1 MODULE TITLE : ELECTRICAL SUPPLY AND DISTRIBUTION SYSTEMS TOPIC TITLE : THE OPERATION OF THREE-PHASE TRANSFORMERS IN PARALLEL AND GENERATORS ON INFINITE BUSBARS LESSON 2 : OPERATING CHARACTERISTICS OF THREE PHASE GENERATORS ON INFINITE BUSBARS ESD - 2-2

2 Published by School of Science & Engineering Teesside University Tees Valley, UK TS1 3BA +44 (0) All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording or otherwise without the prior permission of the Copyright owner. This book is sold subject to the condition that it shall not, by way of trade or otherwise, be lent, re-sold, hired out or otherwise circulated without the publisher's prior consent in any form of binding or cover other than that in which it is published and without a similar condition including this condition being imposed on the subsequent purchaser.

3 1 INTRODUCTION In this lesson we are introduced to another essential item of equipment required for an electrical supply system, the generator (or alternator as a.c. generators are often referred to). The lesson covers aspects of commercial generators and the electrical parameters that affect the efficient output of generated electrical energy. The lesson shows the importance of the 'capability' chart which is utilised to predict limits of the possible actual performance of the industrial generator against the theoretical ideal. YOUR AIMS At the end of this lesson you should be able to: correctly construct the capability chart for a synchronous generator indicate the performance limitations of a generator using the above chart. STUDY ADVICE You will need to have graph paper, a compass and a protractor available to complete this lesson.

4 2 GENERATOR CAPABILITY CHARTS This section deals with the concepts behind, and accurate scaled production of, a special chart which power station engineers and operators use to get the best out of the machinery without incurring electrical or mechanical damage. Although we only use graph paper to produce a scaled drawing, modern power stations display the chart on large monitor screens or in the form of a wallmounted, manually operated mimic diagram. MINDING YOUR Ps AND Qs A main power system generator is primarily a device for converting rotary mechanical power to electrical power. However, most industrial and commercial loads also require reactive power (VAr). This means that unless a consumer generates his own leading or lagging VArs they must be provided by the supply authority so that the output from the national generators will be a combination of real power (P) and reactive power (Q). Thus, MVA = phasor sum of MW + MVAr. Ignoring machine internal losses, the electric power output equals the mechanical power input from the prime mover. Consider FIGURE 1 opposite, which shows a mechanical prime mover driving a synchronous generator which is supplying both real and reactive power (P + Q).

5 3 Engine prime mover Synchronous generator 3φ power out (P + Q) Fuel in Mechanical power DC excitation (E) FIG. 1 Power Generation System You will see from the diagram that the power station operator has control over two parameters the engine's fuel which varies the mechanical power the direct current into the rotor which varies the excitation. Think about FIGURE 1 and the two variable parameters and decide which of the electrical powers, P or Q, is varied by altering the mechanical power and which is varied by altering the d.c. excitation. Variation of... = Variation of P Variation of... = Variation of Q

6 4 Since mechanical prime movers are only capable of providing real power (P), any reactive power (Q) requirement will have to be met by variation of the excitation of the synchronous machine. Therefore Variation of Mechanical Power = Variation of P Variation of Excitation = Variation of Q For example, if a machine is generating real power at unity power factor (u.p.f.), increasing the excitation will produce lagging reactive power. In the same way, decreasing the excitation from the u.p.f. position will produce leading reactive power. (It is the opposite when the machine is being used as a synchronous motor.) INFINITE CAPACITY Remember that the UK power system consists of about 175 synchronous generators operating in parallel and feeding the national grid system. The approximate total grid system capacity is: day MW night MW A national power system such as the national grid is thought of as having infinite capacity since the connection of any one load or loss of any one generator, does not markedly affect voltage and frequency. Therefore, the connection points or nodes of the national grid are known as infinite busbars.

7 5 AN INTRODUCTION TO GENERATOR CAPABILITY CHARTS When two or more synchronous machines are operating as generators on infinite busbars, what is known as the operating or capability chart for any particular machine is of considerable importance. A capability chart is an envelope or system of boundaries within which a particular machine may satisfactorily work without fear of damage due to overload or risk of instability. The limits of operation imposed to prevent damage to the generating set are the prime mover limit the rotor heating limit the stator heating limit the theoretical stability limit the practical stability limit. Consider FIGURE 2 which shows the circuit of a synchronous machine. X S R I E IX S IR V IZ S FIG. 2 Synchronous Machine Equivalent Circuit

8 6 Since the voltages around the circuit must equate, the phasor E must equal the phasor sum of the other volt drops. i.e. E = V + IXS + IR Since the phasor sum of IX S and IR = IZ S, E = V + IZS Take the equation E = V + IZ S and solve it for I. I = E Z S V Look at the equation for I. Since the solution contains a common denominator we should be in a position to conclude that the phasor I (the supply current) is made up of two other phasors. Decide what these two phasors are, which when added together, give the supply current of the machine and rearrange the equation to show this. Our answer is in the text that follows.

9 7 I = E V Z S so I = E Z S V Z S Now remember that I is the sum of the two phasors, so I E V = + Z Z S S Now providing the busbar voltage remains constant (which it does to within a few percent) and since Z S is constant V is constant in magnitude and direction and does not change with Z S variation in excitation or power input E alters in magnitude with excitation and in direction with power input. Z S FIGURE 3 shows the various currents and busbar voltage with the machine under-excited, i.e. leading power factor.

10 8 V Z S δ δ is known as the load angle ψ φ E Z S I ψ X ψ = tan ( S ) 1 R + V Z S This is the correct position for V since Z S is inductive Z S FIG. 3 Phasor Diagram showing leading power factor Note how the addition of the two phasors current I. V Z S and E Z S equals the machine When you multiply each current phasor by the busbar voltage (V), the phasor I becomes an indicator of machine voltamps (VI) so that the phasor diagram can be redrawn as FIGURE 4 showing this. Note that the phasor + V Z S has been dropped since its only function was to establish the position and direction of V. Z S

11 9 V 2 Z S Q δ ψ φ VE Z S VI E since V Z S is constant P FIG. 4 Phasor diagram showing the phasors in FIGURE 3 multiplied by the busbar voltage So what was originally a current diagram (FIGURE 3) becomes a power diagram (FIGURE 4) by multiplying the current phasors by the common busbar voltage. VE This means that V 2 Z is a voltamps phasor as is and of course the S phasor VI. Z S This is why the voltage reference phasor in FIGURE 3 has been replaced with a real power axis (P) and a corresponding reactive power axis (Q). The projection of VI onto the horizontal axis gives the real power in watts. Projection onto the vertical axis gives the reactive power in VArs. FIGURE 5 shows you how vertical locus lines (representing constant real power) and horizontal loci (representing constant reactive power) can also be drawn.

12 10 V 2 Z S Q E ψ I φ Constant VAr line P Constant power line Point P 1 FIG. 5 Phasor diagram with locus lines (It should be noted that the generated voltage E is proportional to the d.c. excitation current fed to the rotor of the generator to establish a magnetic field which when rotated induces the generated voltage E in the stator.) Look at FIGURE 5. It should be apparent that the amount of real power being generated at P can be read off. Clearly one needs to be careful to draw a diagram like this to a suitable scale. Think about each phasor, angle and axis and attempt to list up to six parameters in addition to real power (P) which could also be read off, if scales are known.

13 11 The list could include: the reactive power (Q) the supply current (I) the output power factor (φ) the output voltamps (VI) the load angle (δ) the percentage excitation (E) It is also very important to note that you can obtain unknown quantities from the basic diagram providing one or two parameters are drawn in. DRAWING A LOAD DIAGRAM Exercise The following exercise will take you step by step through the process of drawing and using a load diagram. You'll need some graph paper to do it on. Each step you have to take is indicated by a bullet. On a piece of graph paper long way up (portrait format), draw a vertical axis 40 mm in from the left-hand edge. Label this axis Reactive Power Lead at the top, and Reactive Power Lag at the bottom. Draw a horizontal axis across the centre and label it Real Power. Scale these axes off at 20 mm = 10 units. Do this for 50 units in each case. This represents maximums of 50 MW on the real power axis and 50 MVAr lead and lag on the reactive power axis.

14 12 FIGURE 6 has been included as the solution to this exercise and if you are really stuck (there's no benefit in just looking at it straight away) have a look at the diagram. Try not to look at it all just the area you have difficulty with. Start at the zero point and draw in the phasor V 2 using the values Z S length = 85 mm ψ = 80 Draw the current phasor I 1 using the values length = 60 mm φ = (power factor) = 30 lead Join the ends of V 2 and I 1 to give the excitation phasor E 1. Z S (The length of E 1 should be close to 85 mm if you've followed the instructions correctly.) We can now imagine that our machine is working under these conditions and if we read off the real and reactive power we should be delivering 26 MW and 15 MVAr lead. Check this for yourself on your diagram. What does your diagram show the load angle (δ ) to be? (It should be forty-one degrees.) Now suppose National Control requests us to supply the same power but with 10 MVAr lag (i.e. 26 MW, 10 MVAr lag).

15 13 We don't need to touch the real power input but we must alter...? (the excitation E 1 ). To force the output current to move vertically downwards to 10 MVAr lag we'll have to increase excitation. Do this now and read off E 2 and I 2. Write the values you get in the space provided. E = I = 2 2 Now calculate these values as a percentage of their original values. You should get E 2 = 123 mm and and I 2 = 55 mm. Expressed as a % of their original values: = 144.% 7 for E and = 91.% 7 for I Measure the new load angle (δ ) and note it below. It should be reduced to about FIGURE 6 shows you what you should have drawn for this exercise. Study it carefully to see if there are any differences you can't account for between FIGURE 6 and your own effort. It is important for you to understand the diagram fully at this stage.

16 14 Reactive power lead MVAr 50 V 2 Z S 40 δ E 1 10 I 1 ψ 0 φ E 2 Real power MW 10 I Reactive power lag MVAr 50 FIG. 6 Solution to Exercise

17 15 SELF-ASSESSMENT QUESTION 1 Imagine you are working at your last position, i.e. E 2, I 2 on FIGURE 6. National Control now requests that your output should rise to 45 MW, 30 MVAr lag. What control adjustments (expressed as a percentage) are necessary to achieve this? Remember that you can only make two external adjustments, real power and excitation. Check your solution with that on page 44.

18 16 You should now be able to appreciate that you can move to any point on the chart, that is, to any specified output, by fiddling about with these two parameters. In this way the combined output of all the national generators can be juggled to meet the demand at any time. However, there are snags! What do you think would be the value of the excitation E and the load angle δ if all the real and reactive power were reduced to zero, i.e. I = 0? Write your answer and explanation in the space below and compare your answer in the text that follows. You should have concluded that as the powers, and thus the current, are reduced, E swings closer and closer to V Z S 2. Eventually, when the current is zero, it will lie coincident with V Z S 2 so that δ is also zero. This is the excitation required on no load and is termed 1.0 p.u. or 100% excitation.

19 17 GENERAL LOAD DIAGRAMS: STABILITY LIMITS Using the concepts described in the previous section, what is known as a general load diagram can be drawn. Study FIGURE 7 on the next page and concentrate on the excitation line. Note that since the machine resistance R is usually very small compared to the synchronous reactance X S, R is ignored. So X S becomes the machine impedance Z S and ψ is 90. This assumption will be made from now on since it greatly simplifies matters. We discovered previously that when the machine current is zero, excitation is vertical and lies along the 'Q' line as. V V or Z X 2 2 S S Remember that this special indeed unique situation is referred to as 100% excitation. If this value of excitation is being applied to the machine then, as the real power input is increased, the machine will generate and produce real power (active current) at its terminals. Since power is being produced and since one can think of the excitation and current phasors as being 'fastened together' at their tips, they both follow the arc100% excitation as the power increases. Find the line labelled Stability Limit on FIGURE 7.

20 18 Q lead V 2 Z S 50% Excitation 100% Excitation Excitation Theoretical stability limit MVA lead ψ P MVA lag Q lag FIG. 7 General Load Diagram for Synchronous Generator

21 19 At some particular value of power, excitation will lie along this line. Note how the load angle (δ) would increase as the power increases. Now suppose the mechanical power input has been further increased; but remember that the length of the excitation phasor has not altered Study FIGURE 7 and see if you can work out whether excitation would tend to swing beyond the steady-state stability limit. We should see that excitation would tend to swing above the stability limit if power input is increased. Now attempt Self-Assessment Question 2.

22 20 SELF-ASSESSMENT QUESTION 2 Consider the following: the horizontal axis in FIGURE 7 represents electrical power delivered to the busbars the load angle increases as the mechanical power input increases. What do you think would be the consequences of continuing to increase the mechanical power input? Make a sketch on a separate piece of paper to help you draw conclusions. Check your answers against the solution given on page 44.

23 21 But what happens to the excess power? It's a bit like opening the throttle in a powerful motor car. The rear wheels cannot convert all the power fed to them as forward motion and so they slip on the road surface and synchronism is lost between the power conversion mechanism (tyres) and the road. The same thing happens with the generator in that the excess mechanical power results in the rotor being torn from synchronism with the stator magnetic field (which is connected to the national grid) so that the rotor accelerates away. This results in mechanical overspeed as well as large electrical currents, so that one or more of the protective systems operate to shut down the generator set. It is important therefore that sets are not operated on, or even near, the theoretical stability limit. OPERATIONAL LIMITS ON GENERATOR SETS Bearing in mind what we've just learned about stability limits in the previous section, it's time to look in more detail at the five operational limits imposed on generator sets. (i) the turbine (or prime mover) limit This is also often referred to as the MW limit and is determined by the power output capabilities of the prime mover (engine). This limit gives the maximum active power output line on a capability chart.

24 22 (ii) the rotor heating limit This is the maximum direct current which can be drawn by the rotor for purposes of exciting the machine without leading to overheating. It is often referred to as the excitation limit and determines the maximum excitation circle on the chart and often the lagging reactive limit. (iii) the stator heating limit This is sometimes referred to as the MVA limit. It determines the maximum stator current the set can supply without leading to overheating. The stator heating limit produces the maximum MVA circle on the chart. (Note also that for constant current I and MVA, IX S is constant with its locus a circle with its centre being the origin.) (iv) the theoretical stability limit For any given value of excitation (rotor current) the ability of the machine to remain stable (i.e. in synchronism with the system) becomes less as the power output increases. If there is a sudden increase in power input, a point is reached when the restoring torque is zero. When this happens the machine quickly accelerates out of synchronism.

25 23 (v) the practical stability limit As you know it is undesirable for a machine to be operated to the limit of its theoretical stability and operators must know to what reasonably safe limit the machine may be taken. The practical stability limit is a safety factor which allows the machine to respond to a sudden increase in power demand with no corresponding increase in excitation. This limit is obtained by subtracting an assumed stability margin (usually 0.1 p.u. power) from each point on the theoretical stability limit. These five limits can now be drawn to suitable scales so that they form an envelope or system of boundaries (chart) within which a generating set may safely work without risk of damage or instability. (This chart is sometimes referred to as a shark fin chart.) Look at the example of an operating chart, FIGURE 8, and note the position of the various operating limits.

26 24 Q lead Theoretical stability limit Practical stability limit Turbine limit P Excitation limit Stator heat limit Q lag FIG. 8

27 25 CONSTRUCTING AN OPERATING CHART It is now time to look at the data required to construct an operating chart and how it's done. You'll need to have graph paper, a protractor and a pair of compasses to hand. Assumptions and Working Bases It is an accepted practice when producing and working with operating charts to neglect the machine resistance and consider only the synchronous reactance X S. It is usual to work in per-unit terms taking the following base values the machine rating as the power base S = 1.0 p.u. power the machine terminal voltage per phase as the voltage base V ph = 10. p.u. volts The operating chart, FIGURE 8, is constructed around the machine short circuit ratio (SCR). This is a comparison of the excitation required to produce normal terminal voltage on no-load with the excitation required to overcome the stator demagnetising m.m.f. (i.e. 90 lag load). i.e. SCR = excitation for rated volts on O/C excitation for rated current on S/C

28 26 We have seen the importance of the phasor 1 the short circuit ratio is that SCR =. XS V 2 X S. The reason for introducing If we know the SCR then you can find the length of V X S 2 as well. CONSTRUCTING THE MORE STRAIGHTFORWARD LIMITS The turbine (prime mover) limit, rotor heating limit, stator heating limit and theoretical stability limit are all relatively simple to draw in. The practical stability limit is more involved. All these are dealt with in the following exercise. Exercise 2 A 3-phase synchronous generator rated at 600 MVA is connected to infinite busbars. Using the data for the machine listed below we will methodically construct the machine's operating chart. Short circuit ratio = 0.5 p.u. Excitation limit = 2.8 p.u. Maximum MVA limit = 600 MVA Turbine Power limit = 500 MW Practical Stability margin = 10% full load power. You can now draw the more straightforward lines on the chart. SCR = 1 X S 1 XS = = SCR 20. p.u.

29 27 Busbar voltage per phase = 1.0 p.u. volts V p.u. So = Z 20. = 05. p.u. i.e. 0.5 p.u. lead. S ( ) The MVA limit is 1.0 p.u. power so 500 MW relates to a real power limit of = p.u. Take a sheet of graph paper long way up and draw a horizontal reference across the middle (P axis) and a vertical reference 20 mm in from the edge (Q axis). Mark these off so that 10 mm = 0.1 p.u. Now draw in the theoretical stability limit at 0.5 p.u. lead, i.e. V Z2 S Put the point of the compass at zero. Now open it up to 1.0 p.u. power and swing it in the arc from 1.0 p.u. reactive lag to the real power axis. This gives the maximum voltamps the machine can deliver. This value is also known as the stator heat limit since exceeding this value draws more current than the machine is designed for, leading to overheating.

30 28 Next, draw in a vertical line at p.u. real power. This indicates the turbine or prime mover limit such that operation to the right of this line will overload and damage the turbine. V 2 Next put the compass point at Z on the reactive lead scale, extend it S down the reactive scale for 140 mm and swing in the excitation limit arc. Why 140 mm? Well, at zero current the excitation phasor will be coincident with 2 V, i.e. 50 mm long. This is known as 100% or 1.0 p.u. ZS excitation. We are told that the excitation limit is to be 2.8 p.u. (or 280%) so that mm = 140 mm. So the maximum length of the excitation phasor is 140 mm pivoting 2 from V. Z S FIGURE 9 shows the operating chart completed to this point.

31 29 Reactive lead p.u. 1.0 V 2 Z S Turbine (or prime mover) limit Theoretical stability limit Real power p.u Excitation limit (Rotor heating limit) Reactive lag p.u. Stator heating limit (MVA limit) FIG. 9 Partial Operating Chart: Exercise 2

32 30 We are now ready to put in the practical stability limit. This has been left till last since it is the most complicated to construct. Constructing the practical stability limit Project the turbine limit on your operating chart up until it crosses the theoretical stability limit. Now measure the length of the portion of the theoretical stability limit line between the reactive power axis and the turbine limit and divide it by 10 (remember 10%, i.e. 1/10 practical stability margin in the data). This should give you 83.3 mm/10 = 8.33 mm Divide up the line into 10 equal spaces 8.33 mm long. (This is only to aid construction so faint pencil will do.) V 2 Now draw the 9 lines the full height of as in FIGURE 10. Z S

33 31 Q lead V 2 Z S Turbine limit Stability limit 8.33 mm P Q lag FIG. 10 Next, put the point of the compasses on V Z extending it along the stability limit line to the turbine limit line. 2 S Keeping this radius, swing an arc down until it cuts the next vertical line 8.33 mm to the left of the turbine limit. Put a small cross at the intersection of the vertical line and the arc. Now put the compass pencil on the line 8.33 mm to the left of the turbine limit along the stability limit line. Swing this arc down until it cuts the next vertical line to the left then mark the intersection with a cross.

34 32 Repeat the procedure for all the remaining vertical lines as in FIGURE 11. Compass point Compass pencil Turbine limit V 2 Z S Stability limit 8.33 mm SCR FIG. 11 We are now ready to join up the crosses except that there is one missing on the turbine limit line. It is therefore necessary to go beyond this line by 8.33 mm and swing an arc back as shown in FIGURE 12. Do this now. Joining the crosses should give you a nice smooth curve. We have now put in a practical stability limit based on 10% full load power. An old fashioned term (which sums it up better) is 10% power in hand.

35 33 V 2 Z S 8.3 mm Practical stability limit FIG. 12

36 34 The 10% Practical Stability Limit: The Theory Suppose a machine has a certain excitation on and is working along the practical stability limit line as shown below in FIGURE 13. V 2 Z S Theoretical stability limit E Practical stability limit I Turbine limit FIG. 13 Practical Stability Limit We know that the practical stability limit line has been constructed using 10% power in hand system. So, if the machine is working on the line, a sudden increase in real power input of 10% will move the excitation phasor to the next 10% power increment to the right. Since its length remains unaltered, it will lie coincident to the theoretical stability limit line. This is shown in FIGURE 14.

37 35 V 2 Z S E I Theoretical stability limit Practical stability limit 10% power increase Turbine limit FIG. 14 Real Power Increase on Practical Stability Line Can you now see what will happen when a machine working on a 10% of full load power stability limit line experiences a sudden increase in 10% of full load power? The increase will cause the machine to be working on its limit of stability. Providing a machine is working on, or within, the practical stability limit, it will always have a 10% power-in-hand factor before becoming unstable. For normal operation this is quite adequate. Look at the Capability Chart of FIGURE 8. You will see that a system of boundaries has been formed between the zero power axis, part of the excitation limit, part of the stator MVA limit, part of the turbine limit and the practical stability limit.

38 36 It is often helpful to lightly shade in along the inside of the envelope of boundaries as shown in FIGURE 15. (It will be beneficial if you photocopy two or three copies of this figure for future use in the lesson.)

39 37 Reactive power Q lead p.u. 0.8 Turbine Limit 0.6 Theoretical Stability Limit 0.4 Practical Stability Limit Real power P p.u Excitation Limit Stator Heating Limit Q lag p.u. FIG. 15

40 38 Providing the machine is operated within the boundaries, no risk of damage or instability should ensue. In other words, the machine is capable of working within the boundaries. Hence the name Capability Chart. Before we go any further, review what you have done in this section to make sure you can both read the capability chart and understand the steps needed to construct it. Then test yourself by doing Self-Assessment Question 3.

41 39 SELF-ASSESSMENT QUESTION 3 You are given the following data about a 600 MVA, 11 kv, 50 Hz, 3 ph, star connected, synchronous generator connected to an infinite busbar. SCR = 0.5 maximum power limit = 500 MW excitation limit is that which gives the rated MVA at p.f. = lag Construct the operating chart of the generator assuming a stability limit of 10% of maximum power output. Compare your chart with that shown on page 46.

42 40 GENERATOR PERFORMANCE LIMITS This section takes the operating or capability chart you produced in the previous section and uses it to predict the performance limitations of any particular machine with regard to its real and reactive power output. Look at FIGURE 15 again the capability chart. If the machine is working at any point on the envelope of boundaries, the real and reactive powers can be read off the respective axes. Suppose the machine is operating at the intersection of the stator MVA limit and the excitation limit. You can now determine a certain amount of information about how the machine is working. From FIGURE 15 work out and note in the spaces below and compare with our answers on the next page. the real power output the reactive power output the p.u. excitation the operating power factor the apparent power output.

43 41 the real power output From the intersection of the two limit lines project up onto the p.u. real power axis and read the value. It should be in the order of 0.71 per unit. Since the basic power value of the machine was given as 600 MW the real power figure is found by multiplying the per-unit value by the base value, so that real power = = 426 MW. the reactive power output In a similar manner project across from the intersection of the two limits and read off the p.u. reactive power. It should be in the order of 0.71 per unit. It is just a coincidence that this is the same as your previous reading. The actual reactive power = = 426 MVAr lag. the p.u. excitation Since the machine is working on the excitation limit, the p.u. excitation must be 2.8 (from original data used to construct the chart). the operating power factor This can be obtained by using the real and reactive power in the form (MW jmvar) i.e. ( ) ( 426 j426) S = P jq = So S = Therefore, the operating power factor = cos 45 = p.f. lag. An added bonus is that we can find the apparent power output at the same time, although this will be checked using another method later.

44 42 An alternative method for finding the power factor is to draw in the current phasor from the zero power axis to the stator limit intersection and measure the power factor angle. (See FIGURE 16) Q lead φ P Excitation limit Stator limit Q lag FIG. 16 An alternative method of finding the power factor φ should be in the order of 44 so that cos 44 = p.f. lag. Don't worry that the two methods of finding the power factor don't tie up exactly remember they have been obtained from a scale drawing. the apparent power output Since the machine is working on the stator MVA limit, the apparent power output must therefore be 600 MVA. Now test how well you can interpret the Capability Chart by doing Self- Assessment Question 4.

45 43 SELF-ASSESSMENT QUESTION 4 Look at Diagram 15 again, but suppose now that the machine is working on the practical stability limit and producing 0.6 p.u. real power. Find the apparent power the reactive power the p.u. excitation the operating power factor the control adjustments necessary to enable the machine to produce 0.4 p.u. real power but still work on the practical stability limit. Our answers start on page 47.

46 44 ANSWERS TO SELF-ASSESSMENT QUESTIONS 1. Real power increase = = % increase excitation increase See FIGURE 17. = = % 7 increase 2. For a fixed value of excitation the load angle (δ) increases as the power input increases. This means that if the real power input continues to be increased when excitation lies along the stability limit, the tip of the phasor would swing back towards the zero power axis instead of moving away from it and the electrical power fed to the busbars would tend to decrease. This is a serious situation since there is now a mismatch between the mechanical power input and the electrical power output, i.e. the mechanical power input exceeds the electrical power output. 3. See FIGURE 18 following.

47 45 Reactive power Q lead MVAr 50 V 2 Z S 40 δ E 1 10 I 1 ψ 0 φ Real power MW E 2 10 I Reactive power Q lag MVAr 50 FIG. 17 Solution to Self-Assessment Question 1

48 46 Reactive power Q lead p.u. 0.8 Turbine Limit 0.6 Theoretical Stability Limit 0.4 Practical Stability Limit Real Power p.u Excitation Limit 0.8 Excitation limit pf = lag 1.0 Stator Heating Limit Q lag p.u. FIG. 18

49 47 4. FIGURE 19 shows the construction the apparent power Put the compass point on the zero power axis and the pencil on the intersection of 0.6 p.u. real power and the practical stability limit. Swing the pencil down to cut the real power axis (at about p.u.). The apparent power will be = 375 MVA the reactive power Read this off in p.u. form. It should be about 0.17 p.u. lead. The new excitation length is 69 mm. So excitation must be reduced from 91 mm to 69 mm = 22 mm = = 22 % % 2 reduction. So the reactive power is = 102 MVAr lead.

50 48 Reactive power Q lead p.u. 0.8 Turbine Limit 0.6 Theoretical Stability Limit 0.4 Practical Stability Limit 0.2 φ Real Power p.u Excitation Limit Stator Heating Limit p.u. Q lag p.u. FIG. 19

51 49 the p.u. excitation Put the compass point on operating point. V X S 2 and the pencil point on the Swing the pencil down to cut the reactive power axis. The length should be 69 mm from compass point to pencil point. Since 1.0 p.u. excitation = 50 mm p.u. excitation = = 138p.u.. the operating power factor Find this as before. φ should be about 15.5 so that the power factor = cos φ = 0.96 lead. control adjustments to move to new position. Only two adjustments can be made, i.e. power input and excitation. To reduce power from 0.6 p.u. to 0.4 p.u. means a decrease in real power input of 0.2 p.u. = = 120 MW decrease.

52 50 SUMMARY In this lesson we have seen that it is important to restrict the operation of power system generators to within certain limits in order to ensure system stability and avoid damage. We have developed the operating chart for a large generator, showing the four main limits which constitute operational boundaries. Finally, we have used the chart to determine the output performance limitations of a large generator which must remain within stated operational boundaries.

The Operation of a Generator on Infinite Busbars

The Operation of a Generator on Infinite Busbars The Operation of a Generator on Infinite Busbars In order to simplify the ideas as much as possible the resistance of the generator will be neglected; in practice this assumption is usually reasonable.

More information

Introduction to Synchronous. Machines. Kevin Gaughan

Introduction to Synchronous. Machines. Kevin Gaughan Introduction to Synchronous Machines Kevin Gaughan The Synchronous Machine An AC machine (generator or motor) with a stator winding (usually 3 phase) generating a rotating magnetic field and a rotor carrying

More information

Generators. What its all about

Generators. What its all about Generators What its all about How do we make a generator? Synchronous Operation Rotor Magnetic Field Stator Magnetic Field Forces and Magnetic Fields Force Between Fields Motoring Generators & motors are

More information

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 9 Transmission Line Steady State Operation Welcome to lesson 9, in Power

More information

Lesson 17: Synchronous Machines

Lesson 17: Synchronous Machines Lesson 17: Synchronous Machines ET 332b Ac Motors, Generators and Power Systems Lesson 17_et332b.pptx 1 Learning Objectives After this presentation you will be able to: Explain how synchronous machines

More information

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session Name: Student ID: Signature: THE UNIVERSITY OF NEW SOUTH WALES School of Electrical Engineering & Telecommunications FINALEXAMINATION Session 00 ELEC46 Power System Analysis TIME ALLOWED: 3 hours TOTAL

More information

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES ET 332b Ac Motors, Generators and Power Systems LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES 1 LEARNING OBJECTIVES After this presentation you will be able to: Interpret alternator phasor diagrams

More information

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester Electrical and Electronics Engineering EE 1352 Power System Analysis (Regulation 2008) Time: Three hours Answer all questions Part A (10

More information

Fault Calculation Methods

Fault Calculation Methods ELEC9713 Industrial and Commercial Power Systems Fault Calculation Methods There are two major problems that can occur in electrical systems: these are open circuits and short circuits. Of the two, the

More information

Synchronous Machines

Synchronous Machines Synchronous Machines Synchronous generators or alternators are used to convert mechanical power derived from steam, gas, or hydraulic-turbine to ac electric power Synchronous generators are the primary

More information

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015 ECE 325 Electric Energy System Components 7- Synchronous Machines Instructor: Kai Sun Fall 2015 1 Content (Materials are from Chapters 16-17) Synchronous Generators Synchronous Motors 2 Synchronous Generators

More information

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL 1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Power Systems: Generation, Transmission and Distribution Power Systems: Generation, Transmission and Distribution Power Systems:

More information

EE 451 Power System Stability

EE 451 Power System Stability EE 451 Power System Stability Power system operates in synchronous mode Power system is subjected to a wide range of disturbances (small and large) - Loads and generation changes - Network changes - Faults

More information

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A 1. What are the advantages of an inter connected system? The advantages of an inter-connected system are

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide direct current to the field winding of the synchronous generator. The excitation

More information

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1 ower ystems ower ystem tability QUETION BANK. A cylindrical rotor generator delivers 0.5 pu power in the steady-state to an infinite bus through a transmission line of reactance 0.5 pu. The generator no-load

More information

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.685 Electric Machines Problem Set 10 Issued November 11, 2013 Due November 20, 2013 Problem 1: Permanent

More information

LCR Series Circuits. AC Theory. Introduction to LCR Series Circuits. Module. What you'll learn in Module 9. Module 9 Introduction

LCR Series Circuits. AC Theory. Introduction to LCR Series Circuits. Module. What you'll learn in Module 9. Module 9 Introduction Module 9 AC Theory LCR Series Circuits Introduction to LCR Series Circuits What you'll learn in Module 9. Module 9 Introduction Introduction to LCR Series Circuits. Section 9.1 LCR Series Circuits. Amazing

More information

7. Transient stability

7. Transient stability 1 7. Transient stability In AC power system, each generator is to keep phase relationship according to the relevant power flow, i.e. for a certain reactance X, the both terminal voltages V1and V2, and

More information

MODULE TITLE : MASS AND ENERGY BALANCE TOPIC TITLE : ENERGY BALANCE TUTOR MARKED ASSIGNMENT 3

MODULE TITLE : MASS AND ENERGY BALANCE TOPIC TITLE : ENERGY BALANCE TUTOR MARKED ASSIGNMENT 3 THIS BOX MUST BE COMPLETED Student Code No.... Student's Signature... Date Submitted... Contact e-mail... MODULE TITLE : MASS AND ENERGY BALANCE TOPIC TITLE : ENERGY BALANCE TUTOR MARKED ASSIGNMENT 3 NAME...

More information

Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur Power System Engineering Prof. Debapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture 41 Application of capacitors in distribution system (Contd.) (Refer Slide

More information

Electrical Machines-I Prof. D. Kastha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Electrical Machines-I Prof. D. Kastha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Electrical Machines-I Prof. D. Kastha Department of Electrical Engineering Indian Institute of Technology, Kharagpur Lecture - 20 Potential and Current Transformers (Refer Slide Time: 00:37) So far we

More information

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department Philadelphia University Faculty of Engineering Student Name Student No: Serial No Final Exam, Second Semester: 2015/2016 Electrical Engineering Department Course Title: Power II Date: 21 st June 2016 Course

More information

KINGS COLLEGE OF ENGINEERING Punalkulam

KINGS COLLEGE OF ENGINEERING Punalkulam KINGS COLLEGE OF ENGINEERING Punalkulam 613 303 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING POWER SYSTEM ANALYSIS QUESTION BANK UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A (TWO MARK

More information

EE 3120 Electric Energy Systems Study Guide for Prerequisite Test Wednesday, Jan 18, pm, Room TBA

EE 3120 Electric Energy Systems Study Guide for Prerequisite Test Wednesday, Jan 18, pm, Room TBA EE 3120 Electric Energy Systems Study Guide for Prerequisite Test Wednesday, Jan 18, 2006 6-7 pm, Room TBA First retrieve your EE2110 final and other course papers and notes! The test will be closed book

More information

Module 2 : Transmission Lines. Lecture 10 : Transmisssion Line Calculations Using Smith Chart. Objectives. In this course you will learn the following

Module 2 : Transmission Lines. Lecture 10 : Transmisssion Line Calculations Using Smith Chart. Objectives. In this course you will learn the following Objectives In this course you will learn the following What is a constant VSWR circle on the - plane? Properties of constant VSWR circles. Calculations of load reflection coefficient. Calculation of reflection

More information

ECE 585 Power System Stability

ECE 585 Power System Stability Homework 1, Due on January 29 ECE 585 Power System Stability Consider the power system below. The network frequency is 60 Hz. At the pre-fault steady state (a) the power generated by the machine is 400

More information

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions FAULT CURRENT F F13-13 FAULT CURRENT - Contents 1. Introduction 2. Types of fault conditions 3 fault current must be determined 3.1 Purposes for which of prospective fault current magnitudes are used 3.2

More information

Please bring the task to your first physics lesson and hand it to the teacher.

Please bring the task to your first physics lesson and hand it to the teacher. Pre-enrolment task for 2014 entry Physics Why do I need to complete a pre-enrolment task? This bridging pack serves a number of purposes. It gives you practice in some of the important skills you will

More information

POWER SYSTEM STABILITY

POWER SYSTEM STABILITY LESSON SUMMARY-1:- POWER SYSTEM STABILITY 1. Introduction 2. Classification of Power System Stability 3. Dynamic Equation of Synchronous Machine Power system stability involves the study of the dynamics

More information

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name : Computer Methods in Power Systems Course Code : A60222

More information

Power Factor Improvement

Power Factor Improvement Salman bin AbdulazizUniversity College of Engineering Electrical Engineering Department EE 2050Electrical Circuit Laboratory Power Factor Improvement Experiment # 4 Objectives: 1. To introduce the concept

More information

Dynamics of Machines. Prof. Amitabha Ghosh. Department of Mechanical Engineering. Indian Institute of Technology, Kanpur. Module No.

Dynamics of Machines. Prof. Amitabha Ghosh. Department of Mechanical Engineering. Indian Institute of Technology, Kanpur. Module No. Dynamics of Machines Prof. Amitabha Ghosh Department of Mechanical Engineering Indian Institute of Technology, Kanpur Module No. # 07 Lecture No. # 01 In our previous lectures, you have noticed that we

More information

Module 7. Transformer. Version 2 EE IIT, Kharagpur

Module 7. Transformer. Version 2 EE IIT, Kharagpur Module 7 Transformer ersion EE T, Kharagpur Lesson 5 Testing, Efficiency & Regulation ersion EE T, Kharagpur Contents 5 Testing, Efficiency & regulation 4 5. Goals of the lesson.. 4 5. Determination of

More information

Circuit Analysis and Ohm s Law

Circuit Analysis and Ohm s Law Study Unit Circuit Analysis and Ohm s Law By Robert Cecci Circuit analysis is one of the fundamental jobs of an electrician or electronics technician With the knowledge of how voltage, current, and resistance

More information

Week No. 6 Chapter Six: Power Factor Improvement

Week No. 6 Chapter Six: Power Factor Improvement Week No. 6 Chapter Six: Power Factor Improvement The electrical energy is almost wholly generated, transmitted and distributed in the form of alternating current. Therefore, the question of power factor

More information

(Refer Slide Time: 00:55) Friends, today we shall continue to study about the modelling of synchronous machine. (Refer Slide Time: 01:09)

(Refer Slide Time: 00:55) Friends, today we shall continue to study about the modelling of synchronous machine. (Refer Slide Time: 01:09) (Refer Slide Time: 00:55) Power System Dynamics Prof. M. L. Kothari Department of Electrical Engineering Indian Institute of Technology, Delhi Lecture - 09 Modelling of Synchronous Machine (Contd ) Friends,

More information

Economic Operation of Power Systems

Economic Operation of Power Systems Economic Operation of Power Systems Section I: Economic Operation Of Power System Economic Distribution of Loads between the Units of a Plant Generating Limits Economic Sharing of Loads between Different

More information

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES POWER SEMICONDUCT BASED ELECTRIC DRIVES [Time: 3 Hrs] [Max. Marks: 80] Instructions: Solve any six questions from Q.No (1 or 2), Q.No (3 or 4), Q.No (5 or 6), Q.No (7 or 8), Q.No (9 or 10), Q.No (11 or

More information

CHAPTER 6 STEADY-STATE ANALYSIS OF SINGLE-PHASE SELF-EXCITED INDUCTION GENERATORS

CHAPTER 6 STEADY-STATE ANALYSIS OF SINGLE-PHASE SELF-EXCITED INDUCTION GENERATORS 79 CHAPTER 6 STEADY-STATE ANALYSIS OF SINGLE-PHASE SELF-EXCITED INDUCTION GENERATORS 6.. INTRODUCTION The steady-state analysis of six-phase and three-phase self-excited induction generators has been presented

More information

Chapter 9: Transient Stability

Chapter 9: Transient Stability Chapter 9: Transient Stability 9.1 Introduction The first electric power system was a dc system built by Edison in 1882. The subsequent power systems that were constructed in the late 19 th century were

More information

3 d Calculate the product of the motor constant and the pole flux KΦ in this operating point. 2 e Calculate the torque.

3 d Calculate the product of the motor constant and the pole flux KΦ in this operating point. 2 e Calculate the torque. Exam Electrical Machines and Drives (ET4117) 11 November 011 from 14.00 to 17.00. This exam consists of 5 problems on 4 pages. Page 5 can be used to answer problem 4 question b. The number before a question

More information

Power System Operations and Control Prof. S.N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur. Module 3 Lecture 8

Power System Operations and Control Prof. S.N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur. Module 3 Lecture 8 Power System Operations and Control Prof. S.N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur Module 3 Lecture 8 Welcome to lecture number 8 of module 3. In the previous

More information

EXEMPLAR NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 ( ) (X-Paper) 09:00 12:00

EXEMPLAR NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 ( ) (X-Paper) 09:00 12:00 NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 2008 (12041002) (X-Paper) 09:00 12:00 EXEMPLAR This question paper consists of 7 pages. EXEMPLAR -2- NC(V) TIME: 3 HOURS

More information

Power System Stability GENERATOR CONTROL AND PROTECTION

Power System Stability GENERATOR CONTROL AND PROTECTION Power System Stability Outline Basis for Steady-State Stability Transient Stability Effect of Excitation System on Stability Small Signal Stability Power System Stabilizers Speed Based Integral of Accelerating

More information

JRE SCHOOL OF Engineering

JRE SCHOOL OF Engineering JRE SCHOOL OF Engineering Class Test-1 Examinations September 2014 Subject Name Electromechanical Energy Conversion-II Subject Code EEE -501 Roll No. of Student Max Marks 30 Marks Max Duration 1 hour Date

More information

In the previous chapter, attention was confined

In the previous chapter, attention was confined 4 4 Principles of Power System CHAPTE CHAPTE 8 Unsymmetrical Fault Calculations 8. Usymmetrical Faults on -Phase System 8. Symmetrical Components Method 8. Operator a 8.4 Symmetrical Components in Terms

More information

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India Power System Stability and Control Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India Contents Chapter 1 Introduction to Power System Stability

More information

Fault Analysis Power System Representation

Fault Analysis Power System Representation .1. Power System Representation Single Line Diagram: Almost all modern power systems are three phase systems with the phases of equal magnitude and equal phase difference (i.e., 10 o ). These three phase

More information

LO 1: Three Phase Circuits

LO 1: Three Phase Circuits Course: EEL 2043 Principles of Electric Machines Class Instructor: Dr. Haris M. Khalid Email: hkhalid@hct.ac.ae Webpage: www.harismkhalid.com LO 1: Three Phase Circuits Three Phase AC System Three phase

More information

AC Power Analysis. Chapter Objectives:

AC Power Analysis. Chapter Objectives: AC Power Analysis Chapter Objectives: Know the difference between instantaneous power and average power Learn the AC version of maximum power transfer theorem Learn about the concepts of effective or value

More information

You know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1).

You know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1). Stability 1 1. Introduction We now begin Chapter 14.1 in your text. Our previous work in this course has focused on analysis of currents during faulted conditions in order to design protective systems

More information

GENERATORS: PART 5. The student must be. 2. Explain how the current in a generator increases as it is loaded.

GENERATORS: PART 5. The student must be. 2. Explain how the current in a generator increases as it is loaded. Electrical Equipment - Course 23D.2 GENERATORS: PART 5 NFNTE BUS OPERATON 1. OBJECTVE The student must be able to: 1. Define an "infinite bus". 2. Explain how the current in a generator increases as it

More information

Student Sheet: Self-Assessment

Student Sheet: Self-Assessment Student s Name Date Class Student Sheet: Self-Assessment Directions: Use the space provided to prepare a KWL chart. In the first column, write things you already know about energy, forces, and motion.

More information

University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department

University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department EE471: Electrical Machines-II Tutorial # 2: 3-ph Induction Motor/Generator Question #1 A 100 hp, 60-Hz, three-phase

More information

What happens when things change. Transient current and voltage relationships in a simple resistive circuit.

What happens when things change. Transient current and voltage relationships in a simple resistive circuit. Module 4 AC Theory What happens when things change. What you'll learn in Module 4. 4.1 Resistors in DC Circuits Transient events in DC circuits. The difference between Ideal and Practical circuits Transient

More information

Brief Steady of Power Factor Improvement

Brief Steady of Power Factor Improvement International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 5 (2013), pp. 531-539 International Research PublicationHouse http://www.irphouse.com Brief Steady of Power Factor Improvement

More information

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study.

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study. Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study. Marcelo Rodrigo García Saquicela, Ernesto Ruppert Filho, José Luis Azcue

More information

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz EE 742 Chapter 3: Power System in the Steady State Y. Baghzouz Transmission Line Model Distributed Parameter Model: Terminal Voltage/Current Relations: Characteristic impedance: Propagation constant: π

More information

Answers to examination-style questions. Answers Marks Examiner s tips

Answers to examination-style questions. Answers Marks Examiner s tips (a) (i) With the object on the spring: the mean value of x = 72 mm, e = 70 mm (ii).4% Each reading was ±0.5 mm. As the extension was the subtraction of two readings the absolute errors are added to give

More information

Series and Parallel ac Circuits

Series and Parallel ac Circuits Series and Parallel ac Circuits 15 Objectives Become familiar with the characteristics of series and parallel ac networks and be able to find current, voltage, and power levels for each element. Be able

More information

f = 1 T 6 a.c. (Alternating Current) Circuits Most signals of interest in electronics are periodic : they repeat regularly as a function of time.

f = 1 T 6 a.c. (Alternating Current) Circuits Most signals of interest in electronics are periodic : they repeat regularly as a function of time. Analogue Electronics (Aero).66 66 Analogue Electronics (Aero) 6.66 6 a.c. (Alternating Current) Circuits Most signals of interest in electronics are periodic : they repeat regularly as a function of time.

More information

Elementary Theory of DC Permanent Magnet Motors

Elementary Theory of DC Permanent Magnet Motors Much appreciation to David Cowden at Ga. Tech.: Web citation from 10/15/2004 http://www.srl.gatech.edu/education/me3110/primer/motors.htm Motors Introduction This section contains information about implementing

More information

ELG4125: Power Transmission Lines Steady State Operation

ELG4125: Power Transmission Lines Steady State Operation ELG4125: Power Transmission Lines Steady State Operation Two-Port Networks and ABCD Models A transmission line can be represented by a two-port network, that is a network that can be isolated from the

More information

GENERATOR INTERCONNECTION APPLICATION

GENERATOR INTERCONNECTION APPLICATION GENERATOR INTERCONNECTION APPLICATION FOR BUY-ALL/SELL-ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 1 MW Electric Utility Contact Information Great Lakes Energy

More information

ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I

ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR-621220 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I Unit I Introduction 1. What are the three basic types

More information

Electromagnetic Energy Conversion Exam 98-Elec-A6 Spring 2002

Electromagnetic Energy Conversion Exam 98-Elec-A6 Spring 2002 Front Page Electromagnetic Energy Conversion Exam 98-Elec-A6 Spring 2002 Notes: Attempt question 1 and FOUR (4) other questions (FVE (5) questions in all). Unless you indicate otherwise, the first five

More information

MITOCW free_body_diagrams

MITOCW free_body_diagrams MITOCW free_body_diagrams This is a bungee jumper at the bottom of his trajectory. This is a pack of dogs pulling a sled. And this is a golf ball about to be struck. All of these scenarios can be represented

More information

12. Introduction and Chapter Objectives

12. Introduction and Chapter Objectives Real Analog - Circuits 1 Chapter 1: Steady-State Sinusoidal Power 1. Introduction and Chapter Objectives In this chapter we will address the issue of power transmission via sinusoidal or AC) signals. This

More information

Electrical Machines and Energy Systems: Operating Principles (Part 2) SYED A Rizvi

Electrical Machines and Energy Systems: Operating Principles (Part 2) SYED A Rizvi Electrical Machines and Energy Systems: Operating Principles (Part 2) SYED A Rizvi AC Machines Operating Principles: Synchronous Motor In synchronous motors, the stator of the motor has a rotating magnetic

More information

Module 4. Single-phase AC Circuits

Module 4. Single-phase AC Circuits Module 4 Single-phase AC Circuits Lesson 14 Solution of Current in R-L-C Series Circuits In the last lesson, two points were described: 1. How to represent a sinusoidal (ac) quantity, i.e. voltage/current

More information

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION PART: A 1. Define per unit value of an electrical quantity. Write equation for base impedance with respect to 3-phase system. 2. What is bus admittance

More information

COPYRIGHTED MATERIAL. DC Review and Pre-Test. Current Flow CHAPTER

COPYRIGHTED MATERIAL. DC Review and Pre-Test. Current Flow CHAPTER Kybett c0.tex V3-03/3/2008 8:44pm Page CHAPTER DC Review and Pre-Test Electronics cannot be studied without first understanding the basics of electricity. This chapter is a review and pre-test on those

More information

Stepping Motors. Chapter 11 L E L F L D

Stepping Motors. Chapter 11 L E L F L D Chapter 11 Stepping Motors In the synchronous motor, the combination of sinusoidally distributed windings and sinusoidally time varying current produces a smoothly rotating magnetic field. We can eliminate

More information

Dynamics of the synchronous machine

Dynamics of the synchronous machine ELEC0047 - Power system dynamics, control and stability Dynamics of the synchronous machine Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct October 2018 1 / 38 Time constants and

More information

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION EE 6501 POWER SYSTEMS UNIT I INTRODUCTION PART A (2 MARKS) 1. What is single line diagram? A Single line diagram is diagrammatic representation of power system in which the components are represented by

More information

UNIT I INTRODUCTION Part A- Two marks questions

UNIT I INTRODUCTION Part A- Two marks questions ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR-621220 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING DESIGN OF ELECTRICAL MACHINES UNIT I INTRODUCTION 1. Define specific magnetic

More information

Module 3 : Sequence Components and Fault Analysis

Module 3 : Sequence Components and Fault Analysis Module 3 : Sequence Components and Fault Analysis Lecture 12 : Sequence Modeling of Power Apparatus Objectives In this lecture we will discuss Per unit calculation and its advantages. Modeling aspects

More information

Smith Chart Figure 1 Figure 1.

Smith Chart Figure 1 Figure 1. Smith Chart The Smith chart appeared in 1939 as a graph-based method of simplifying the complex math (that is, calculations involving variables of the form x + jy) needed to describe the characteristics

More information

2009 Assessment Report Physics GA 1: Written examination 1

2009 Assessment Report Physics GA 1: Written examination 1 2009 Physics GA 1: Written examination 1 GENERAL COMMENTS The number of students who sat for the 2009 Physics examination 1 was 6868. With a mean score of 68 per cent, students generally found the paper

More information

2 Electric Field Mapping Rev1/05

2 Electric Field Mapping Rev1/05 2 Electric Field Mapping Rev1/05 Theory: An electric field is a vector field that is produced by an electric charge. The source of the field may be a single charge or many charges. To visualize an electric

More information

Practical Algebra. A Step-by-step Approach. Brought to you by Softmath, producers of Algebrator Software

Practical Algebra. A Step-by-step Approach. Brought to you by Softmath, producers of Algebrator Software Practical Algebra A Step-by-step Approach Brought to you by Softmath, producers of Algebrator Software 2 Algebra e-book Table of Contents Chapter 1 Algebraic expressions 5 1 Collecting... like terms 5

More information

Estimating Generator Capability Curves

Estimating Generator Capability Curves Estimating Generator Capability Curves University of Wisconsin-Madison October 1, 13 Simplistic generator models often use rectangle constraints for active and reactive output limits. That is, generators

More information

Chapter 8: Unsymmetrical Faults

Chapter 8: Unsymmetrical Faults Chapter 8: Unsymmetrical Faults Introduction The sequence circuits and the sequence networks developed in the previous chapter will now be used for finding out fault current during unsymmetrical faults.

More information

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation James Ranjith Kumar. R, Member, IEEE, Amit Jain, Member, IEEE, Power Systems Division,

More information

Electric Machinery Fundamentals

Electric Machinery Fundamentals Solutions Manual to accompany Chapman Electric Machinery Fundamentals Fifth Edition Stephen J. Chapman BAE Systems Australia i Solutions Manual to accompany Electric Machinery Fundamentals, Fifth Edition

More information

Analyzing the Effect of Ambient Temperature and Loads Power Factor on Electric Generator Power Rating

Analyzing the Effect of Ambient Temperature and Loads Power Factor on Electric Generator Power Rating Analyzing the Effect of Ambient Temperature and Loads Power Factor on Electric Generator Power Rating Ahmed Elsebaay, Maged A. Abu Adma, Mahmoud Ramadan Abstract This study presents a technique clarifying

More information

Chapter 1: Logic systems

Chapter 1: Logic systems Chapter 1: Logic systems 1: Logic gates Learning Objectives: At the end of this topic you should be able to: identify the symbols and truth tables for the following logic gates: NOT AND NAND OR NOR XOR

More information

An Ultra Low Resistance Continuity Checker

An Ultra Low Resistance Continuity Checker An Ultra Low Resistance Continuity Checker By R. G. Sparber Copyleft protects this document. 1 Some understanding of electronics is assumed. Although the title claims this is a continuity checker, its

More information

Chapter 4. Synchronous Generators. Basic Topology

Chapter 4. Synchronous Generators. Basic Topology Basic Topology Chapter 4 ynchronous Generators In stator, a three-phase winding similar to the one described in chapter 4. ince the main voltage is induced in this winding, it is also called armature winding.

More information

Making the grade: Part II

Making the grade: Part II 1997 2009, Millennium Mathematics Project, University of Cambridge. Permission is granted to print and copy this page on paper for non commercial use. For other uses, including electronic redistribution,

More information

Making the grade. by Chris Sangwin. Making the grade

Making the grade. by Chris Sangwin. Making the grade 1997 2009, Millennium Mathematics Project, University of Cambridge. Permission is granted to print and copy this page on paper for non commercial use. For other uses, including electronic redistribution,

More information

Three Phase Systems 295

Three Phase Systems 295 Three Phase Systems 95 9. MEASUEMENT OF POE Star-Connected Balanced Load with Neutral Point Power can be measured in this case by connecting a single wattmeter with its current coil in one line and the

More information

Basics of Electric Circuits

Basics of Electric Circuits António Dente Célia de Jesus February 2014 1 Alternating Current Circuits 1.1 Using Phasors There are practical and economic reasons justifying that electrical generators produce emf with alternating and

More information

Slope Fields: Graphing Solutions Without the Solutions

Slope Fields: Graphing Solutions Without the Solutions 8 Slope Fields: Graphing Solutions Without the Solutions Up to now, our efforts have been directed mainly towards finding formulas or equations describing solutions to given differential equations. Then,

More information

ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models

ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas A&M University, overbye@tamu.edu 1 Announcements Read Chapter

More information

FALL 2004 Midterm Exam #2, Part A

FALL 2004 Midterm Exam #2, Part A Physics 152 FALL 2004 Midterm Exam #2, Part A Roster No.: Score: 17 points possible Exam time limit: 50 minutes. You may use a calculator and both sides of ONE sheet of notes, handwritten only. Closed

More information

CHAPTER 2 CAPACITANCE REQUIREMENTS OF SIX-PHASE SELF-EXCITED INDUCTION GENERATORS

CHAPTER 2 CAPACITANCE REQUIREMENTS OF SIX-PHASE SELF-EXCITED INDUCTION GENERATORS 9 CHAPTER 2 CAPACITANCE REQUIREMENTS OF SIX-PHASE SELF-EXCITED INDUCTION GENERATORS 2.. INTRODUCTION Rapidly depleting rate of conventional energy sources, has led the scientists to explore the possibility

More information

The Farad is a very big unit so the following subdivisions are used in

The Farad is a very big unit so the following subdivisions are used in Passages in small print are for interest and need not be learnt for the R.A.E. Capacitance Consider two metal plates that are connected to a battery. The battery removes a few electrons from plate "A"

More information

Draft Version 1 Mark scheme Further Maths Core Pure (AS/Year 1) Unit Test 1: Complex numbers 1

Draft Version 1 Mark scheme Further Maths Core Pure (AS/Year 1) Unit Test 1: Complex numbers 1 1 w z k k States or implies that 4 i TBC Uses the definition of argument to write 4 k π tan 1 k 4 Makes an attempt to solve for k, for example 4 + k = k is seen. M1.a Finds k = 6 (4 marks) Pearson Education

More information