECIMEN TILT

TEST OF MEASURED SOLAR HEAT GAIN VARIATION WITH RESPECT TO TEST SPECIMEN TILT Collins, M.R., and Harrison, S.J., "Test of Measured Solar Heat Gain Variation with Respect to Test Specimen Tilt", SHRE Transactions, Vol. 107 (1), pp. 691-699, 2001. Copyright 2001, merican Society of

More information

DIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: PNEUTEK, INC.

DIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: PNEUTEK, INC. ICC ES Report ICC ES () 7 () www.icc es.org Most Widely Accepted and Trusted ESR 1 Reissued /1 This report is subject to renewal /. DIVISION: METALS SECTION: METAL FASTENINGS SECTION: 1 STEEL ING REPORT

More information

CAE 463/524 Building Enclosure Design Fall 2012

CAE 463/524 Building Enclosure Design Fall 2012 CAE 463/524 Building Enclosure Design Fall 2012 Lecture 8: Fenestration (+ exam review) Dr. Brent Stephens, Ph.D. Department of Civil, Architectural and Environmental Engineering Illinois Institute of

More information

Determining of Thermal Conductivity Coefficient of Pressed Straw (Name of test)

Determining of Thermal Conductivity Coefficient of Pressed Straw (Name of test) CONSTRUCTION HEAT PHYSICS LABORATORY INSTITUTE OF ARCHITECTURE AND CONSTRUCTION OF KAUNAS UNIVERSITY Test and calculation carried out according to: Product: 12 December 2012 LITHUANIAN NATIONAL ACCREDITATION

More information

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6986/ARL-SA6987 Revision 0 ARL

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6986/ARL-SA6987 Revision 0 ARL ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6986/-SA6987 Revision 0 Subject: Sound Absorption Test Date: 01 February 2017 Contents: on Sound Absorption Data, One-third Octave

More information

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6266/ARL-SA6274 Revision 0 ARL

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6266/ARL-SA6274 Revision 0 ARL ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6266/-SA6274 Revision 0 Subject: Sound Absorption Test Date: 17 February 2015 Contents: on Sound Absorption Data, One-third Octave

More information

CAE 331/513 Building Science Fall 2016

CAE 331/513 Building Science Fall 2016 CAE 331/513 Building Science Fall 2016 Week 3: September 8, 2016 Heat transfer in buildings: Finish radiation, then solar radiation and windows Advancing energy, environmental, and sustainability research

More information

Thermal and mechanical modeling of thermal breaks in structural steel point transmittances

Thermal and mechanical modeling of thermal breaks in structural steel point transmittances Thermal and mechanical modeling of thermal breaks in structural steel point transmittances Presented to the American Society of Mechanical Engineers Presented by: Scott Hamel P.E., Ph.D. Co-Author: Sava

More information

BACK TO BASICS: PIPE INSULATION

BACK TO BASICS: PIPE INSULATION BACK TO BASICS: PIPE INSULATION INDUSTRIAL REFRIGERATION CONSORTIUM RESEARCH & TECHNOLOGY FORUM MAY 2-3, 2012 Todd Jekel, Ph.D., P.E. Assistant Director, IRC Overview 1 2 3 4 Basics of insulation & insulation

More information

INVESTIGATING GLAZING SYSTEM SIMULATED RESULTS WITH REAL MEASUREMENTS

INVESTIGATING GLAZING SYSTEM SIMULATED RESULTS WITH REAL MEASUREMENTS INVESTIGATING GLAZING SYSTEM SIMULATED RESULTS WITH REAL MEASUREMENTS Mark Luther 1, Timothy Anderson 2, and Tim Brain 3 1 School of Architecture and Building, Deakin University, Geelong, Australia 2 School

More information

Reflectec Thermal Fabric & Reflectec Fiberboard

Reflectec Thermal Fabric & Reflectec Fiberboard MODIFIED ASTM E 1354 CONE CALORIMETER THERMAL RESPONSE TEST (Final Report) TEST REPORT Reflectec Thermal Fabric & Reflectec Fiberboard Project No. 16723-113972 April 22, 2003 Prepared for: John W. Mallette

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 0077-2 First edition 2003-0-0 Thermal performance of windows, doors and shutters Calculation of thermal transmittance Part 2: Numerical method for frames Performance thermique

More information

Vincent Barraud SOPREMA BASICS OF THERMAL INSULATION

Vincent Barraud SOPREMA BASICS OF THERMAL INSULATION Vincent Barraud SOPREMA BASICS OF THERMAL INSULATION Summary Part 1 - What is thermal conductivity? Part 2 - How the thermal conductivity is measured? Part 3 How to certify a lambda value? Part 1 - What

More information

SL27C SL32C. ScreenLine. Technical Catalogue. english. double-glazed unit 27 mm 32 mm

SL27C SL32C. ScreenLine. Technical Catalogue. english. double-glazed unit 27 mm 32 mm VENETIAN SL27C SL32C BLIND english Technical Catalogue double-glazed unit 27 mm 32 mm dimensions technical specification SL27C SL32C System C C SL27C VENETIAN SL32C BLIND The venetian blinds SL27C and

More information

ISO INTERNATIONAL STANDARD. Thermal performance of windows, doors and shutters Calculation of thermal transmittance Part 1: Simplified method

ISO INTERNATIONAL STANDARD. Thermal performance of windows, doors and shutters Calculation of thermal transmittance Part 1: Simplified method INTERNATIONAL STANDARD ISO 10077-1 First edition 2000-07-15 Thermal performance of windows, doors and shutters Calculation of thermal transmittance Part 1: Simplified method Performance thermique des fenêtres,

More information

QIRT th International Conference on Quantitative InfraRed Thermography

QIRT th International Conference on Quantitative InfraRed Thermography 10 th International Conference on Quantitative InfraRed Thermography July 27-30, 2010, Québec (Canada) Quantitative infrared wall inspection *CE Dept., Cracow University of Technology, Kraków, Poland,

More information

THREE HOLE SPLICE CLEVIS FOR B52 Standard finishes: ZN, GRN Wt./C 126 Lbs. (57.1 kg)

THREE HOLE SPLICE CLEVIS FOR B52 Standard finishes: ZN, GRN Wt./C 126 Lbs. (57.1 kg) CLEVIS FITTINGS B169 TWO HOLE SPLICE Wt./C 84 Lbs. (38.1 kg) B168 THREE HOLE SPLICE Wt./C 126 Lbs. (57.1 kg) B167 Wt./C 178 Lbs. (80.7 kg) 3 1 /2 (88.9) B170 TWO HOLE SPLICE Wt./C 123 Lbs. (55.8 kg) 5

More information

PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. PRODUCT: SUN TUNNEL Domes TYPES: Acrylic and Polycarbonate

PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. PRODUCT: SUN TUNNEL Domes TYPES: Acrylic and Polycarbonate PERFORMANCE TEST REPORT Rendered to: VELUX AMERICA, INC. PRODUCT: SUN TUNNEL Domes TYPES: Acrylic and Polycarbonate Report No.: E3490.01-106-31 Report Date: 07/13/15 Test Record Retention Date: 06/18/19

More information

THERMAL SIMULATION REPORT. TCL2013-Origin-01 Prepared For:

THERMAL SIMULATION REPORT. TCL2013-Origin-01 Prepared For: THERMAL SIMULATION REPORT Report Number: TCL2013-Origin-01 Prepared For: Origin Frames Ltd Unit 3 Sunters End Hillbottom Road Sands Industrial Estate High Wycombe Bucks HP12 4HS Window System Identifier:

More information

Calculating the heat transfer coefficient of frame profiles with internal cavities

Calculating the heat transfer coefficient of frame profiles with internal cavities Calculating the heat transfer coefficient of frame profiles with internal cavities SUBMITTED: December 2001 REVISED: January 2004 PUBLISHED: March 2004 Peter A. Noyé, M.Sc (Eng) Department of Civil Engineering,

More information

ANSI/SPRI ES-1 Test Reports UL Classified Products

ANSI/SPRI ES-1 Test Reports UL Classified Products Introduction to ES-1 The ANSI/SPRI ES-1 Roof Edge Standard is a reference for those who design, specify or install edge materials used with low slope roofs. This standard focuses primarily on design for

More information

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6712/ARL-SA6713 Revision 0 ARL

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6712/ARL-SA6713 Revision 0 ARL ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6712/-SA6713 Revision 0 Subject: Sound Absorption Test Date: 17 May 2016 Contents: on Sound Absorption Data, One-third Octave bands

More information

NFRC Errata and Addendum Log

NFRC Errata and Addendum Log NFRC 101-2017 NFRC Errata and Addendum Log E2A7 (May 2018) Participant Product Density Conductivity Emissivity Azon Azon Eagle Window and Doors Tremco Azo-Core 13 Azo-Core 17 Eagle Window and Doors- Eagle

More information

Hanson Overhead Garage Door Company proudly presents: Residential 400 Series

Hanson Overhead Garage Door Company proudly presents: Residential 400 Series Hanson Overhead Garage Door Company proudly presents: Residential 400 Series 410 411 Traditional Raised Panel 410 411 EFFICIENCY 6.85 R-VALUE INTERIOR VINYL SKIN Constructed of top quality materials, highly

More information

CONSTRUCTION MATERIALS

CONSTRUCTION MATERIALS CONSTRUCTION MATERIALS T E C H N O L O G I E S LABORATORY TEST REPORT Report for: 6 Cherry Ave Penticton, BC VA L7 Canada Product(s): Deksmart Ultra 68mil Decking Membrane Manufacturer: O Sullivan Films,

More information

Standard Practices for Air Speed Calibration Testing

Standard Practices for Air Speed Calibration Testing Standard Practices for Air Speed Calibration Testing Rachael V. Coquilla Bryza Wind Lab, Fairfield, California Air speed calibration is a test process where the output from a wind measuring instrument

More information

SENSOR. Weather TRANSMITTERS

SENSOR. Weather TRANSMITTERS Weather SENSOR TRANSMITTERS 4~20mA Environmental Monitoring Probe Sets Anemometer (Wind Speed) Wind Vane Light Energy Sensor (Pyranometer) Solar Radiation Shield Model THP-CL Humidity Sensor Temperature

More information

Lecture 4 Insulated glass units

Lecture 4 Insulated glass units ADVANCED DESIGN OF GLASS STRUCTURES Lecture 4 Insulated glass units Viorel Ungureanu 5011-1-011-1-CZ-ERA MUNDUS-EMMC Introduction An insulating glass unit (IGU) is a structural transparent element aiming

More information

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6956 Revision 1 ARL

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6956 Revision 1 ARL ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT -SA6956 Revision 1 Subject: Sound Absorption Test Date: 04 January 2017 Contents: on Sound Absorption Data, One-third Octave bands Sound

More information

P5 Heat and Particles Revision Kinetic Model of Matter: States of matter

P5 Heat and Particles Revision Kinetic Model of Matter: States of matter P5 Heat and Particles Revision Kinetic Model of Matter: States of matter State Size Shape Solid occupies a fixed volume has a fixed shape Liquid occupies a fixed volume takes the shape of its container

More information

Designation: NWI DIF Horizontal Hail impact Standard

Designation: NWI DIF Horizontal Hail impact Standard Designation: NWI DIF Horizontal Hail impact Standard 2.1.2015 Standard Test Method for Materials attached to Vertical or Near Vertical Surfaces and Their Resistance to Horizontally Propelled Freezer Ice

More information

Cat# LED Linear High Bay 100W

Cat# LED Linear High Bay 100W Cat# 71724 LED Linear High Bay 100W QPL ID # PRNKSMPK OVERALL LAMP PARAMETERS LED DRIVER LIFESPAN & ENVIRONMENT OTHERS Model: Input Voltage Input Current Input Power Power Factor Luminance Luminous Efficiency

More information

DEVELOPMENT OF THE MEASURING SYSTEM FOR ANALYSING THE THERMAL PROPERTIES OF CLOTHING

DEVELOPMENT OF THE MEASURING SYSTEM FOR ANALYSING THE THERMAL PROPERTIES OF CLOTHING DEVELOPMENT OF THE MEASURING SYSTEM FOR ANALYSING THE THERMAL PROPERTIES OF CLOTHING Dubravko ROGALE; Snježana FIRŠT ROGALE & Ivana ŠPELIĆ Abstract:The measuring system for assessing static and dynamic

More information

TEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES

TEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES SEMI G38-0996 N/A SEMI 1987, 1996 TEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES 1 Purpose The purpose of this test is to determine

More information

EXTERIOR FRAMING EXTERIOR FRAMING

EXTERIOR FRAMING EXTERIOR FRAMING 1 EXTERIOR FRAMING BUILDSTRONG www.buildstrong.com 2 TABLE OF CONTENTS Product Identification...........................5 General Product Information....................... 4-5 Compliance Guaranteed...............................

More information

THE IMPLICATION OF ENERGY EFFICIENT BUILDING ENVELOPE DETAILS FOR ICE AND SNOW FORMATION PATTERNS ON BUILDINGS

THE IMPLICATION OF ENERGY EFFICIENT BUILDING ENVELOPE DETAILS FOR ICE AND SNOW FORMATION PATTERNS ON BUILDINGS THE IMPLICATION OF ENERGY EFFICIENT BUILDING ENVELOPE DETAILS FOR ICE AND SNOW FORMATION PATTERNS ON BUILDINGS Neil Norris, Dave André and Peter Adams, Morrison Hershfield Limited, and Mike Carter and

More information

17.01 Maxblock Sunshades by Tubelite Description

17.01 Maxblock Sunshades by Tubelite Description 17.01 Description Description Effectively reduce Solar Heat Gain by shading vision glass areas of the building envelope with Tubelite s Maxblock tm sun shades. Cooling costs can be significantly lowered,

More information

Solar Flat Plate Thermal Collector

Solar Flat Plate Thermal Collector Solar Flat Plate Thermal Collector INTRODUCTION: Solar heater is one of the simplest and basic technologies in the solar energy field. Collector is the heart of any solar heating system. It absorbs and

More information

AR/IA 241 LN 231 Lecture 4: Fundamental of Energy

AR/IA 241 LN 231 Lecture 4: Fundamental of Energy Faculty of Architecture and Planning Thammasat University A/IA 24 LN 23 Lecture 4: Fundamental of Energy Author: Asst. Prof. Chalermwat Tantasavasdi. Heat For a specific substance, the heat given to the

More information

UNIT FOUR SOLAR COLLECTORS

UNIT FOUR SOLAR COLLECTORS ME 476 Solar Energy UNIT FOUR SOLAR COLLECTORS Flat Plate Collectors Outline 2 What are flat plate collectors? Types of flat plate collectors Applications of flat plate collectors Materials of construction

More information

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z540-1-1994 A.A. JANSSON Inc. 2070 Airport Road Waterford, MI 48327-1204 Justin Frazzini Phone: 248 674 4811 CALIBRATION Valid To: August 31, 2016

More information

Building Envelope Requirements Overview Page 3-4

Building Envelope Requirements Overview Page 3-4 Building Envelope Requirements Overview Page 3-4 The benefit of a high reflectance surface is obvious: while dark surfaces absorb the sun s energy (visible light, invisible infrared. and ultraviolet radiation)

More information

A quantitative infrared thermography method for the assessment of windows thermal transmittance

A quantitative infrared thermography method for the assessment of windows thermal transmittance A quantitative infrared thermography method for the assessment of windows thermal transmittance FRANCESCO BIANCHI, GIORGIO BALDINELLI, FRANCESCO ASDRUBALI Department of Engineering University of Perugia

More information

Project PAJ2 Dynamic Performance of Adhesively Bonded Joints. Report No. 3 August Proposed Draft for the Revision of ISO

Project PAJ2 Dynamic Performance of Adhesively Bonded Joints. Report No. 3 August Proposed Draft for the Revision of ISO NPL Report CMMT(A)81 Project PAJ2 Dynamic Performance of Adhesively Bonded Joints Report No. 3 August 1997 Proposed Draft for the Revision of ISO 11003-2 Adhesives - Determination of Shear Behaviour of

More information

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents Type test report O Plus Dry Bushing 69 kv system, 0 kv BIL, 000 A Table of contents Abstract... 2 2 Certification... 2 Introduction.... Description and ratings....2 Overview of tests.... Applicable standards....4

More information

REPORT NUMBER: GZU-001 ORIGINAL ISSUE DATE:

REPORT NUMBER: GZU-001 ORIGINAL ISSUE DATE: REPORT NUMBER: 131119020GZU-001 ORIGINAL ISSUE DATE: 2013-12-12 EVALUATION CENTER TEST REPORT Intertek Testing Services Shenzhen Ltd. Guangzhou Branch Block E, No.7-2 Guang Dong Software Science Park,

More information

1040 SLIDING MALL FRONT

1040 SLIDING MALL FRONT APRIL, 00 00 SLIDING MALL FRONT INDEX INDEX... ELEVATIONS/VERTICAL SECTION DETAILS... HORIZONTAL SECTION DETAILS... EGRESS DOOR... - STACK AREA LAYOUT... - SIZE LIMITATIONS... HARDWARE...0 LAWS AND BUILDING

More information

Morris Products 53 Carey Road, Queensbury, NY 12804

Morris Products 53 Carey Road, Queensbury, NY 12804 Catalog Number 71604 UPC Number 60198671604 Description LED Ultra Thin Canopy Fixture 45W Voltage: 120/208/240/277 QPL ID # P89A8PQ3 Features Intergral Cooling Fin Releases the Heat Efficiently to Maintain

More information

VOC TEST REPORT M1. 6 April Regulation or protocol Conclusion Version of regulation or protocol

VOC TEST REPORT M1. 6 April Regulation or protocol Conclusion Version of regulation or protocol Dana Lim A/S Københavnsvej 220 4600 Køge DENMARK Eurofins Product Testing A/S Smedeskovvej 38 8464 Galten Denmark VOC@eurofins.com www.eurofins.com/voc-testing VOC TEST REPORT M1 6 April 2017 1 Sample

More information

Heat stress index. Dewpoint. pressure. altitude

Heat stress index. Dewpoint. pressure. altitude Kestrel 4200 Measures Volume air flow in cfm, L/s, m³/s, m³/m, m³/h Air velocity (current, average, and maximum) Heat stress index Windchill Relative humidity Dewpoint in F or C Humidity ratio Barometric

More information

ME 4/549 Lab Assignment 5: Single Block Experiment Spring 2006 due 1 June 2006

ME 4/549 Lab Assignment 5: Single Block Experiment Spring 2006 due 1 June 2006 ME 4/549 Lab Assignment 5: Single Block Experiment Spring 2006 due 1 June 2006 version May 23, 2006 1 Objective The objective of the laboratory exercise is to measure the convective heat transfer coefficient

More information

ESRL Module 8. Heat Transfer - Heat Recovery Steam Generator Numerical Analysis

ESRL Module 8. Heat Transfer - Heat Recovery Steam Generator Numerical Analysis ESRL Module 8. Heat Transfer - Heat Recovery Steam Generator Numerical Analysis Prepared by F. Carl Knopf, Chemical Engineering Department, Louisiana State University Documentation Module Use Expected

More information

Capstone Design: Energy Efficient Windows Triple Pane Window Analysis

Capstone Design: Energy Efficient Windows Triple Pane Window Analysis University of Tennessee, Knoxville Trace: Tennessee Research and Creative Exchange University of Tennessee Honors Thesis Projects University of Tennessee Honors Program 5-2010 Capstone Design: Energy Efficient

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Atlanta, GA Sound Absorption CONDUCTED: 2016-10-14 Page 1 of 8 ON: D-GIK Panels TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National Institute of

More information

Standard Test Method for Thermal Conductivity of Refractories 1

Standard Test Method for Thermal Conductivity of Refractories 1 Designation: C 201 93 (Reapproved 1998) Standard Test Method for Thermal Conductivity of Refractories 1 This standard is issued under the fixed designation C 201; the number immediately following the designation

More information

*Refer to IBC Section , applicable when fall protection is required. Glass stresses are designed for a safety factor of of 4.0 (IBC ).

*Refer to IBC Section , applicable when fall protection is required. Glass stresses are designed for a safety factor of of 4.0 (IBC ). Architectural Railing Division C.R.Laurence Co., Inc. 2503 E Vernon Ave. Los Angeles, CA 90058 (T) 800.421.6144 (F) 800.587.7501 www.crlaurence.com 12 JAN 2011 SUBJ: TAPER-LOC SYSTEM DRY-GLAZE LAMINATED

More information

product manual H-3220A Benkelman Beam

product manual H-3220A Benkelman Beam 05.12 product manual H-3220A Benkelman Beam General The H-3220A Benkelman Beam Apparatus is a convenient and accurate device used for measuring the deflection of flexible pavements under moving wheel

More information

Certificate of Accreditation

Certificate of Accreditation PERRY JOHNSON LABORATORY ACCREDITATION, INC. Certificate of Accreditation Perry Johnson Laboratory Accreditation, Inc. has assessed the Laboratory of:. (Hereinafter called the Organization) and hereby

More information

Standard Test Method for Steady-State Heat Transfer Properties of Horizontal Pipe Insulation 1

Standard Test Method for Steady-State Heat Transfer Properties of Horizontal Pipe Insulation 1 Designation: C 335 95 Standard Test Method for Steady-State Heat Transfer Properties of Horizontal Pipe Insulation 1 This standard is issued under the fixed designation C 335; the number immediately following

More information

File SV16101 Project 05CA December 1, 2005 REPORT

File SV16101 Project 05CA December 1, 2005 REPORT File SV16101 Project 05CA51080 December 1, 2005 REPORT on COMMERCIAL INSPECTION AND TESTING INVESTIGATION OF Roof Panel Coatings for Thermal Emittance and Solar Reflectance Astec Paints Australia LTD Australia

More information

Collector test according to EN ,2:2002

Collector test according to EN ,2:2002 Test Report: KTB Nr. 2003-18-b-en Collector test according to EN 12975-1,2:2002 for: RM Solar Ltd Brand Name: S-Class Responsible for Testing: Dipl.-Ing. (FH) A. Schäfer Date: 17th July 2006 Address: Fraunhofer-Institute

More information