Coal Combustion Residuals Unit Inflow Design Flood Control System Plan

Size: px
Start display at page:

Download "Coal Combustion Residuals Unit Inflow Design Flood Control System Plan"

Transcription

1 Coal Combustion Residuals Unit Inflow Design Flood Control System Plan Virginia Electric and Power Company Chesterfield Power Station Upper (East) Pond Chesterfield County, Virginia GAI Project Number: C October 2016 Prepared by: GAI Consultants, Inc. Richmond Office 4198 Cox Road, Suite 114 Glen Allen, Virginia Prepared for: Virginia Electric and Power Company 5000 Dominion Boulevard Glen Allen, Virginia 23060

2 Coal Combustion Residuals CCR Unit Inflow Design Flood Control System Plan Upper (East) Pond Chesterfield Power Station, Chesterfield County, Virginia Page i Table of Contents 1.0 Introduction Purpose Initial Inflow Design Flood Control System Plan Site Configuration Flow Into the Upper (East) Pond Flow From the Upper (East) Pond Surface Water Requirements Conclusion References... 6 Table 1 Table 2 Drawing Summary of Channel Geometries and Capacities Summary of Culvert Properties and Capacities E1-114 Plan View Existing Conditions Appendix A Hydrologic and Hydraulic Assessment 2016 GAI Consultants C / October 2016

3 Coal Combustion Residuals CCR Unit Inflow Design Flood Control System Plan Upper (East) Pond Chesterfield Power Station, Chesterfield County, Virginia Page 1 Certification/Statement of Professional Opinion The Coal Combustion Residuals CCR Unit Inflow Design Flood Control System Plan (Plan) for the Chesterfield Power Station Upper (East) Pond was prepared by GAI Consultants, Inc. (GAI). The Plan was based on certain information that, other than for information GAI originally prepared, GAI has relied on but not independently verified. This Certification/Statement of Professional Opinion is therefore limited to the information available to GAI at the time the Plan was written. On the basis of and subject to the foregoing, it is my professional opinion as a Professional Engineer licensed in the Commonwealth of Virginia that the Plan has been prepared in accordance with good and accepted engineering practices as exercised by other engineers practicing in the same discipline(s), under similar circumstances, at the same time, and in the same locale. It is my professional opinion that the Plan was prepared consistent with the requirements of (c) of the United States Environmental Protection Agency s Standards for the Disposal of Coal Combustion Residuals in Landfills and Surface Impoundments, published in the Federal Register on April 17, 2015 with an effective date of October 19, 2015 (40 CFR 257 Subpart D). The use of the words certification and/or certify in this document shall be interpreted and construed as a Statement of Professional Opinion and is not and shall not be interpreted or construed as a guarantee, warranty or legal opinion. GAI Consultants, Inc. Kevin M. Bortz, P.E. Assistant Engineering Manager Date C / October 2016

4 Coal Combustion Residuals CCR Unit Inflow Design Flood Control System Plan Upper (East) Pond Chesterfield Power Station, Chesterfield County, Virginia Page 2 Acronyms CCR CCR Rule CFR DEQ Dominion EPA GAI H&H IDFCS Plan Station UEP VPDES VPDES Permit Coal Combustion Residuals Standards for the Disposal of Coal Combustion Residuals in Landfills and Surface Impoundments, 40 CFR 257 Subpart D (2015) Code of Federal Regulations Virginia Department of Environmental Quality Virginia Electric and Power Company d/b/a Dominion United States Environmental Protection Agency GAI Consultants, Inc. Hydrologic and Hydraulic Inflow Design Flood Control System CCR Unit Inflow Design Flood Control System Plan Dominion Chesterfield Power Station Upper (East) Pond Virginia Pollutant Discharge Elimination System Virginia Pollutant Discharge Elimination System Permit No. VA C / October 2016

5 Coal Combustion Residuals CCR Unit Inflow Design Flood Control System Plan Upper (East) Pond Chesterfield Power Station, Chesterfield County, Virginia Page Introduction The Chesterfield Power Station (Station) is owned by Virginia Electric and Power Company d/b/a Dominion Virginia Power (Dominion) and is located in Chesterfield, VA. The Station includes the Upper (East) Pond (UEP) impoundment, which is used for the long term storage of coal combustion residuals (CCR). The UEP is located on Dominion property at the Chesterfield Power Station in Chesterfield County, Virginia (coordinates 37 o North and 77 o West) and is bounded by the Old Channel of the James River on the south, Henricus Historical Park on the east, and Aiken Swamp on the north. The UEP is regulated as an existing CCR surface impoundment under the Environmental Protection Agency s Standards for the Disposal of Coal Combustion Residuals in Landfills and Surface Impoundments [40 CFR 257 Subpart D] published in the Federal Register on April 17, 2015 with an effective date of October 19, 2015 (CCR Rule). The UEP is currently regulated by Virginia Department of Environmental Quality (DEQ) Virginia Pollutant Discharge Elimination System Permit No. VA (VPDES Permit). 2.0 Purpose This CCR Unit Inflow Design Flood Control System Plan (Plan) is prepared pursuant to (c) of the CCR Rule [40 CFR (c)]. 3.0 Initial Inflow Design Flood Control System Plan In accordance with (a)(2), an initial Hazard Potential Classification was prepared for the UEP under current conditions. The UEP was determined to be a significant hazard potential CCR impoundment (GAI Consultants, 2016). As required by (a)(3), the inflow design flood for a significant hazard potential CCR surface impoundment is a 1,000-year flood. As required by (c)(1), this Plan includes: Documentation of how the inflow design flood control system (IDFCS) has been designed, constructed, operated, and maintained to adequately manage flow into the UEP during and following the peak discharge of the inflow design flood [ (a)(1)]; Documentation of how the IDFCS has been designed, constructed, operated, and maintained to adequately manage flow from the UEP so as to collect and control the peak discharge resulting from the inflow design flood [ (a)(2)]; and Documentation of how the IDFCS has been designed, constructed, operated, and maintained to adequately address the requirements of [ (b)]. 3.1 Site Configuration The UEP consists of earthen embankments and stored CCR contained within the embankments. Perimeter channels convey stormwater runoff to a stormwater sediment pond situated at the east end of the UEP. The stormwater sediment pond discharges through VPDES Permit Outfall 005. Drawing E1-114 depicts existing conditions at the UEP. 3.2 Flow Into the Upper (East) Pond The UEP embankment crest is at approximate elevation 41 at its lowest point, and the crest ranges from three feet to 35 feet above the approximate surrounding ground elevation. As such, there is no stormwater flow into the UEP and no need for a corresponding control system. The criteria established in (a)(1) are therefore met. C / October 2016

6 Coal Combustion Residuals CCR Unit Inflow Design Flood Control System Plan Upper (East) Pond Chesterfield Power Station, Chesterfield County, Virginia Page Flow From the Upper (East) Pond Interior perimeter channels and culverts, in conjunction with the stormwater sediment pond, comprise the IDFCS for the UEP. Drawing E1-114 depicts existing conditions at the UEP and identifies the interior perimeter channels and culverts and the stormwater sediment pond. The bottom elevation of the stormwater sediment pond is at approximately 26 feet and the top of stormwater sediment pond containment (coincident with the UEP embankment crest) is at approximate minimum elevation 41 feet. Discharge from the stormwater sediment pond is controlled by a principal spillway riser tower structure, which is a 6 foot by 6 foot square concrete box. The tower structure is fitted with six 16-inch diameter flanged pipe openings (with five being available for discharge) with the lowest available opening at invert elevation feet (Virginia Power, 1992). The principal spillway outfall pipe is a 24-inch diameter concrete pipe, which discharges to VPDES Permit Outfall 005. In this Plan, management of the inflow design flood is defined as having the capacity to convey the peak discharge resulting from the flood. The capacity of each stormwater runoff control feature was evaluated and compared to the peak discharge resulting from the inflow design flood (1,000-year flood). Hydrologic and hydraulic (H&H) analyses are contained in Appendix A. Information for the components of the IDFCS was obtained from the 2003 Closure Plan, New Ash Pond Stop Log Conversion, DCR (Virginia Power, 1992), site topographic mapping, and site observations. Constructed geometry for the interior perimeter channels and culverts is summarized in Table 1 and Table 2 respectively, along with the 1,000-year peak discharges and capacities. Table 1 Summary of Channel Geometry and Capacities Interior Perimeter Channel North Perimeter Channel Segment Number Lining Channel Slope (ft/ft) Bottom Width (ft) Depth* (ft) Side Slopes (Left, Right H:1V) 1,000- year peak discharge (cubic feet per second)** Capacity (cubic feet per second)** 1 Grass , Concrete , ,224 3 Concrete , ,562 West Perimeter Channel 1 Grass , South Perimeter Channel 1 Grass , Concrete , Concrete , ,984 4 Concrete , ,415 *For concrete channels, depth listed is the depth of concrete. Capacity listed includes grassed conveyance above the top of the concrete lining. ** Discharge and capacity are listed for the downstream end of a channel reach. C / October 2016

7 Coal Combustion Residuals CCR Unit Inflow Design Flood Control System Plan Upper (East) Pond Chesterfield Power Station, Chesterfield County, Virginia Page 5 Culvert Table 2 Summary of Culvert Properties and Capacities Material Diameter (ft) Length (ft) Culvert Slope (ft/ft) 1,000-year peak discharge (cubic feet per second) Capacity (cubic feet per second) East Culvert CMP * West Culvert Concrete Ductile Iron South Culvert CMP * * Capacity includes overflow channel to stormwater sediment pond. The analyses indicate that all interior perimeter channels and culverts that are part of the IDFCS are capable of passing the peak discharge from the 1,000-year flood. The UEP stormwater sediment pond was modeled for its performance during a 1,000-year flood. Appendix A contains calculations and results of the modeling. The model shows that the pool in the stormwater sediment pond from a 1,000-year flood would attain an estimated peak water surface elevation of feet. The UEP embankment crest provides containment from the stormwater sediment pond pool and has a minimum containment at approximate elevation 41 feet. Channels, culverts, and the stormwater sediment pond are routinely inspected (Dominion, 2014). These inspections meet the IDFCS requirements for maintenance in the CCR Rule. 3.4 Surface Water Requirements 40 CFR states that a facility shall not cause a discharge of pollutants into waters of the United States that is in violation of the National Pollutant Discharge Elimination System (NPDES) under section 402 of the Clean Water Act, as amended. DEQ administers the NPDES program in Virginia under the VPDES program. The UEP is regulated under an existing VPDES Permit. Discharges from the UEP are limited and monitored in accordance with the requirements in the VPDES permit, which functions to satisfy the requirements of (b) of the CCR Rule. 4.0 Conclusion It is GAI s opinion, based on a review of available material and additional analyses performed for this Plan, that the existing UEP Inflow Design Flood Control System is in compliance with the requirements in of the CCR Rule for a significant hazard impoundment. C / October 2016

8 Coal Combustion Residuals CCR Unit Inflow Design Flood Control System Plan Upper (East) Pond Chesterfield Power Station, Chesterfield County, Virginia Page References Dominion Report of 2014 Safety Inspection, Chesterfield Power Station Upper Ash Pond Dam. GAI Consultants Inc Dominion Chesterfield Power Station, Upper (East) Pond-Max Drawdown- Stability. GAI Consultants Inc Initial Hazard Potential Classification Assessment Report, Upper (East) Pond, Chesterfield Power Station, Chesterfield County, Virginia. United States Environmental Protection Agency CFR Parts 257 and 261 Hazardous and Solid Waste Management System; Disposal of Coal Combustion Residuals from Electric Utilities; Final Rule. April 17, Virginia Department of Environmental Quality. Virginia Pollutant Discharge Elimination System (VPDES) Permit No. VA Virginia Power New Ash Pond Stop Log Conversion, DCR , January C / October 2016

9 Coal Combustion Residuals CCR Unit Inflow Design Flood Control System Plan Upper (East) Pond Chesterfield Power Station, Chesterfield County, Virginia DRAWING C / October 2016

10 PROJECT DRAWING TITLE PLAN VIEW - EXISTING CONDITIONS CLIENT DRAWN BY: CHECKED BY: APPROVED BY: NEIMAJC BORTZKM JOYCEJM GAI FILE NUMBER: C C-E1-114 DWG TYPE: SCALE: ISSUE DATE: ALT./CLIENT DRAWING NUMBER: UPPER (EAST) POND INFLOW DESIGN REPORT DOMINION AS SHOWN 10/7/2016 NO.: DATE: DWN: CHK: APV: DESCRIPTION: REVISION RECORD CHESTERFIELD POWER STATION CHESTERFIELD COUNTY, VIRGINIA GLEN ALLEN, VIRGINIA REVISION SHEET NO.: GAI DRAWING NUMBER: E1-114 ISSUING OFFICE: Murrysville 4200 Triangle Lane, Export, PA OF 1

11 Coal Combustion Residuals CCR Unit Inflow Design Flood Control System Plan Upper (East) Pond Chesterfield Power Station, Chesterfield County, Virginia APPENDIX A Hydrologic and Hydraulic Assessment C / October 2016

12 1 of 76 SUBJECT CHESTERFIELD POWER STATION-UPPER (EAST) POND _ HYDROLOGIC AND HYDRAULIC CAPACITY ASSESSMENT _ BY BERKEME DATE 10/05/2016 PROJ. NO. C _ CHKD. BY URBANCE DATE 10/07/2016 APPENDIX A TABLE OF CONTENTS: SHEET* Objective. 2 Methodology. 2 References... 2 Rainfall Data.. 3 Curve Numbers 3 Time of Concentration Data 4 Summary of Hydraulic Calculations 4 Attachment 1 Drainage Area Map. 6 Attachment 2 Stage-Discharge for Pond.. 8 Attachment 3 Hydraflow Routing Attachment 2 Hydraulic Capacity for Channels. 37 Attachment 3 Hydraulic Capacity for Culverts. 62 *Appendix sheet numbers correspond to italic numbers in the upper right hand corner of each page. Z:\Energy\2015\C DOM-Chesterfld Pond Closu\Working Docs\CCR Rule documents\a initial submission and working folders\inflow Design Report\H&H Capacity Analysis-Significant - REV for CCR Compliance.docx

13 2 of 76 SUBJECT CHESTERFIELD POWER STATION-UPPER (EAST) POND _ HYDROLOGIC AND HYDRAULIC CAPACITY ASSESSMENT _ BY BERKEME DATE 10/05/2016 PROJ. NO. C _ CHKD. BY URBANCE DATE 10/07/2016 OBJECTIVE: The purpose of this assessment is to estimate the hydrologic and hydraulic (H&H) capacity for the current site configuration at the Chesterfield Power Station s Upper (East) Pond (UEP) for the inflow design flood event to show compliance with the updated CCR Rule. Section of the Environmental Protection Agency (EPA) Coal Combustion Residual (CCR) Rule established in April 2015 states that the inflow design flood control system (for CCR surface impoundments) must adequately manage flow into the Impoundment during and following the peak discharge of the inflow design flood. The UEP (CCR) Impoundment is regulated as a significant hazard CCR surface impoundment, and per the CCR Rule, the inflow design flood is the 1,000-year event. This calculation will estimate peak discharges for the 1,000-year event for surface runoff control structures (channels, culverts, and stormwater sediment pond) that control and contain stormwater discharge from the impoundment. The peak discharges will be compared to calculated hydraulic capacity for each structure to demonstrate compliance with the CCR Rule. METHODOLOGY: Drainage areas to site features requiring evaluation were delineated using project mapping. A Drainage Area Map is included in these calculations (sheet 7). Under the inflow design flood, benches were assumed to be ineffective as diversions when delineating watersheds. The Natural Resources Conservation Service (NRCS) TR-55 method and the computer program Hydraflow Hydrographs were utilized to estimate peak flow rates to each runoff control structure. Hydraflow calculations are included as Attachment 2 to this calculation. Rainfall data for the site location were obtained from NOAA Atlas 14. REFERENCES 1. TR-55, Urban Hydrology For Small Watersheds, Natural Resources Conservation Services, June NOAA Atlas 14. Rainfall data for Dutch Gap Conservation Area, Accessed 12/10/2015 (for Closure Plan Calculations). 3. Hydraflow Hydrographs Extension for AutoCAD Civil 3D. Version 10 by Autodesk, Inc Tuck Mapping As-Built Contour Data. March 3, Upper (East) Pond Max Drawdown Stability Calculation, GAI Consultants Inc., December 17, Z:\Energy\2015\C DOM-Chesterfld Pond Closu\Working Docs\CCR Rule documents\a initial submission and working folders\inflow Design Report\H&H Capacity Analysis-Significant - REV for CCR Compliance.docx

14 3 of 76 SUBJECT CHESTERFIELD POWER STATION-UPPER (EAST) POND _ HYDROLOGIC AND HYDRAULIC CAPACITY ASSESSMENT _ BY BERKEME DATE 10/05/2016 PROJ. NO. C _ CHKD. BY URBANCE DATE 10/07/ Revised Closure Plan, Upper (East) Pond, Chesterfield Power Station, Chesterfield County, Virginia. GAI Consultants, Inc Closure Plan Drawings, Upper East Pond, Chesterfield Power Station, Chesterfield County, Virginia. GAI Consultants, Inc Survey from D & M Surveyors P.C., September 29, RAINFALL DATA: Rainfall data for the site were obtained from Reference 2. These values are summarized below: 2-year, 24-hour event = 3.36 in (for use in Time of Concentration Calculation) 1,000-year, 24-hour event = 13.1 in CURVE NUMBERS: The following curve numbers used in the H&H Calculations of Reference 6 were also used for this assessment: The following curve numbers were used to represent the site conditions currently present: Coal Combustion Residuals (CCR) = 85 Vegetated Final Soil Cover (good condition) = 74 Gravel Haul Roads = 89 Z:\Energy\2015\C DOM-Chesterfld Pond Closu\Working Docs\CCR Rule documents\a initial submission and working folders\inflow Design Report\H&H Capacity Analysis-Significant - REV for CCR Compliance.docx

15 4 of 76 SUBJECT CHESTERFIELD POWER STATION-UPPER (EAST) POND _ HYDROLOGIC AND HYDRAULIC CAPACITY ASSESSMENT _ BY BERKEME DATE 10/05/2016 PROJ. NO. C _ CHKD. BY URBANCE DATE 10/07/2016 Water (Stormwater Sediment Pond) = 98 The Hydraflow model was used to calculate a composite curve number for each watershed. TIME OF CONCENTRATION DATA: Time of concentration (TOC) flow paths were estimated within the Hydraflow model using the methods provided in TR-55, incorporating sheet flow, shallow concentrated flow, and channel flow segments. Slopes and channel dimensions were estimated from the project mapping which was developed from survey information (Reference 4). A minimum TOC of 6 minutes was used. The following roughness coefficients were used in the sheet flow calculations (Reference 6): CCR (No Vegetation) = 0.03 Final Cover with Good Vegetation = 0.24 Channel geometry and Manning s values for use in the TOC calculations were taken from Reference 6. SUMMARY OF HYDRAULIC CALCULATIONS: Capacity of the channels was estimated using the computer program Bentley FlowMaster (v8i), and capacity of the culverts was estimated using the Federal Highway Administration (FHWA) software HY-8. Channel dimensions and culvert properties were taken from References 4, 6, 7, and 8. Cross sections for each channel segment were taken at the downstream end of the channel segment where the entire watershed has contributed runoff. The stormwater sediment pond was modeled in Hydraflow, using the average end area method to estimate storage. Contour areas were estimated from Reference 4. The following Information on the pond s outlet structures was taken from References 5, 6, and 7 and entered into the Hydraflow model: Pond outfall culvert is 24-inches in diameter, with an inlet invert elevation of 12.0 and an outlet invert elevation of 7.6. The length of the culvert is approximately 192 (Reference 7). The riser tower has a crest elevation of 44.0 feet, and the inside of the riser is a 6 foot by 6 foot square (Reference 6). The riser has five open 16-inch diameter orifices with inverts at the following elevations feet, feet, feet, feet, and feet (Reference 5). The embankment is at elevation ft (Reference 7). Z:\Energy\2015\C DOM-Chesterfld Pond Closu\Working Docs\CCR Rule documents\a initial submission and working folders\inflow Design Report\H&H Capacity Analysis-Significant - REV for CCR Compliance.docx

16 5 of 76 SUBJECT CHESTERFIELD POWER STATION-UPPER (EAST) POND _ HYDROLOGIC AND HYDRAULIC CAPACITY ASSESSMENT _ BY BERKEME DATE 10/05/2016 PROJ. NO. C _ CHKD. BY URBANCE DATE 10/07/2016 A summary of results is provided in Table 1 and Table 2. Table 1: Summary of Channel/Culvert Hydraulic Capacity Culvert/Channel 1,000-year peak flow rate (cfs) Capacity (cfs) North Perimeter Channel Segment North Perimeter Channel Segment ,224 North Perimeter Channel Segment ,562 South Perimeter Channel Segment South Perimeter Channel Segment South Perimeter Channel Segment ,984 South Perimeter Channel Segment ,415 West Perimeter Channel East Culvert (North Perimeter Channel) West Culvert (West Perimeter Channel) South Culvert (South Perimeter Channel) Table 2: Stormwater Sediment Basin Hydraulic Capacity Pond 1,000-year Water Surface Elevation (ft) Embankment Crest/Allowable WSE (ft) Stormwater Sediment Pond Z:\Energy\2015\C DOM-Chesterfld Pond Closu\Working Docs\CCR Rule documents\a initial submission and working folders\inflow Design Report\H&H Capacity Analysis-Significant - REV for CCR Compliance.docx

17 6 of 76 SUBJECT CHESTERFIELD POWER STATION-UPPER (EAST) POND _ HYDROLOGIC AND HYDRAULIC CAPACITY ASSESSMENT _ BY BERKEME DATE 10/05/2016 PROJ. NO. C _ CHKD. BY URBANCE DATE 10/07/2016 ATTACHMENT 1 DRAINAGE AREA MAP Z:\Energy\2015\C DOM-Chesterfld Pond Closu\Working Docs\CCR Rule documents\a initial submission and working folders\inflow Design Report\H&H Capacity Analysis-Significant - REV for CCR Compliance.docx

18 7 of 76 DRAWING TITLE DRAWN BY: CHECKED BY: APPROVED BY: BERKEME URBANCE DWG TYPE: SCALE: ISSUE DATE: AS SHOWN --/--/---- EXISTING CONDITIONS - DRAINAGE AREA MAP PROJECT UPPER ASH POND IDFCSP CHESTERFIELD POWER STATION NO.: DATE: DWN: CHK: APV: DESCRIPTION: REVISION RECORD CHESTER CHESTERFIELD COUNTY, VIRGINIA ISSUING OFFICE: Murrysville 4200 Triangle Lane, Export, PA CLIENT DOMINION SHEET NO.: GLEN ALLEN, VIRGINIA GAI FILE NUMBER: MBB H&H Worksheet-REV ALT./CLIENT DRAWING NUMBER: GAI DRAWING NUMBER: REVISION E OF 1

19 8 of 76 SUBJECT CHESTERFIELD POWER STATION-UPPER (EAST) POND _ HYDROLOGIC AND HYDRAULIC CAPACITY ASSESSMENT _ BY BERKEME DATE 10/05/2016 PROJ. NO. C _ CHKD. BY URBANCE DATE 10/07/2016 ATTACHMENT 2 STAGE-DISCHARGE FOR POND Z:\Energy\2015\C DOM-Chesterfld Pond Closu\Working Docs\CCR Rule documents\a initial submission and working folders\inflow Design Report\H&H Capacity Analysis-Significant - REV for CCR Compliance.docx

20 Chesterfield SEDIMENTATION POND STAGE-DISCHARGE ANALYSIS SUBJECT CHESTERFIELD POWER STATION-UPPER (EAST) POND _ HYDROLOGIC AND HYDRAULIC CAPACITY ASSESSMENT _ BY URBANCE BERKEME DATE 06/15/2016 PROJ. NO. C _ CHKD. BY URBANCE BERKEME DATE 06/15/ of 76 Elev (ft) Head on first orifice row Flow in first row (cfs) Head on second orifice row Flow in second row (cfs) Head on third orifice row Flow in Head on third fourth row (cfs) orifice row Flow in fourth row (cfs) Head on fifth orifice row Flow in fifth row (cfs) Head on riser Orifice Flow in Weir Flow in Riser Riser Net Flow in Riser Head on Outlet Pipe Total Allowable Orifice Flow in Flow V^2 / 2g Outlet Pipe (cfs) Orifice Orifice Orifice Orifice Orifice RISER DATA BARREL HDPE - n = Circular - 16" Circular - 16" Circular - 16" Circular - 16" Circular - 16" Crest 44 Diameter (ft) 2 Invert Invert Invert Invert Invert Area (sf) Inlet Invert 12 Diam (in) Diam (in) Diam (in) Diam (in) Diam (in) Perimeter (ft) Outlet Invert 7.6 Area (sf) Area (sf) Area (sf) Area (sf) Area (sf) Weir C 3.33 Outlet TW centroid el centroid el centroid el centroid el centroid el Orifice C 0.6 Area (sf) C 0.6 C 0.6 C 0.6 C 0.6 C 0.6 Length (ft) 192 No. holes 1 No. holes 1 No. holes 1 No. holes 1 No. holes 1 Ke 0.5 R (ft) 0.5 The outlet pipe calculation is based on outlet control The equation used is the outlet control equation in HDS - 5: H = (1 + Ke + (29 * n^2 * L)/R^1.33) * V^2 / 2g Chesterfield sed pond discharge.xlsx Riser Discharge north

21 10 of 76 SUBJECT CHESTERFIELD POWER STATION-UPPER (EAST) POND _ HYDROLOGIC AND HYDRAULIC CAPACITY ASSESSMENT _ BY BERKEME DATE 10/05/2016 PROJ. NO. C _ CHKD. BY URBANCE DATE 10/07/2016 ATTACHMENT 3 HYDRAFLOW ROUTING Z:\Energy\2015\C DOM-Chesterfld Pond Closu\Working Docs\CCR Rule documents\a initial submission and working folders\inflow Design Report\H&H Capacity Analysis-Significant - REV for CCR Compliance.docx

22 1 11 of 76 Watershed Model Schematic Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v Project: Chesterfield Hydraulic Capacity REV-1000yr.gpw Tuesday, 06 / 14 / 2016

23 Hydrograph Summary Report 2 12 of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Hyd. Hydrograph Peak Time Time to Hyd. Inflow Maximum Total Hydrograph No. type flow interval Peak volume hyd(s) elevation strge used Description (origin) (cfs) (min) (min) (cuft) (ft) (cuft) 1 SCS Runoff , South Perimeter Channel 1 2 SCS Runoff , South Perimeter Channel 2 3 Combine ,907 1, SPC 2 Total 4 SCS Runoff ,233, South Perimeter Channel 3 5 Combine ,573,200 3, Total flow to South Perimeter Channe 6 SCS Runoff , South Perimeter Channel 4 7 Combine ,239,426 5, South Perimeter Total 8 SCS Runoff , West Perimeter Channel (West Culve 9 SCS Runoff , North Perimeter Channel 1 10 Combine ,436 8, NPC 1 Total 11 SCS Runoff , North Perimeter Channel 2 12 Combine ,334 10, NPC 2 Total 13 SCS Runoff , North Perimeter Channel 3 14 Combine ,130,716 12, North Perimeter Channel Total 15 SCS Runoff , Temporary Sed Pond 16 Combine ,257,634 7, 14, Total To Sed Pond 17 Reservoir ,653, ,247,439 <no description> Note: Hydraflow does not have an input option for a 1,000yr return interval, so the 1,000yr rainfall was entered as input for the 10yr return period. Chesterfield Hydraulic Capacity REV-1000yr.gpw Return Period: 10 Year Tuesday, 06 / 14 / 2016

24 Hydrograph Report 3 13 of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 1 South Perimeter Channel 1 Hydrograph type = SCS Runoff Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 717 min Time interval = 1 min Hyd. volume = 155,489 cuft Drainage area = ac Curve number = 74* Basin Slope = 0.0 % Hydraulic length = 0 ft Tc method = User Time of conc. (Tc) = 6.00 min Total precip. = in Distribution = Type II Storm duration = 24 hrs Shape factor = 484 * Composite (Area/CN) = [(3.600 x 85) + (7.300 x 74)] / Q (cfs) South Perimeter Channel 1 Hyd. No Year Q (cfs) Hyd No. 1 Time (min)

25 Hydrograph Report 4 14 of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 2 South Perimeter Channel 2 Hydrograph type = SCS Runoff Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 717 min Time interval = 1 min Hyd. volume = 184,418 cuft Drainage area = ac Curve number = 74 Basin Slope = 0.0 % Hydraulic length = 0 ft Tc method = User Time of conc. (Tc) = 6.00 min Total precip. = in Distribution = Type II Storm duration = 24 hrs Shape factor = 484 Q (cfs) South Perimeter Channel 2 Hyd. No Year Q (cfs) Hyd No. 2 Time (min)

26 Hydrograph Report 5 15 of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 3 SPC 2 Total Hydrograph type = Combine Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 717 min Time interval = 1 min Hyd. volume = 339,907 cuft Inflow hyds. = 1, 2 Contrib. drain. area = ac Q (cfs) SPC 2 Total Hyd. No Year Q (cfs) Time (min) Hyd No. 3 Hyd No. 1 Hyd No. 2

27 Hydrograph Report 6 16 of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 4 South Perimeter Channel 3 Hydrograph type = SCS Runoff Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 734 min Time interval = 1 min Hyd. volume = 1,233,292 cuft Drainage area = ac Curve number = 78* Basin Slope = 0.0 % Hydraulic length = 0 ft Tc method = TR55 Time of conc. (Tc) = min Total precip. = in Distribution = Type II Storm duration = 24 hrs Shape factor = 484 * Composite (Area/CN) = [( x 85) + ( x 74)] / Q (cfs) South Perimeter Channel 3 Hyd. No Year Q (cfs) Time (min) Hyd No. 4

28 TR55 Tc Worksheet 7 17 of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Hyd. No. 4 South Perimeter Channel 3 Description A B C Totals Sheet Flow Manning's n-value = Flow length (ft) = Two-year 24-hr precip. (in) = Land slope (%) = Travel Time (min) = = Shallow Concentrated Flow Flow length (ft) = Watercourse slope (%) = Surface description = Unpaved Unpaved Unpaved Average velocity (ft/s) = Travel Time (min) = = Channel Flow X sectional flow area (sqft) = Wetted perimeter (ft) = Channel slope (%) = Manning's n-value = Velocity (ft/s) = Flow length (ft) ({0}) Travel Time (min) = = 1.56 Total Travel Time, Tc min

29 Hydrograph Report 8 18 of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 5 Total flow to South Perimeter Channel 3 Hydrograph type = Combine Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 719 min Time interval = 1 min Hyd. volume = 1,573,200 cuft Inflow hyds. = 3, 4 Contrib. drain. area = ac Q (cfs) Total flow to South Perimeter Channel 3 Hyd. No Year Q (cfs) Time (min) Hyd No. 5 Hyd No. 3 Hyd No. 4

30 Hydrograph Report 9 19 of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 6 South Perimeter Channel 4 Hydrograph type = SCS Runoff Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 737 min Time interval = 1 min Hyd. volume = 666,227 cuft Drainage area = ac Curve number = 74 Basin Slope = 0.0 % Hydraulic length = 0 ft Tc method = TR55 Time of conc. (Tc) = min Total precip. = in Distribution = Type II Storm duration = 24 hrs Shape factor = 484 Q (cfs) South Perimeter Channel 4 Hyd. No Year Q (cfs) Time (min) Hyd No. 6

31 TR55 Tc Worksheet of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Hyd. No. 6 South Perimeter Channel 4 Description A B C Totals Sheet Flow Manning's n-value = Flow length (ft) = Two-year 24-hr precip. (in) = Land slope (%) = Travel Time (min) = = Shallow Concentrated Flow Flow length (ft) = Watercourse slope (%) = Surface description = Unpaved Unpaved Paved Average velocity (ft/s) = Travel Time (min) = = Channel Flow X sectional flow area (sqft) = Wetted perimeter (ft) = Channel slope (%) = Manning's n-value = Velocity (ft/s) = Flow length (ft) ({0}) Travel Time (min) = = 2.01 Total Travel Time, Tc min

32 Hydrograph Report of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 7 South Perimeter Total Hydrograph type = Combine Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 734 min Time interval = 1 min Hyd. volume = 2,239,426 cuft Inflow hyds. = 5, 6 Contrib. drain. area = ac Q (cfs) South Perimeter Total Hyd. No Year Q (cfs) Time (min) Hyd No. 7 Hyd No. 5 Hyd No. 6

33 Hydrograph Report of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 8 West Perimeter Channel (West Culvert) Hydrograph type = SCS Runoff Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 717 min Time interval = 1 min Hyd. volume = 54,240 cuft Drainage area = ac Curve number = 74 Basin Slope = 0.0 % Hydraulic length = 0 ft Tc method = User Time of conc. (Tc) = 6.00 min Total precip. = in Distribution = Type II Storm duration = 24 hrs Shape factor = 484 Q (cfs) West Perimeter Channel (West Culvert) Hyd. No Year Q (cfs) Hyd No. 8 Time (min)

34 Hydrograph Report of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 9 North Perimeter Channel 1 Hydrograph type = SCS Runoff Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 721 min Time interval = 1 min Hyd. volume = 403,196 cuft Drainage area = ac Curve number = 84* Basin Slope = 0.0 % Hydraulic length = 0 ft Tc method = TR55 Time of conc. (Tc) = min Total precip. = in Distribution = Type II Storm duration = 24 hrs Shape factor = 484 * Composite (Area/CN) = [(4.300 x 85) + (0.630 x 89) + (5.270 x 74)] / Q (cfs) North Perimeter Channel 1 Hyd. No Year Q (cfs) Time (min) Hyd No. 9

35 TR55 Tc Worksheet of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Hyd. No. 9 North Perimeter Channel 1 Description A B C Totals Sheet Flow Manning's n-value = Flow length (ft) = Two-year 24-hr precip. (in) = Land slope (%) = Travel Time (min) = = 2.64 Shallow Concentrated Flow Flow length (ft) = Watercourse slope (%) = Surface description = Unpaved Unpaved Paved Average velocity (ft/s) = Travel Time (min) = = 3.93 Channel Flow X sectional flow area (sqft) = Wetted perimeter (ft) = Channel slope (%) = Manning's n-value = Velocity (ft/s) = Flow length (ft) ({0}) Travel Time (min) = = 5.85 Total Travel Time, Tc min

36 Hydrograph Report of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 10 NPC 1 Total Hydrograph type = Combine Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 720 min Time interval = 1 min Hyd. volume = 457,436 cuft Inflow hyds. = 8, 9 Contrib. drain. area = ac Q (cfs) NPC 1 Total Hyd. No Year Q (cfs) Time (min) Hyd No. 10 Hyd No. 8 Hyd No. 9

37 Hydrograph Report of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 11 North Perimeter Channel 2 Hydrograph type = SCS Runoff Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 730 min Time interval = 1 min Hyd. volume = 288,896 cuft Drainage area = ac Curve number = 74 Basin Slope = 0.0 % Hydraulic length = 0 ft Tc method = TR55 Time of conc. (Tc) = min Total precip. = in Distribution = Type II Storm duration = 24 hrs Shape factor = 484 Q (cfs) North Perimeter Channel 2 Hyd. No Year Q (cfs) Time (min) Hyd No. 11

38 TR55 Tc Worksheet of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Hyd. No. 11 North Perimeter Channel 2 Description A B C Totals Sheet Flow Manning's n-value = Flow length (ft) = Two-year 24-hr precip. (in) = Land slope (%) = Travel Time (min) = = Shallow Concentrated Flow Flow length (ft) = Watercourse slope (%) = Surface description = Unpaved Unpaved Unpaved Average velocity (ft/s) = Travel Time (min) = = Channel Flow X sectional flow area (sqft) = Wetted perimeter (ft) = Channel slope (%) = Manning's n-value = Velocity (ft/s) = Flow length (ft) ({0}) Travel Time (min) = = 2.31 Total Travel Time, Tc min

39 Hydrograph Report of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 12 NPC 2 Total Hydrograph type = Combine Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 721 min Time interval = 1 min Hyd. volume = 746,334 cuft Inflow hyds. = 10, 11 Contrib. drain. area = ac Q (cfs) NPC 2 Total Hyd. No Year Q (cfs) Time (min) Hyd No. 12 Hyd No. 10 Hyd No. 11

40 Hydrograph Report of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 13 North Perimeter Channel 3 Hydrograph type = SCS Runoff Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 731 min Time interval = 1 min Hyd. volume = 384,385 cuft Drainage area = ac Curve number = 75* Basin Slope = 0.0 % Hydraulic length = 0 ft Tc method = TR55 Time of conc. (Tc) = min Total precip. = in Distribution = Type II Storm duration = 24 hrs Shape factor = 484 * Composite (Area/CN) = [(0.700 x 89) + ( x 74)] / Q (cfs) North Perimeter Channel 3 Hyd. No Year Q (cfs) Time (min) Hyd No. 13

41 TR55 Tc Worksheet of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Hyd. No. 13 North Perimeter Channel 3 Description A B C Totals Sheet Flow Manning's n-value = Flow length (ft) = Two-year 24-hr precip. (in) = Land slope (%) = Travel Time (min) = = Shallow Concentrated Flow Flow length (ft) = Watercourse slope (%) = Surface description = Unpaved Unpaved Paved Average velocity (ft/s) = Travel Time (min) = = Channel Flow X sectional flow area (sqft) = Wetted perimeter (ft) = Channel slope (%) = Manning's n-value = Velocity (ft/s) = Flow length (ft) ({0}) Travel Time (min) = = 3.80 Total Travel Time, Tc min

42 Hydrograph Report of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 14 North Perimeter Channel Total Hydrograph type = Combine Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 722 min Time interval = 1 min Hyd. volume = 1,130,716 cuft Inflow hyds. = 12, 13 Contrib. drain. area = ac Q (cfs) North Perimeter Channel Total Hyd. No Year Q (cfs) Time (min) Hyd No. 14 Hyd No. 12 Hyd No. 13

43 Hydrograph Report of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 15 Temporary Sed Pond Hydrograph type = SCS Runoff Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 726 min Time interval = 1 min Hyd. volume = 887,493 cuft Drainage area = ac Curve number = 84* Basin Slope = 0.0 % Hydraulic length = 0 ft Tc method = TR55 Time of conc. (Tc) = min Total precip. = in Distribution = Type II Storm duration = 24 hrs Shape factor = 484 * Composite (Area/CN) = [(6.800 x 100) + ( x 74)] / Q (cfs) Temporary Sed Pond Hyd. No Year Q (cfs) Time (min) Hyd No. 15

44 TR55 Tc Worksheet of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Hyd. No. 15 Temporary Sed Pond Description A B C Totals Sheet Flow Manning's n-value = Flow length (ft) = Two-year 24-hr precip. (in) = Land slope (%) = Travel Time (min) = = Shallow Concentrated Flow Flow length (ft) = Watercourse slope (%) = Surface description = Unpaved Unpaved Unpaved Average velocity (ft/s) = Travel Time (min) = = 3.75 Channel Flow X sectional flow area (sqft) = Wetted perimeter (ft) = Channel slope (%) = Manning's n-value = Velocity (ft/s) = Flow length (ft) ({0}) Travel Time (min) = = 0.00 Total Travel Time, Tc min

45 Hydrograph Report of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 16 Total To Sed Pond Hydrograph type = Combine Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 723 min Time interval = 1 min Hyd. volume = 4,257,634 cuft Inflow hyds. = 7, 14, 15 Contrib. drain. area = ac Q (cfs) Total To Sed Pond Hyd. No Year Q (cfs) Time (min) Hyd No. 16 Hyd No. 7 Hyd No. 14 Hyd No. 15

46 Hydrograph Report of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Hyd. No. 17 <no description> Hydrograph type = Reservoir Peak discharge = cfs Storm frequency = 10 yrs Time to peak = 859 min Time interval = 1 min Hyd. volume = 3,653,877 cuft Inflow hyd. No. = 16 - Total To Sed Pond Max. Elevation = ft Reservoir name = SW Sed Pond (with Rating Curve) Max. Storage = 3,247,439 cuft Storage Indication method used. Wet pond routing start elevation = ft. Q (cfs) <no description> Hyd. No Year Q (cfs) Time (min) Hyd No. 17 Hyd No. 16 Total storage used = 3,247,439 cuft

47 Pond Report of 76 Hydraflow Hydrographs Extension for AutoCAD Civil 3D 2013 by Autodesk, Inc. v10 Tuesday, 06 / 14 / 2016 Pond No. 6 - SW Sed Pond (with Rating Curve) Pond Data Contours -User-defined contour areas. Average end area method used for volume calculation. Begining Elevation = ft Stage / Storage Table Stage (ft) Elevation (ft) Contour area (sqft) Incr. Storage (cuft) Total storage (cuft) , , , , , , , , ,612 1,057, , ,747 1,284, , ,272 1,517, , ,108 1,757, , ,538 2,005, , ,109 2,259, , ,264 2,519, , ,880 2,786, , ,566 3,063, , ,264 3,378, , ,030 3,867, , ,318 4,501, , ,318 5,135, , ,318 5,770,160 Culvert / Orifice Structures Weir Structures [A] [B] [C] [PrfRsr] [A] [B] [C] [D] Rise (in) = Span (in) = No. Barrels = Invert El. (ft) = Length (ft) = Slope (%) = n/a N-Value = n/a Orifice Coeff. = Multi-Stage = n/a No No No Crest Len (ft) = Crest El. (ft) = Weir Coeff. = Weir Type = Multi-Stage = No No No No Exfil.(in/hr) = (by Wet area) TW Elev. (ft) = 0.00 Note: Culvert/Orifice outflows are analyzed under inlet (ic) and outlet (oc) control. Weir risers checked for orifice conditions (ic) and submergence (s). Stage / Storage / Discharge Table Stage Storage Elevation Clv A Clv B Clv C PrfRsr Wr A Wr B Wr C Wr D Exfil User Total ft cuft ft cfs cfs cfs cfs cfs cfs cfs cfs cfs cfs cfs , , ,057, ,284, ,517, ,757, ,005, ,259, ,519, ,786, ,063, ,378, ,867, ,501, ,135, ,770,

INFLOW DESIGN FLOOD CONTROL SYSTEM PLAN 40 C.F.R. PART PLANT YATES ASH POND 2 (AP-2) GEORGIA POWER COMPANY

INFLOW DESIGN FLOOD CONTROL SYSTEM PLAN 40 C.F.R. PART PLANT YATES ASH POND 2 (AP-2) GEORGIA POWER COMPANY INFLOW DESIGN FLOOD CONTROL SYSTEM PLAN 40 C.F.R. PART 257.82 PLANT YATES ASH POND 2 (AP-2) GEORGIA POWER COMPANY EPA s Disposal of Coal Combustion Residuals from Electric Utilities Final Rule (40 C.F.R.

More information

STREUVER FIDELCO CAPPELLI, LLC YONKERS DOWNTOWN DEVELOPMENT PHASE 1. DRAFT ENVIRONMENTAL IMPACT STATEMENT For: PALISADES POINT

STREUVER FIDELCO CAPPELLI, LLC YONKERS DOWNTOWN DEVELOPMENT PHASE 1. DRAFT ENVIRONMENTAL IMPACT STATEMENT For: PALISADES POINT STREUVER FIDELCO CAPPELLI, LLC YONKERS DOWNTOWN DEVELOPMENT PHASE 1 DRAFT ENVIRONMENTAL IMPACT STATEMENT For: PALISADES POINT Prepared by: PAULUS, SOKOLOWSKI & SARTOR STORMWATER MANAGEMENT 1. Methodology

More information

Stage Discharge Tabulation for Only Orifice Flow

Stage Discharge Tabulation for Only Orifice Flow Stage Discharge Tabulation for Only Orifice Flow DEPTH STAGE DISCHARGE (meters) (feet) (meters) (feet) (m 3 /s) (ft 3 /s) 0 0.20 0.40 0.60 0.80 1.00 1.20 1.40 1.60 1.80 2.00 0.7 1.3 2.0 2.6 3.3 3.9 4.6

More information

This site will utilize an infiltration berm to manage the two-year/24-hour volume increase.

This site will utilize an infiltration berm to manage the two-year/24-hour volume increase. High Street TETRA TECH, INC. By: RH Date: 1/30/2017 Subject: High Street Checked By: JB Date: 2/1/2017 PCSM Design and Evaluation PURPOSE: The purpose of these calculations is to design a Post-Construction

More information

This site will utilize an infiltration berm to manage the two-year/24-hour volume increase.

This site will utilize an infiltration berm to manage the two-year/24-hour volume increase. Gates TETRA TECH, INC. By: RH Date: 1/30/2017 Subject: Gates Road Checked By: JB Date: 2/1/2017 PCSM Design and Evaluation PURPOSE: The purpose of these calculations is to design a Post-Construction Stormwater

More information

******************* Project Description ******************* File Name... NAAF Stormwater Improvement Project 11_21_2014.SPF

******************* Project Description ******************* File Name... NAAF Stormwater Improvement Project 11_21_2014.SPF Autodesk Storm and Sanitary Analysis 2014 - Version 8.1.62 (Build 1) ----------------- *** Project Description *** File Name... NAAF Stormwater Improvement Project 11_21_2014.SPF Analysis Options Flow

More information

Submitted to: St. Johns River Power Park New Berlin Road Jacksonville, FL 32226

Submitted to: St. Johns River Power Park New Berlin Road Jacksonville, FL 32226 RUN-ON/RUN-OFF CONTROL SYSTEM PLAN RUN-ON AND RUN-OFF CONTROL SYSTEM PLAN St. Johns River Power Park Byproduct Storage Area B Phase I Development Submitted to: St. Johns River Power Park 11201 New Berlin

More information

This site will utilize an infiltration berm to manage the two-year/24-hour volume increase.

This site will utilize an infiltration berm to manage the two-year/24-hour volume increase. Gates TETRA TECH, INC. By: RH Date: 11/11/2016 Subject: Gates Road Checked By: JB Date: 11/13/2016 PCSM Design and Evaluation PURPOSE: The purpose of these calculations is to design a Post-Construction

More information

STRUCTURAL STABILITY ASSESSMENT

STRUCTURAL STABILITY ASSESSMENT STRUCTURAL STABILITY ASSESSMENT CFR 257.73(d) Bottom Ash Pond Complex Cardinal Plant Brilliant, Ohio October, 2016 Prepared for: Cardinal Operating Company Cardinal Plant Brilliant, Ohio Prepared by: Geotechnical

More information

Continuing Education Course #101 Drainage Design with WinTR-55

Continuing Education Course #101 Drainage Design with WinTR-55 1 of 5 Continuing Education Course #101 Drainage Design with WinTR-55 1. WinTR-55 uses the Kinematic Wave method for calculating storm runoff rates and volumes. 2. According to the Velocity Method, the

More information

LOCATED IN INDIAN RIVER COUNTY PREPARED FOR S.J.R.W.M.D. AND F.W.C.D. DECEMBER, 2003 Updated 2007 Updated May 2014 PREPARED BY

LOCATED IN INDIAN RIVER COUNTY PREPARED FOR S.J.R.W.M.D. AND F.W.C.D. DECEMBER, 2003 Updated 2007 Updated May 2014 PREPARED BY FELLSMERE WATER CONTROL DISTRICT EAST MASTER DRAINAGE PLAN AND STORMWATER HYDROLOGIC ANALYSIS OF THE GRAVITY DRAINAGE SYSTEM LOCATED BETWEEN THE EAST BOUNDARY, LATERAL U, THE MAIN CANAL, AND DITCH 24 LOCATED

More information

DAVID NOEL KELLY CIVIL. David Noel Kelly :24:14-04'00'

DAVID NOEL KELLY CIVIL. David Noel Kelly :24:14-04'00' DAVID NOEL KELLY CIVIL David Noel Kelly 2014.07.22 10:24:14-04'00' TABLE OF CONTENTS Stormwater Management Summary Checklist for Stormwater Report Illicit Discharge Statement Runoff Summary Existing Conditions

More information

HISTORY OF CONSTRUCTION FOR EXISTING CCR SURFACE IMPOUNDMENT PLANT GASTON ASH POND 40 CFR (c)(1)(i) (xii)

HISTORY OF CONSTRUCTION FOR EXISTING CCR SURFACE IMPOUNDMENT PLANT GASTON ASH POND 40 CFR (c)(1)(i) (xii) HISTORY OF CONSTRUCTION FOR EXISTING CCR SURFACE IMPOUNDMENT PLANT GASTON ASH POND 40 CFR 257.73(c)(1)(i) (xii) (i) Site Name and Ownership Information: Site Name: E.C. Gaston Steam Plant Site Location:

More information

Section 4: Model Development and Application

Section 4: Model Development and Application Section 4: Model Development and Application The hydrologic model for the Wissahickon Act 167 study was built using GIS layers of land use, hydrologic soil groups, terrain and orthophotography. Within

More information

Stormwater Guidelines and Case Studies. CAHILL ASSOCIATES Environmental Consultants West Chester, PA (610)

Stormwater Guidelines and Case Studies. CAHILL ASSOCIATES Environmental Consultants West Chester, PA (610) Stormwater Guidelines and Case Studies CAHILL ASSOCIATES Environmental Consultants West Chester, PA (610) 696-4150 www.thcahill.com Goals and Challenges for Manual State Stormwater Policy More Widespread

More information

STORMWATER REPORT FRITO LAY SUBDIVISION NO. 3

STORMWATER REPORT FRITO LAY SUBDIVISION NO. 3 STORMWATER REPORT FRITO LAY SUBDIVISION NO. 3 May 2018 STORMWATER REPORT I. Subdivision Data a. The parcel is adjacent to the existing Frito Lay property in Topeka; and the subject plat application encompasses

More information

ARTICLE 5 (PART 2) DETENTION VOLUME EXAMPLE PROBLEMS

ARTICLE 5 (PART 2) DETENTION VOLUME EXAMPLE PROBLEMS ARTICLE 5 (PART 2) DETENTION VOLUME EXAMPLE PROBLEMS Example 5.7 Simple (Detention Nomograph) Example 5.8 Offsite and Unrestricted Areas (HEC-HMS) Example 5.9 Ponds in Series w/ Tailwater (HEC-HMS) Example

More information

EROSION CONTROL NARRATIVE

EROSION CONTROL NARRATIVE EROSION CONTROL NARRATIVE Erosion and sediment control has been designed for the Willow Bend Phase I Subdivision according to UDFCD and the City of Thornton criteria, in order to minimize erosion and sediment

More information

Table of Contents Project Description... 1 Summary of Existing Conditions... 1 Summary of Proposed Conditions... 1 Stormwater Compliance... 2 Collecti

Table of Contents Project Description... 1 Summary of Existing Conditions... 1 Summary of Proposed Conditions... 1 Stormwater Compliance... 2 Collecti Table of Contents Project Description... 1 Summary of Existing Conditions... 1 Summary of Proposed Conditions... 1 Stormwater Compliance... 2 Collection... 2 Treatment... 3 Storage... 3 Disposal... 4 Soils...

More information

WATER MANAGEMENT REPORT FOR PAGE ESTATES

WATER MANAGEMENT REPORT FOR PAGE ESTATES WATER MANAGEMENT REPORT FOR PAGE ESTATES SLB Consulting of SW Florida, LLC PO Box 2826 Bonita Springs, FL. 34133 Phone: 239-948-9566 sandra@slbconsult.com C.O.A. # 25395 September 1, 2014 Sandra L. Bottcher

More information

Mr. Michael Malone CPS Energy 145 Navarro Street San Antonio, Texas Project No

Mr. Michael Malone CPS Energy 145 Navarro Street San Antonio, Texas Project No January 17, 2018 Mr. Michael Malone 145 Navarro Street San Antonio, Texas 78205 Project No. 0337367 Environmental Resources Management CityCentre Four 840 West Sam Houston Pkwy N. Suite 600 Houston, Texas

More information

Standards for Soil Erosion and Sediment Control in New Jersey May 2012

Standards for Soil Erosion and Sediment Control in New Jersey May 2012 STANDARD FOR SEDIMENT BASIN Definition A barrier, dam, excavated pit, or dugout constructed across a waterway or at other suitable locations to intercept and retain sediment. Basins created by construction

More information

DRAINAGE REPORT FOR THORNTON SELF STORAGE THORNTON, COLORADO

DRAINAGE REPORT FOR THORNTON SELF STORAGE THORNTON, COLORADO DRAINAGE REPORT FOR THORNTON SELF STORAGE THORNTON, COLORADO Prepared by: Bowman Consulting 603 Park Point Dr. Suite 100 Golden, CO 80401 (303)-801-2900 June 29, 2015 Revised August 14, 2015 CERTIFICATE

More information

CCR Rule Annual Inspection Report (cont.) 2

CCR Rule Annual Inspection Report (cont.) 2 The inspection findings consisted of maintenance items and items that were not observed to be signs or potential signs of significant structural weakness. No deficiencies or disrupting conditions that

More information

APPENDIX B HYDROLOGY

APPENDIX B HYDROLOGY APPENDIX B HYDROLOGY TABLE OF CONTENTS 1.0 INTRODUCTION... 1 2.0 PROBABLE MAXIMUM PRECIPITATION (PMP)... 1 3.0 DESIGN FLOW CALCULATION... 1 4.0 DIVERSION CHANNEL SIZING... 2 5.0 REFERENCES... 4 LIST OF

More information

Suitable Applications Sediment traps should be considered for use:

Suitable Applications Sediment traps should be considered for use: Categories EC Erosion Control SE Sediment Control TC Tracking Control WE Wind Erosion Control Non-Stormwater NS Management Control Waste Management and WM Materials Pollution Control Legend: Primary Objective

More information

WQ Outlet Design Single Orifice Orifice diameter = 24. Perforated riser/orifice Plate Outlet area per perforation row = 4

WQ Outlet Design Single Orifice Orifice diameter = 24. Perforated riser/orifice Plate Outlet area per perforation row = 4 These calculations should be used when designing the outlet structures for extended wet and dry detention basins (Sections 4. 7 and 4.8). The water quality outlet size and the trash rack design will vary

More information

Sediment Trap. At multiple locations within the project site where sediment control is needed.

Sediment Trap. At multiple locations within the project site where sediment control is needed. Sediment Trap SE-3 Objectives EC Erosion Control SE Sediment Control TR Tracking Control WE Wind Erosion Control Non-Stormwater NS Management Control Waste Management and WM Materials Pollution Control

More information

PONDNET.WK1 - Flow and Phosphorus Routing in Pond Networks

PONDNET.WK1 - Flow and Phosphorus Routing in Pond Networks PONDNET.WK1 - Flow and Phosphorus Routing in Pond Networks Version 2.1 - March 1989 William W. Walker, Jr. Ph.D., Environmental Engineer 1127 Lowell Road, Concord, Massachusetts 01742 508-369-8061 PONDNET.WK1

More information

Sediment Trap. A temporary runoff containment area, which promotes sedimentation prior to discharge of the runoff through a stabilized spillway.

Sediment Trap. A temporary runoff containment area, which promotes sedimentation prior to discharge of the runoff through a stabilized spillway. Sediment Trap SC-15 Source: Caltrans Construction Site Best Management Practices Manual, 2003. Description A temporary runoff containment area, which promotes sedimentation prior to discharge of the runoff

More information

City of Thornton Attn: Tim Semones Development Engineeering 9500 Civic Center Dr. Thornton, CO 80229

City of Thornton Attn: Tim Semones Development Engineeering 9500 Civic Center Dr. Thornton, CO 80229 Development Engineering Land Surveying Construction Administration District Services October 20, 2017 City of Thornton Attn: Tim Semones Development Engineeering 9500 Civic Center Dr. Thornton, CO 80229

More information

Appendix D. Stormwater Pollution Prevention Plan

Appendix D. Stormwater Pollution Prevention Plan Appendix D Stormwater Pollution Prevention Plan STORMWATER POLLUTION PREVENTION PLAN FOR FOSTER CHURCH INC. BRETHREN GOSPEL HALL FEBRUARY 2011 Prepared by Civil Tec CONSULTING ENGINEERS 67 Brookside Avenue

More information

CITY OF CAPE CORAL STORMWATER MASTER PLAN PHASE II - PART 1 BASINS 4, 10, & 14 SUB-BASIN DRAINAGE IMPROVEMENTS HYDRAULIC ANALYSIS SUMMARY

CITY OF CAPE CORAL STORMWATER MASTER PLAN PHASE II - PART 1 BASINS 4, 10, & 14 SUB-BASIN DRAINAGE IMPROVEMENTS HYDRAULIC ANALYSIS SUMMARY CITY OF CAPE CORAL STORMWATER MASTER PLAN PHASE II - PART 1 BASINS 4, 10, & 14 SUB-BASIN DRAINAGE IMPROVEMENTS HYDRAULIC ANALYSIS SUMMARY Cape Coral, FL Prepared for: The City of Cape Coral Public Works

More information

MIDDLESEX COUNTY Department of Planning and Community Development P.O. Box 427, Saluda, VA Phone: Fax:

MIDDLESEX COUNTY Department of Planning and Community Development P.O. Box 427, Saluda, VA Phone: Fax: MIDDLESEX COUNTY Department of Planning and Community Development P.O. Box 427, Saluda, VA 23149 Phone: 804-758-3382 Fax: 804-758-0061 LAND DISTURBANCE PERMIT SUBMISSION REQUIREMENTS In order to expedite

More information

Chapter 5 CALIBRATION AND VERIFICATION

Chapter 5 CALIBRATION AND VERIFICATION Chapter 5 CALIBRATION AND VERIFICATION This chapter contains the calibration procedure and data used for the LSC existing conditions model. The goal of the calibration effort was to develop a hydraulic

More information

Appendix E Guidance for Shallow Flooding Analyses and Mapping

Appendix E Guidance for Shallow Flooding Analyses and Mapping Appendix E Guidance for Shallow Flooding Analyses and Mapping E.1 Introduction Different types of shallow flooding commonly occur throughout the United States. Types of flows that result in shallow flooding

More information

ENGINEER S CERTIFICATION OF FAULT AREA DEMONSTRATION (40 CFR )

ENGINEER S CERTIFICATION OF FAULT AREA DEMONSTRATION (40 CFR ) PLATTE RIVER POWER AUTHORITY RAWHIDE ENERGY STATION BOTTOM ASH TRANSFER (BAT) IMPOUNDMENTS LARIMER COUNTY, CO ENGINEER S CERTIFICATION OF FAULT AREA DEMONSTRATION (40 CFR 257.62) FOR COAL COMBUSTION RESIDUALS

More information

EROSION CONTROL NARRATIVE

EROSION CONTROL NARRATIVE EROSION CONTROL NARRATIVE Erosion and sediment control has been designed for the Willow Bend Phase I Subdivision according to UDFCD and the City of Thornton criteria, in order to minimize erosion and sediment

More information

SINCE 1959 SITE NARRATIVE Major Site Plan Application Lot 18 Harbinger Park Powells Point, Currituck County, North Carolina Prepared For: Richard M No

SINCE 1959 SITE NARRATIVE Major Site Plan Application Lot 18 Harbinger Park Powells Point, Currituck County, North Carolina Prepared For: Richard M No SINCE 1959 SITE NARRATIVE Major Site Plan Application Lot 18 Harbinger Park Powells Point, Currituck County, North Carolina Prepared For: Richard M Norris & Brooke R Norris 101 Baker Ave. Kill Devil Hills,

More information

design, construction, operation, and maintenance of the BAP is consistent with recognized and generally accepted good engineering standards.

design, construction, operation, and maintenance of the BAP is consistent with recognized and generally accepted good engineering standards. design, construction, operation, and maintenance of the BAP is consistent with recognized and generally accepted good engineering standards. In addition to the field inspection, Associated Engineers, Inc.

More information

September 6, City of Thornton 9500 Civic Center Drive Thornton, CO (303) RE: Maverik Thornton, CO - Drainage Report

September 6, City of Thornton 9500 Civic Center Drive Thornton, CO (303) RE: Maverik Thornton, CO - Drainage Report September 6, 2016 City of Thornton 9500 Civic Center Drive Thornton, CO 80229 (303) 538-7295 RE: Maverik Thornton, CO - Drainage Report As per your request, we are submitting to you the drainage report

More information

Pressure Head: Pressure head is the height of a column of water that would exert a unit pressure equal to the pressure of the water.

Pressure Head: Pressure head is the height of a column of water that would exert a unit pressure equal to the pressure of the water. Design Manual Chapter - Stormwater D - Storm Sewer Design D- Storm Sewer Sizing A. Introduction The purpose of this section is to outline the basic hydraulic principles in order to determine the storm

More information

Rucker Pond. Background

Rucker Pond. Background Rucker Pond Background The Rucker Basin consists of two subbasins (East and West) that drain to a single area known as Rucker Pond. Both subbasins have the same hydraulic parameters, but have different

More information

Project Description. Project Options. End Analysis On... Apr 26, :00:00. Rainfall Details

Project Description. Project Options. End Analysis On... Apr 26, :00:00. Rainfall Details Project Description File Name... 323 - Att Pond 3 East PIPES ONLY.SPF Project Options Flow Units... Elevation Type... Hydrology Method... EPA SWMM Infiltration Method... Link Routing Method... Enable Overflow

More information

APPENDIX B WORKSHEETS & EXHIBITS

APPENDIX B WORKSHEETS & EXHIBITS APPENDIX B WORKSHEETS & EXHIBITS A worksheet provides the designer a representation of a measure that allows for input of specific design criteria. The plan designer will be required to assess field conditions

More information

TPDES: Soil, Erosion and Sedimentation Methods

TPDES: Soil, Erosion and Sedimentation Methods SAWS TPDES: Soil, Erosion and Sedimentation Methods Philip Handley Supervisor-Resource Protection & Compliance August 25, 2014 TPDES: Soil, Erosion and Sedimentation Methods Soil Common term: Dirt Common

More information

Hydrology and Hydraulics Design Report. Background Summary

Hydrology and Hydraulics Design Report. Background Summary To: National Park Services Montezuma Castle National Monument Richard Goepfrich, Facility Manager From: Multicultural Technical Engineers Date: Tuesday - February 13, 2018 Subject: 30% Hydrology and Hydraulics

More information

Objectives: After completing this assignment, you should be able to:

Objectives: After completing this assignment, you should be able to: Data Analysis Assignment #1 Evaluating the effects of watershed land use on storm runoff Assignment due: 21 February 2013, 5 pm Objectives: After completing this assignment, you should be able to: 1) Calculate

More information

Big Rivers Electric Corporation Disposal of Coal Combustion Residuals (CCR) from Electric Utilities Final Rule CCR Impoundment Liner Assessment Report

Big Rivers Electric Corporation Disposal of Coal Combustion Residuals (CCR) from Electric Utilities Final Rule CCR Impoundment Liner Assessment Report Big Rivers Electric Corporation Disposal of Coal Combustion Residuals (CCR) from Electric Utilities Final Rule CCR Impoundment Liner Assessment Report CCR Surface Impoundment Information Name: Operator:

More information

UTILITY REPORT FOR THORNTON SELF STORAGE THORNTON, COLORADO

UTILITY REPORT FOR THORNTON SELF STORAGE THORNTON, COLORADO UTILITY REPORT FOR THORNTON SELF STORAGE THORNTON, COLORADO Prepared by: Bowman Consulting 63 Park Point Dr. Suite 1 Golden, CO 841 (33)-81-29 June 29, 215 Revised August 14, 215 Revised September 3, 215

More information

Rock & Aggregate Drop Inlet Protection

Rock & Aggregate Drop Inlet Protection Rock & Aggregate Drop Inlet Protection SEDIMENT CONTROL TECHNIQUE Type 1 System Sheet Flow Sandy Soils Type 2 System [1] Concentrated Flow Clayey Soils Type 3 System Supplementary Trap Dispersive Soils

More information

Advanced /Surface Hydrology Dr. Jagadish Torlapati Fall 2017 MODULE 2 - ROUTING METHODS

Advanced /Surface Hydrology Dr. Jagadish Torlapati Fall 2017 MODULE 2 - ROUTING METHODS Routing MODULE - ROUTING METHODS Routing is the process of find the distribution of flow rate and depth in space and time along a river or storm sewer. Routing is also called Flow routing or flood routing.

More information

3301 East 120 th Avenue Assited Living & Memory Care

3301 East 120 th Avenue Assited Living & Memory Care UTILITY REPORT FOR 3301 East 120 th Avenue Assited Living & Memory Care 1 st Submittal January 23, 2016 2 nd Submittal March 04, 2016 Prepared for: 3301 E. 120 th Ave, LLC. 8200 E. Maplewood Ave., Suite

More information

D. B. G R A Y E N G I N E E R I N G I N C.

D. B. G R A Y E N G I N E E R I N G I N C. STORMWATER MANAGEMENT REPORT 948 Hunt lub Road Ottawa, Ontario Report No. 12020-SWM August 27, 2012 Revised April 21, 2014 Revised December 9, 2014 Revised April 14, 2015 D. B. G R A Y E N G I N E E R

More information

Stormwater Capacity Analysis for Westover Branch Watershed

Stormwater Capacity Analysis for Westover Branch Watershed Stormwater Capacity Analysis for Westover Branch Watershed Pimmit Run Little Pimmit Run, Mainstem Stohman's Run Gulf Branch Pimmit Run Tributary Little Pimmit Run, W. Branch Little Pimmit Run, E. Branch

More information

INTRODUCTION TO HYDROLOGIC MODELING USING HEC-HMS

INTRODUCTION TO HYDROLOGIC MODELING USING HEC-HMS INTRODUCTION TO HYDROLOGIC MODELING USING HEC-HMS By Thomas T. Burke, Jr., PhD, PE Luke J. Sherry, PE, CFM Christopher B. Burke Engineering, Ltd. October 8, 2014 1 SEMINAR OUTLINE Overview of hydrologic

More information

UPPER COSUMNES RIVER FLOOD MAPPING

UPPER COSUMNES RIVER FLOOD MAPPING UPPER COSUMNES RIVER FLOOD MAPPING DRAFT BASIC DATA NARRATIVE FLOOD INSURANCE STUDY SACRAMENTO COUTY, CALIFORNIA Community No. 060262 November 2008 Prepared By: CIVIL ENGINEERING SOLUTIONS, INC. 1325 Howe

More information

Continuing Education Associated with Maintaining CPESC and CESSWI Certification

Continuing Education Associated with Maintaining CPESC and CESSWI Certification Continuing Education Associated with Maintaining CPESC and CESSWI Certification Module 2: Stormwater Management Principles for Earth Disturbing Activities Sponsors: ODOTs Local Technical Assistance Program

More information

BRANDON LAKES AVENUE PRE AND POST CONDITIONS DRAINAGE REPORT

BRANDON LAKES AVENUE PRE AND POST CONDITIONS DRAINAGE REPORT BRANDON LAKES AVENUE PRE AND POST CONDITIONS DRAINAGE REPORT Hillsborough County Public Works County Center, 22nd Floor 601 E. Kennedy Blvd. Tampa, FL 33602 BRANDON LAKES AVENUE DRAINAGE IMPROVEMENTS Capital

More information

CCR Surface Impoundment Location Restrictions Demonstration. MidAmerican Energy Company, Louisa Generating Station

CCR Surface Impoundment Location Restrictions Demonstration. MidAmerican Energy Company, Louisa Generating Station CCR Surface Impoundment Location Restrictions Demonstration MidAmerican Energy Company, Louisa Generating Station Final October 17, 2018 CCR Surface Impoundment Location Restrictions Demonstration Prepared

More information

FINAL DRAINAGE REPORT Villages at Riverdale Carriage Homes Thornton, CO

FINAL DRAINAGE REPORT Villages at Riverdale Carriage Homes Thornton, CO FINAL DRAINAGE REPORT Villages at Riverdale Carriage Homes Thornton, CO October 14, 2016 Revised: March 30, 2017 JN: 15096 Prepared for: PCS Group, Inc. 1001 16 th Street #3 B-180 Denver, CO 80265 P: 303.561.4905

More information

VIRGINIA ELECTRIC AND POWER COMPANY CHESTERFIELD POWER STATION LOWER ASH POND CHESTERFIELD COUNTY, VIRGINIA

VIRGINIA ELECTRIC AND POWER COMPANY CHESTERFIELD POWER STATION LOWER ASH POND CHESTERFIELD COUNTY, VIRGINIA Prepared for Dominion 5000 Dominion Boulevard Glen Allen, Virginia 23060 EMERGENCY ACTION PLAN VIRGINIA ELECTRIC AND POWER COMPANY CHESTERFIELD POWER STATION LOWER ASH POND CHESTERFIELD COUNTY, VIRGINIA

More information

HISTORY OF CONSTRUCTION FOR EXISTING CCR SURFACE IMPOUNDMENT PLANT GADSDEN ASH POND 40 CFR (c)(1)(i)-(xii)

HISTORY OF CONSTRUCTION FOR EXISTING CCR SURFACE IMPOUNDMENT PLANT GADSDEN ASH POND 40 CFR (c)(1)(i)-(xii) HISTORY OF CONSTRUCTION FOR EXISTING CCR SURFACE IMPOUNDMENT PLANT GADSDEN ASH POND 40 CFR 257.73(c)(1)(i)-(xii) (i) Site Name and Ownership Information: Site Name: Site Location: Site Address: Gadsden

More information

Eastlake Assited Living & Memory Care

Eastlake Assited Living & Memory Care UTILITY REPORT FOR Eastlake Assited Living & Memory Care 1 st Submittal January 23, 2016 2 nd Submittal March 04, 2016 June 7, 2016 Final Submittal August 08, 2016 Prepared for: 3301 E. 120 th Ave, LLC.

More information

Materials. Use materials meeting the following.

Materials. Use materials meeting the following. 208.01 Section 208. SOIL EROSION AND SEDIMENTATION CONTROL 208.01 Description. Install and maintain erosion and sedimentation controls to minimize soil erosion and to control sedimentation from affecting

More information

City of Columbia BMP Manual. Detailed Unified Sizing Criteria Example Wet Pond Design

City of Columbia BMP Manual. Detailed Unified Sizing Criteria Example Wet Pond Design City of Columbia BMP Manual Detailed Unified Sizing Criteria Example Wet Pond Design April 17, 2013 Wet Pond Example: Unified Sizing Criteria Methodology Base Data Location: Rome, GA Site Drainage Area

More information

Location Restriction Demonstration

Location Restriction Demonstration Location Restriction Demonstration R.M. Heskett Station Coal Ash Landfill Prepared for Montana-Dakota Utilities Company October 2018 Minneapolis, MN, Bismarck, ND Location Restrictions Demonstration October

More information

9. Flood Routing. chapter Two

9. Flood Routing. chapter Two 9. Flood Routing Flow routing is a mathematical procedure for predicting the changing magnitude, speed, and shape of a flood wave as a function of time at one or more points along a watercourse (waterway

More information

APPENDIX G APPENDIX G SEDIMENT CONTAINMENT SYSTEM DESIGN RATIONALE

APPENDIX G APPENDIX G SEDIMENT CONTAINMENT SYSTEM DESIGN RATIONALE APPENDIX G SEDIMENT CONTAINMENT SYSTEM DESIGN RATIONALE March 18, 2003 This page left blank intentionally. March 18, 2003 G-2 FIGURES Page # Figure G.1 Estimated Runoff from Precipitation Over Different

More information

Prayer Center of Brookfield

Prayer Center of Brookfield 11805 W. Hampton Avenue Milwaukee, WI 53225 414-462-9005 www.onesourceconsult.com Project: Prayer Center of Brookfield Location: NW ¼ & SW ¼ of Section 15, T7N, R20E in the City of Brookfield, Wisconsin

More information

WEST CATARACT CREEK DAM FINAL DESIGN REPORT

WEST CATARACT CREEK DAM FINAL DESIGN REPORT DAMsel In Distress Engineering 2112 S Huffer Ln Flagstaff, AZ 86011 (520) 981-9515 WEST CATARACT CREEK DAM FINAL DESIGN REPORT Prepared for: Dr. Charles Schlinger Mr. Mark Lamer TABLE OF CONTENTS Contents

More information

Chapter 7 Mudflow Analysis

Chapter 7 Mudflow Analysis Chapter 7 Mudflow Analysis 7.0 Introduction This chapter provides information on the potential and magnitude of mud floods and mudflows that may develop in Aspen due to rainfall events, snowmelt, or rain

More information

Notes: Space for as many as two segments per flow type can be used for each worksheet. Include a map, schematic, or description of flow segments.

Notes: Space for as many as two segments per flow type can be used for each worksheet. Include a map, schematic, or description of flow segments. Worksheet 3: Time of Concentration (Tc) or travel time (Tt) Project By Date Location Checked Date Check one: Present Developed Check one: Tc Tt through subarea Notes: Space for as many as two segments

More information

Sediment Control Practices. John Mathews Ohio Dept. of Natural Resources, Division of Soil and Water Resources

Sediment Control Practices. John Mathews Ohio Dept. of Natural Resources, Division of Soil and Water Resources Sediment Control Practices John Mathews Ohio Dept. of Natural Resources, Division of Soil and Water Resources Practices Treat the Largest Soil Particles Sand Sand Silt Clay Treated Untreated Settleable

More information

WELCOME Lake Wabukayne OPEN HOUSE

WELCOME Lake Wabukayne OPEN HOUSE WELCOME Lake Wabukayne Sediment Removal Project OPEN HOUSE We are here to: Update you, the community, on recent developments and activities at Lake Wabukayne Present the preferred alternative and receive

More information

PRELIMINARY CULVERT ANALYSIS REPORT FOR CULVERT NO. 008-C OREGON AVENUE OVER PINEHURST CREEK

PRELIMINARY CULVERT ANALYSIS REPORT FOR CULVERT NO. 008-C OREGON AVENUE OVER PINEHURST CREEK PRELIMINARY CULVERT ANALYSIS REPORT FOR CULVERT NO. 008-C OREGON AVENUE OVER PINEHURST CREEK Prepared for The District of Columbia Department of Transportation Washington, D.C. Prepared by Parsons Transportation

More information

Determination of Urban Runoff Using ILLUDAS and GIS

Determination of Urban Runoff Using ILLUDAS and GIS Texas A&M University Department of Civil Engineering Instructor: Dr. Francisco Olivera CVEN689 Applications of GIS to Civil Engineering Determination of Urban Runoff Using ILLUDAS and GIS Tae Jin Kim 03.

More information

STORMWATER MANAGEMENT REPORT

STORMWATER MANAGEMENT REPORT STORMWATER MANAGEMENT REPORT THE FAIRWAYS AT EDGEWOOD LOTS 5 & 6, BLOCK 1201 TOWNSHIP OF RIVER VALE BERGEN COUNTY, NEW JERSEY PREPARED BY: DAPHNE A. GALVIN PROFESSIONAL ENGINEER LICENSE NO. 24GE03434900

More information

UNIVERSITY OF BOLTON. ENGINEERING, SPORTS and SCIENCES BSC CIVIL ENGINEERING SEMESTER 1 EXAMINATION 2014/2015 WATER ENGINEERING MODULE NO: BLT3023

UNIVERSITY OF BOLTON. ENGINEERING, SPORTS and SCIENCES BSC CIVIL ENGINEERING SEMESTER 1 EXAMINATION 2014/2015 WATER ENGINEERING MODULE NO: BLT3023 [TW59] UNIVERSITY OF BOLTON ENGINEERING, SPORTS and SCIENCES BSC CIVIL ENGINEERING SEMESTER 1 EXAMINATION 014/015 WATER ENGINEERING MODULE NO: BLT303 Date: Tuesday, 0 January 015 Time: 10.00-1.00 INSTRUCTIONS

More information

Probable Maximum Precipitation Study

Probable Maximum Precipitation Study Probable Maximum Precipitation Study Virginia Floodplain Management Association Workshop Thursday, October 29, 2015 Robert T. Bennett, PE, RA, CFM DCR Dam Safety & Floodplain Management Definition (4VAC50-20-50.H)

More information

APPENDIX B DESIGN CRITERIA FOR TEMPORARY WATER QUALITY BMPS USED DURING CONSTRUCTION

APPENDIX B DESIGN CRITERIA FOR TEMPORARY WATER QUALITY BMPS USED DURING CONSTRUCTION APPENDIX B DESIGN CRITERIA FOR TEMPORARY WATER QUALITY BMPS USED DURING CONSTRUCTION This Appendix presents design criteria and example calculations for the following temporary water quality BMPs for use

More information

Chapter 10 - Sacramento Method Examples

Chapter 10 - Sacramento Method Examples Chapter 10 Sacramento Method Examples Introduction Overview This chapter presents two example problems to demonstrate the use of the Sacramento method. These example problems use the SACPRE and HEC-1 computer

More information

INITIAL INFLOW DESIGN FLOOD CONTROL SYSTEM PLAN EXISTING CCR IMPOUNDMENTS CCR Rule Section

INITIAL INFLOW DESIGN FLOOD CONTROL SYSTEM PLAN EXISTING CCR IMPOUNDMENTS CCR Rule Section INITIAL INFLOW DESIGN FLOOD CONTROL SYSTEM PLAN EXISTING CCR IMPOUNDMENTS CCR Rule Section 257.82 ASBURY POWER PLANT 21133 Uphill Lane Asbury, Missouri 64832 October 17, 2016 EMPIRE DISTRICT ELECTRIC COMPANY

More information

PENNSYLVANIA DEPARTMENT OF TRANSPORTATION ENGINEERING DISTRICT 3-0

PENNSYLVANIA DEPARTMENT OF TRANSPORTATION ENGINEERING DISTRICT 3-0 PENNSYLVANIA DEPARTMENT OF TRANSPORTATION ENGINEERING DISTRICT 3-0 LYCOMING COUNTY S.R.15, SECTION C41 FINAL HYDROLOGIC AND HYDRAULIC REPORT STEAM VALLEY RUN STREAM RELOCATION DATE: June, 2006 REVISED:

More information

Stormwater Drainage Design Report. Reeve & Associates, Inc. Maverik, Inc. 88th Avenue and Pecos Street. Thornton, CO

Stormwater Drainage Design Report. Reeve & Associates, Inc. Maverik, Inc. 88th Avenue and Pecos Street. Thornton, CO 88th Avenue and Pecos Street Stormwater Drainage Design Report Reeve & Associates, Inc. Solutions You Can Build On for Maverik, Inc. 88th Avenue and Pecos Street Thornton, CO submitted to Reeve & Associates,

More information

HOTEL KANATA 160 HEARST WAY KANATA, ONTARIO SERVICING REPORT. Prepared for: David Johnston Architect. Prepared By:

HOTEL KANATA 160 HEARST WAY KANATA, ONTARIO SERVICING REPORT. Prepared for: David Johnston Architect. Prepared By: HOTEL KANATA 160 HEARST WAY KANATA, ONTARIO SERVICING REPORT Prepared for: David Johnston Architect Prepared By: BaseTech Consulting Inc. 309 Roywood Crescent Newmarket, Ontario L3Y 1A6 BCI Project No.

More information

Technical Memorandum No

Technical Memorandum No Pajaro River Watershed Study in association with Technical Memorandum No. 1.2.10 Task: Evaluation of Four Watershed Conditions - Sediment To: PRWFPA Staff Working Group Prepared by: Gregory Morris and

More information

Section 3.0 Existing Systems Hydrology and Hydraulics

Section 3.0 Existing Systems Hydrology and Hydraulics Section 3.0 Existing Systems Hydrology and Hydraulics This chapter summarizes the results and methodology of MACTEC s evaluation of the existing drainage systems and lakes for the City of Maitland, Florida.

More information

J.H. Campbell Generating Facility Pond A - Location Restriction Certification Report

J.H. Campbell Generating Facility Pond A - Location Restriction Certification Report J.H. Campbell Generating Facility Pond A - Location Restriction Certification Report Pursuant to: 40 CFR 257.60 40 CFR 257.61 40 CFR 257.62 40 CFR 257.63 40 CFR 257.64 Submitted to: Consumers Energy Company

More information

Specifications Whitcomb Elementary School Demolition January 15, 2016

Specifications Whitcomb Elementary School Demolition January 15, 2016 SECTION 31 2500 - EROSION CONTROL PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The provisions of the Contract Documents apply to the work of this Section. B. The Virginia Erosion and Sediment Control Handbook,

More information

Template for Sediment and Erosion Control Plan General Instructions. Section Instructions

Template for Sediment and Erosion Control Plan General Instructions. Section Instructions Template for Sediment and Erosion Control Plan General Instructions Introduction: Soil erosion and sediment deposition from farmlands can contribute to degraded surface water quality. Sediment delivery

More information

Stone Outlet Sediment Trap

Stone Outlet Sediment Trap 3.12 Sediment Control Description: A stone outlet sediment trap is a small detention area formed by placing a stone embankment with an integral stone filter outlet across a drainage swale for the purpose

More information

Basic Hydraulics June 2007

Basic Hydraulics  June 2007 Basic Hydraulics www.concrete-pipe.org June 2007 2007 Overview Open Channel Flow Manning Equation Basic Culvert Design Sanitary Sewer Design Flow, Velocity Stormwater Sewer Design Flow, Velocity 2 Open

More information

Limited Visual Dam Safety Inspections OA Oahu Reservoir No Oahu, Hawaii

Limited Visual Dam Safety Inspections OA Oahu Reservoir No Oahu, Hawaii Limited Visual Dam Safety Inspections OA00137 Oahu Reservoir No. 155 Oahu, Hawaii Prepared by: U.S. ARMY CORPS OF ENGINEERS HONOLULU DISTRICT STATE OF HAWAII DEPARTMENT OF LAND AND NATURAL RESOURCES May

More information

Bushkill Creek 3 rd Street Dam Removal Analysis

Bushkill Creek 3 rd Street Dam Removal Analysis Bushkill Creek 3 rd Street Dam Removal Analysis HEC HMS Runoff and Routing Model Stephen Beavan, Melanie DeFazio, David Gold, Peter Mara and Dan Moran CE 421: Hydrology Fall 2010 December 15, 2010 Contents

More information

Chapter 7 Mudflow Analysis

Chapter 7 Mudflow Analysis Chapter 7 Mudflow Analysis 7.0 Introduction This chapter provides information on the potential and magnitude of mud floods and mudflows that may develop in Aspen due to rainfall events, snowmelt, or rain

More information

SERVICING BRIEF & STORMWATER MANAGEMENT REPORT Colonial Road Sarsfield (Ottawa), Ontario. Report No June 15, 2017

SERVICING BRIEF & STORMWATER MANAGEMENT REPORT Colonial Road Sarsfield (Ottawa), Ontario. Report No June 15, 2017 SERVICING BRIEF & STORMWATER MANAGEMENT REPORT 2980 Colonial Road Sarsfield (Ottawa), Ontario Report No. 16033 June 15, 2017 D. B. G R A Y E N G I N E E R I N G I N C. Stormwater Management - Grading &

More information

HYDROLOGY REPORT Tentative Tract No. 5978

HYDROLOGY REPORT Tentative Tract No. 5978 ATTACHMENT 5 October 2016 HYDROLOGY REPORT Tentative Tract No. 5978 City of Simi Valley County of Ventura Prepared For: Landsea Holdings Corporation 7525 Irvine Center Drive Suite 200 Irvine, CA 92618

More information

DEPARTMENT OF CIVIL AND ENVIRONMENTAL ENGINEERING Urban Drainage: Hydraulics. Solutions to problem sheet 2: Flows in open channels

DEPARTMENT OF CIVIL AND ENVIRONMENTAL ENGINEERING Urban Drainage: Hydraulics. Solutions to problem sheet 2: Flows in open channels DEPRTMENT OF CIVIL ND ENVIRONMENTL ENGINEERING Urban Drainage: Hydraulics Solutions to problem sheet 2: Flows in open channels 1. rectangular channel of 1 m width carries water at a rate 0.1 m 3 /s. Plot

More information

Electronic Submission Format Guide Anthracite Preparation Plant Permit Application

Electronic Submission Format Guide Anthracite Preparation Plant Permit Application Electronic Submission Format Guide Anthracite Preparation Plant Permit Application Module 1: Application Section A through Section J, the Application Checklist, and all narrative responses Act 67 / 68

More information