HYGROTHERMAL CHARACTERISTICS OF PUMICE AGGREGATE CONCRETE USED FOR MASONRY WALL BLOCKS

Size: px
Start display at page:

Download "HYGROTHERMAL CHARACTERISTICS OF PUMICE AGGREGATE CONCRETE USED FOR MASONRY WALL BLOCKS"

Transcription

1 HYGROTHERMAL CHARACTERISTICS OF PUMICE AGGREGATE CONCRETE USED FOR MASONRY WALL BLOCKS Kus, Hülya Dr.Eng., Assoc. Professor, Istanbul Technical University, Faculty of Architecture, In recent years, computer simulation programs have been increasingly utilized for performance analysis of building and its parts. Despite the databases incorporated into the simulation programs, it is sometimes required to have measured data related to material properties in order to get more accurate results and thus to make better interpretations and assessments. In the context of an extensive research, water vapour transmission and hygroscopic moisture adsorption properties of pumice aggregate concrete composite material were measured for such purposes. In this paper, tests are described in detail and the measurement results are presented. Beside careful consideration and long periods of time required for conducting reliable tests, the heterogeneous material characteristics in particular necessitate further tests and analysis on hygrothermal properties. Keywords: Hygrothermal characteristics, pumice aggregate concrete, vapour transmission, sorption INTRODUCTION Pumice aggregate concrete (PAC) hollow block, a relatively new product, is observed to be utilized increasingly as an alternative infill masonry wall unit to autoclaved aerated concrete block and hollow brick, in the construction of both residential and commercial buildings of Turkey. In order to develop the technical data and enhance the scientific knowledge about the characteristics of PAC blocks and the hygrothermal performance of external walls built with these blocks, an extensive research based on laboratory measurements, numerical analyses, and field observations was conducted (Kus et.al. 2010). Laboratory studies of: (i) material characteristics tests for determining thermal and moisture related properties of pumice aggregate concrete composite; and (ii) hot-box measurements for investigating heat and moisture flow through PAC block walls under various indoor and outdoor testing conditions constituted an important part of the research program. The pore structure plays an important role in the hygrothermal performance of pumice aggregate concrete composite like for other inorganic mineral materials. Therefore, studies on moisture related properties were considered important for: (i) proper understanding the characteristics of pumice aggregate concrete and thus to make accurate assessments and interpretations on the hygrothermal behaviour based on the hot-box measurement results obtained by monitoring of temperature and relative humidity in PAC block test walls; and (ii) improving the material database of hygrothermal simulation softwares in order to increase the accuracy of calculation results.

2 In this paper, determination of the water vapour transmission and hygroscopic sorption properties of pumice aggregate concrete is handled in detail. The test results are presented and discussed based on the test procedure; preparation of test samples, the testing equipment, and the measurement course. WATER VAPOUR TRANSMISSION TEST SET-UP Water vapour transmission test was conducted in compliance with the standard EN ISO Hygrothermal performance of building materials and products -- Determination of water vapour transmission [EN ISO 12572] according to wet cup method. Tests lasted over a period of five weeks including one week for the preparation of test samples and cups, and four weeks for the measurement period. Ten plates were first cut (with wet saw) from original wall blocks having one-row of hollows, since these blocks were the most appropriate for the dimensions of test samples required. Discs having a diameter of 88mm were then drilled out from these plates. The thickness of the hollow walls, i.e. pumice aggregate concrete solid parts of the blocks, constituted the thickness of the samples. Seven samples were selected among ten, having the proper shapes to be used in the tests. The dimensions were then measured by means of a digital caliper and the sample surface areas of both sides were accurately calculated through copying the sample surfaces on a millimetre-squared sheet of graph paper. All samples were conditioned under 23 C and 50% RH before conducting the test. The edges of the samples were sealed with elastic putty, and then they were mounted on top of plastic circular cups in which saturated salt solutions were placed in a glass prior to closing the open mouth with the sample. The tightness of the edges was controlled and the cups were put in the climate chamber. The preparations before the vapour transmission test are seen in Figure 1. Wall Block Drilling out of disc Drying of samples in the Sealing of sample samples oven edges Figure 1: Preparation of samples for vapour transmission test Test conditions were arranged as 93% RH in the test cup, and %50 RH and 23 C in the climate chamber in compliance with EN ISO standard according to set C given in Table 1. Test conditions and tolerances are given in Table 1. 94% relative humidity in the test cups was obtained using saturated KNO 3 solutions in glasses placed in the plastic cups. Table 1: Test conditions and tolerances given in the standard EN ISO Tolerances Conditions Relative Humidity % Set Temperature C - % RH Dry state Wet state C Set point Tolerance Set point Tolerance C 23-50/93 23±0,5 50 ±3 93 ±3

3 The climate chamber (Weiss WK model) and the test cups employed in the test are demonstrated in Figure 2. The accuracy of conditions in the climate chamber displayed on the digital screen was controlled with a protimeter. The temperature and relative humidity within the test chamber were continuously recorded during the test period. Test cups placed in the preconditioned climate chamber were periodically weighed and rotated. The mass changes in time were measured, and the water vapour transfer rates and the water vapour resistance factor were calculated according to EN ISO Climate chamber Preliminary controls before conducting test Test cups on the shelf Figure 2: Climate chamber and the samples Screen set conditions Graphical display of realized conditions Weighing Figure 3: Measurements of water vapour transmission test Before the calculation of average values based on the test data, the corrections were made for the masked edge effect of the samples using Equation 1, as given in the standard EN g me /g = d/π S ln (2/(1+exp(-2 π b/d))) (Equation 1) where gme is the vapour transmission rate with masked edge, in kg/(m 2 s); g is the vapour transmission rate ignoring the masked edge, in kg/( m 2 s); d is the thickness of the specimen, in m; b is the width of the masked edge, in m; S is the hydraulic diameter, in m, (four times the test area divided by the perimeter). Since the pumice aggregate concrete is highly permeable, the corrections were also made for the resistance of air layer thickness between the saturated salt solution and the base of the sample. Following equation was used to obtain the final results: W c = 1/(A Δp v /G)-(d a /δ a ) (Equation 2) where

4 Temperature C, RH %, Absolute moisture gr/kg da is the thickness of the air layer; δa is the water vapour permeability of air. HYGROSCOPIC SORPTION TEST SET-UP Hygroscopic sorption property of pumice aggregate concrete was determined using desiccator method in accordance with the standard EN ISO Hygrothermal performance of building materials and products Determination of hygroscopic sorption properties (EN ISO 12571). The test period including the determination of dry densities of test samples lasted over four months. Test method is based on precise weighing of test samples attained equilibrium state under controlled temperature and relative humidity conditions. In adsorption isotherm, defined by the wetting process of oven dry sample under increasing equilibrium relative humidities at a specified temperature, sorption curves through moisture adsorption are measured. In desorption isotherm, defined by the drying process of water saturated sample under decreasing equilibrium relative humidities at a specified temperature, sorption curves through moisture desorption are measured. In this study, in order to be used in the computer simulation programs, only adsorption curve was determined for pumice aggregate concrete. Seven test samples measuring 24mm 102mm 60mm were cut with wet saw from original pumice aggregate concrete hollow blocks. Dry densities were determined after drying in the oven at 105 C. Oven dried samples were then put in the desiccator in which specified relative humidity conditions were attained with different saturated salt solutions. Salts used in the test and the corresponding relative humidity values are given in Table 2. Table 2: Salts and RH values used in the sorption test LiCl MgCl 2 Mg(NO 3 ) 2 NaCl KNO 3 K 2 SO 4 12% 33% 54% 75% 92% 96% The tightness of the desiccator was ensured by means of a non-hardening butyl mastic strip (Figure 4a). Temperature and relative humidity conditions in the desiccator were monitored using a humidity sensor and the data was recorded by a datalogger throughout the test (Figure 4b) May 25-May 15-Jun 6-Jul 27-Jul 17-Aug Date a) Test samples in the desiccator. b) Monitored conditions inside the desiccator. Figure 4: Sorption test Test samples were periodically weighed with minimum 24 hours of intervals at specified RH conditions until they attained an equilibrium state with constant mass. Adsorption isotherms T RH Abs

5 Mass g for each test condition were determined in accordance with the test procedure given in the standard EN ISO according to the following equation: u = (m m 0 ) / m 0 (Equation 3) where u is the moisture content mass by mass m is the mass of test sample m 0 is the mass of dry test sample. RESULTS The average oven-dry density of the samples employed in the water vapour transmission test was determined as 786 kg/m 3. The mass change over time (vapour transfer rate) measured during the vapour transmission test is demonstrated in Figure 5. As it is seen in the diagram, the steady state conditions for each sample were obtained at different times during the test period MASS CHANGE Linear (1) Linear (2) Linear (4) Linear (5) Linear (6) Linear (7) Linear (8) R² = 0,9998 R² = 0,9993 R² = 0,9971 R² = 0,9966 R² = 0,9902 R² = 0,9987 R² = 0, Time (days) Figure 5: Vapour transfer rate of pumice aggregate concrete samples In Table 3, the vapour transmission test results are presented. The values represent the mean values of seven pumice aggregate concrete samples. Table 3: Average results of samples in the vapour transmission test. G [kg/s] g=g/a [kg/m 2 s] W c kg/(m 2 s Pa) Z [m 2 s Pa /kg] thickness d [m] δ [kg/(m s Pa)] μ=δ a /δ - s d = μ d [m] 2.24E E E E E E E E-02 The average dry density of pumice aggregate concrete samples used in the sorption test was found to be about 785 kg/m 3. Figure 6 shows the measured (equilibrium) moisture contents of test samples subjected to increasing relative humidity levels reached by different salt

6 solutions. The moisture adsorption behaviour of pumice aggregate concrete is displayed in Figure 7, as sorption curve reflecting the averages of seven samples. W kg/m average 11 LiCl MgCl2 Mg(NO3)2 NaCl KNO3 K2SO4 Salt Figure 6: The equilibrium moisture contents of pumice aggregate concrete at different salt solutions. 50 y = 0,0001x 3-0,0158x 2 + 0,8508x - 0,02 R² = 0, ,5 W kg/m , Relative Humidity, φ [%] Figure 7: Adsorption curve for pumice aggregate concrete. CONCLUSIONS Tests and analysis conducted to determine the hygrothermal characteristics of porous building materials is important for a correct understanding of the characteristics of pumice aggregate concrete composite. Thus, more accurate performance assessments and interpretations can be made through input of measured data both in (i) the experimental studies and (ii) computer simulations performed on hygrothermal behaviour of walls built with pumice aggregate concrete hollow blocks. Since there is very limited scientific data and technical information on pumice aggregate concrete in general, and also limited data available in the international literature will not directly reflect the properties of the national products, test results obtained in the context of the research project were found to be quite useful.

7 ACKNOWLEDGEMENTS The material characteristics tests of pumice aggregate concrete were conducted within the research project, TUBITAK 107M532 Hygrothermal Performance of External Walls Made of Pumice Agregate Concrete Blocks, Energy and Economic Efficiency through Life Cycle supported by The Scientific and Technical Research Council of Turkey. BMG-HIG is greatly acknowledged for opening their laboratories to conduct the vapour transmission test. REFERENCES Kus, H., Edis, E., Özkan, E., and Göçer, Ö. "Performance assessment of pumice aggregate concrete block walls", 8 th International (8IMS), Dresden, Germany, July 4-7, EN ISO 12572: 2001 Hygrothermal performance of building materials and products -- Determination of water vapour transmission properties. EN ISO 12571: 2000 Hygrothermal performance of building materials and products -- Determination of hygroscopic sorption properties.

Hygrothermal Properties and Performance of Sea Grass Insulation

Hygrothermal Properties and Performance of Sea Grass Insulation Hygrothermal Properties and Performance of Sea Grass Insulation Marlene Stenberg Hagen Eriksen, M.Sc. Student, Technical University of Denmark; m_hagen@ofir.dk Theresa Back Laursen, M.Sc. Student, Technical

More information

NON STATIONARY DIFFUSION TUBE Functional Sample Diffusion Tube

NON STATIONARY DIFFUSION TUBE Functional Sample Diffusion Tube MILENA PAVLÍKOVÁ, ZBYŠEK PAVLÍK, ROBERT ČERNÝ Department Materials Engineering and Chemistry Faculty Civil Engineering Czech Technical University in Prague The functional sample Diffusion Tube is instrumental

More information

MOISTURE PERMEABILITY DATA PRESENTED AS A MATHEMATICAL FUNCTION APPLICABLE TO HEAT AND MOISTURE TRANSPORT MODELS

MOISTURE PERMEABILITY DATA PRESENTED AS A MATHEMATICAL FUNCTION APPLICABLE TO HEAT AND MOISTURE TRANSPORT MODELS MOISTURE PERMEABILITY DATA PRESENTED AS A MATHEMATICAL FUNCTION APPLICABLE TO HEAT AND MOISTURE TRANSPORT MODELS Dr. Graham H. Galbraith Glasgow Caledonian University Mr. R. Craig McLean The University

More information

WUFI Workshop at NTNU /SINTEF Fundamentals

WUFI Workshop at NTNU /SINTEF Fundamentals WUFI Workshop at NTNU /SINTEF 2008 Fundamentals Contents: From steady-state to transient Heat storage and -transport Moisture storage and -transport Calculation of coupled transport Model limitations 2

More information

Influence of Air Space on Multi-layered Material Water Vapor Permeability Measurement

Influence of Air Space on Multi-layered Material Water Vapor Permeability Measurement Influence of Air Space on Multi-layered Material Water Vapor Measurement Yang Wu 1, Mavinkal K. Kumaran 2, Paul Fazio 1 Abstract The effect of interface between material layers in building envelope is

More information

Chapter 2 Inputs for Hygrothermal Simulation Tools

Chapter 2 Inputs for Hygrothermal Simulation Tools Chapter 2 Inputs for Hygrothermal Simulation Tools The hygrothermal performance of a construction material can be assessed by analysing energy, moisture, and air balances. The hygrothermal balances consider

More information

CIGRE SC A2 & D1 JOINT COLLOQUIUM 2011, KYOTO JAPAN. Water Saturation Limits and Moisture Equilibrium Curves of Alternative Insulation Systems

CIGRE SC A2 & D1 JOINT COLLOQUIUM 2011, KYOTO JAPAN. Water Saturation Limits and Moisture Equilibrium Curves of Alternative Insulation Systems CIGRE SC A2 & D1 JOINT COLLOQUIUM 2011, KYOTO JAPAN http://cigre2011-a2d1.org/ CIGRE A2 & D1 2011 Doshisha University, Kyoto PS2: Materials Water Saturation Limits and Moisture Equilibrium Curves of Alternative

More information

The article analyzes the process of vapor transfer through building materials, taking into account their real operation

The article analyzes the process of vapor transfer through building materials, taking into account their real operation ISSN: 0975-766X CODEN: IJPTFI Available Online through Research Article www.ijptonline.com ABOUT OPERATIONAL FACTOR INFLUENCE ON VAPOR PERMEABILITY OF HEAT-INSULATING MATERIALS A.S. Petrov, V.N. Kupriyanov

More information

Faculty of Mechanical Engineering Institute of Wood and Paper Technology

Faculty of Mechanical Engineering Institute of Wood and Paper Technology Faculty of Mechanical Engineering Institute of Wood and Paper Technology Investigations to the unsteady sorption behaviour of thermally modified wood and its connection to the alteration of pore structure

More information

DVS INTRINSIC. The easy-to-use solution to complex water sorption challenges.

DVS INTRINSIC. The easy-to-use solution to complex water sorption challenges. DVS INTRINSIC The easy-to-use solution to complex water sorption challenges www.surfacemeasurementsystems.com D V S I n t rin s i c The easy-to-use solution to complex water sorption challenges from Surface

More information

A Dynamic Method Determining Equilibrium Moisture Content of Porous Materials

A Dynamic Method Determining Equilibrium Moisture Content of Porous Materials A Dynamic Method Determining Equilibrium Moisture Content of Porous Materials Shinsaku Tada *1 and Kazumasa Watanabe * *1 Texte, Inc., -6-44-3, Misawa, Hino, Tokyo 191-3, Japan * Tottori University of

More information

Effect of moisture transfer on heat energy storage in simple layer walls

Effect of moisture transfer on heat energy storage in simple layer walls Effect of moisture transfer on heat energy storage in simple layer walls C. MAALOUF 1, A.D. TRAN LE 1, M. LACHI 1, E. WURTZ 2, T.H. MAI 1 1-Laboratoire Thermomécanique/GRESPI, Faculté des Sciences, University

More information

Assoc. Prof. Dr. Ruta MINIOTAITE

Assoc. Prof. Dr. Ruta MINIOTAITE KAUNAS UNIVERSITY OF TECHNOLOGY, LITHUANIA VAPOUR PERMEABILITY AND WATER ABSORPTION OF DIFFERENT EXTERIOR PAINT SYSTEMS Assoc. Prof. Dr. Ruta MINIOTAITE Increasing focus on the durability aspects of buildings

More information

Analysis of external and internal mass transfer resistance at steady state diffusion experiments on small clear wood specimens

Analysis of external and internal mass transfer resistance at steady state diffusion experiments on small clear wood specimens COST FP0802 Workshop Experimental and Computational Micro-Characterization Techniques in Wood Mechanics, Vila Real, 27 28 April 2011 Analysis of external and internal mass transfer resistance at steady

More information

EXPERIMENTAL AND NUMERICAL INVESTIGATION OF THE HYGROTHERMAL BEHAVIOUR OF CORK CONCRETE PANELS IN NORTH ALGERIA. Jijel, Algeria.

EXPERIMENTAL AND NUMERICAL INVESTIGATION OF THE HYGROTHERMAL BEHAVIOUR OF CORK CONCRETE PANELS IN NORTH ALGERIA. Jijel, Algeria. EXPERIMENTAL AND NUMERICAL INVESTIGATION OF THE HYGROTHERMAL BEHAVIOUR OF CORK CONCRETE PANELS IN NORTH ALGERIA Chadi Maalouf a, Hocine Boussetoua a,b, Tala Moussa a, Mohammed Lachi a, Azzedine Belhamri

More information

DETERMINATION OF THE DIFFUSION COEFFICIENT OF NEW INSULATORS COMPOSED OF VEGETABLE FIBERS I. BOULAOUED, A. MHIMID

DETERMINATION OF THE DIFFUSION COEFFICIENT OF NEW INSULATORS COMPOSED OF VEGETABLE FIBERS I. BOULAOUED, A. MHIMID DETERMINATION OF THE DIFFUSION COEFFICIENT OF NEW INSULATORS COMPOSED OF VEGETABLE FIBERS I. BOULAOUED, A. MHIMID Laboratoire d Etudes des Systèmes Thermiques et Energétiques, Ecole Nationale d'ingénieurs

More information

APPLICATION OF NELSON'S SORPTION ISOTHERM TO WOOD COMPOSITES AND OVERLAYS' Qinglin Wu

APPLICATION OF NELSON'S SORPTION ISOTHERM TO WOOD COMPOSITES AND OVERLAYS' Qinglin Wu APPLICATION OF NELSON'S SORPTION ISOTHERM TO WOOD COMPOSITES AND OVERLAYS' Qinglin Wu Assistant Professor Louisiana Forest Products Laboratory School of Forestry, Wildlife, and Fisheries Louisiana State

More information

DVS Intrinsic Compact and Economical Dynamic Vapor Sorption System

DVS Intrinsic Compact and Economical Dynamic Vapor Sorption System DVS Intrinsic Compact and Economical Dynamic Vapor Sorption System The easy-to-use solution to complex water sorption challenges from SMS: High quality water isotherms and efficient water activity measurements

More information

Determination of moisture surface transfer coefficients under transient conditions

Determination of moisture surface transfer coefficients under transient conditions Determination of moisture surface transfer coefficients under transient conditions T. Bednar & J. Dreyer University of Technology Vienna, Vienna, Austria ABSTRACT: Detailed investigations on surface transfer

More information

THE TEMPERATURE DEPENDENCE OF MOISTURE PERMEABILITY. G.H. Galbraith, J.S. Guo, R.C. McLean, C.K. Lee, D.J. Kelly

THE TEMPERATURE DEPENDENCE OF MOISTURE PERMEABILITY. G.H. Galbraith, J.S. Guo, R.C. McLean, C.K. Lee, D.J. Kelly THE TEMPERATURE DEPENDENCE OF MOSTURE PERMEABLTY G.H. Galbraith, J.S. Guo, R.C. McLean, C.K. Lee, D.J. Kelly THE TEMPERATURE DEPENDENCE OF MOSTURE PERMEABLTY 1 Department of Building & Surveying, Glasgow

More information

Thermal Analysis Excellence

Thermal Analysis Excellence Thermal Analysis Excellence Sorption Test Systems SPS11-1µ SPSx-1µ High Load SPSx-1µ Advance SPS23-1n Multi-Sample Moisture Sorption Analysis Simple, Accurate and Reliable Sorption Test Systems Moisture

More information

Crystallization behavior of freeze-dried lactose and lactitol as detected from the loss of sorbed water

Crystallization behavior of freeze-dried lactose and lactitol as detected from the loss of sorbed water Crystallization behavior of freeze-dried lactose and lactitol as detected from the loss of sorbed water Kirsi Jouppila and Pia Laine Department of Food and Environmental Sciences Introduction Amorphous

More information

On the estimation of moisture permeability and advection coefficients of a wood fibre material using the optimal experiment design approach

On the estimation of moisture permeability and advection coefficients of a wood fibre material using the optimal experiment design approach arxiv:175.2869v2 [math.oc] 9 Jul 217 Julien Berger Polytech Annecy Chambéry, LOCIE, France Thomas Busser Polytech Annecy Chambéry, LOCIE, France Denys Dutykh CNRS LAMA, Université Savoie Mont Blanc, France

More information

MIGRATION EXPERIMENT. Functional Sample Migration Experiment

MIGRATION EXPERIMENT. Functional Sample Migration Experiment Functional Sample Migration Experiment MILENA PAVLÍKOVÁ, LUKÁŠ FIALA, ZBYŠEK PAVLÍK Department of Materials Engineering and Chemistry Faculty of Civil Engineering Czech Technical University in Prague Functional

More information

Automated multi-vapor gravimetric sorption analyzer for advanced research applications

Automated multi-vapor gravimetric sorption analyzer for advanced research applications Automated multi-vapor gravimetric sorption analyzer for advanced research applications Automated multi-vapor gravimetric sorption analyzer for advanced research applications Key benefits of the DVS Advantage

More information

HYGROTHERMAL BEHAVIOUR OF A HEMP CONCRETE WALL: COMPARISON BETWEEN EXPERIMENTAL AND NUMERICAL RESULTS

HYGROTHERMAL BEHAVIOUR OF A HEMP CONCRETE WALL: COMPARISON BETWEEN EXPERIMENTAL AND NUMERICAL RESULTS HYGROTHERMAL BEHAVIOUR OF A HEMP CONCRETE WALL: COMPARISON BETWEEN EXPERIMENTAL AND NUMERICAL RESULTS Thibaut COLINART 1, Patrick Glouannec 1, Thomas Pierre 1, and Philippe Chauvelon 1 1 LIMATB, Université

More information

Evaluation of Comsol as a tool for pinpointing moisture entering locations from inside surface moisture

Evaluation of Comsol as a tool for pinpointing moisture entering locations from inside surface moisture Excerpt from the Proceedings of the COMSOL Conference 2010 Paris Evaluation of Comsol as a tool for pinpointing moisture entering locations from inside surface moisture A.W.M. (Jos) van Schijndel, Eindhoven

More information

Adsorption boundary curve influenced by step interval of relative humidity investigated by Dynamic Vapour Sorption equipment

Adsorption boundary curve influenced by step interval of relative humidity investigated by Dynamic Vapour Sorption equipment IRG/WP 11-40547 THE INTERNATIONAL RESEARCH GROUP ON WOOD PROTECTION Section 4 Processes and Properties Adsorption boundary curve influenced by step interval of relative humidity investigated by Dynamic

More information

Surface Measurement Systems

Surface Measurement Systems Surface Measurement Systems Euro Food s Water, Brussels, Belgium: March 2006 pattwool@smsuk.co.uk SMS - History Company formed in 1992/university spin-off Hotbed of innovation 10 Ph.D. s First Product

More information

An inverse modelling approach to estimate the hygric parameters of clay-based masonry during a moisture buffer value test

An inverse modelling approach to estimate the hygric parameters of clay-based masonry during a moisture buffer value test Accepted Manuscript An inverse modelling approach to estimate the hygric parameters of clay-based masonry during a moisture buffer value test Samuel Dubois, F.R.I.A Grant holder, Ph.D Student Fionn McGregor,

More information

MOISTURE TRANSPORT AND DEHYDRATION IN HEATED GYPSUM, AN NMR STUDY

MOISTURE TRANSPORT AND DEHYDRATION IN HEATED GYPSUM, AN NMR STUDY MOISTURE TRANSPORT AND DEHYDRATION IN HEATED GYPSUM, AN NMR STUDY G.H.A. van der Heijden (1), L. Pel (1) and K. Kopinga (1) (1) Transport in Porous materials, Applied Physics, Eindhoven University of Technology,

More information

MEASUREMENTS OF THE THERMAL CONDUCTIVITIES OF SOME COMMONLY USED INSULATING MATERIALS AFTER WETTING

MEASUREMENTS OF THE THERMAL CONDUCTIVITIES OF SOME COMMONLY USED INSULATING MATERIALS AFTER WETTING Environmental Engineering and Management Journal November 214, Vol.13, No. 11, 2881-288 http://omicron.ch.tuiasi.ro/eemj/ Gheorghe Asachi Technical University of Iasi, Romania MEASUREMENTS OF THE THERMAL

More information

DYNAMIC VAPOR SORPTION ANALYZER FULLY AUTOMATED COMPACT BENCH-TOP DVS ANALYZER, FOR FAST AND ACCURATE SORPTION MEASUREMENTS.

DYNAMIC VAPOR SORPTION ANALYZER FULLY AUTOMATED COMPACT BENCH-TOP DVS ANALYZER, FOR FAST AND ACCURATE SORPTION MEASUREMENTS. DYNAMIC VAPOR SORPTION ANALYZER FULLY AUTOMATED COMPACT BENCH-TOP DVS ANALYZER, FOR FAST AND ACCURATE SORPTION MEASUREMENTS. www.hidenisochema.com The IGAsorp is a fully automated compact bench-top DVS

More information

Equilibrium Moisture Content of Triticale Seed

Equilibrium Moisture Content of Triticale Seed An ASABE Meeting Presentation Paper Number: 13162333 Equilibrium Moisture Content of Triticale Seed Mahmoud K. Khedher Agha a, b, Won Suk Lee a, Ray A. Bucklin a, Arthur A. Teixeira a, Ann R. Blount c

More information

Experimental Assessment of Thermal Conductivity of a Brick Block with Internal Cavities Using a Semi-scale Experiment

Experimental Assessment of Thermal Conductivity of a Brick Block with Internal Cavities Using a Semi-scale Experiment Int J Thermophys (2013) 34:909 915 DOI 10.1007/s10765-012-1332-8 Experimental Assessment of Thermal Conductivity of a Brick Block with Internal Cavities Using a Semi-scale Experiment Zbyšek Pavlík Lukáš

More information

Influence of water on the total heat transfer in evacuated insulations

Influence of water on the total heat transfer in evacuated insulations Bavarian Center for Applied Energy Research Influence of water on the total heat transfer in evacuated insulations Ulrich Heinemann ZAE Bayern, Würzburg, Germany ulrich.heinemann@zae.uni-wuerzburg.de 7

More information

Comparison of probabilistic approaches to the mould growth problem

Comparison of probabilistic approaches to the mould growth problem Comparison of probabilistic approaches to the mould growth problem Zoltán Sadovský & Oľga Koronthályová & Peter Matiašovský Institute of Construction and Architecture, Slovak Academy of Sciences, Bratislava,

More information

Interpretation of Full Sorption-Desorption Isotherms as a Tool for Understanding Concrete Pore Structure

Interpretation of Full Sorption-Desorption Isotherms as a Tool for Understanding Concrete Pore Structure Interpretation of Full Sorption-Desorption Isotherms as a Tool for Understanding Concrete Pore Structure The MIT Faculty has made this article openly available. Please share how this access benefits you.

More information

Complete Moisture Analysis

Complete Moisture Analysis Complete Moisture Analysis Water Activity Instrumentation Dew Point Water Activity & Moisture Analysis Moisture Sorption Isotherms Capacitance Water Activity Accessories PRODUCT CATALOG 2013-2014 DEW POINT

More information

DESIGN OF ULTRA-THIN BONDED HOT MIX WEARING COURSE (UTBHMWC) MIXTURES

DESIGN OF ULTRA-THIN BONDED HOT MIX WEARING COURSE (UTBHMWC) MIXTURES Test Procedure for DESIGN OF ULTRA-THIN BONDED HOT MIX WEARING COURSE TxDOT Designation: Tex-247-F Effective Date: August 2008 August 2016. 1. SCOPE 1.1 This test method determines the proper proportions

More information

Estimation Method of Emission Rate and Effective Diffusion Coefficient using Micro Cell

Estimation Method of Emission Rate and Effective Diffusion Coefficient using Micro Cell Estimation Method of Emission Rate and Effective Diffusion Coefficient using Micro Cell Kaoru TAKIGASAKI 1,2, Kazuhide ITO 2,3 1 Maeda Corporation, Japan 2 Tokyo Polytechnic University, Japan 3 Kyushu

More information

The Design and Development of a Low Cost Wood Moisture Sensor

The Design and Development of a Low Cost Wood Moisture Sensor The Design and Development of a Low Cost Wood Moisture Sensor By Nicholas Hoffman Charlie Schreier Dr. Margaret Pinnell ETHOS Program The University of Dayton Stove Efficiency Testing Water boiling test

More information

ASAP: Accelerated Stability Assessment Program. Improved Protocol and Data Analysis for Accelerated Shelf-Life Estimation of Solid.

ASAP: Accelerated Stability Assessment Program. Improved Protocol and Data Analysis for Accelerated Shelf-Life Estimation of Solid. ASAP: Accelerated Stability Assessment Program Improved Protocol and Data Analysis for Accelerated Shelf-Life Estimation of Solid Dosage Forms Kenneth C. Waterman Research Fellow, Pfizer Inc A more rapid

More information

METEOROLOGY 110 Lab 4 Name. Meteorological Measurements

METEOROLOGY 110 Lab 4 Name. Meteorological Measurements METEOROLOGY 110 Lab 4 Name I. Response speeds of thermometers Meteorological Measurements How do you know what the air temperature is? Most people would answer: I read a thermometer. But is the thermometer

More information

AquaFlux A New Instrument for Water Vapour Flux Density Measurement

AquaFlux A New Instrument for Water Vapour Flux Density Measurement AquaFlux A New Instrument for Water Vapour Flux Density Measurement E. P. Berg, F.. Pascut, L. I. iortea, D. O Driscoll, P. Xiao, and R. E. Imhof chool of Engineering, outh Bank University, 103 Borough

More information

Techniques for Fast Measurements of Low Dewpoint in Portable Hygrometers

Techniques for Fast Measurements of Low Dewpoint in Portable Hygrometers Techniques for Fast Measurements of Low Dewpoint in Portable Hygrometers Speaker / Author: Nick Malby, Michell Instruments Ltd, 48 Lancaster Way Business Park, Ely, Cambridgeshire. CB6 3NW. UK. +44 1353

More information

Thermal conductivity of thermal mortars with EPS and silica aerogel

Thermal conductivity of thermal mortars with EPS and silica aerogel Thermal conductivity of thermal mortars with EPS and silica aerogel Filipa Silveira Baptista da Silva May 2017 Civil Engineering, Architecture and Georresources Department, Instituto Superior Técnico,

More information

11/23/ (4) Harmonization Stage 6: <1241> Water Solid Interactions in Pharmaceutical Systems (USP34 NF29 2S) BRIEFING

11/23/ (4) Harmonization Stage 6: <1241> Water Solid Interactions in Pharmaceutical Systems (USP34 NF29 2S) BRIEFING BRIEFING 1241 Water Solid Interactions in Pharmaceutical Systems, USP 32 page 759. The European Pharmacopoeia is the coordinating pharmacopeia for the international harmonization of the compendial standards

More information

Understanding Importance of Water Sorption Isotherm Shape, Hysteresis, and Models on Pharmaceutical Materials

Understanding Importance of Water Sorption Isotherm Shape, Hysteresis, and Models on Pharmaceutical Materials Understanding Importance of Water Sorption Isotherm Shape, Hysteresis, and Models on Pharmaceutical Materials Dr. Daniel J. Burnett Surface Measurement Systems, Ltd. Dburnett@surfacemeasurementsystems.com

More information

How to Determine the Long-Term Performance of Vacuum Insulation Panels

How to Determine the Long-Term Performance of Vacuum Insulation Panels How to Determine the Long-Term Performance of Vacuum Insulation Panels Roland Caps Board Member of VIPA Chief Research Officer and Founder of va-q-tec AG QUALICHeCK Workshop Brussels, 15 Dec. 2016 Vacuum

More information

3D Thermal-Diffusion Analysis on a Moisture Loaded Epoxy Sample

3D Thermal-Diffusion Analysis on a Moisture Loaded Epoxy Sample Excerpt from the Proceedings of the COMSOL Conference 2010 Boston 3D Thermal-Diffusion Analysis on a Moisture Loaded Epoxy Sample S. Madduri* 1, W. Infantolino 2, and B.G.Sammakia 1 1 Department of Mechanical

More information

Determination of Clay-Sand Plaster Hygrothermal Performance: Influence of Different Types of Clays on Sorption and Water Vapour Permeability

Determination of Clay-Sand Plaster Hygrothermal Performance: Influence of Different Types of Clays on Sorption and Water Vapour Permeability Determination of Clay-Sand Plaster Hygrothermal Performance: Influence of Different Types of Clays on Sorption and Water Vapour Permeability Erik Altmäe 1, Aime Ruus 1, Jane Raamets 1 and Ernst Tungel

More information

Measurement of Acoustic Properties of light weight concrete SL-Deck

Measurement of Acoustic Properties of light weight concrete SL-Deck DELTA Test Report TEST Reg. no. 100 Measurement of Acoustic Properties of light weight concrete SL-Deck Performed for Abeo A/S Project no.: I100486 Page 1 of 25 30 June 2014 DELTA Venlighedsvej 4 2970

More information

Influence of a Refurbishing on an Old Residential building's Wall in Paris in Summer: Mass and Heat Transfer Approach

Influence of a Refurbishing on an Old Residential building's Wall in Paris in Summer: Mass and Heat Transfer Approach Influence of a Refurbishing on an Old Residential building's Wall in Paris in Summer: Mass and Heat Transfer Approach K. Azos-Diaz1*, B. Tremeac1, F. Simon2, D. Corgier2 and C. Marvillet1 1 Laboratoire

More information

ASTM C STEADY-STATE HEAT FLUX MEASUREMENTS AND THERMAL TRANSMISSION PROPERTIES BY MEANS OF THE HEAT FLOW METER APPARATUS

ASTM C STEADY-STATE HEAT FLUX MEASUREMENTS AND THERMAL TRANSMISSION PROPERTIES BY MEANS OF THE HEAT FLOW METER APPARATUS Page 1 of 10 ASTM C 518 04 STEADY-STATE HEAT FLUX MEASUREMENTS AND THERMAL TRANSMISSION PROPERTIES BY MEANS OF THE HEAT FLO METER APPARATUS Rockwool Premium Plus Insulation Project No. 3194876SAT-001A

More information

The Effects of Moisture-Sorption Cycles on Some Physical Properties and Nutritional Contents of Agricultural Grains

The Effects of Moisture-Sorption Cycles on Some Physical Properties and Nutritional Contents of Agricultural Grains The Effects of Moisture-Sorption Cycles on Some Physical Properties and Nutritional Contents of Agricultural Grains O. Chukwu and E.S.A. Ajisegiri Department of Agricultural Engineering, Federal University

More information

Liquid water is one of the

Liquid water is one of the Formanski 71 1/07/09 8:57 Page 71 V olume 5 - Number 7 - May 2009 (71-75) Abstract Liquid water is one of the agents responsible for damage of building materials. Therefore determination of its content

More information

Measuring TEWL or Moisture Flux Across Artificial Skin

Measuring TEWL or Moisture Flux Across Artificial Skin Measuring TEWL or Moisture Flux Across Artificial Skin DVS Application Note 56 Armando R. Garcia, Jiyi Khoo and Dan Burnett Surface Measurement Systems Ltd. The measurement of water flux through human

More information

Determination of the deliquescence point in salt mixtures and in in-situ multicomponent salts with DVS equipment

Determination of the deliquescence point in salt mixtures and in in-situ multicomponent salts with DVS equipment SWBSS2014 3 rd International Conference on Salt Weathering of Buildings and Stone Sculptures 14-16 October 2014 Determination of the deliquescence point in salt mixtures and in in-situ multicomponent salts

More information

New Methods for Measuring Water Desorption and Vapour Permeation Rates in Membranes

New Methods for Measuring Water Desorption and Vapour Permeation Rates in Membranes New Methods for Measuring Water Desorption and Vapour Permeation Rates in Membranes L. I. iortea, D. O Driscoll, E. P. Berg, P. Xiao, F.. Pascut and R. E. Imhof School of Engineering, South Bank University,

More information

A Thermal and moisture property database for common building and insulation materials

A Thermal and moisture property database for common building and insulation materials http://irc.nrc-cnrc.gc.ca A Thermal and moisture property database for common building and insulation materials NRCC-45692 Kumaran, M.K. A version of this document is published in / Une version de ce document

More information

Relative Humidity Weight Time Relative Humidity Weight Time Temperature Weight Time Moisture Pickup mg/10g Change In Mass (%) - Dry Moisture Uptake of Choline Bitartrate* Date: 07 Dec 2001 Time:

More information

5th Pan American Conference for NDT 2-6 October 2011, Cancun, Mexico. Determination of thermal technical properties of ceramics masonry components

5th Pan American Conference for NDT 2-6 October 2011, Cancun, Mexico. Determination of thermal technical properties of ceramics masonry components Determination of thermal technical properties of ceramics masonry components Jiri ZACH 1, Jiri BROZOVSKY 1, Jitka HROUDOVA 1 1 Institute of Building Materials and Components, Faculty of Civil Engineering,

More information

Agry 465 Exam October 18, 2006 (100 points) (9 pages)

Agry 465 Exam October 18, 2006 (100 points) (9 pages) Agry 465 Exam October 18, 2006 (100 points) (9 pages) Name (4) 1. In each of the following pairs of soils, indicate which one would have the greatest volumetric heat capacity, and which would have the

More information

Electrical Resistivity of Compacted Kaolin and its Relation with Suction

Electrical Resistivity of Compacted Kaolin and its Relation with Suction Electrical Resistivity of Compacted Kaolin and its Relation with Suction Dias, Ana Sofia ana.sofia.dias@tecnico.ulisboa.pt Summary The electrical characteristics of compacted kaolin were studied and related

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK Unit 4 Heol Aur Dafen Industrial Estate Dafen Carmarthenshire SA14 8QN Contact: Mr P Evans Tel: +44 (0)1554 784040 Fax: +44 (0)1554 784041 E-Mail: pevans@gstl.co.uk Website: www.gstl.co.uk locations: Testing

More information

1D-HAM. Coupled Heat, Air and Moisture Transport in Multi-layered Wall Structures. Manual with brief theory and an example. Version 2.

1D-HAM. Coupled Heat, Air and Moisture Transport in Multi-layered Wall Structures. Manual with brief theory and an example. Version 2. 1D-HAM Coupled Heat, Air and Moisture Transport in Multi-layered Wall Structures. Manual with brief theory and an example. Version 2.0 30 t=70 days (1680 h) 100 Temperatures ( C) v (g/m³) 25 20 15 10 5

More information

Moisture Sorption Analysis of Pharmaceuticals

Moisture Sorption Analysis of Pharmaceuticals Moisture Sorption Analysis of Pharmaceuticals Robert L. Hassel, Ph.D. TA Instruments, 109 Lukens Drive, New Castle, DE 19720, USA ABSTRACT This paper describes the design features of the Q5000 SA, a new

More information

Introduction HMTTSC Nikolay Smirnov 1,*, Vladimir Tyutikov 1, and Vadim Zakharov 1

Introduction HMTTSC Nikolay Smirnov 1,*, Vladimir Tyutikov 1, and Vadim Zakharov 1 Mathematical and physical modeling of heat transfer through window with heat-reflecting screens to determine the potential of reducing thermal costs for microclimate parameters maintaining Nikolay Smirnov,*,

More information

SIMULATION OF HEAT AND MOISTURE INDUCED STRESS AND STRAIN OF HISTORIC BUILDING MATERIALS

SIMULATION OF HEAT AND MOISTURE INDUCED STRESS AND STRAIN OF HISTORIC BUILDING MATERIALS SIMULATION OF HEAT AND MOISTURE INDUCED STRESS AND STRAIN OF HISTORIC BUILDING MATERIALS Natalie Leonor Williams Portal 1, Angela Sasic Kalagasidis 1, and A.W.M. van Schijndel 2 1 Chalmers University of

More information

SOUTH AFRICAN NATIONAL STANDARD

SOUTH AFRICAN NATIONAL STANDARD ISBN 978-0-626-30857-5 SOUTH AFRICAN NATIONAL STANDARD Particle and relative densities of aggregates WARNING This document references other documents normatively. Published by SABS Standards Division 1

More information

STATIC GAS MONITOR Type SGM/DEW Revision A of 20 aprile 2016

STATIC GAS MONITOR Type SGM/DEW Revision A of 20 aprile 2016 APPLICATIONS Moisture monitoring of air or gas (SF6) Suitable for indoor or outdoor Industrial, medical or aerospace fields HIGHLIGHTS High voltage circuit breakers commonly used for distribution and transmission

More information

The CPT in unsaturated soils

The CPT in unsaturated soils The CPT in unsaturated soils Associate Professor Adrian Russell (UNSW) Mr David Reid (Golder Associates) Prof Nasser Khalili (UNSW) Dr Mohammad Pournaghiazar (UNSW) Dr Hongwei Yang (Uni of Hong Kong) Outline

More information

Determination of water and salt transport parameters of porous materials using methods of inverse modelling

Determination of water and salt transport parameters of porous materials using methods of inverse modelling Computational Methods and Experimental Measurements XIII 349 Determination of water and salt transport parameters of porous materials using methods of inverse modelling L. Fiala, Z. Pavlík, M. Pavlíková

More information

e-newsletter n 6 August 31 st, 2018 New calibration facility developed at PTB for relative humidity, associated to dtdlas transfer standard

e-newsletter n 6 August 31 st, 2018 New calibration facility developed at PTB for relative humidity, associated to dtdlas transfer standard e-newsletter n 6 August 31 st, 2018 New calibration facility developed at PTB for relative humidity, associated to dtdlas transfer standard PTB has developed a test facility to characterize humidity sensors

More information

Mathematical Modelling of Ceramic Block Heat Transfer Properties

Mathematical Modelling of Ceramic Block Heat Transfer Properties Proceedings of the 3 RD INTERNATIONAL CONFERENCE ADVANCED CONSTRUCTION 18-19 October, 2012, Kaunas, Lithuania Kaunas University of Technology, Faculty of Civil Engineering and Architecture Studentu st.

More information

Probabilistic models of construction materials Prof. Liudmyla Trykoz

Probabilistic models of construction materials Prof. Liudmyla Trykoz Probabilistic models of construction materials Prof. Liudmyla Trykoz Ukrainian State University of Railway Transport, Kharkiv, Ukraine The subject of our research is properties of building materials. The

More information

THERMAL CONDUCTIVITY OF BUILDING MATERIALS: AN OVERVIEW OF ITS DETERMINATION

THERMAL CONDUCTIVITY OF BUILDING MATERIALS: AN OVERVIEW OF ITS DETERMINATION 15 THERMAL CONDUCTIVITY OF BUILDING MATERIALS: AN OVERVIEW OF ITS DETERMINATION E Latif *, M Pruteanu *** and G R Rhydwen *, D C Wijeyesekera *, S Tucker **, M A Ciupala *, D Newport * * School of Computing,

More information

Moisture content in concrete

Moisture content in concrete Universal Moisture Transport Model in Concrete under Natural Environment Takumi Shimomura Nagaoka University of Technology Moisture content in concrete Shrinkage and creep of concrete Transport of aggressive

More information

Salt Crystallization in Hydrophobic Porous Materials

Salt Crystallization in Hydrophobic Porous Materials Hydrophobe V 5 th International Conference on Water Repellent Treatment of Building Materials Aedificatio Publishers, 97-16 (28) Salt Crystallization in Hydrophobic Porous Materials H. Derluyn 1, A.S.

More information

Salt Damage at Petra, Jordan: A Study of the Effects of Wind on Salt Distribution and Crystallisation

Salt Damage at Petra, Jordan: A Study of the Effects of Wind on Salt Distribution and Crystallisation Salt Damage at Petra, Jordan: A Study of the Effects of Wind on Salt Distribution and Crystallisation Dr. Fadi Bala awi Assistant Professor Department of Conservation science Queen Rania's Institute of

More information

Test Report. RI Acoustic Lab. Measurement of Sound Absorption Coefficient for RockDelta NoiStop Noise Barrier. 20 Feb. 07

Test Report. RI Acoustic Lab. Measurement of Sound Absorption Coefficient for RockDelta NoiStop Noise Barrier. 20 Feb. 07 Test Report RI Acoustic Lab Measurement of Sound Absorption Coefficient for RockDelta NoiStop Noise Barrier 20 Feb. 07 Title Measurement of Sound Absorption Coefficient for RockDelta NoiStop Noise Barrier

More information

A review and statistical study of existing hysteresis models for cementitious materials

A review and statistical study of existing hysteresis models for cementitious materials A review and statistical study of existing hysteresis models for cementitious materials Zhidong Zhang, Mickaël Thiery, Véronique Baroghel-Bouny To cite this version: Zhidong Zhang, Mickaël Thiery, Véronique

More information

Analysis of thermal effects in grouped silos of grain elevators

Analysis of thermal effects in grouped silos of grain elevators Int. Agrophysics, 2006, 20, 301-307 INTERNATIONAL Agrophysics www.ipan.lublin.pl/int-agrophysics Analysis of thermal effects in grouped silos of grain elevators A. apko and J.A. Prusiel* Institute of Civil

More information

INFLUENCE OF AGGREGATE INTERFACE IN CONCRETE ON PERMEABILITY

INFLUENCE OF AGGREGATE INTERFACE IN CONCRETE ON PERMEABILITY OS2-4 INFLUENCE OF AGGREGATE INTERFACE IN CONCRETE ON PERMEABILITY Koki Tagomori (1), Takeshi Iyoda (2) (1) Graduate school of Engineering, Shibaura Institute of Technology, Japan (2) Department of Civil

More information

Design, Testing and Pharmaceutical Applications of a Gas Pressure Controller Device for Solid - Gas Microcalorimetric Titration

Design, Testing and Pharmaceutical Applications of a Gas Pressure Controller Device for Solid - Gas Microcalorimetric Titration Design, Testing and Pharmaceutical Applications of a Gas Pressure Controller Device for Solid - Gas Microcalorimetric Titration A. Bakri University Joseph Fourier Faculty of Pharmacy Pharmaceutical Engineering

More information

Mass determination of 1 kg silicon spheres for Avogadro project

Mass determination of 1 kg silicon spheres for Avogadro project IMEKO 20 th TC3, 3 rd TC16 and 1 st TC22 International Conference Cultivating metrological knowledge 27 th to 30 th November, 2007. Merida, Mexico. Mass determination of 1 kg silicon spheres for Avogadro

More information

Building and Environment

Building and Environment Building and Environment 44 (2009) 688 693 Contents lists available at ScienceDirect Building and Environment journal homepage: www.elsevier.com/locate/buildenv Influence of cementitious binder content

More information

ADSORPTION EQUILIBRIUM MOISTURE CONTENTS OF LONG-GRAIN ROUGH RICE

ADSORPTION EQUILIBRIUM MOISTURE CONTENTS OF LONG-GRAIN ROUGH RICE ADSORPTION EQUILIBRIUM MOISTURE CONTENTS OF LONG-GRAIN ROUGH RICE M. M. Banaszek, T. J. Siebenmorgen STUDENT MEMBER ASAE ASSOc. MEMBER ASAE ABSTRACT The effects of temperature, relative humidity, and initial

More information

5. AN INTRODUCTION TO BUILDING PHYSICS

5. AN INTRODUCTION TO BUILDING PHYSICS 5. AN INTRODUCTION TO BUILDING PHYSICS P. Wouters, S. Martin ABSTRACT This chapter places the System Identification Competition in a broader context of evaluating the thermal performances of building components.

More information

PRO LIGNO Vol. 11 N pp

PRO LIGNO Vol. 11 N pp CATALYTIC HEAT TREATMENT OF WOOD Nadir AYRILMIS Department of Wood Mechanics and Technology, Forestry Faculty, Istanbul University, Istanbul, Turkey, Tel: 90 212 338 2400, Fax: 90 212 338 2424, Email:

More information

Standard Test Methods for Glass-Bonded Mica Used as Electrical Insulation 1

Standard Test Methods for Glass-Bonded Mica Used as Electrical Insulation 1 Designation: D 1039 94 (Reapproved 1999) e1 An American National Standard Standard Test Methods for Glass-Bonded Mica Used as Electrical Insulation 1 This standard is issued under the fixed designation

More information

THERMAL TRANSMITTANCE OF MULTI-LAYER GLAZING WITH ULTRATHIN INTERNAL PARTITIONS. Agnieszka A. Lechowska 1, Jacek A. Schnotale 1

THERMAL TRANSMITTANCE OF MULTI-LAYER GLAZING WITH ULTRATHIN INTERNAL PARTITIONS. Agnieszka A. Lechowska 1, Jacek A. Schnotale 1 THERMAL TRANSMITTANCE OF MULTI-LAYER GLAZING WITH ULTRATHIN INTERNAL PARTITIONS Agnieszka A. Lechowska 1, Jacek A. Schnotale 1 1 Cracow University of Technology, Department of Environmental Engineering,

More information

INFLUENCE OF HYSTERETIC MOISTURE TRANSFER ON CONCRETE DURABILITY

INFLUENCE OF HYSTERETIC MOISTURE TRANSFER ON CONCRETE DURABILITY VIII International Conference on Fracture Mechanics of Concrete and Concrete Structures FraMCoS-8 J.G.M. Van Mier, G. Ruiz, C. Andrade, R.C. Yu and X.X. Zhang (Eds) INFLUENCE OF HYSTERETIC MOISTURE TRANSFER

More information

Moisture Sorption Analysis of Pharmaceuticals

Moisture Sorption Analysis of Pharmaceuticals Moisture Sorption Analysis of Pharmaceuticals Robert L. Hassel, Ph.D. TA Instruments, 109 Lukens Drive, New Castle, DE 19720, USA ABSTRACT This paper describes the design features of the Q5000 SA, a new

More information

Moisture in Buildings. Steffen Vissing Andersen. VIA University College Campus Horsens

Moisture in Buildings. Steffen Vissing Andersen. VIA University College Campus Horsens Moisture in Buildings Steffen Vissing Andersen VIA University College Campus Horsens 009 Contents 1. Moisture in the air... 3 1.1. Absolute humidity diagram...3 1.. Water vapour pressure diagram... 4 1.3.

More information

Data Sheet. Functional Safety Characteristic Safety Values for BE.. Brakes * _0715*

Data Sheet. Functional Safety Characteristic Safety Values for BE.. Brakes * _0715* Drive Technology \ Drive Automation \ System Integration \ Services *22291814_0715* Data Sheet Functional Safety Characteristic Safety Values for BE.. Brakes Edition 07/2015 22291814/EN SEW-EURODRIVE Driving

More information

The influence of solar radiation on the distribution of temperatures in historic masonry

The influence of solar radiation on the distribution of temperatures in historic masonry Advanced Computational Methods and Experiments in Heat Transfer XII 181 The influence of solar radiation on the distribution of temperatures in historic masonry P. Beran Institute of Theoretical and Applied

More information

Standard Test Method for Measuring the Steady-State Thermal Transmittance of Fenestration Systems Using Hot Box Methods 1

Standard Test Method for Measuring the Steady-State Thermal Transmittance of Fenestration Systems Using Hot Box Methods 1 Designation: 97 AMERICAN SOCIETY FOR TESTING AND MATERIALS 100 Barr Harbor Dr., West Conshohocken, PA 19428 Reprinted from the Annual Book of ASTM Standards. Copyright ASTM Standard Test Method for Measuring

More information

Design for Airtightness and Moisture Control in New Zealand housing

Design for Airtightness and Moisture Control in New Zealand housing Design for Airtightness and Moisture Control in housing paola leardini the university of auckland [school of architecture & planning] thomas van raamsdonk pro clima nz limited current issues Indoor Air

More information